CX-100. Installation Instructions. PIR Occupancy Sensor SPECIFICATIONS

Similar documents
with Light Level, Isolated Relay and Manual On features

v3 360 Passive Infrared Line Voltage Occupancy Sensor

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

O ccupancy and Light Level Sensor L ow Vo l tage Ceiling Fixture Mount

LOAD AWG Solid CU Wire Only LINE NEUT FSP-211. High/Low PIR Occupancy Sensor 230 VAC, 50 Hz 1200W max ballast 5E4

CONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology

SELECTABLE MODE HIGH/LOW/OFF PIR FIXTURE INTEGRATED INDOOR/OUTDOOR MOTION/PHOTO SENSOR

High/Low Bay Passive Infrared Occupancy Sensor

Installing the FSP-211 Sensor in Light Fixture

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE WITH BLUETOOTH

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING

ASSEMBLY AND INSTALLATION INSTRUCTIONS

ASSEMBLY AND INSTALLATION INSTRUCTIONS

No: /16 rev. 1 Installation Instructions Instructions d Installation Instrucciones de Instalación UNIT DESCRIPTION

ASSEMBLY AND INSTALLATION INSTRUCTIONS

High Bay Occupancy Sensor for Use with Electronic Ballast HID Luminaires

Eco-$mart, Inc. TOLL FREE:(888) FAX:(941)

Dual Technology Wall Mount Occupancy Sensor

Infrared Wall Mount Occupancy Sensor

Dual Technology Wall Mount Occupancy Sensor

No: /18 rev. 1 Installation Instructions Instructions d Installation Instrucciones de Instalación

DESCRIPTION & OPERATION: PIR OCCUPANCY SENSOR MSWSFSP221B-D FEATURES:

ETC Installation Guide

Occupancy Sensors for High-Bay Applications

STEALTH. STL200 Installation Manual. Specifications: STL200 STL200H STL200HB. Switching Capacity: 8 amps

STEALTH. STL110 Installation Manual. Specifications: STL110 STL110HB STL110H STL110R. Switching Capacity:

2 Pendant Adjustment. Pendant Slider Plate. 3/4 (19mm) IP, (29mm) O.D. Knockouts. 1/2 (13mm) IP, (22mm) O.D. Knockout

3000W multi Pir light controller

Smart Task Motion Activated Task Light Installation Manual

Mini Sensor. Outdoor Motion Sensor. Installation Manual

STL200/277 Installation Manual STL200/277

Dual Technology Ceiling Mount Sensor

CXB Series SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. LED Luminaire TO INSTALL: INSTALLATION INSTRUCTIONS INSTRUCTIONS D INSTALLATION

STL200/277 Installation Manual STL200/277

FSP-211 DIGITAL HIGH/LOW PIR FIXTURE INTEGRATED SENSOR

FIXTURE INTEGRATED DAYLIGHT DIMMING PHOTOSENSOR

3000W MULTI PIR LIGHT CONTROLLER

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL

Installation Instructions

Wireless Occupancy Sensor User Guide

microos Occupant Sensors One Way microostm Occupant Sensor Two Way microostm Occupant Sensor Sensors

SmartBox RAB. Installation Manual. Outdoor Motion Sensor. It s easy to add. motion detection to all your outdoor lights! Contents.

Installation Manual. Specifications: Cautions: TURN OFF ALL POWER AT CIRCUIT BREAKER / FUSE PANEL.

Smart Post RAB. Installation Manual. Outdoor Motion Sensor. It s easy to add. motion detection to your post lantern! Contents.

MM540 Installation Instructions IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

MM340 Installation Instructions IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

Multiples EM_ 1.4. Install 1X1/1X2/1X3/1X4 Housings. Installation Instructions for. This product is suitable for indoor locations.

Energy Saving Module (HG-ESM-01)

351 DOOR CLOSER WITH DOUBLE LEVER ARM (OP) INSTALLATION INSTRUCTIONS

Wireless Ceiling Motion Sensor for Occupancy / Vacancy Detection with integrated diagnostic tools INSTALLATION GUIDE

WATTSTOPPER OEM SENSOR GUIDE INTEGRATED LIGHTING CONTROLS. designed to be better.

IR-3000 Wireless PIR Sensor. Owner s Manual

Tilting & Swiveling Plasma/LCD Flat Panel Wall Mount Installation Guide Model: A380SM

FLT-02 User Manual. Contents. Page 2 Page 3 Page 4 Page 5-7 Page 8

Important Safety Instructions

Spa & Hot Tub Necessities. Cover Removal System Installation & Use Manual

Tilting Flat Panel Wall Mount Installation Guide

Wireless Ceiling Mount Sensor

PMT-L31 (for Low Ceilings) PMT-H35 (for High Ceilings)

Tuff Dome. Installation Manual. vandal resistant. Outdoor Motion Sensor. Contents. Specifications. Switching Capacity:

MM750 Installation Instructions

DLA-E (Philips EvoKit) The DLA-E is designed to install in the mounting slot of the Philips EvoKit SR retrofit kit.

Assembly Instructions for model: VMPR1

USERS GUIDE EAGLE SMR MOTION SENSOR

SELECTIVE CALL INTERCOM SYSTEM MODEL: IM-5000 MASTER STATION

TekLink TL100 with Passive Infrared Sensing System Overview

Install the Housing. Installation Instructions for Entra Round or Square Type IC, Air-tight New Construction Adjustable LED Housing EN3_-LH9_ 1.

Round or Square Type IC Wall Wash Housing with Lamp for Flangeless Trims

FFLED18 INSTALLATION INSTRUCTIONS

Indoor Contact Input Photosensor

Tilting, Swiveling & Rotating Flat Panel Wall Mount

Installation Instructions SKU# , Rated Voltage V~ 50Hz

INSTALLATION MANUAL PBC-UMS

ES Series Features Detecting distance twice that of conventional

LC200DS1 Double Stud Articulating Wall Mount for Flat Panel Screens up to 32" with up to 200mm x 200mm VESA Mounting Patterns

LL-105-R LED Dimmer & 0-10V Bridge Setup Guide

FFLED18 INSTALLATION INSTRUCTIONS

TABLE OF CONTENTS WARRANTY

DLC-PDC PHOTODIODE CONTROLLER

General-Purpose Photoelectric Sensor

EBDSM-PRM Product Guide

Wall Mount Bracket YM-81

UPLIFT 2-Leg Height Adjustable Standing Desk

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE LED SURFACE AMBIENT LUMINAIRE FACTORY SETTINGS. Configuration Value

Assembly Instructions for Model: VMPR1

ODSOD-ID. D u a l - R e l ay Decora Wall Sw i t c h Occupancy Sensor

DA6002D-DA10004D. INSTALLATION / OWNER'S MANUAL Mobile Power Amplifiers

WORLD-BEAM QS18AFF200 Sensors with Foreground Suppression

Wireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE

UPLIFT 2-Leg Height Adjustable Standing Desk - For use with UPLIFT Eco and Eco Curve desktops -

Instruction page index: Installation Instructions for Bosca Models BOS-XX-C-XX, & BOS-XX-S-XX. Page 1 of 5

MantelMount. TM1A Installation Instructions IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS

Experiencing trouble with your zboost setup? Installation Tips. Please note the following important factors in determining zboost performance:


LLK-AR45 LED Lighting Heatsink Enclosure Kit. LLK-AR45 LED Illuminator Heatsink Enclosure Kit

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

DA560D COMPACT SERIES. INSTALLATION / OWNER'S MANUAL Mobile Power Amplifiers

Transcription:

SPECIFICATIONS CX-1 PIR Occupancy Sensor Voltage... 24VDC Current Consumption... 19mA* Power Supply... WattStopper Power Pack Isolated Relay Rating... 1A@24VDC Time Adjustment... 15 seconds 3 minutes Sensitivity Adjustment... Minimum Maximum Light Level Adjustment... 3 2FC *Current consumption can be slightly higher when only one sensor per power pack is used. Installation Instructions Santa Clara, CA 955

UNIT DESCRIPTION The CX-1 is a 24VDC passive infrared (PIR) occupancy sensor which controls lighting and HVAC systems based on occupancy and has a light level feature that can be used to keep sections of lights from turning on if the ambient light level is sufficient. The CX-1 contains an isolated relay with Normally Open and Normally Closed outputs for interfacing with HVAC or EMS. PIR sensing systems are passive systems which react to changes in infrared energy (moving body heat) within the coverage area. PIR sensors must directly see motion of an occupant to detect them, so careful consideration must be given to sensor placement. COVERAGE PATTERNS Coverages shown are maximum and represent coverage for walking motion. Actual coverage will vary slightly depending on mounting height and furnishings. Masking the lens: Opaque adhesive tape is supplied so that sections of the sensor s lens can be masked. This restricts the sensor s view and allows you to eliminate coverage in unwanted areas. 16ft 5ft. TOP 8ft 8ft TOP 55ft. SIDE 16ft 1ft 1ft SIDE 7ft15ft 25ft 55ft Dense Wide Angle Lens (Standard) up to 2 sq ft for walking motion up to 1 sq ft for desktop motion 5ft TOP 3ft 15ft 1 15ft 55ft 85 9ft Long Range Lens (-1) up to 9 linear ft for walking motion TOP SIDE 3 ft 3ft 15ft 33 using MB-1 with maximum rotation 15ft SIDE 67ft 33.5ft 38ft 21ft 1ft 1ft 21ft 33.5ft 38ft Two-Sided Aisleway Lens (-3) up to 134 linear ft for walking motion 67ft 1 ft 1 ft 2 ft 3 ft 4 ft 5 ft One-Sided Aisleway Lens (-4) up to 5 linear ft for walking motion Call 8.879.8585 for Technical Support

INSTALLATION The CX-1 sensors can be mounted to walls or ceilings with the supplied swivel bracket, and the supplied junction box cover plate if necessary (see figure C). Mounting at fixture height is most effective. The -3 & -4 sensors can also be mounted to industrial fixtures by using the MB-1 industrial mount bracket. Mounting Ceiling: It is best to leave approximately six inches between the sensor and the wall so that the Tightening Screw can be easily accessed. Orient the Base Bracket s Half- Circle Notch in the direction that the sensor will point. Wall: Orient the Base Bracket s Half-Circle Notch, up. Procedures: Reference Surface Angle Post Bracket 1. Mount the Base Bracket to the mounting surface with screws. Base Bracket Half-Circle Notch Tightening Screw fig. A 2. At the center of the Base Bracket, drill a hole in the ceiling or wall (unless mounting to a junction box) large enough to thread the sensor s wires through. 3. Guide the sensor s wires into the Base Bracket and through the hole in the ceiling or wall. 4. Connect the sensor to the Base Bracket by angling the Post Bracket so that it is in line with the half circle notch, as illustrated in figure A. Push the ball into the Base Bracket opening until it snaps into place, being careful not to pinch the wires. The brackets can be easily connected or disconnected using this orientation. Nut Ceiling Mounted Wall Mounted Parallel to vertical at 1 foot mounting height Reference Surface Angle fig. B www.wattstopper.com Parallel to wall at 1 foot mounting height

5. Insert the Tightening Screw and Nut into the Base Bracket as illustrated. 6. Use the Reference Surface Angle to adjust the sensor for optimum coverage. When mounted at ten feet, the Reference Surface Angle should be parallel to the wall or the vertical (see figure B). (As the mounting height decreases, the sensor will be tilted up slightly; as the mounting height increases, the sensor will be tilted down slightly). 7. Tighten the Tightening Screw. Industrial Mount Bracket MB 1 In an industrial setting, the MB-1 can be used to mount the CX-1-3 or CX-1 4 to a variety of structures or fixtures, including fluorescent fixtures. The MB-1 features an L shaped bracket and sensor housing. The housing can be positioned so that the sensor s view is straight down (CX 1 3), or directioned down an aisle (CX 1 4). When mounting the CX 1 4 with the MB-1 bracket fully rotated, the coverage pattern will extend slightly behind the sensor s mounting position (see, Coverage Patterns). The chart at right can help to position the MB-1 for the coverage desired. Sensor Angle Adjustment Predrilled Holes While watching the PIR sensing indicator (red LED) for flashes, have a person walk back and forth at the far end of the space. Increase or decrease mounting angle as needed until the desired coverage is achieved. Tighten the Tightening Screw to hold this position. Junction Box Cover Plate Installation fig. C Junction Box with Mud-Ring CX-1-4 Swivel Bracket Junction Box Cover Plate (Mount to a 3 Mudring) MB-1 Mounting Distance of height coverage behind 12 2.5 18 4 24 5 3 6.5 Ceiling Call 8.879.8585 for Technical Support

WIRING DIRECTIONS CAUTION Turn power off at the circuit breaker before installing power packs or sensors. Each WattStopper BZ series power pack can supply power for up to 6 CX-1 sensors. When using more sensors than this, multiple power packs are required. REFER TO THE WIRING DIAGRAMS ON THE NEXT PAGE FOR THE FOLLOWING PROCEDURES: FIRST connect the low voltage: RED wire (+24VDC) from power pack to VIOLET wire on sensor. BLACK wire (Return) from power pack to GREEN wire on sensor. Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY ONLY connect: BLUE wire from power pack to YELLOW wire on sensor. Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY, DEPENDENT ON LIGHT LEVEL (AMBIENT LIGHT) connect: BLUE wire from power pack to BLUE wire on sensor. Wiring ONE LIGHTING LOAD FOR OCCUPANCY CONTROL, AND A SECOND LOAD FOR OCCUPANCY AND LIGHT LEVEL (AMBIENT LIGHT) CONTROL connect: BLUE wire from power pack to YELLOW wire on sensor. BLUE wire from slave pack to BLUE wire on sensor. BLACK wire from slave pack to GRAY wire on sensor. Wiring the ISOLATED RELAY: (The Isolated Relay is rated for 1A @24VDC) Connect the wires necessary to the application that requires this output. RED (Common) (must be used for proper operation) BROWN (Normally Closed) Open when occupancy is detected ORANGE (Normally Open) Closed when occupancy is detected www.wattstopper.com

Occupancy and Light Level Controlled Lighting N Hot White Red (Line) Power Pack White (Neutral) Red (Load) Switch Lighting Load Auxiliary Pack Red Blue Isolated Relay Outputs Wires Normally Closed Contact BRN Common RED Normally Open Contact ORN Control Output 24VDC YEL Common GRN Blue Light Level Output 24VDC +24VDC Common BLU VIO GRA Hot N OFF switch Red (load) Light Level Lighting Load Multiple Sensors and Lighting Red (Line) White (Neutral) N Hot White Power Pack Red (Load) Switch Lighting Load Red Blue Control Output 24VDC (YEL) Common (GRN) +24VDC (VIO) Control Output 24VDC (YEL) Common (GRN) +24VDC (VIO) Red Blue Hot Power Pack Red (Load) N White Switch Lighting Load Red (Line) White (Neutral) Call 8.879.8585 for Technical Support

SENSOR ADJUSTMENT THE SENSORS ARE FACTORY PRESET* TO ALLOW FOR QUICK INSTALLATION IN MOST APPLICATIONS. However, verification of proper wiring or coverage, or customizing of the sensor s settings can be done through the following steps. Before starting, make sure the office furniture is installed, lighting circuits are turned on, and the HVAC systems are in the overridden/on position. VAV systems should be set to their highest airflow. There is a warm-up period when power is first applied to the sensor for one to two minutes. 1. For testing, set the Time Delay to minimum, 15 seconds. See chart below for DIP switch configurations. 2. Ensure that the Sensitivity and Light Level trimpots are set to maximum, fully clockwise. 3. Remain still. The lights should turn off after approximately 15 seconds (If not, see Troubleshooting). 4. Set the desired Time Delay. 5. Readjust the angle of the sensor if necessary. Time Delay: The Time Delay is set with DIP Switches 1 thru 4. Light Level feature: The Light Level feature holds lights off upon initial entry into the space if adequate ambient light exists. It will not turn the lights off if they are on. Adjust the Light Level during daylight hours when ambient light in the area is adequate. Avoid mounting the sensor too close to lighting fixtures. 1. Set the Time Delay to minimum, 15 seconds. 2. Set the Light Level trimpot to minimum, fully counterclockwise. 3. Be still and allow the lights to turn off. 4. Move a hand in front of sensor every 1 seconds (to keep sensor activated), and without blocking any light from reaching the sensor, in small increments, turn Light Level adjustment toward maximum, waiting at least 5 seconds between increments, until the lights turn on. Then turn it back slightly. At this setting the lights will not turn on with occupancy if the ambient light is above the current level. 5. Set the desired Time Delay. 6. Readjust the angle of the sensor if necessary. * Time Delay=18 minutes / Sensitivity & Light Level settings=maximum. on 1 2 3 4 5 Time Delay DIP Switch Sensitivity Adjustment Time Delays 15 seconds 2 minutes 4 minutes 6 minutes 8 minutes 1 minutes 12 minutes 14 minutes 16 minutes 18 minutes 2 minutes 22 minutes 24 minutes 26 minutes 28 minutes 3 minutes Override LED Light Level Adjustment DIP Switch # 1 2 3 4 5 =factory preset

TROUBLESHOOTING CAUTION Turn power off at the circuit breaker before working with or near high voltage. Lights do not turn on with occupancy, and the following condition exists: LED does NOT flash: When power is initially applied to the sensor, there is a warm-up period of up to 6 seconds before the LED is active. 1. Check that the circuit breaker has been turned back on. 2. Check the Sensitivity settings. Increase (clockwise) as needed. 3. Check all sensor and power pack wire connections. 4. Check for 24VDC at sensor (violet and green or gray wires). - If 24VDC is present, replace the sensor. - If 24VDC is not present, check that high voltage is present to power pack. If it is, replace power pack. LED does flash: 1. The Light Level setting or the Sensitivity may be set too low. 2. If the sensor s Light Level feature has been utilized, the lights connected to the Light Level Output might be held off because of the level of ambient light in the controlled area. - To test whether the Light Level adjustment is the problem, cover the PIR lens with your hand for 5 seconds to see if the lights turn on, or turn the Light Level adjustment toward maximum (clockwise). If the lights turn on, the Light Level setting was keeping the lights off. Increase the Light Level setting slightly or follow the procedures under Sensor Adjustment to adjust the Light Level setting. - The Sensitivity adjustment should be set to maximum, unless a decrease is made due to an Unwanted Sensor Activations adjustment. 3. Check all sensor and power pack wire connections. 4. Check for 24VDC at the power pack s blue wire connection to sensor while someone moves in front of sensor to activate the LED. If there is no voltage, replace the sensor. If there is voltage, replace the power pack. Call 8.879.8585 for Technical Support

Lights do not turn off automatically: 1. The sensor may be experiencing activations from outside the controlled area or from some type of interference (see Unwanted Sensor Activations next page). 2. Check all sensor and power pack wire connections. 3. Disconnect power pack s blue wire: If the lights do not turn off, replace power pack. Reconnect blue wire. If the lights turn off, the problem may be in the sensor to check: - Reconnect the blue wire. - Turn sensitivity and time delay to minimum and allow the sensor to time out. If the lights turn off, the sensor is working properly (see number 1., above, and Sensor Adjustment for readjustment of sensor). Unwanted Sensor Activations (LED flashes): Possible causes 1. Improper sensor location or angle adjustment causing detection outside of desired coverage area. 2. Sensitivity set too high. 3. Sensor located too close to HVAC or VAV vents with heavy air flow. Possible solutions 1. Mask the lens to reduce PIR coverage (see Masking the lens, under Coverage Patterns ). 2. Reduce the sensitivity (counterclockwise) as needed (see Sensor Adjustment ). 3. Adjust the sensor angle (see Sensor Adjustment ). 4. Relocate the sensor. Override: To override all sensor functions, set DIP switch #5 to on. This bypasses the occupancy and light level control functions of the sensor, but still allows the lights to be manually controlled with a light switch. www.wattstopper.com

ORDERING INFORMATION CX-1 CX-1-1 CX-1-3 CX-1-4 MB-1 BZ-5 BZ-15 Occupancy Sensor, Dense Wide Angle Lens (Std) Occupancy Sensor, Long Range Lens Occupancy Sensor, Two-Sided Aisleway Lens Occupancy Sensor, One-Sided Aisleway Lens Industrial Mount Bracket Power Pack: 12/277VAC, 5/6Hz, 24VDC, 225mA w/relay connected, 2A ballast/2a incandescent Power Pack, Hold ON/OFF, Manual ON: 12/277VAC, 5/6Hz, 24VDC, 225mA w/relay connected, 2A ballast/2a incandescent All sensors are white. WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation. 28 De La Cruz Boulevard, Santa Clara, CA 955 Technical Support: 8.879.8585 www.wattstopper.com 7-4-r5 8/213 Please Recycle