Multilin DGT. Distributed Generation Trip Control Fast & Wireless Trip of Distributed Generators. Control. Advanced Communications

Similar documents
SEL Serial Radio Transceiver. The industry-recognized standard for reliable, low-latency wireless communications

CONTROL MICROSYSTEMS SCADAWave Radio Transceiver. Hardware Manual

SPECIAL SPECIFICATION 6744 Spread Spectrum Radio

Accutech GP10. Wireless gauge pressure field unit

Accutech AP10. Wireless absolute pressure field unit

SPECIAL SPECIFICATION 1806 Spread Spectrum Wireless Modem

The wireless alternative to expensive cabling...

RM24100A. Introduction. 1 Features. 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE compliant) Operating Manual English 1.

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

RM24100D. Introduction. 1 Features. 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE compliant) Operating Manual English 1.

Reason RT431. GE Grid Solutions. GPS Precision-Time Clock. Precise Time Synchronization. Compact Design. Hardened for Industry. Time Synchronization

Accutech AM20. Wireless acoustic monitor field unit

Accutech DP20. Wireless differential pressure field unit

Quick Start Guide: FLEX-RP-B/FLEX-RP-B-LL. Connect Battery. Warnings

Wireless Interface RAD-ISM-900-SET-BD-BUS Two-way (point-to-point) Monitoring and Control with Expandable I/O Options User Manual

Wireless Dual Discrete Input Transmitter Series XYR 5000, Model WW59x Specifications - Americas

Accutech FL10. Wireless float level field unit

SEL-3060 Ethernet Radio Data Sheet

SCADA and Telemetry Solutions. SCADALink IO900. Modular Wireless I/O System. User Manual Version V1.3 for SCADALink IO900 BENTEK SYSTEMS LTD

RM24100A. *Maximum transmit power output levels and local radio frequency regulator bodies must be obeyed in the country of operation.

PRODUCT SPECIFICATION AND MODEL SELECTION GUIDE

1 INTRODUCTION ORDER CODE / INFORMATION

The wireless alternative to expensive cabling...

RM24100D. Introduction. Features. 2.4GHz 100mW RS232 / RS485 / RS422 DSSS Radio Modem (IEEE compliant) Operating Manual English 1.

Preliminary. DN-900 Series. 900 MHz Wireless Serial Modems

Preliminary. RF Data Transmission Rates 38.4, 115.2, 200 and 500 kbps

Wireless Acoustic Transmitters Series XYR 5000, Model WN571 Specifications - Americas

Accutech RT10. Wireless RTD temperature field unit

21R14A Receiver 14 Control/1 Alarm/1 Safety relays 120 VAC Power Supply

Wireless Analog/Digital Link NEMA 4x Transmitter/DIN-rail Receiver Set

CL4790 HARDWARE INTEGRATION GUIDE VERSION 3.0. Americas: Europe: Hong Kong:

Accutech TC10. Wireless thermocouple temperature field unit

Wireless Temperature Transmitters Series XYR 5000, Model WT5xx/WT5xxR/WT5xxT Specifications - Americas

SOUTHERN AVIONICS COMPANY. SE125 Transmitter. SE125 Transmitter 1-1

The wireless alternative to expensive cabling...

USER'S MANUAL. Model : K

Specification Sym Notes Minimum Typical Maximum Units 900 MHz Operating Frequency Range MHz

Remote Site Monitoring

Operations Manual Edition 3.1

SEL Radio Accessories Guide

Wireless Base Radio. Wireless Transmitters

The wireless alternative to expensive cabling...

MAXI Remote Location Kit MRLK 900 Installation and Configuration Manual

SEL Radio Accessories Guide

IT-24 RigExpert. 2.4 GHz ISM Band Universal Tester. User s manual

SPECIAL SPECIFICATION 6574 Low Power Wireless Modem

Wireless Communications Module Stand-Alone HE200WCM910 and SmartStack HE800WCM900 / HE-WCM900* * HE- denotes plastic case.

DN-90 Series. 900 MHz Wireless Serial Modems

DNT900. Low Cost 900 MHz FHSS Transceiver Module with I/O

AcuMesh Wireless RS485 Network. User's Manual SOLUTION

Wireless Multi Discrete Input Transmitter Series XYR 6000, Model STXW500 Specifications

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

Airmux-400 Broadband Wireless Multiplexer

Trio K-Series. License-free serial data radio KR900 KR240 KP900 KP240 KB900 KB240

0.0 FREEWAVE Radios:

Four Reasons. To Go Wireless NL900S NL6000 NL900 NL5500. Wireless Highspeed Ethernet Transceiver. VHF/UHF Modem

MODEL WAVE BRIDGE (ST-97) WIRELESS BRIDGE

SF Series. 900 MHz Wireless Switch Follower/Remote Control Receiver (with On-Board 10-Amp Relays) Typical Applications

TM1600. Circuit Breaker Analyzer System

CBCT TM CIRCUIT BREAKER COIL TESTER

A01-eNETL2TUV_Manual_RevH.doc. GE MDS enetl2t/u/v Manual P/N A01 Rev H

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

Mobile Activation Case

Landis+Gyr. S4e MFMM Cellnet User Manual. Bulletin Revision A. DOCUMENT HISTORY Bulletin:

GPNP Inc. NT384 NT1 User Manual. Revision /6/2002. Information in this guide is subject to change without notification.

TOSHIBA International Corp

Reason RT430/RT434. GE Grid Solutions. GNSS Precision-Time Clocks. Precise Time Synchronization. Flexible Design. Hardened for Industry.

SureCross DX80 FlexPower EZ-LIGHT Node with Integrated Battery

CL4490 HARDWARE INTEGRATION GUIDE VERSION 1.0. FCC Notice.

FREEWAVE Radios:

Architectural/Engineering Specification for a. Microwave Perimeter Intrusion Detection System

DNT2400. Low Cost 2.4 GHz FHSS Transceiver Module with I/O

MDS SD4 Software-Controlled Digital Communications Firmware Release 1.x.x

Operations Manual for RFExtender Setup

Quick Start Guide. ELPRO 905U-L-T Wireless I/O Transmitter Unit. man_905u-l-t_quickstart_v1.9.doc

Accutech AI10 & AV10. Wireless multi-input field unit

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

RECTANGULAR RAPID FLASHING BEACON WITH LARGE LED ARRAYS TAPCO RRFB-XL : Solar Powered; Extra Large LED Arrays, Wirelessly Synchronized

Ambient Level Controller

COMMPAK I/O8. Wireless On/Off Control USER MANUAL

DNT90MC DNT90MP. Low Cost 900 MHz FHSS Transceiver Modules with I/O

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

Quick Start Guide. ELPRO 905U-L-T Wireless I/O Transmitter Unit. man_905u-l-t_quickstart_v1-7.doc

Getting Started with TrangoLink

Low Loss Combiner LLC-1900-IN DATA SHEET. Overview

Improve asset protection and utilization

ACUMESH - WIRELESS RS485 NETWORK KEY FEATURES ACUMESH - WIRELESS METERING SYSTEM

Accutech BR10. Wireless base radio

TABLE OF CONTENTS APPENDIX A... 8 APPENDIX B... 9 APPENDIX C... 12

X-Band Redundant LNA Systems

Product catalog. May Where any application finds its wireless solution L E X Y C O M T E C H N O L O G I E S, I N C

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O PRODUCT INFORMATION B&B ELECTRONICS

3500/64M Dynamic Pressure Monitor

JBus/Modbus Communication Card

INSTALLATION and OPERATION INSTRUCTIONS. FOR FiberLink BI-DIRECTIONAL AMPLIFIER WITH DIVERSITY MW-FBDA-800AB-50W-DIV

PACSystems* RX3i IC695MDL765

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Wireless Antenna Installation Guide

Guide. Installation. Wilson Electronics, Inc. In-Building Wireless Amplifi er. Contents:

CAT-1 TM Transmission Line Monitoring Systems

Transcription:

Multilin DGT Distributed Generation Trip Control Fast & Wireless Trip of Distributed Generators The desire for green power and rapid developments in renewable energy sources are driving the growth of distributed generation. Many power distribution companies are now encouraging small power producers to interconnect to the utility grid. As Distributed Generation (DG) becomes more prevalent, DG interconnection to the utility network requires an affordable, reliable, and high speed solution that can prevent power from being fed back to the grid during undesirable situations, such as power line maintenance, electrical faults, etc. In the event of a fault, the Distributed Generator needs to disconnect from the grid prior to the reclosing operation of the utility substation breaker. The Multilin DGT is a wireless transfer trip solution that enables fast and secure disconnect of multiple distributed generators from the electrical power system. The Multilin DGT delivers a cost effective and long range transfer trip capability for enhanced safety, utmost reliability and maximum asset protection. Key Benefits Cost-effective, wireless and fast transfer trip solution Transfers trip and status confirmation faster than standard breaker reclose time Reliable and secure long distance transfer trip to multiple Distributed Generators Extremely resistant to interference due to frequency hopping spread spectrum technology Packaged & Engineered system tested to industry standards Applications Ideal for applications that require transferring of trip signals from Power Distribution Utility Substations or Recloser Sites to multiple (1-7) Distributed Generators interconnected to the distribution grid. Suitable for direct outdoor application Control Transfer trip issued from up to 2 locations on the feeder - substation and recloser site Point to Multipoint: transfer trip issued to maximum 7 Distributed Generation sites Trip status of DG sites transferred back to utility substation and recloser site Advanced Communications Secure communication with frequency hopping spread spectrum technology High speed transfer trip in 30 msec ong distance 30 mile range with repeater Reliable communication with 32 bit CRC icense free operation in the 902-928 ISM band (N. America) 100% tested for RF performance -40 C to +75 C High sensitivity -106dBm @ 1x10-6 bit error rate EnerVista Setup Software Separate setup software based on user application Utility & Distributed Generator owner Single click option for quick connect to devices provides real-time feedback on device status Single step configuration for DG owner

DGT Distributed Generation Trip Control Overview The desire for green power and rapid developments in renewable energy sources are driving the growth of distributed generation. Many Power Distribution Companies are now encouraging small power producers to interconnect to the Utility grid. Independent power producers are typically customers who install small scale generating units up to 10 MW in size to offset their load and sell excess power to the local distribution Utility for grid support and reliable supply. As Distributed Generation (DG) becomes more prevalent, DG interconnection to the Utility network requires an affordable, reliable, and high speed solution that can prevent power from being fed back to the grid during undesirable situations, such as power line maintenance, electrical faults, etc. In the event of a fault, the Distributed Generator needs to disconnect from the grid prior to the reclosing operation of the Utility Substation breaker. The following factors determine the need for automatic Distributed Generation disconnect from the power grid when the substation breaker trips open: Safety Hazard: A power line assumed to be disconnected remains energized. This can be unsafe for the public, line personnel working on the feeder, etc. Distributed Generation Damage: If a main Utility breaker closes out of sync, the Distributed Generator can be damaged Customer equipment damage: Frequency and voltage provided to customers can vary significantly and damage apparatus Figure 2: Wireless network that allows transfer trip from point to multi-point. GE Energy is the industry leader in introducing a revolutionary and innovative Distributed Generation disconnect solution that is highspeed, cost-effective, wireless, long range, reliable and secure. Transfer Trip Control System There are three types of Distributed Generation Trip Control (DGT) devices available for a wireless transfer trip system. In a point-to-multipoint system, a first control device is required at the Utility Substation, a second control device between the substation and the generation site, and a third control device at each Distributed Generation site. A point-to-multipoint system can support up to 7 distributed generation sites. However, in a point-to-point system, one control is installed at the Utility Substation and a second control at the Distributed Generation site. A point-to-point system supports one remote generation site. Each DGT control device location is based on its respective function. The substation unit is required to transfer trip signals from the Utility Substation, the downstream control unit is needed to repeat the Substation trip signal to each DG site, and the DG site control device is needed to receive the trip signal from the substation and initiate the disconnect of the local breaker. The following three controls complete the Distributed Generation Trip (DGT) Control network: DGT-U A DGT-U is a trip control device implemented at the Utility Substation for transferring wireless trip signals to remote DG sites (up to 7 sites) and receiving status notification back from each DG site after a trip operation has been completed. The transfer trip timing is 30 milliseconds. There is an option to locate a second DGT-U control at a recloser site on the distribution feeder. In this instance, the recloser sends a trip command to the remote DGT-D unit(s). The DGT-D then responds by initiating a trip and sending status confirmation back to the DGT-U at the recloser site and the DGT-U at the Substation. Figure 1: Distributed Generator feeds a faulted grid in the absence of a transfer trip solution. DGT-R A DGT-R is a Repeater device installed at or near the Utility Substation for coordinating wireless communication among the Utility and its various generation site(s). In a point to multipoint system, all communication is 2 GEDigitalEnergy.com

DGT Distributed Generation Trip Control coordinated through the DGT-R unit in order to achieve a maximum distance of 30 miles and communicate with multiple generation sites. DGT-D A DGT-D is a trip control needed at the Distributed Generation site for receiving trip signals from the Utility Substation and sending a wireless status notification back to the Substation after a trip operation has been performed. The disconnect status transmit timing is 300 milliseconds. The control devices in a DGT network continuously map data. The DGT-U and the DGT-D control units constantly transmit and receive an event (trip status =1) or a no event (no activity = 0) data between themselves via the DGT-R. Distributed Generation Disconnect Sequence and Timing The following steps describe how the application of DGT Controls enable safe and timely Distributed Generator disconnect from the Utility grid: Fault at power distribution line [1] Substation relay detects the fault [2] Relay triggers DGT-U Control device at the substation to transfer a trip signal via Repeater control device (DGT-R) to remote distributed generation site [3] Trip signal transferred in 30 milliseconds from DGT-U to the remote site DGT-D Control unit at Distributed Generation site receives trip signal [4] DGT-D triggers on site disconnect device to trip Disconnect device (breaker, switch, etc) at DG site disconnects generator from the Utility grid [5] DGT-D Control at DG site transmits status confirmation back to Utility Substation via Repeater device DGT-R [6] Status confirmation transferred in 300 milliseconds from DGT-D to substation DGT-U unit at substation receives status confirmation info [7] Wireless Technology The DGT control provides highly reliable longrange communication over up to 30 miles. The DGT uses frequency hopping spread spectrum radios that operate in the license free spectrum between 902 and 928 MHz. The radios hop between 128 channels with a bandwidth of 130 khz. The frequency hopping technique makes 1 2 3 4 Fault Occurs Fault detected DGT-U Transfers Trip Signal DGT-D Receives Trip Signal the radios extremely resistant to interference. Frequency hopping also establishes a high level of security because data transmission occurs on a variety of frequencies in a random pattern. In addition, the DGT uses a 32-bit CRC algorithm to further insure security and reliability of data. The DGT s are able to operate in a point to multipoint configuration and transmit digital status among themselves at extremely high speeds. GE Energy s unique wireless data transmission technology allows transfer trip signals to be sent and received by the end sites in 30 milliseconds. While the DGT radios provide very robust wireless communication, radio line of site is needed to insure maximum range and performance. This path is achieved by mounting the DGT antenna at a suitable height above surrounding terrain and obstructions. Breaker Trips at DG Site Status Confirmation Sent to Substation Status info received in Substation 1 2 3 4 5 6 7 Fault detection Transfer Trip Figure 3: Sequence and timing for isolating a Distributed Generator from a faulted grid. 5 6 7 DGT system Transfer Status Confirmation 30 msec Breaker tripped 150 msec The DGT-U, DGT-R and DGT-D control devices are completely packaged units that include the appropriate DGT transceivers, power supply, necessary input and output terminations, antenna jumper cable and lightning protection in a weather resistant and lockable NEMA 4 enclosure. The only connections required are for primary power, wiring to external devices (where necessary) and external antenna cable. All wiring connections are made within the enclosure leaving no connections exposed to environmental factors. DGT units are designed to be installed in a wall mount or pole mount configuration. GEDigitalEnergy.com 3

DGT Distributed Generation Trip Control ED Indicators Each transceiver in any DGT Control has a set of ED indicators to enable users to observe status of each device and its performance. DGT-U: There are 11 indicators in the DGT-U transceiver. DGT-R: The DGT-R transceiver consists of 3 indicators. DGT-D: The DGT-D transceiver contains 6 indicators. Below are some of the common ED s: The Power ED illuminates when power is applied to the radio The Service ED flashes when a radio alarm condition is detected. The IN ED is lit only when energized in the event of a trip. The ink ED illuminates when the radio has established a connection. EnerVista Software The EnerVista is an industry leading software program that simplifies every aspect of using the DGT Control. The EnerVista software not only provides all the essential tools to configure the DGT devices, it also provides exceptional levels of security in creating the Distributed Generation Trip network and encrypting configuration files for download. For ease of use, there are two versions of the DGT software dependant upon User application. The DGT-Utility software is for the Power Utility Company and the DGT-DG software is for the independent power producer. DGT-Utility Software Using the DGT-Utility software a Utility user builds a DGT network. The software then creates encrypted data files that contain all necessary information and settings for the DGT-R and DGT-U devices. The DGT-Utility software also creates a DGT-D setting file to be sent to the distributed generation owner to authorize their DGT-D device to join the network. Only the utility can add DGT-D devices to a DGT Network. The configuration set up is simple with an online and offline menu available for ease of use. Configuration files are unique to each DGT network. A quick connect button allows the user to easily connect to the selected device. DGT-DG Software The Distributed Generation software allows User to upload a settings file or get diagnostics from a DGT-D control by simply clicking on the menu option. A quick connect button also allows the User to easily connect to the DGT-D device. Enervista aunchpad Enervista aunchpad is a powerful software package that provides Users with all the set up and support tools needed for configuring and maintaining Multilin s DGT Controls. The set up software within aunchpad allows configuring devices in real time by communicating using serial connection or offline by creating setting files to be sent to devices at a later time. Included in aunchpad is a document archiving and management system that ensures critical documentation is up to date and available when needed. Documents made available include: Manuals Brochures Wiring Diagrams FAQ s Help File Figure 4: DGT-Utility creates the setting files for all the devices. 4 GEDigitalEnergy.com

DGT Distributed Generation Trip Control ENCOSURE Enclosure Dimensions: 13.75 H x 11.85 W x 6.5 D (35 x 30.1 x 16.5 cm) Approximate Weight: Humidity: 21 lb. (9.53 kg) Testing: IEEE 1613 INPUT Type Coil resistance: Power draw: INPUT 95% at + 40 C Non-Condensing Dry contact 1400 ohms maximum 400 mw Type Form A-relay (service output is Form B) Contact material: Operate time: Continuous carry: Silver alloy < 10ms 5 A Make & Carry for 0.2s: 30A per ANSI C37.90 COMMUNICATION Frequency: Data transfer rate: Format: 900 MHz 106 Kbps 8 data bits, no parity bit, 1 stop bit atency: Range: Security: Frequency: Sensitivity: POWER SUPPY Nominal DC Min/Max DC: Nominal AC: Min/Max AC: Voltage loss hold up: Voltage withstand: Power consumption: Internal fusing: Interrupt rating: ENVIRONMENT Ambient operating temperature: Ambient storage temperature: 60 msec (round trip) 30 miles 32 bit CRC icense free 902-928 MHz -106 dbm at 1x10-6 Bit error rate 125 to 250 VDC 100/350 VDC 120 to 240 VAC at 50/60 Hz 88/260 VAC at 50/60 Hz >25 ms 30 V above maximum rating 20 to 30 W typical, 60 W maximum Ratings: 2 A/600V AC = 200,000 A DC = 100,000 A -40 C to + 60 C -40 C to + 85 C Humidity: CERTIFICATION < 90% at 40 C, non-condensing ISO: Manufactured under an ISO 9001 registered program CSA: FCC ID: IC ID: IEEE 1547: DGT transceivers are approved for Class1, Division 2 E5MDS-E806 3738A-MDSE80 Enables Compliance Figure 5: Distributed Generation Trip Controls packaged for direct outdoor application GEDigitalEnergy.com 5

1 9 2 3 10 11 4 5 6 7 8 12 13 14 15 16 PWR 6-30 VDC(2A max) + - DGT Distributed Generation Trip Control DGT-U Standard Features DGT-U radio for substation application [A1] Power Supply: 24 VDC, 125 VAC/VDC, 90-375 VDC [A2] 125 VDC relay for trip status output [A3] A3 A4 A1 125 VDC relay for trip status confirmation input [A4] I/O: 1 Input, 8 Outputs ED s: 11 (1 Input, 7 Output, 1 power, 1 link, 1 service) + + - - 24 VDC/2.1A OK 24-28 V SOA POWER SUPPY SDP 2-24-100T NEMA 4 Enclosure N CE Bulkhead lightning arrester with connection for DGT-U antenna feedline [A13] ightning Arrester (nominal breakdown voltage 230 V) ANTENNA CABE A2 PC connection cable: 1 RJ11 to DB9 cable (6 feet) Terminal blocks for field connection Jumper cable for connection from lightning arrester to DGT-U transceiver 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Internal heater: 10 watt POWER SUPPY ANTENNA I/O DGT-U A13 DGT-R Standard Features DGT-R radio for Repeater application [A1] Power Supply: 24 VDC, 125 VAC/VDC, 90-375 VDC [A2] I/O: None ED s: 3 (1 power, 1 link, 1 service) NEMA 4 Enclosure Bulkhead lightning arrester with connection for DGT-U antenna feedline [A13] AN COM1 COM2 PWR INK ightning Arrester (nominal breakdown voltage 230 V) Terminal Blocks for field connection ANTENNA CABE A1 Jumper cable for connection from lightning arrester to DGT-R transceiver Internal heater: 10 watt + + - - 24 VDC/2.1A OK 24-28 V SOA POWER SUPPY SDP 2-24-100T 1 2 3 CE N POWER SUPPY A2 ANTENNA DGT-R A13 6 GEDigitalEnergy.com

1 5 6 7 8 9 2 10 3 11 4 12 13 14 15 16 DGT Distributed Generation Trip Control DGT-D Standard Features DGT-D radio for application at DG Site [A1] Power Supply: 24 VDC, 125 VAC/VDC, 90-375 VDC [A2] 125 VDC relay for trip status output [A3] A3 A4 A1 125 VDC relay for trip status confirmation input [A4] I/O: 1 Input, 8 Outputs ED s: 6 (1 input, 2 output, 1 power, 1 link, 1 service) + + - - 24 VDC/2.1A OK 24-28 V SOA POWER SUPPY SDP 2-24-100T NEMA 4 Enclosure N CE Bulkhead lightning arrester with connection for DGT-U antenna feedline [A13] A2 ightning Arrester (nominal breakdown voltage 230 V) ANTENNA CABE PC connection cable: 1 RJ11 to DB9 cable (6 feet) Terminal blocks for field connection Jumper cable for connection from lightning arrester to DGT-D transceiver 1 2 3 4 5 6 7 8 Internal heater: 10 watt POWER SUPPY I/O ANTENNA DGT-D * Specifications subject to change without notice A13 GEDigitalEnergy.com 7

Ordering To order select the basic model and the desired features from the Selection Guide below: DGT U and D Models Distributed Generation Trip Control DGT * * * Basic Unit DGT U DGT Utility Substation Control DGT D DGT Distributed Generation Site Control Power Supply H 125 V DC / V AC (no internal battery or charger) ; 90-375 V DC 24 V DC (no internal battery or charger) Antenna & Cable 1 6.4 db Yagi Antenna, 50 feet cable, with connectors 2 6.4 db Yagi Antenna, 100 feet cable, with connectors 3 6.4 db Yagi Antenna, 150 feet cable, with connectors 4 6.4 db Yagi Antenna, 200 feet cable, with connectors 5 6.4 db Yagi Antenna, 250 feet cable, with connectors 0 None DGT R Model Distributed Generation Trip Control DGT * * * Basic Unit DGT R DGT Repeater Control Power Supply H 125 V DC / V AC (no internal battery or charger) ; 90-375 V DC 24 V DC (no internal battery or charger) Antenna & Cable 1 7.0 db Omni Antenna, 50 feet cable, with connectors 2 7.0 db Omni Antenna, 100 feet cable, with connectors 3 7.0 db Omni Antenna, 150 feet cable, with connectors 4 7.0 db Omni Antenna, 200 feet cable, with connectors 5 7.0 db Omni Antenna, 250 feet cable, with connectors 0 None GEDigitalEnergy.com IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council. NIST is a registered trademark of the National Institute of Standards and Technology. GE, the GE monogram, Multilin, Flexogic, EnerVista and CyberSentry are trademarks of General Electric Company. GE reserves the right to make changes to specifications of products described at any time without notice and without obligation to notify any person of such changes. GEA-12898(E) English Copyright 2015, General Electric Company. All Rights Reserved. 150210