GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50

Similar documents
Level Switch NRS 2-50 NRS Original Installation Instructions English

Conductivity Controller LRR 1-50 LRR Original Installation Instructions English

LRR 1-53 URB 50 LRR Conductivity Controller LRR 1-52 Conductivity Controller LRR 1-53 Operating & Display Unit URB 50

GESTRA Steam Systems LRS 1-7. English. Installation & Operating Instructions Conductivity Switch

GESTRA Steam Systems LRS 1-7. English. Installation & Operating Instructions Conductivity Switch

GESTRA Steam Systems NRGT 26-1 NRGT 26-1S. English. Installation & Operating Instructions Level Transmitter NRGT 26-1, NRGT 26-1S

Level Controller NRR Original Installation Instructions English

Level Switch NRS Original Installation Instructions English

GESTRA Steam Systems NRS English. Installation Instructions Switching Controller Type NRS 1 40

GESTRA Steam Systems NRS Installation Instructions Control Unit NRS

Level Switch Type NRS Original Installation Instructions English

NRS Installation Instructions Level Switch Type NRS 1-42

Control Unit LRR Original Installation Instructions English

LRG LRG LRG 17-40

GESTRA Steam Systems. URZ 40a. English. Installation Manual Control Element for Actuator URZ 40a

Operating & Display Unit URB 2. Original Installation Instructions English

NRS Installation Instructions Level Switch NRS 1-41

LRG LRG LRG 17-40

ecotrans Lf 01/02 Transmitter / Switching Device for Conductivity Type B Operating Instructions 02.07/

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50

NRG NRG NRG NRG

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

Power supply CP-E 24/0.75

Operating instructions Fail-safe delay timer AZS About this document. Content

NRG NRG NRG

Operating Instruction

MINI-PS AC/2X15DC/1

GESTRA. GESTRA Steam Systems NRG Installation Instructions Level electrode NRG 16-42

Level Limit Switch nivotester FTL 325 P

Power supply CP-D 24/1.3

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

MINI MCR-SL-UI-I-LP-NC

Power supply CP-E 24/2.5

Electronic Circuit Breaker with reset input ESS20-1..

SET Installation and Operating Instructions. Level switch for two sensors

Operating Instructions

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Strain Gauge Measuring Amplifier BA 662

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Power supply CP-D 24/4.2 Primary switch mode power supply

Power supply CP-E 24/20.0

QUINT-PS-24DC/24DC/10

Liquid level monitoring relay CM-ENS.2x

MINI-PS AC/24DC/1.3

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

Installation and Operating Instructions for Phase Demodulator Type _.2

Power supply CP-E 24/2.5

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the Soliwave M microwave barrier

Power supply CP-D 12/2.1

Installation and Operational Instructions for ROBA -switch Type 017._00.2

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

Radio System Strobe Wizard Plus Freemask

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Electrical devices may only be mounted and connected by electrically skilled persons.

Type CP-S, CP-C & CP-A Switch mode

URB 1. Installation Instructions Operating Terminal and Display Unit URB 1

QUINT-PS AC/24DC/40

Digital Input Output Module 24 V for Ex n Zone 2 Series 9472/35

Electronic timer CT-TGD.22

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-T 24/20.0 Primary switch mode power supply

Power supply CP-T 48/5.0 Primary switch mode power supply

Technical Information Smartec CLD18

GFL-1000 User Manual Ground Fault Locator

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Power supply CP-T 24/10.0 Primary switch mode power supply

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

LRG LRG GESTRA Steam Systems. Installation Instructions Conductivity Electrode LRG Conductivity Electrode LRG 17-40

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

QUINT-PS/ 3AC/24DC/10

1 Safety instructions. 2 Device components. 3 Function. KNX Heating actuator 6gang RMD 230 V. Order-No. :

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

Level Limit Switch nivotester FTL 370, FTL 372

Moeller Electric Corporation

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

UNO-PS/1AC/24DC/150W. Primary-switched power supply unit. Data sheet. 1 Description

Operating instructions Electronic level sensor LK / / 2008

JUMO ecotrans Lf 03 Microprocessor Transmitter / Switching Device for conductivity or resistivity and temperature

ED701 General Industry Pressure Transmitter

3B SCIENTIFIC PHYSICS

Power supply CP-T 24/40.0 Primary switch mode power supply

QUINT-PS/ 3AC/24DC/40

GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26 phone: / , fax: / ,

Technical Information Smartec CLD18

Wireless Room Thermostat Installation and Operation Y6630D1007

Technical Information itemp TMT180

DIGEM f 96 x 48 EK. Applications. Description

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

Franck-Hertz Control Unit

Thermistor motor protection relays

CM-IWM.11 Insulation monitoring relay

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

Transcription:

GESTRA Steam Systems LRS 1-50 EN English Installation & Operating Instructions 819223-02 Conductivity Switch LRS 1-50

Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety note...5 Directives and standards EU Pressure Equipment Directive 2014/68/EU...6 VdTÜV Bulletin "Water Monitoring 100"...6 LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)...6 ATEX (Atmosphère Explosible)...6 Note on the Declaration of Conformity / Declaration by the Manufacturer...6 Technical data LRS 1-50...7 Scope of supply...8 Name plate / marking...8 In control cabinet: Mounting the conductivity switch Dimensions LRS 1-50...9 Key...9 Installation in control cabinet...9 In control cabinet: Wiring the conductivity switch Wiring diagram for conductivity switch LRS 1-50...10 Key...10 Connection of supply voltage...11 Connecting output contacts...11 Connecting conductivity electrode LRG 12-2, LRG 16-4, LRG 17-1 and LRG 19-1, resistance thermometer TRG 5-....11 Connection of conductivity electrode LRG16-9...11 Attention...11 In the plant: Wiring the conductivity electrode Connecting conductivity electrode LRG 12-2, LRG 16-4, LRG 17-1 and LRG 19-1, resistance thermometer TRG 5-....12 Connection of conductivity electrode LRG16-9...12 2

Contents - continued - Page Factory setting...13 Changing factory settings Switch selection of unit of measurement...13 Operating the conductivity switch Key to codes on seven-segment display...14 Commissioning procedure Setting parameters...15 Setting switchpoints and parameters...16 Operation, alarm and test Checking indication and functions of MIN / MAX output contacts...17 Troubleshooting Indication, diagnosis and remedy...18 Further Notes Action against high frequency interference...19 Decommissioning / replacing the equipment...19 Disposal...19 3

Important notes Usage for the intended purpose The conductivity switch LRS 1-50 in conjunction with conductivity electrodes LRG 1.-.. is used as limit switch, for instance in steam boilers, (pressurized) hot-water installations and condensate and feedwater tanks. The conductivity switch detects and indicates a MIN and a MAX conductivity limit. The conductivity switch LRS 1-50 is designed for use in combination with the following conductivity electrodes: LRG 12-1, LRG 16-4, LRG 16-9, LRG 17-1 and LRG 19-1. Function The conductivity switch LRS 1-50 in conjunction with the conductivity electrode LRG 1.-.. measures the electrical conductivity in conductive liquids. The conductivity electrodes LRG 12-2, LRG 16-4, LRG 17-1, LRG 19-1 or the LRG 16-9 with integrated resistance thermometer for detecting the fluid temperature can be used with the conductivity switch. To measure the temperature you can also use a separate resistance thermometer Pt 100. When connecting the conductivity electrode LRG 1.-.. a reference measurement is taken and by setting the correction factor CF accordingly the conductivity readings are adapted to the specific conditions of the installation If a resistance thermometer is used, not only the electrical conductivity but also the water temperature will be measured. The conductivity readings can then be referenced to the standard reference temperature of 25 C and the conductivity value will be automatically compensated for temperature. For this purpose the water temperature is constantly measured by the conductivity switch and the conductivity reading is automatically compensated as a function of the adjusted temperature coefficient tc (%/ C). Even if the temperature changes, thanks to the adjusted linear temperature compensation, the measured value is referenced to 25 C over the whole measuring range and indicated on the 7-segment LED display. The MAX /MIN limits can be variably adjusted within the measuring range. When the MIN or MAX limit is reached, the MIN or MAX output contact is switched over and MIN or MAX LED is illuminated. The equipment will be reset once the value passes outside the preset hysteresis. Any faults or malfunctions in the conductivity electrode, the electrical connection or the settings will be indicated by the 7-segment LED display. In the event of a malfunction a MIN and MAX alarm will be triggered. If an error occurs in the conductivity switch LRS 1-50, MIN and MAX alarms are raised and the system is restarted. Parameter settings can be changed or a MIN/MAX alarm be simulated by operating the rotary button. The electrical conductivity is measured in µs/cm. In some countries ppm (parts per million) is used instead. Conversion: 1µS/cm = 0.5 ppm. The conductivity switch can be adjusted accordingly. 4

Important notes - continued - Safety note The equipment must only be installed, wired and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who - through adequate training - have achieved a recognised level of competence. Danger The terminal strips of the equipment are live during operation. This presents the danger of electric shock! Always cut off power supply to the equipment before mounting, removing or connecting the terminal strips! Attention The name plate specifies the technical features of the equipment. Note that any piece of equipment without its specific name plate must neither be commissioned nor operated. 5

Directives and standards EU Pressure Equipment Directive 2014/68/EU The conductivity control & monitoring equipment LRG 1.-.., LRS 1-5.., LRR 1-5.. meets the safety requirements of the Pressure Equipment Directive (PED). The conductivity control & monitoring equipment is EC type approved according to EN 12952/EN 12953. These Directives state, among other things, the requirements made on limiting systems and equipment for steam boiler plants and (pressurised) hotwater installations. VdTÜV Bulletin "Water Monitoring 100" The conductivity switch LRS 1-50 in conjunction with the conductivity electrode LRG 1.-.. is type approved according to VdTÜV Bulletin "Water Monitoring 100".The VdTÜV Bulletin "Water Monitoring 100" states the requirements made on water monitoring equipment. LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility) The equipment meets the requirements of the Low Voltage Directive 2014/35/EU and the EMC Directive 2014/30/EU. ATEX (Atmosphère Explosible) According to the European Directive 2014/34/EU the equipment must not be used in explosion risk areas. Note The conductivity electrodes LRG 12-1, LRG 16-4, LRG 16-9, LRG 17-1 and LRG 19-1 are simple items of electrical equipment as specified in EN 60079-11 section 5.7. According to the European Directive 2014/34/EU the equipment must be equipped with approved Zener barriers if used in potentially explosive areas. Applicable in Ex zones 1, 2 (1999/92/EC). The equipment does not bear an Ex marking. Note on the Declaration of Conformity / Declaration by the Manufacturer For details on the conformity of our equipment according to the European Directives see our Declaration of Conformity or our Declaration of Manufacturer. The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under www.gestra.com/documents or can be requested from us. 6

Technical data LRS 1-50 Supply voltage 24 VDC +/ 20% Fuse external 0.5 A (semi-delay) Power consumption 4 VA Connection of conductivity electrode 1 input for conductivity electrode LRG 12-1, LRG 16-4, LRG 17-1 and LRG 19-1 (cell constant 1 cm -1 ), 3 poles with screen 1 input for conductivity electrode LRG 16-9 (cell constant 0.5 cm -1 ), with integrated resistance thermometer Pt 100, 5 poles with screen. Measuring voltage 0.8 Vss, pulse duty factor tv = 0.5, frequency 20-10000 Hz. Measuring range 1 to 10,000 μs/cm at 25 C or 1 to 5,000 ppm at 25 C. Switching hystereses MIN limit: + 3 % of the adjusted MIN limit, MAX limit: 3 % of the adjusted MAX limit. Outputs LRS 1-50: 2 volt-free change-over contacts, 8 A 250 V AC / 30 V DC cos ϕ = 1. Provide inductive loads with RC combinations according to manufacturer's specification to ensure interference suppression Indicators and adjusters 1 rotary button with integrated push-button for parameter setting and testing MAX /MIN alarm, 1 seven-segment LED display, four digits, 2 red LEDs for MAX/MIN alarm, 1 four-pole code switch for configuration settings Housing Housing material: base: polycarbonate, black; front: polycarbonate, grey Conductor size: 1 x 4.0 mm 2 solid, per wire, or 1 x 2.5 mm 2 per stranded wire with sleeve to DIN 46228 or 2 x 1.5 mm 2 per stranded wire with sleeve to DIN 46228 (min. 0.1 mm) Terminal strips can be detached. Fixing of housing: Mounting clip on supporting rail TH 35, EN 60715 Electrical safety Pollution degree 2 for installation in control cabinet with protection IP 54, completely insulated Protection Housing: IP 40 to EN 60529, Terminal strip: IP 20 to EN 60529 Weight approx. 0.2 kg Ambient temperature when system is switched on: 0... 55 C, during operation: -10... 55 C Transport temperature 20... +80 C (<100 hours), defrosting time of the de-energized equipment before it can be put into operation: 24 hours. 7

Technical data - continued - LRS 1-50 - continued - Storage temperature 20... +70 C, defrosting time of the de-energized equipment before it can be put into operation: 24 hours. Relative humidity max. 95%, no moisture condensation Approvals: TÜV certificate VdTÜV Bulletin "Wasserüberwachung 100" (= Water Monitoring 100): Requirements made on water monitoring equipment Type approval: TÜV WÜL XX-XXX (see name plate). Scope of supply LRS 1-50 1 Conductivity switch LRS 1-50 1 Adhesive label ppm 1 Installation manual Name plate / marking Name plate (on top) Type designation Safety note Manufacturer Name plate (at the bottom) Fuse, provided on site Power consumption Protection External fuse for output contacts Ambient temperature Output contacts Supply voltage Type approval no. Type approval no. Connection for conductivity electrode Measuring range Disposal note Fig. 1 8

In control cabinet: Mounting the conductivity switch Dimensions LRS 1-50 46 120 15 1 74 4 3 Fig. 2 2 Key 1 Upper terminal strip 2 Lower terminal strip 3 Housing 4 Supporting rail type TH 35, EN 60715 Installation in control cabinet The conductivity switch LRS 1-50 is clipped onto the support rail type TH 35, EN 60715 in the control cabinet. Fig. 1 4 9

In control cabinet: Wiring the conductivity switch Wiring diagram for conductivity switch LRS 1-50 MIN MAX MIN MAX 9 0 9 0 M 0.5 A (semidelay) 5 M 0.5 A (semidelay) 5 Fig. 3 6 8 8 7 Key 5 Connection of supply voltage 24 V DC with fuse 0.5 A (semi-delay), provided on site 6 Conductivity electrode LRG 1.-.. (Terminal 6/7: A resistance thermometer can be connected) 7 Conductivity electrode LRG 16-9 with integrated resistance thermometer 8 Central earthing point (CEP) in control cabinet 9 MIN output contact 0 MAX output contact 10

In control cabinet: Wiring the conductivity switch - continued - Connection of supply voltage The equipment is supplied with 24 V DC and fused with an external semi-delay fuse 0.5 A. Please use a safety power supply unit with safe electrical isolation. The power supply unit must be electrically isolated from dangerous contact voltages and must meet at least the requirements on double or reinforced isolation according to one of the following standards: DIN EN 50178, DIN EN 61010-1, DIN EN 60730-1 or DIN EN 60950. Connecting output contacts Wire the upper terminal strip 1 (terminals 16-23) according to the desired switching functions. Provide an external slow-blow fuse 2.5 A for the output contacts. When switching off inductive loads, voltage spikes are produced that may impair the operation of control and measuring systems. Connected inductive loads must be provided with suppressors such as RC combinations as specified by the manufacturer. When used as conductivity limiter, the conductivity switch LRS 1-50 does not interlock automatically when readings exceed the MAX limit. If an interlock function is required for the installation it must be provided in the follow-up circuitry (safety circuit). The circuitry must meet the requirements of the EN 50156. Connecting conductivity electrode LRG 12-2, LRG 16-4, LRG 17-1 and LRG 19-1, resistance thermometer TRG 5-.. To connect the equipment use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 2 x 0.5 mm 2. Wire terminal strip in accordance with the wiring diagram. Fig. 3 Connect the screen only once to the central earthing point (CEP) in the control cabinet. Make sure that connecting cables leading to the equipment are segregated and run separately from power cables. Connection of conductivity electrode LRG16-9 The conductivity electrode LRG 16-9 is equipped with a sensor plug-in connection type M 12, with 5 poles, A-coded, pin assignment see Fig. 3. For connecting the equipment preconfigured control cable assemblies (with male and female connectors) of various lengths are available as add-on equipment. To connect the conductivity switch LRS 1-50 remove the connector and wire the terminal strip according to the wiring diagram. Fig. 3. Connect the screen only once to the central earthing point (CEP) in the control cabinet. If you do not use the prefabricated control cable assembly, use screened five-core control cable, e. g. LiYCY 5 x 0.5 mm 2, for connecting the equipment. In addition, connect at the electrode end a screened female connector to the control cable. Make sure that connecting cables leading to the equipment are segregated and run separately from power cables. Attention n Do not use unused terminals as support point terminals. 11

In the plant: Wiring the conductivity electrode Connecting conductivity electrode LRG 12-2, LRG 16-4, LRG 17-1 and LRG 19-1, resistance thermometer TRG 5-.. To connect the equipment use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 3 x 0.5 mm 2. Wire terminal strip in accordance with the wiring diagram. Fig. 3 Connect the screen only once to the central earthing point (CEP) in the control cabinet. Max. cable length between conductivity electrode / resistance thermometer and conductivity switch: 30 m, with conductivities from 1 to 10 μs/cm: max. 10 m. Make sure that connecting cables leading to the equipment are segregated and run separately from power cables. Connection of conductivity electrode LRG16-9 The conductivity electrode LRG 16-9 is equipped with a sensor plug-in connection type M 12, with 5 poles, A-coded, pin assignment see Fig. 3. For connecting the equipment preconfigured control cable assemblies (with male and female connectors) of various lengths are available as add-on equipment. Note that the recommended control cable is not UV-resistant and, if installed outdoors, must be protected by a UV-resistant plastic tube or cable duct. To connect the conductivity switch LRS 1-50 remove the connector and wire the terminal strip according to the wiring diagram. Fig. 3 Connect the screen only once to the central earthing point (CEP) in the control cabinet. If you do not use the prefabricated control cable assembly, use screened five-core control cable, e. g. LiYCY 5 x 0.5 mm 2, for connecting the equipment. In addition, connect at the electrode end a screened female connector to the control cable. Max. cable length between conductivity electrode and switch: 30 m, with conductivities from 1 to 10 μs/cm: max. 10 m. Make sure that connecting cables leading to the equipment are segregated and run separately from power cables. Tools Attention n To commission the equipment please refer to the installation & operating manuals for LRG 12-2, LRG 16-4, LRG 16-9, LRG 17-1, LRG 19-1 and TRG 5-... n Make sure that connecting cables leading to the equipment are segregated and run separately from power cables. n Check the connection of the screen to the central earthing point (CEP) in the control cabinet. n Screwdriver, size 3.5 x 100 mm, completely insulated according to VDE 0680-1. 12

Factory setting Conductivity Switch LRS 1-50 n MAX switchpoint AL.Hi = 6000 μs/cm n MIN switchpoint AL.Lo = 500 μs/cm n Switching hysteresis: +/ 3% (fixed setting) n Correction factor CF: 1 n Temperature compensation inp: No n Temperature coefficient tc: 2.1 % / C n Code switch a: All switches are set to OFF. Changing factory settings Danger The upper terminal strip of the equipment is live during operation. This presents the danger of electric shock! Always cut off power supply to the equipment before mounting, removing or connecting the terminal strips! Switch selection of unit of measurement The electrical conductivity is measured in µs/cm. In some countries ppm (parts per million) is used instead. Conversion: 1 µs/cm = 0.5 ppm. Use the code switch a to set the desired unit of measurement. This unit setting is then applicable for all conductivity readings and settings. If you choose ppm as unit of measurement, please stick the adhesive label supplied with the equipment onto the unit specification on the housing. To change the setting proceed as follows: n Insert a screwdriver to the right and left of the arrow markings between the terminal strip and the front frame. n Unlock terminal strip on the left and right side For this purpose move screwdriver in direction of the arrow. n Remove the terminal strip n Set switch S4 of code switch a to ON = ppm (parts per million) n Re-attach lower terminal strip. n Apply supply voltage. Equipment is restarted. a Fig. 4 Attention Do not change the code switch a settings of S1, S2 and S3. 13

Operating the conductivity switch Key to codes on seven-segment display 5432 Seven-segment display Fig. 5 Rotary button with integrated pushbutton MAX LED red MIN LED red Code Description Indicated when rotary button is turned to the right: AL.Hi Alarm High MAX switchpoint adjustable between 1 and 9999 μs/cm AL.Lo Alarm Low MIN switchpoint Correction factor, adjustable between 0.05 and 5,000, adjustable CF Correction Factor in increments of 0.001 inp Input Pt 100 Temperature compensation YES (no) tc Temperature coefficient test Test Tests output relays Temperature coefficient T k 0.0 3.0 % per C, adjustable in increments of 1 %. Indicated when in parameterization mode: quit Quit Input not confirmed done Done Input confirmed Indicated if malfunctions occur: E.001 Error Temperature sensor defective, temperature reading too low E.002 Error Temperature sensor defective, temperature reading too high E.005 Error Sensor defective, measured value too low E.006 Error Sensor defective, measured value too high E.013 Error MIN switchpoint above MAX switchpoint 14

Commissioning procedure Setting parameters 5432 Seven-segment display Rotary button with integrated pushbutton MAX LED red MIN LED red Fig. 5 Start Activity Display Function Switch on supply voltage. Water level between MIN and MAX. Seven-segment display shows equipment and software version. Seven-segment display shows actual value System test, takes approx. 3 sec. System switches to operating mode Setting parameters Activity Seven-segment display Function Turn rotary button until the desired parameter is indicated. Press and hold down the pushbutton (of the rotary button) Turn rotary button. Press push-button. Each time you press the button the system moves to the next digit. If no further operation is performed: After the input has been finished: Press and hold down the push-button. Display toggles between parameter and the saved value setting. First digit (0000) flashing. A new value is indicated. 2nd, 3rd or 4th digit is flashing. (from right to left) "quit" is indicated for a moment. Then the display toggles between parameter and the old value setting. "done" is indicated for a moment. Then the display toggles between parameter and the new value setting. For selecting the parameter Parameterization mode active. You can change the first digit. To increase the value turn rotary button to the right, to decrease turn it to the left. 2nd, 3rd or 4th digit can be changed by turning the rotary button. To increase the value turn rotary button to the right, to decrease turn it to the left. The system switches automatically back to parameter and the input is not confirmed. The input is confirmed and the system switches automatically back to parameter. Turn rotary button until the next parameter is indicated. Or turn the rotary button until the actual value is shown. If no operation is performed the actual value will be indicated automatically after 30 sec. 15

Commissioning Setting switchpoints and parameters Setting MIN/MAX switchpoints Activity Select parameter AL.Lo, set the desired conductivity and save the setting. Select parameter AL.HI, set the desired conductivity and save the setting. Function Adjust MIN limit between 1 and 9999 μs/cm or 1 and 5000 ppm. Adjust MAX limit between 1 and 9999 μs/cm or 1 and 5000 ppm. Conductivity electrode LRG 1.-..: Setting the correction factor Select correction factor CF, set the required value and save the setting. Once the operating temperature is reached measure the electrical conductivity of a water sample (at 25 C). Set the correction factor (in increments) until the indicated actual value agrees with the reference measured value. As a result the conductivity readings will be adapted to the specific conditions of the installation and any deviations during operation will be compensated for. Conductivity electrode LRG 1.-.. with separate resistance thermometer and LRG 16-9 Enable temperature compensation Select setting inp and turn rotary button to the right. The word "YES" appears. Save the setting. Setting the temperature coefficient tc Select temperature coefficient tc, set the required percentage value and save the setting. If required: Select correction factor CF, set the required value and save the setting. Once the operating temperature is reached measure the electrical conductivity of a water sample (at 25 C). Set the temperature coefficient (in increments) until the indicated actual value agrees with the reference measured value. During operation the indicated conductivity reading may deviate from the reference value due to e. g. dirt deposits or contamination. Change the correction factor (in increments) until the indicated actual value agrees with the reference measured value. 16

Operation, alarm and test Checking indication and functions of MIN / MAX output contacts 5432 Seven-segment display Rotary button with integrated pushbutton MAX LED red MIN LED red Fig. 5 Operation Activity Display Function Conductivity between MIN and MAX. The actual value is shown on the seven-segment display. MIN and MAX LEDs are not illuminated. MIN output contact 16/18 open, 17/18 closed. MAX output contact 21/23 open, 22/23 closed. Reading below MIN conductivity limit MIN LED illuminated red MIN alarm MIN output contact 16/18 closed, 17/18 open. Switchpoint "MAX conductivity" exceeded. MAX alarm MAX LED illuminated red MAX output contact 21/23 closed, 22/23 open. Testing MIN alarm and MAX alarm Activity Display Function During operation: Conductivity between MIN and MAX. Select parameter Test. Press and hold down push-button. Seven-segment display: Test is flashing Test finished, release pushbutton. Seven-segment display: Test is indicated. MAX LED is illuminated red for 3 sec. MIN and MAX LEDs not illuminated for 1 sec. MIN LED is illuminated red for 3 sec. MAX output contact 21/23 closed, 22/23 open. MIN output contact 16/18 open, 17/18 open. MAX output contact 21/23 open, 22/23 closed. MIN output contact 16/18 closed, 17/18 open. Note: If you continue to hold down the push-button, a new test is started. You can abort the test any moment by releasing the push-button. Turn the rotary button until the actual value is shown. If no operation is performed the actual value will be indicated automatically after 30 sec. 17

Troubleshooting Indication, diagnosis and remedy Attention Before carrying out the fault diagnosis please check: Supply voltage: Is the equipment supplied with the mains voltage specified on the name plate? Wiring: Is the wiring in accordance with the wiring diagram? Faults indicated by the seven-segment display Error code Error Remedy E.001 E.002 E.005 E.006 Temperature sensor defective, temperature reading too low Temperature sensor defective, temperature reading too high Conductivity electrode defective, measured value too low. Conductivity electrode defective, measured value too high. Check resistance thermometer, conductivity electrode LRG 16-9 and, if necessary, replace it with a new one. Check wiring (short circuit, interruption?) Check conductivity electrode and, if necessary, replace it. Check electrical connection. Check conductivity electrode and, if necessary, replace it. Check electrical connection. E.013 MIN switchpoint above MAX switchpoint Re-adjust the switchpoints. In the event of a malfunction a MIN and MAX alarm will be triggered. Attention n Please refer to the installation & operating manuals for LRG 12-2, LRG 16-4, LRG 16-9, LRG 17-1, LRG 19-1 and TRG 5-.. for further fault-finding and troubleshooting. Note If a malfunction occurs in the conductivity switch, MIN and MAX alarms will be triggered and the equipment is restarted. Should this happen over and over again, replace the equipment with a new one. 18

Further Notes Action against high frequency interference High frequency interference can occur for example as a result of out-of-phase switching operations. Should such interference occur and lead to sporadic failures, we recommend the following actions in order to suppress any interference. n Provide inductive loads with RC combinations according to manufacturer's specification to ensure interference suppression. n Make sure that all connecting cables leading to the conductivity electrode are segregated and run separately from power cables. n Increase the distance to sources of interference. n Check the connection of the screen. Check the connection of the screens of the equipment as stipulated in the respective installation & operating manuals. If equipotential bonding currents are to be expected (e. g. in outdoor installations) connect screen only at one end. n HF interference suppression by means of hinged-shell ferrite rings. Decommissioning / replacing the equipment n Switch off supply voltage and cut off power supply to the equipment. n Remove the lower and upper terminal strips Fig. 6 n Insert a screwdriver to the right and left of the arrow markings between the terminal strip and the front frame. n Unlock terminal strip on the left and right side For this purpose move screwdriver in direction of the arrow. n Remove the terminal strip n Release the white fixing slide at the bottom of the equipment and take the equipment off the supporting rail. Fig. 6 Disposal For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal. If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country. 19

Agencies all over the world: www.gestra.com GESTRA AG Münchener Straße 77 28215 Bremen Germany Telefon +49 421 3503-0 Telefax +49 421 3503-393 E-mail info@de.gestra.com Web www.gestra.de 819223-02/02-2017cm (808884-02) GESTRA AG Bremen Printed in Germany