Enhancement of Reactive Power Capability of DFIG using Grid Side Converter

Similar documents
Harnessing of wind power in the present era system

Analysis of Single Phase Self-Excited Induction Generator with One Winding for obtaining Constant Output Voltage

CONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.

Pak. J. Biotechnol. Vol. 13 (special issue on Innovations in information Embedded and communication Systems) Pp (2016)

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

ROBUST ANALYSIS OF PID CONTROLLED INVERTER SYSTEM FOR GRID INTERCONNECTED VARIABLE SPEED WIND GENERATOR

Voltage Regulated Five Level Inverter Fed Wind Energy Conversion System using PMSG

Application of Fuzzy Logic Controller in Shunt Active Power Filter

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

SINGLE PHASE BRIDGELESS PFC FOR PI CONTROLLED THREE PHASE INDUCTION MOTOR DRIVE

29 Level H- Bridge VSC for HVDC Application

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

A Novel Voltage and Frequency Control Scheme for a Wind Turbine Driven Isolated Asynchronous Generator

COMPARISON OF UPQC AND DVR IN WIND TURBINE FED FSIG UNDER ASYMMETRIC FAULTS

PERFORMANCE ANALYSIS OF A NEW CONVERTER FOR SWITCHED RELUCTANCE MOTOR DRIVE WITH COMPONENT SHARING

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Harmonics Reduction in a Wind Energy Conversion System with a Permanent Magnet Synchronous Generator

Enhanced Performance of Multilevel Inverter Fed Induction Motor Drive

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Voltage Control and Power System Stability Enhancement using UPFC

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

B.Tech Academic Projects EEE (Simulation)

A Novel Five-level Inverter topology Applied to Four Pole Induction Motor Drive with Single DC Link

Modeling & Simulation of PMSM Drives with Fuzzy Logic Controller

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM

International Journal of Advance Engineering and Research Development

Analysis of Hybrid Renewable Energy System using NPC Inverter

Exercise 3. Doubly-Fed Induction Generators EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Doubly-fed induction generator operation

Vienna Rectifier Fed BLDC Motor

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

NOWADAYS, there is much interest in connecting various

Modeling and Simulation of Wind Farm with STATCOM in PSCAD/EMTDC Environment

A VARIABLE SPEED PFC CONVERTER FOR BRUSHLESS SRM DRIVE

Chhattisgarh Swami Vivekanand Technical University, Bhilai

Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation

Voltage stability enhancement using an adaptive hysteresis controlled variable speed wind turbine driven EESG with MPPT

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012

ISSN: [Yadav* et al., 6(5): May, 2017] Impact Factor: 4.116

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Volume I Issue VI 2012 September-2012 ISSN

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

SYNCHRONOUS MACHINES

DC BUS VOLTAGE CONTROL OF PWM CONVERTERS IN PMSG IN WIND POWER SYSTEM Krishnamoorthy.M 1 Andal. S 2 M.Varatharaj 3

Charge Pump Phase Locked Loop Synchronization Technique in Grid Connected Solar Photovoltaic Systems

VSC Based HVDC Active Power Controller to Damp out Resonance Oscillation in Turbine Generator System

Analysis of Voltage Source Inverters using Space Vector PWM for Induction Motor Drive

Reactive Power Support to PV Grid System Using Voltage Source Converters to Enhance PV Penetration Level

Performance Analysis of DFIG based Wind Energy Conversion System Using Direct Power Controller

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS

SVPWM Based Speed Control of Induction Motor with Three Level Inverter Using Proportional Integral Controller

Sensorless Control of BLDC Motor Drive Fed by Isolated DC-DC Converter

Power Quality Improvement Wind/PV Hybrid System by using Facts Device

Voltage and Current Waveforms Enhancement using Harmonic Filters

Comparison of SPWM,THIPWM and PDPWM Technique Based Voltage Source Inverters for Application in Renewable Energy

Modeling and Simulation of Matrix Converter Using Space Vector PWM Technique

Stability of Voltage using Different Control strategies In Isolated Self Excited Induction Generator for Variable Speed Applications

CHAPTER 3 MODIFIED SINE PWM VSI FED INDUCTION MOTOR DRIVE

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Laboratory Investigation of Variable Speed Control of Synchronous Generator With a Boost Converter for Wind Turbine Applications

ISSN Vol.04,Issue.16, October-2016, Pages:

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

A Switched Boost Inverter Fed Three Phase Induction Motor Drive

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

MODELING AND SIMULATON OF THREE STAGE INTERLEAVED BOOST CONVERTER BASED WIND ENERGY CONVERSION SYSTEM

Designing Of Distributed Power-Flow Controller

VIENNA RECTIFIER FED BLDC MOTOR

DC-Voltage fluctuation elimination through a dc-capacitor current control for PMSG under unbalanced grid voltage conditions

Direct AC/AC power converter for wind power application

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

International Journal of Emerging Technology in Computer Science & Electronics (IJETCSE) ISSN: Volume 8 Issue 1 APRIL 2014.

Performance of DVR & Distribution STATCOM in Power Systems

Space Vector Modulated Voltage Source Converter for Stand Alone Wind Energy Conversion System

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Transient Stability Improvement of Multi Machine Power Systems using Matrix Converter Based UPFC with ANN

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Module 7. Electrical Machine Drives. Version 2 EE IIT, Kharagpur 1

Performance Evaluation of PWM Converter Control Strategy for PMSG Based Variable Speed Wind Turbine

Park s Vector Approach to detect an inter turn stator fault in a doubly fed induction machine by a neural network

Voltage Balancing Control of Improved ZVS FBTL Converter for WECS

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

ScienceDirect. Modeling and Simulation of Solar PV and DFIG Based Wind Hybrid System

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Application of Matrix Converter in Wind Energy Conventional System Employing PMSG

Harmonic Analysis of Sine PWM and hysteresis current controller

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Self-Excitation and Voltage Control of an Induction Generator in an Independent Wind Energy Conversion System

A NEW C-DUMP CONVERTER WITH POWER FACTOR CORRECTION FEATURE FOR BLDC DRIVE

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Simulation And Hardware Analysis Of Three Phase PWM Rectifier With Power Factor Correction

MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR

Comparative Analysis of Space Vector Pulse-Width Modulation and Third Harmonic Injected Modulation on Industrial Drives.

Transcription:

Enhancement of Reactive Power Capability of DFIG using Grid Side Converter V. Sumitha 1 R. Gnanadass 2 Abstract - In the new electricity grid code, reactive power generation by wind farms, which must operate similarly to other conventional power plants, is a major concern during both steady-state and fault conditions. This article presents the reactive power capability of a doubly-fed induction generator (DFIG) through the use of performance capability curves. The real and reactive power capability of conventional DFIG, the Unified Architecture (UA) is analyzed for various firing angles and modulation indexes (μ) of the grid side converters (GSC).The performance of both the DFIG models are compared and the enhanced reactive power capability is illustrated. The simulation is carried out in simulink based MATLAB environment. Keywords - DFIG, GSC, UA, capability curve, reactive power capability. 116 I. INTRODUCTION Wind power, which has been proved to be a potential source for generation of electricity with minimal environmental impact, is the fastest-growing source for electric power generation, and it is expected to remain so in the future. At the end of 2007, the wind- installed capacity stands at over 94,112 MW worldwide, which is more than 20 GW from the capacity in 2006 [1]. With the advancement of aerodynamic designs, wind turbines can capture several megawatts of power, and this substantial amount of wind power can supplement the base power demand when such wind energy conversion systems (WECS) are integrated into the grid. Due to large penetration and matured technology, wind farms must fulfill almost the same requirements as conventional power plants. According to new grid codes, wind farms have to supply not only active power, but also to supply/consume the reactive power to/from the grid. The requirements are defined with respect to the power factor as a function of the voltage at the point of common coupling (PCC) with the main grid. Thus, the reactive power management becomes an integral issue in the gridconnected wind farms. The DFIG is commonly used in variable-speed large wind turbines. The DFIG has the ability to provide precise speed control and good power factor with a converter that is rated as low as 25% of the machine power rating. Due to its many advantages, such as improved power quality, high energy efficiency and controllability, reduced power converter rating, etc., the variable-speed wind turbine using a DFIG is becoming popular for large power generation from wind. The paper first received 11 Mar 2010 and in revised form 1 July 2010. Digital Ref: A170801269 1 EEE Department, Pondicherry Engineering College, Pondicherry 605 014, E mail: sumivaithi@yahoo.co.in 2 EEE Department, Pondicherry Engineering College, Pondicherry 605 014 In order to determine the technical viability of the DFIG for a wind generator application, the capabilities of the DFIG need to be determined. Recently, some research has given attention to the steady-state P-Q curve of a DFIG [2 4]. Tapia et al.(2003)derived P- Q curves by imposing only rotor current limitation for different operating temperatures. Similarly, [3] presents P- Q curves of a DFIG for different terminal voltages by considering only rotor current limits. Lund et al. [4] derived P-Q curves of a DFIG by imposing rotor current, stator current, and rotor voltage limits. But none of these authors considered the reactive power capability of a gridside converter (GSC). Considering the GSC reactive power capability will substantially change the operating range and operation of a DFIG. Peterson [5] proposed a new unified architecture (UA) of a DFIG using three converters; using a third converter drastically changed the reactive capability. The reactive power capability of a conventional DFIG and a unified DFIG has been obtained by extending the analysis of steady-state model of operation of a DFIG with a power grid through the use of performance capability curves. First, three steady-state models of DFIGs are derived in terms of (i) stator and rotor voltage (V S and V R), (ii) stator voltage and rotor current (V S and I R ), and (iii) stator voltage and stator current (V S and I S ) to derive the limitations in reactive power production, caused by the rotor voltage, the rotor current, and the stator current, respectively. Second, reactive power capability from the GSC is derived and included. Finally, a complete P-Q diagram of a DFIG is developed by optimization of rotor speed employing the maximum power point tracking (MPPT) algorithm. The effect of stator voltage variation on capability curves is also demonstrated [6]. This paper presents simulation results of a Grid-connected DFIG. The carrier-based Sinusoidal PWM modulation for grid-side converters have been proposed in this paper. Firing angle control has been developed to control the converters to provide independent control of active and reactive power and keep the DC-link voltage constant. To enhance the reactive capability of the DFIG machine one more grid side converter is added in series with already existing grid side converter. Hence, named as series grid side converter (SGSC) and the former named as parallel grid side converter (PGSC). This newly proposed architecture is named as unified architecture (UA) of a DFIG using three converters by Peterson[5].Both the configurations i.e. conventional DFIG and UA are simulated, the performance are compared and graphs are plotted. The effect of variation of the modulation index is also discussed and the plots are shown.

Asian Power Electronics Journal, Vol. 4, No.3 December 2010 In this paper the firing angle control limitation is proposed to vary the reactive power of the DFIG by varying the firing angle of the rotor side converter. The rotor side converter (RSC) is designed such that the output dc voltage is controlled by changing the firing angle of the converter. This dc output voltage is fed to the dc link capacitor. This dc link capacitor is the source of the grid side converter (inverter). This inverter synchronizes the low frequency ac voltage to the grid frequency ac voltage. Hence this system is called the power conditioning system (PCS). II. MODELLING OF DFIG The DFIG is a wound rotor induction generator having three-phase windings on the rotor and stator. The stator is directly connected to the grid, and the rotor power is fed by variable frequency power electronic converters, as given in Fig.1. The power electronic converter system consists of two back-to-back pulse width modulated (PWM) voltagefed current-regulated converters, namely, the rotor or machine-side converter (MSC) and GSC, which are controlled independently. The MSC is used to convert the rotor frequency power to DC power and then feed back to the AC system using the GSC, which converts DC power to AC power at the system frequency. The rotor voltage induced by the MSC in the rotor circuit is a complex quantity that represents two control variables. Usually, the field-oriented approach is employed for controlling the MSC, which allows the control of active and reactive powers, independently, of the stator side. The fundamental steady-state equations for the DFIG are given by Eqs. (1) (4) [7] at the fundamental frequency. Higher harmonics, losses in core and windings, and losses in the converter are neglected for simplification. Voltage equations: V s = j S S (1) V r = R R I R + j ( S R ) R. (2) Flux equations: S = L S I S + L M I R ; (3) R = L R I R + L M I S ; (4) where L S = Lo S + L M and L R = Lo R + L M. Eliminating flux linkages using Eqs. (3) and (4), we have V S = j S (L S I S + L M I R ) ; (5) V R = R R I R + j s S (L R I R + L M I). (6) The equivalent circuit corresponding to Eqs. (5) and (6) is illustrated in Fig. 2. The conventional DFIG architecture in which the GSC is connected in parallel with the grid performs very well at power processing. Utilizing a series grid-side converter (SGSC) in addition to the GSC, which shares the same DC bus as the MSC and is connected in series with the stator winding of the DFIG, it is possible to inject series voltage and phase angle into the grid, similar to the unified power flow controller (UPFC), which has several benefits and provides necessary compensation during abnormal conditions. Fig. 2: Steady-state per phase equivalent circuit of DFIG. This configuration is termed Unified Architecture (UA) and is given in Fig. 3. During normal and abnormal conditions, the GSC (termed as parallel GSC [PGSC]) facilitates the normal power processing capabilities for sub-synchronous and super-synchronous modes of operation of the DFIG. During normal operating conditions, the SGSC facilitates only reactive power capability, and during abnormal conditions, the SGSC injects series voltage and phase angle for necessary compensation required for secure and stable operation. In both normal and extreme conditions, the SGSC provides reactive power injection to the grid [8, 9].The cost of the converter depends on the rating. Hence, the rating of the SGSC must be chosen wisely for economical operation. The rating of the SGSC is taken as 15% of the DFIG stator rating in this work. III. NEW SERIES GSC DFIG ARCHITECTURE Fig. 3: Unified architecture (UA) Fig. 1: DFIG with back-to-back PWM voltage source converters (conventional DFIG). In this section, only static performance, such as injection/absorption of reactive power to/from grid during abnormal/normal conditions, is discussed. For reactive power support, the injection of series voltage must be in phase quadrant with the stator (or line) current. Hence, the injection of series voltage will not change the stator terminal voltage substantially. Stator terminal voltage will always be the addition of grid voltage and series injected voltage. The capability curve for UA, as given in Fig. 3, 117

can be obtained by adding the reactive power from the SGSC. IV. SINUSOIDAL PWM TECHNIQUE USED IN THE GSC The sinusoidal reference wave V ref is created, a modulation method to commutate the switches is required. There are many methods to modulate the reference wave, with the most well known the so-called sinusoidal pulse width modulation (SPWM), which uses a triangular carrier to generate the PWM as illustrated in Fig. 4. In this method, there are two important parameters to define: the amplitude modulation ratio, or modulation index μ, and the frequency modulation ratio p. Definitions are given by μ = V ref max / V tri max (7) p = f T / f S (8) where V ref max and V tri max are the amplitudes of the V ref and V tri respectively. On the other hand, f S is the frequency of the main supply and f T the frequency of the triangular carrier. The modulation method described in Fig. 4. has a harmonic content that changes with p and μ. Furthermore, to avoid sub harmonics, it is also desired that p be an integer. If p is an odd number, even harmonics will be eliminated. If p is a multiple of three, then the PWM modulation of the three phases will be identical. When μ increases, the amplitude of the fundamental voltage increases proportionally, but some harmonics decreases. This method is used in this paper for the grid side converters (GSCs) [10]. V. SIMULINK DIAGRAM For the analysis of real and reactive power capability of the DFIG model, simulation is carried out in SIMULINK block set of MATLAB. The performance of the DFIG models are analyzed for various firing angles and modulation indexes of the grid side converters (GSCs). The DFIG model connected to grid system and P-Q load is given in Fig. 5. The conventional DFIG with the parallel grid side converter (PGSC) is given in Fig. 6. This consists of an asynchronous machine from which rotor winding are tapped and connected to low frequency converter called rotor side converter (RSC). This delivers dc voltage to the DC link capacitor, the capacitor acts as the source to the inverter called the grid side converter (GSC) which synchronize the voltage from the rotor to the grid. DFIG with both parallel grid side converter (PGSC) and series grid side converter (SGCS) is given in is given in Fig. 7. Fig. 4: Sinusoidal PWM technique. The only modification is the addition of one more inverter in series with converter-inverter circuit. This also takes the input from the DC link capacitor. Fig. 5: Simulink model of DFIG 118

Asian Power Electronics Journal, Vol. 4, No.3 December 2010 Fig. 6: DFIG with PGSC (conventional DFIG) Fig. 7: DFIG with PGSC and SGSC (Unified Architecture) VI. SIMULATION RESULTS The DFIG was modeled in simulink to analyze the power system parameters such as real power and reactive power. The firing angle of the rotor side converter (RSC) is controlled to vary the real and reactive power of the DFIG models. The case study for the reactive power capability of DFIG models is illustrated. Case 1: The DFIG with parallel grid side converter (conventional DFIG). Case 2: The DFIG with parallel and series grid side converter (UA).For various modulation index (μ) of the both PGSC and SGSC. The comparison of both the DFIG models is illustrated. Case 1: Conventional DFIG The real power variation is almost constant for the firing angle (alpha) between10º to 80º and the real power increases as alpha is varied from 90º to 180º(operating region). The variation of the real power with firing angle (alpha) is plotted in Fig. 8a.The reactive power is almost constant for the firing angle between10º to 80º and starts increasing in negative direction from 90º to 180º. The variation of reactive power with alpha is given in Fig. 8b. The reactive power varies as the load to the system is varied. According to the load added the reactive power supply to grid is varied. The variation of reactive power with load is traced in Fig. 8c.The reactive power does not drastically vary with wind velocity. It is almost constant throughout the operating region. So we can take it as fixed speed operating system. The variation of reactive power with wind velocity is as in the Fig.8d. the plot between the real and reactive power for variation of alpha is known as the capability curve (P-Q curve) of the DFIG machine. The capability curve of the DFIG is shown in Fig. 8e. The 3D view of the variation of real and reactive power of the DFIG machine with firing angle alpha is presented in Fig. 8f. 119

Fig. 8 a: Alpha Vs. real power Fig.8 b: Alpha Vs. Reactive power Fig. 8f: 3D view of real and reactive power Vs. Alpha Case 2: Unified Architecture (UA) The real power variation is almost similar to that of the conventional DFIG. The variation of the real power with firing angle (alpha) is plotted in Fig. 9a.The reactive power production trace as shown in Fig. 9b, is similar to as the convention al DFIG, but the reactive power production is higher then compared to the conventional DFIG. The reactive power varies as the load to the system is varied. As shown in Fig. 9c, when the load is added to the system the reactive power supply to grid is varied. The reactive power does not vary too much with wind velocity in the operating region as in the Fig. 9d. The capability curve of the DFIG is shown in Fig. 9e. The 3D view of the variation of real and reactive power of the DFIG machine with firing angle alpha is dissipated in Fig. 9f. Fig. 8c: Reactive power Vs. load Fig. 9a: Alpha Vs. real power, Fig. 8d: Reactive power Vs. wind velocity Fig. 9b: Alpha Vs. Reactive power 120 Fig. 8e: P-Q curve Fig. 9c: Reactive power Vs. load

Asian Power Electronics Journal, Vol. 4, No.3 December 2010 There is no considerable increase in the reactive power capability of the UA, when the modulation index (μ) of SGSC is varied from 0.7 to 0.9. So it is enough that the modulation index (μ) of the PGSC is varied, the reactive power capability of the UA is varied. Fig. 9d: Reactive power Vs. wind velocity When we compare the performance of the DFIG models, the real power delivery of both the machines are the same in the operating region. The reactive power delivery of the UA is more than conventional DFIG in the operating region. The capability curve (P-Q curve) is extended for UA than conventional DFIG. The plots are shown in Fig. 11a, Fig. 11b, and Fig. 11c. Fig. 9e: P-Q curve Fig. 11a: Alpha Vs Real Power Fig. 9f: 3D view of real and reactive power Vs. Alpha A. Enhancement of reactive power capability In this case study the variation of reactive power capability of UA is demonstrated with variable modulation index (μ). The reactive power capability of UA is observed by keeping the modulation index (μ) of SGSC at constant value (for a value of 0.8) and the modulation index (μ) of PGSC is varied from 0.7 to 0.9, the graph is illustrated in Fig. 10. The reactive power capability of the DFIG increases as the modulation index (μ) of the PGSC increases. Fig. 11b: Alpha Vs Reactive Power Fig. 11c: P-Q curve VII. CONCLUSION Fig. 10: Reactive Power Vs Alpha for Various μ of PGSC The real and reactive power capability of the DFIG model is analyzed for various firing angles and modulation indexes of the grid side converters (GSCs). The reactive power production is improved as the modulation index is increased. The simulation demonstrates the enhanced reactive power capability of the UA. 121

VIII. APPENDIX Parameters of simulated DFIG Rated power 1.5 MW Stator Voltage 575 V Rs (stator resistance) 0.0071 p.u Rr (rotor resistance) 0.005 p.u (referred to stator) Ls (stator inductace) 0.171 p.u Lr (rotor inductance) 0.156.p.u. (referred to stator) Lm(magnetizing inductance) 2.9 p.u. Number of pole pairs 3 Inertia constant 5.04 VII. REFERENCES [1] Global Wind Energy Council, available at: http://www.gwec.net. [2] A. Tapia, G. Tapia, J.X. Ostolaza and J.R. Saenz, Modeling and control of a wind urbine driven doubly fed induction generator, IEEE Trans. Energy Conversion, Vol. 18, No. 2, June 2003, pp. 194 204. [3] K. Mustafa and J. V. Milanovic, Reactive power control strategies for DFIG-based plants, IEEE Trans. Energy Conversion, Vol. 22, No. 2, June 2007, pp. 389 396. [4] T. Lund, P. Sørensen and J. Eek, Reactive power capability of a wind turbine with doubly fed induction generator, Wind Energy, Vol. 10, No. 4, July/August 2007, pp. 379 394. [5] A. Peterson, Analysis Modeling and Control of Doubly- Fed Induction Generators for Wind Turbines, Ph.D. Thesis, Chalmers University of Technology, Goteborg, Sweden, 2005. [6] Bharat Singh and S. N. Singh Reactive Capability Limitations of Doubly-fed induction generator, Electric Power Components and Systems, Vol. 37, No. 4, 2009, pp. 427 440. [7] Boldea, Variable Speed Generators, Boca Raton, FL: CRC Press, 2006. [8] Singh, V. Emmoji and S. N. Singh, Performance evaluation of series and parallel connected grid side converters of DFIG, IEEE PES General Meeting 2008, Pittsburgh, PA, 20 24 July 2008. [9] Akhmatov Variable-speed wind turbines with doubly-fed induction generator part 1: Modelling in Dynamic Simulation Tools, Wind Eng., Vol.26, No. 2, March 2002, pp.85-108. [10] Muhammad h. Rashid, Power Electronics Handbook, University of Florida, 2003. BIOGRAPHIES V. Sumitha received the Undergraduate Degree in Electrical Engineering Pondicherry engineering college in 2003 and pursuing her M.Tech in the same college. Her field of interest is power systems, enhancement of reactive power of DFIG. R. Gnanadass received the Undergraduate Degree in Electrical Engineering and the Masters degree in Power Systems Engineering with Distinction in 1991 and 1993, respectively. He has obtained the Ph.D. degree in the Department of Electrical & Electronics Engineering, Pondicherry Engineering College, Pondicherry, India in July 2005. He is working as a teaching faculty in Pondicherry Engineering College since 1996. He was with the Department of Electrical and Computer Engineering, Iowa State University, Ames, USA from March 2007 to March 2008 to carry out his Postdoctoral studies under BOYSCAST fellowship sponsored by Department of Science and Technology, Government of India. He published 30 research articles in the journals. His field of interest is power system privatization, reactive power pricing and management, voltage stability, concepts of power system restructuring and optimization problems. 122