VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Similar documents
GIS Disconnector Switching Operation VFTO Study

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Tab 2 Voltage Stresses Switching Transients

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

Research Article Ferroresonance Study on the VT in the Karoon 4 Power Plant 400 kv GIS Substation

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY. Approach for Fault Detection in GIS.

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Analysis of Very Fast Transient over Voltages of Transformer in Gas Insulated Substation (GIS) using Wavelet Technique

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

High voltage engineering

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

Modeling insulation in high-voltage substations

Effect of Shielded Distribution Cable on Very Fast Transients

Research Article Resistive Ferroresonance Limiter for Potential Transformers

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Electrical Power and Energy Systems

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

ABSTRACT 1 INTRODUCTION

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Ferroresonance Experience in UK: Simulations and Measurements

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Analyzing and Modeling the Lightning Transient Effects of 400 KV Single Circuit Transmission Lines

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS

Power Quality and Reliablity Centre

New Modeling of Metal Oxide Surge Arresters

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

In power system, transients have bad impact on its

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Do Capacitor Switching Transients Still Cause Problems?

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Power Quality Basics. Presented by. Scott Peele PE

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

G. KOEPPL Koeppl Power Experts Switzerland

Electromagnetic Interference in the Substation Jose up 400/115 kv

Chapter 1. Overvoltage Surges and their Effects

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

TECHNICAL REPORT. Insulation co-ordination

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

ANALYSIS OF VERY FAST TRANSIENT OVER VOLTAGES IN GAS INSULATED SUBSTATION

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

Sources of transient electromagnetic disturbance in medium voltage switchgear

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

URL:

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Frequency Domain Analysis of Capacitor Transient Overvoltages

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Transient recovery voltage analysis for various current breaking mathematical models: shunt reactor and capacitor bank de-energization study

Simulation Study of Voltage Surge Distribution in a Transformer Winding

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Simulation and Analysis of Power System Transients using EMTP-RV

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Applications of PSCAD / EMTDC

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

DEPARTMENT OF EEE QUESTION BANK

Abstract. 1 Introduction

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Transformers connected via a cable Overvoltage protection

Measurements for validation of high voltage underground cable modelling

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

Insulation Co-ordination For HVDC Station

Electric Stresses on Surge Arrester Insulation under Standard and

Overvoltage Protection of Light Railway Transportation Systems

FERRORESONANCE SIMULATION STUDIES USING EMTP

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

Transcription:

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran, Iran ABSTRACT GIS substation due to its wide range of functions in power system due to its high reliability and easier maintenance are considered in the distribution network. For this Purpose in this paper the GIS 132KV substation model is studied[1]. In GIS 132KV with opening and closing the disconnect switch, the VFTO fast transient overvoltage with few nanoseconds forehead time is occurred[7]. This waves is released during the phase conductors and its caused tension in insulators and electrical equipment such as transformers. Transient electromagnetic field has been created, by these waves penetrates to environment by holes between GIS compartments and causes the effect on the electrical equipment and cables. These overvoltages have range about a few hundred MHz frequencies. In this substation the compartments transient voltage and its maximum amplitude at different points for different switching performance is calculated [2]. In this paper the simulations have been conducted with the EMTP software and simulation results are presented. KEYWORDS: GIS substation, Restrike, Switching, VFTO I. INTRODUCTION The gas substations in transmission and distribution networks due to protection from pollution, high reliability, ease of development in substation, need less space have spread widely. Fast transient overvoltages that caused by switching is one of the fundamental problems that comes in this substations. Opening and closing the disconnect switch in compartment caused arc (RESTRIKE) and surge overvoltage. The following arc between the key contacts, surge voltages in conductors is published and with propagation and reflection during the conductor, it will be strengthened [3]. Due to the substantially conductive capacitive property, arc needs 2 to 4 nanoseconds. In this substation many RESTRIKES during switching operations occur. This RESTRIKE caused fast transient overvoltages that have forehead time in the range of a few nanoseconds and high oscillation frequency, that its value is less than the system BIL [1], [2]. This REATRIKE has effect on insulators and may cause FLASHOVER and thus earth error, so we need to reduce the amount of VFTO in GIS substation. Since the measuring these type of overvoltages with high frequencies is very difficult and requires the skill and accuracy as well high costs and expensive equipment, the simulation of VFTO is necessary[3]. These simulations are able to estimate the size of VFTO and its forehead time and its effect on different equipment, etc and it runs easily and correctly under actual GIS model. II. MODELING OF EQUIPMENT A single-line diagram of GIS substation is shown in figure 1: 335 Vol. 5, Issue 2, pp. 335-346

Figure 1: Single-line diagram of 132KV substation This post includes voltage measuring transformers CVT and current measuring transformers CT, overhead transmission lines, cables, XLPE and ground keys and other equipment [4]. To calculate the transient currents, determinate the equivalent circuit of equipment and the sparks path between breaker contacts are essential. In order for modeling the equipment, integrated elements and also distributed line parameters can be used [4]. The surge impedance of the transmission line can be calculated by using the follow equation: In this equation (a) is internal diameter of high voltage bus and (b) is outer diameter of compartments as showed in figure 2: ( ) Figure 2: Internal arrangement of 132KV bus-bar Because transient frequency is high, in the range of KHZ and MHZ, The capacitive property of in transformer is the dominant so in order to modeling them the capacitor is used. In circuit design its value is 2nf. In order to simulation, the worse case is voltage at the end of open cable. Equivalent of equipment in GIS substation are given in table 1: 336 Vol. 5, Issue 2, pp. 335-346

Table 1: Equivalent of equipment in GIS substation Output power lines Incoming power lines The installed transformers Disconnect switch DS Breaker CB Ground keys Arms and distances and spherical containers surge impedance=30ω, wave propagation speed=150, capacitor to ground=400pf surge impedance=30ω, wave propagation speed=180 open close open close CT PT capacitor to ground=2nf surge impedance=72ω, wave propagation speed=1.9 ns, capacity=32 pf, capacitor to ground=25pf surge impedance=72ω, wave propagation speed=0.4 ns Capacitor=50 pf, surge impedance=46ω, wave propagation speed=4.2 ns, capacitor to ground=30pf by transmission line with surge impedance=46ω surge impedance=75ω,, capacitor to ground=50pf capacitor to ground=100pf equivalent to Capacitors=15 pf The arc between contacts of disconnect switch with a 0.5 resistor in series has been modeled [3], [5], [6]. This resistance has a nonlinear function that shows in EMTP. It was a mathematical equation is given below: ( ) is at the time of 1ns is placed. Figure 3 shows the above equation basis of the assumptions [6, 8, and 9]. Figure 3: spark model for studies of VFTO In figure 4 a part of model is showed in EMTP software: 337 Vol. 5, Issue 2, pp. 335-346

III. SIMULATION RESULTS Figure 4: a part of model in EMTP software Order to evaluate fast transient overvoltages caused by switching in GIS132KV substation the 6 below case is considered: 1) By assuming connector generator G1, disconnect switch and circuit breaker is closed, and the Q59 disconnect switch key operated by the same time of breaker performance. 2) Following the first case, after closing circuit disconnect switch key, assuming the closing of an additional bass, CB is acted. 3) With respect to the 1 and 2 after closing the GT1, second generator can be connected to the middle of GIS 132KV, now the condition of 1 can be considered for second generator. 4) With respect to connecting mode of GT2, the second case condition can be considered for that. 5) After the connecting of generators, one of the outputs feeder lines can be connected, this work is done in two steps. CB line through a disconnect switch can be energizing while supply line CB is open. 6) To mode 5, by assuming all of disconnect switch is operated; circuit breaker or the same supply line CB is acted. According to the cases is achieved, to have better comparison of the results, peaks of transient voltage amplitude in switching modes in the different equipment substation is presented in Table 2. 1) VFTO near generator of performance of disconnect switch 2) VFTO near CB of performance of circuit disconnect switch 3) VFTO on both sides of the open breaker 4) VFTO in converter increases For top switching cases, some of equipment has been studied. In order to see the results of cases, the following table was drawn. It showed the maximum amplitude of VFTO: cases switching mode 1 [V] Table 2: maximum amplitude of VFTO switching mode 2 [V] switching mode 3 [V] switching mode 4 [V] switching mode 5 [V] switching mode 6 [V] 1 1.85 - - - - - 2 1.85 - - - - - 3 1.85 1.84 1.7 1.83 1.2 1.85 4 1.5 1.5 - - - - To check these results, the waveforms in the different states can be investigated. For example to comparison the amplitude of VFTO on the sides of CB for switching modes, 5 to 8 waveforms are plotted. According to the figure it can be observed the amplitude of VFTO is dropped in figure 9. 338 Vol. 5, Issue 2, pp. 335-346

Figure 5: VFTO on the sides of CB for switching mode 1 Figure 6: VFTO on the sides of CB for switching mode 2 Figure 7: VFTO on the sides of CB for switching mode 3 Figure 8: VFTO on the sides of CB for switching mode 4 339 Vol. 5, Issue 2, pp. 335-346

Figure 9: VFTO on the sides of CB for switching mode 5 To compare simulation results at position 6 between the cable terminals and the sides of CB the figure 10 can be considered. It is observed from that voltage at the end of cable is reduced in comparison with sides of CB. Figure 10: VFTO on the sides of CB and end of cable at position 6 With performance of all disconnect switch if CB is open from output supply line and its affiliates DS is also open, and then it can be seen that the amount VFTO in increasing converter drastically reduced. By comparison its waveforms with step 2, the decrease of that is observed: Figure 11: VFTO in increasing converter step 2 340 Vol. 5, Issue 2, pp. 335-346

Figure 12: VFTO in Transformer Duo to calculate the overvoltages on the sides of CB, when CB and DS are open, it can showed in figure 13: Figure 13: VFTO on the sides of CB due to openness disconnect switch According to the results it can be seen the amount of overvoltages VFTO due to openness disconnect switch and CB has fallen sharply. Stored charge effects at levels VFTO Stored charge in the unit before switching positions is dependent the design of disconnecting switch and it is usually less than 0.3PU. In order to consider the effect of stored charge levels of switching, this effect can be observed for different loads and achieve waveforms for each load and in this situation evaluate the effect of switching to reduce VFTO for different load. For this purpose by drawing the table 3 the peak of VFTO amplitude on the each part of GIS substation according to the stored charge can be observed and compared the range of its variation with different loads. Results of simulation are given in table 3: Table 3: simulation results of changing the load at high voltage bus Stored charge In high voltage bus VFTO in input Cable is out VFTO on the sides of CB VFTO on the sides of closed DS VFTO on the sides of open DS 0 PU 0.45 1.55 1.3 1.3-1.2 PU -1.4 2 1.57 1.6 1.2 PU 1.36 1.7 1.24 1.26 1 PU 1.8 1.41 1.25 1.25 0.3 PU 0.6 1.41 1.25 1.25 341 Vol. 5, Issue 2, pp. 335-346

VFTO on bus-bar 1.3 VFTO on input of 1.1 transformer 1.57 1.16 It is clear by increasing load from 0.3 to 1.2, maximum amplitude of VFTO on the transformer input is decreased from 1.08 to 1.04, but at the -1.2 PU it observed the value is increased to 1.16. So it is possible by reducing the value of stored charge in to the larger load with positive sign, the amplitude of VFTO on the transformer input be reduce. We can have results for other modes of different substation equipment. As other example the comparison of waveforms for 1.2 PU and 1 PU showed in figure 14 and 15: 1.17 1.04 1.2 1.05 1.3 1.08 Figure 14: VFTO on the input of output cable with stored charge (1.2PU) Figure 15: VFTO on the output cable with stored charge (1 PU) According to figures 16 and 17, amplitude of VFTO on the sides of CB at 1.2 PU in high voltage bus has range about 1 PU. This range of variation at 1 PU is reduced to 0.8. It can be seen by reducing the stored charge this range of variation is reduced. Figure 16: VFTO on the sides of CB with stored charge (1.2PU) 342 Vol. 5, Issue 2, pp. 335-346

Figure 17: VFTO on the sides of CB with stored charge (1PU) To comparison simulation results with stored charge on the sides of closed DS, figures 18 and 19 are presented: Figure 18: VFTO on the sides of closed DS with stored charge (1.2PU) Figure 19: VFTO on the sides of closed DS with stored charge (1PU) It is clear from these figures the range of variation at 1.2 PU is more than 1 PU. Other result is shown in figure from 20 to 23. 343 Vol. 5, Issue 2, pp. 335-346

Figure 20: VFTO on the sides of open DS with stored charge (1.2PU) Figure 21: VFTO on the sides of open DS with stored charge (1PU) Results at input of increasing converter are showed at follow figure: Figure 22: VFTO at input of increasing converter with stored charge (1.2PU) 344 Vol. 5, Issue 2, pp. 335-346

Figure 23: VFTO at input of increasing converter with stored charge (1PU) In figures 24 and 24 the magnitude of VFTO with stored charge is presented: Figure 24: VFTO at bus-bar when the stored charge is 1.2 PU Figure 25: VFTO at bus-bar when the stored charge is 1 PU It is clear from the results; VFTO in substation equipment is reduced specially with stored charge. IV. CONCLUSIONS In this paper we model different parts of GIS 132KV substation by using EMTP-RV software to study fast transient overvoltage VFTO during switching operations. These waves have very low rise time and very high amplitude near 5 PU and that isn t controllable by lightning arrester. In GIS substation, 345 Vol. 5, Issue 2, pp. 335-346

at time of switching with increasing distance from place of switching, the amplitude and frequency is reduced and by increasing speed and switching performance, Number of arc is reduced[8,2]. In this substation model is designed and parameters are chosen. High transient voltage VFTO during different switching operations has been studied. In this simulation VFTO amplitude is less than 2PU so one of the ways to reduce overvoltages VFTO, addition to using a resistor in parallel with switch is using the stored charge [2]. This means that there is no threat due to VFTO and its amplitude is reduced and there is no need to apply any kind of lightning arrester to reducing these overvoltages [5]. As future work to reduce the fast transient overvoltage VFTO, we can use RC filter in circuit and by using resistor in circuit not only will reduce this overvoltages but also its gradient is reduced. REFERENCE [1]. San-Min Yeo and Chul-Hwan Kim Analysis of Transient Overvoltages Within a 245 kv Korean Thermal,Plant Journal of Electrical Engineering & Technology Vol.7 No.3, pp. 297~303,2012 [2]. D.A. Woodford, L.M. Wedepohl, Impact of Circuit Breaker Pre-Strike on Transmission Line Energization Transients, IPST '97, Seattle, pp. 250-253, June 22-26, 1997. [3]. V.V. Kumar, J. Thomas M., M. S. Naidu, VFTO Computation in a 420 kv GIS, High Voltage Engineering Symposium, 22-27 August 1999 Conference Publication No. 467, IEE, 1999 [4]. J.A.Martinez, P.Chowdhuri, R.Iravani, A.Keri, D.Povh, Modeling Guidelines For Very Fast Transients In Gas Insulated Substations, IEEE Working Group on Modeling and Analysis of System Transients, 2005. [5]. V. V. Kumar, J. Thomas M., M. S. Naidu. "Influence of Switching Conditions on the VFTO Magnitudes in a GIS", IEEE Trans. On Power Delivery, Vol. 16, No. 4, October 2001 [6]. D. Povh, H. Schmitt, O. Volcker, R. Witzmann,"Modelling and Analysis Guidelines for Very Fast Transients", IEEE Transactions on Power Delivery, Vol. 11, No. 4, October 1996. [7].M. Stosur, M. Szewczyk, W. Piasecki,M. Florkowski, M. Fulczyk " GIS Disconnector Switching Operation VFTO Study" Modern Electric Power Systems 2010 [8]. Li Q. and Wu M., Simulation Method for the Applications of Ferromagnetic Materials in Suppressing High-Frequency Transients Within GIS, IEEE Transactions on Power Delivery, Vol. 22, No. 3, pp. 1628-1632, July 2007 AUTHOR Shohreh Monshizadeh was born in Kermanshah, Iran. She received her B.S degree from Islamic Azad University-Toiserkan Branch. She is currently M.S student in the Islamic Azad University-South Tehran Branch. 346 Vol. 5, Issue 2, pp. 335-346