Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Similar documents
Impact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

IEEE sion/1547revision_index.html

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Hybrid Islanding Detection Method for Distributed Generators

Proposed test procedure for the laboratory characterisation of gridconnected

Anti-IslandingStrategyforaPVPowerPlant

ECE 528 Understanding Power Quality

E N G I N E E R I N G M A N U A L

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Islanding Detection Method Based On Impedance Measurement

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Grid Converters for Photovoltaic

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

An experimental Study of an Improved Active Frequency Drift Anti-Islanding Method for PV Application

Inverter-Based Resource Disturbance Analysis

Table of Contents. Introduction... 1

Generation Interconnection Requirements at Voltages 34.5 kv and Below

EE Grid-Tied PV Systems. Y. Baghzouz Spring 2011

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Automatic Phase-Shift Method for Islanding Detection of Grid-Connected Photovoltaic Inverters

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Connection Impact Assessment Application

Renewable Energy Systems

Protective Relaying for DER

POWER QUALITY AND SAFETY

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

IEEE Major Revision of Interconnection Standard

Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications

Southern Company Interconnection Requirements for Inverter-Based Generation

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

Islanding Detection Techniques for Distributed Energy Resources-Review

Technical Interconnection Requirements For Transmission Voltage Customers for Service at 60,000 to 287,000 Volts R XX

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Testing Advanced Photovoltaic Inverters Conforming to IEEE Standard 1547 Amendment 1

Non-detection zone of LOM protection for converter connected wind turbines

The Connecticut Light and Power Company

REACTIVE POWER BASED ANTI-ISLANDING SCHEME FOR SYNCHRONOUS DISTRIBUTED GENERATORS

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Implementation of Revised IEEE Standard 1547

A Hybrid Anti-Islanding Method for Inverter-Based Distributed Generation

Impact Assessment Generator Form

1200 MW Fault Induced Solar Photovoltaic Resource Interruption Disturbance Report

TEST REPORT AS :2005 and AS :2005 Grid connection of energy systems via inverters Grid protection requirements

IEEE sion/1547revision_index.html

Small-scale PV Inverters EEA Conference, Wellington. Bill Heffernan, Patrick Chen and Ankur Mishra June 2016

Public Consultation on the Regulatory Framework for Small Scale Grid Connected Solar PV Systems Standards Technical Standards

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

IEEE Std Bulk System Opportunities from New Distributed Energy Resource Interconnection and Interoperability Standards

Grid Code 2015 for Small Scale Distributed Generation (SSDG) Net Metering Scheme Version June 2017 Central Electricity Board

DER Ride-Through Performance Categories and Trip Settings Presentation at PJM Ride-Through Workshop, Philadelphia, PA, October 1-2, 2018

EVALUATION OF ANTI-ISLANDING PROTECTION SCHEMES

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

DYNAMIC VOLTAGE RESTORER FOR VOLTAGE SAG MITIGATION IN OIL & GAS INDUSTRY

Project acronym: Multi-island

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Inverter Source Requirement Document of ISO New England (ISO-NE)

HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES

A Novel Grid Connected PV Micro Inverter

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

FNN comments on NC HVDC submitted to ENTSO E

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online):

Technical Requirements For Generation Connected to The ODEC System

A New Islanding Detection Method Based On Wavelet-transform and ANN for Inverter Assisted Distributed Generator

Fundamentals of Grid Connected Photo-Voltaic Power Electronic Converter Design

Delhi Technological University (formerly DCE) Delhi-42, India

HOOSIER ENERGY REC, INC. Requirements for Connection of Generation Facilities. to the HE Transmission System

Utility Interconnection and System Protection

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry

Wind Power Facility Technical Requirements CHANGE HISTORY

each time the Frequency is above 51Hz. Continuous operation is required

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana

APS M1P Single-phase Micro-inverter Installation and User Manual

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Form B. Connection Impact Assessment Application Form Distribution System

ISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION. Saurabh Talwar

Rapid Backup Power Solution Guide with Stabiliti PCS

Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid

Programmable Grid Simulator THE POWER TEST EXPERTS

Transcription:

Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA

Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std 1547 1547-1 through 1547-8 Anti-islanding Passive methods Active methods Islanding tests on local inverters

Publication Year: 2003

IEEE Std. 1547 scope and purpose Scope: The standard establishes criteria and requirements for interconnection of distributed resources (DR) with electric power systems (EPS). Purpose : The document provides a uniform standard for interconnection of distributed resources with electric power systems. It provides requirements relevant to the performance, operation, testing, safety considerations, and maintenance of the interconnection.

Interconnection System Response to Abnormal Voltages

Interconnection System Response to Abnormal Frequencies

Maximum Harmonic Current Distortion

Synchronization Parameter Limits for Synchronous Interconnection

Maximum Voltage Distortion for Synchronous Machines

Expansion of IEEE Std. 1547 (http://grouper.ieee.org/groups/scc21) 2011 1547.8 Recommended Practice for Establishing Methods and Procedures that Provide Supplemental Support for Implementation Strategies for Expanded Use of IEEE Standard 1547 Pending

Medium Voltage Standard in Germany (10 kv-110 kv)

Medium Voltage Standard in Germany (10 kv-110 kv)

Medium Voltage Standard in Germany (10 kv-110 kv)

Inverter Response to Power Outage - Test Islanding occurs when the disconnected part of the power network is sustained by the connected PV systems for a significant period of time. Islanding is not desirable for several reasons: Creation of a hazard for utility line workers by touching a line that is supposed to be de-energized, lack of control over voltage and frequency in the island. Interference with restoration of normal service.

Expected inverter response PV inverter manufacturers market inverters that are expected to meet current interconnection standards (i.e., IEEE Std. 1547): They are expected to disconnect within 10 cycles if the voltage drops below 50% or rises above 120% of its nominal value. disconnect within 10 cycles if the supply frequency drops below 59.3 Hz or rises above 60.5 Hz. disconnect within 2 seconds cycles If the voltage drops to a value between 50%-88%, disconnect within 1 second if the voltage rises to a value between 110%-120% of the nominal value.

Inverter islanding detection Standard protection of grid-connected PV systems consists of four relays that will prevent islanding under most circumstances. over-voltage relay, under-voltage relay, over-frequency relay, under-frequency relay. However, if the local load closely matches the power produced by the inverter, the voltage and/or frequency deviations after a power outage may be too small to detect, i.e., fall within the non-detection zone. In this case, additional schemes are required to minimize the probability of an island to occur.

Voltage and frequency deviations Let the ratio of P S /P D = α, and Q S /Q D = β. Before disconnect, P (1 ) V / D 1 V ' V 1 2 R After utility disconnect, Q D 2 (1 ) V / L 1 ' 1

Possible Cases Case A: P S > 0 and Q S > 0: The voltage decreases. The frequency depends on the values of α and β. Case B: P S > 0 and Q S < 0: Both the voltage and frequency decrease. Case C: P S < 0 and Q S > 0: Both the voltage and frequency increase. Case D: P S < 0 and Q S < 0: The voltage increases. The frequency depends on the values of α and β. Case E: P S = 0 and Q S 0: The voltage remains constant, while the frequency changes (decreases if Q S < 0 or increases if Q S > 0). Case F: P S 0 and Q S = 0: The frequency remains constant, while the voltages changes (increases P S < 0 or decreases if P S > 0). Case G: P S = 0 and Q S = 0: Both the voltage and frequency remain constant.

Common Active Anti-Islanding Techniques Voltage harmonic monitoring: inverter monitors voltage total harmonic distortion and shuts down if this parameter exceeds some threshold. Phase jump detection: phase between inverter's terminal voltage and its output current is monitored for sudden jumps. Slide-mode frequency shift: the voltage-current phase angle of inverter is made a function of system frequency. Impedance measurement: perturbation periodically applied to inverter current. This will force a detectable change in voltage if the utility voltage is disconnected. Active frequency drift: inverter uses a slightly distorted output current to cause the frequency of the voltage to drift up or down when utility is disconnected.

PV System A: 18 kw Fixed Array (installed in 1999) Inverter Manufacturer: Trace Technologies Inc., Rating: 30 kva, 120/208V, 3-Phase. Anti-islanding technique for critical case: unknown

Schematic diagram of Test Circuit

Test Procedure and Apparatus Connect the transient recorder, load bank, and meters for reading current or power flow into the load and utility grid as shown in Figure. Adjust the load bank to the desired fraction of load relating to generated power. Open the utility disconnect while recording the voltage and current waveshapes. Repeat the two steps above for different generation-load power mismatch levels.

PV System A Switching Events Event No. Case P S (kw) P D (kw) Q S = -Q D (kvar) A.1 D -9.8 14.8-0.8 A.2 B 4.9 15.1-0.9 A.3 E 15 14.9-0.8 Case B: P S > 0 and Q S < 0: the voltage decreases and frequency 0. Case D: P S < 0 and Q S < 0: The voltage increases, and frequency 0. Case E: P S = 0 and Q S < 0: The voltage remains constant, and frequency 0.

Event A.1 (α = -0.66, β = -1)

Event A.2 (α = +0.32, β = -1)

Event A.3 (α 0, β = -1)

PV System B: 25 kw 2-Axis Tracking (installed in 2003) Inverter Manufacturer: Advanced Energy Systems, LTD Inverter Rating: 30 kva, 120/208V, 3-Phase. Anti-islanding technique for critical case: unknown

PV System B Switching Events Event No. Case P S (kw) P D (kw) Q S = -Q D (kvar) B.1 D -4.7 20.3-1.2 B.2 B 4.7 20.3-1.3 B.3 E 0.1 20.4-1.2

Event B.1 (α = -0.26, β = -1 )

Event B.2 (α = +0.26, β = -1)

Event B.3 (α 0, β = -1)

Test Summary Both systems shut down in less than 5 cycles after the utility outage in compliance with the Interconnection standard that allows up to 10 cycles. The over-voltage and under-voltages relays isolated the inverter when there was mismatch between the PV power and local load power. The under-frequency relay isolated the inverter when there was a match between the PV power and local load power. Although small, the reactive power generated by both inverters will ultimately drive the frequency of the islanded system to zero, thus triggering the under-frequency relay under all resistive load conditions. An adjustable reactive load (in addition to the resistive load) would be needed to match both real and reactive powers and test for islanding under zero deviation in both voltage and frequency.

SIMPLE TEST ON 2 KW PV SYSTEM PV Array Size: 2 kw (peak) DC-side measurement AC-side measurement Response to an overvoltage ( V < 1.2 pu) Response to a large overvoltage (V > 1.2 pu)

DC-SIDE VOLTAGE AND CURRENT The inverter utilizes the Perturb-and-Observe method for MPPT. The voltage is perturbed by nearly 4 V, or 1.5% of the nominal value every 2 seconds.

AC-SIDE VOLTAGE AND CURRENT The AC current THD measures nearly 4% (the limit is 5%).

INVERTER RESPONSE TO 14% OVERVOLTAGE The inverter shut down after 56 cycles. The inverter is in compliance with IEEE Std. 1457 which allows up to a maximum of 60 cycles for 1.1 < V < 1.2 p.u.

INVERTER RESPONSE TO 33% OVERVOLTAGE The inverter shut down within 8 cycles. The inverter is in compliance with IEEE Std. 1457 which calls for a maximum of 10 cycles for V > 1.2 p.u.

Break!