Industrial and Commercial Power Systems Topic 7 EARTHING

Similar documents
Earthing of Low Voltage Electrical Systems: Personnel Protection Equipment Protection

HV Substation Earthing Design for Mines

Earthing of Electrical Devices and Safety

Grounding and Lightning arrestors

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

TN, TT & IT Earthing Arrangements

Grounding for Power Quality

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

FAQ ON EARTHING STANDARDS 16/08/2018

Options to Improve the MEN System into the 21 st Century

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

ABSTRACT 1 INTRODUCTION

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

EPG. by Chris C. Kleronomos

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

CROSS-CONNECT CABINET

2 Grounding of power supply system neutral

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Earthing Guidance Notes

LIMITING THE DANGER OF ELECTRIC CURRENT SHOCK IN RELATION TO THE MEAN OF NEUTRAL POINT EARTHING IN THE MV NETWORKS

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

CONTINUING EDUC ATION

Status Date Prepared Reviewed Endorsed Approved

ECE 528 Understanding Power Quality

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Underground System Design TADP 547

Grounding Recommendations for On Site Power Systems

High Voltage Pylon Earth Measurements

The Confusion Surrounding Stray Voltage

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

RISK MANAGEMENT IN A LOW VOLTAGE NETWORK ON SAFETY ISSUES FROM ASSET MANAGEMENT PERSPECTIVE

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT

Chapter 6. WIRING SYSTEMS Safe Electrical Design

ET 40 - Electrician Theory Examination Marking Schedule


ENSURING PUBLIC SAFETY THROUGH PROPER EARTHING IN LOW VOLTAGE NETWORKS

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

Guidelines for the design, installation, testing and maintenance of main earthing systems in substations

Upgrading Your Electrical Distribution System To Resistance Grounding

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing

SCIENCE & TECHNOLOGY

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

Attendee Announcements

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

THE EFFECTS OF INCREASED FAULT CURRENT ON THE EXISTING SUBSTATION GROUNDING SYSTEM a Case Study

Sizing conductors and selecting protection devices

Outdoor Installation 2: Lightning Protection and Grounding

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

Fatima Michael college of Engineering and Technology

kv AC substation

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Investigation on the Performance of Different Lightning Protection System Designs

EPR Fundamentals of Calculation of Earth Potential Rise in the Underground Power Distribution Cable Network by Ashok K.

Residual Current Operated Circuit-Breakers (RCCBs)

Grounding and Bonding

Substation HV Cables. Document Number: 1-11-FR-07

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Earth Mat Design for a 66kv Substation

Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Stray Voltage and Swimming Pools

The Variable Threshold Neutral Isolator (VTNI)

IEEE Southern Alberta Section, Industrial Applications and Power & Energy Chapter Technical Program. Venue: Operator. Speaker Travel: Stantec

UNDERSTANDING. Ground Resistance Testing. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-On Measurements

Operating Instructions. Earthing System Test Equipment. Off-Frequency Low Current Injector LCI2000C. Tuned Voltmeter TVM1100

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Chapter E LV Distribution

Compact Model of a Combined Overhead-Cable Line for Ground Fault Application Transfer Analysis

Company Directive STANDARD TECHNIQUE : TP21A/2. Relating to Safety Limits for Touch and Step Voltages - Earthing System Design/Assessment

Safety through proper system Grounding and Ground Fault Protection

Article 250 Grounding & Bonding

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

American Electrical Institute

Protection of Electrical Networks. Christophe Prévé

Investigation of Earth Potential Rise on a typical single phase HV network

PERFORMANCE ASSESSMENT OF SUBSTATION SITE EARTHING USING FLUKE 1625 GROUND TESTER

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

ModieLoad. Static capacitive load unit 9.8A 240vac single phase. CAUTION: Ensure only Phase to Neutral connection CAT IV 300V

1. Introduction to Power Quality

Frequently Asked Question on Isolated Power Supply(IPS)

Earthing for EMC in Installations

Wisconsin Contractors Institute Continuing Education

Reference Number PDS 04 (RIC Standard: EP SP)

6. Internal lightning protection

Transcription:

The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 7 EARTHING

1 INTRODUCTION Advantages of earthing (grounding): Limitation of touch and step potentials to prevent electric shock Equi-potential bonding of exposed metal conductors to prevent electric shock Limitation of over-voltages on equipment for prevention of damage Fast operation of electrical protection and limitation of earth fault damage

General requirements: low impedance path (resistance and reactance) to earth conductor of local supply system and thence to earth of supply at main substation items need earthing (eg metal casings) must be connected to main earth by conductors of low enough impedance to provide equipotential bonding between all equipment items. Avoid earth loops. earth potential rise (EPR) associated with any fault current must be limited to safe levels earth conductors capable of handling fault current without thermal or mechanical damage

2 METHODS OF POWER SYSTEM EARTHING

Methods of earthing Unearthed system Solidly earthed system Resistance earthed system Reactance earthed system Use of an earthing transformer

Advantages of Solidly earthed systems High fault current and fast protection operation Better personnel and equipment safety Earth fault current easy to detect Unearthed systems Line to earth fault will not interrupt supply thus improves reliability Low fault current (limited by capacitance) will not cause damage

Disadvantages of Solidly earthed systems Line to earth fault causes loss of supply Line to ground fault current may be high enough to cause damage Unearthed systems Line-line fault current may be low and may not trip protection May have prolonged arc faults Line-line voltage imposed on phase insulation if earth fault occurs Overvoltages may cause increased insulation stress if there is an earth fault Finding faults may be difficult Regular maintenance is required

3 PERSONNEL PROTECTION

Standards AS/NZS 60479.1:2002 : Effects of current on human beings and livestock - General aspects In USA and Canada: IEEE Std.80 1986 Dalziel s electrocution equation

Dalziel s electrocution equation: Defines a specific energy (I 2 t) as determining factor for potential electrocution (fibrillation). Values based on tests carried out on humans and animals.

Code of Practice, Electrical Safety Act 2002 IEC approach (also Australia): Special locations: A1 (<67kV) or A2 (>66kV) Frequented locations: B1 (<67kV) or B2 (>66kV) IEEE

4 TYPICAL SITUATIONS IN SUBSTATIONS

Possible hazardous situations which can occur when there is an earth surface potential rise (EPR) in vicinity of an earth electrode due to fault current flowing to earth through that earth electrode.

Step potential : voltage difference between a person's feet when spaced 1m apart. Touch potential: voltage difference between exposed metal object, connected directly to earth electrode, and ground surface potential where feet are placed (usually distance of 1m is used). Grid (mesh) potential: maximum possible touch voltage in an earth grid area. Transferred potential: voltage difference between earth surface potential and exposed metal object connected to remote earth (effectively at true earth potential of zero volts).

Potential hazards due to Earth Potential Rise from a fault.

5 EARTHING FOR EQUIPMENT PROTECTION - THERMAL EFFECTS

earth faults are most common type of electrical fault. heating of fault current cause significant damage. arcing earth fault, or high impedance arcing fault is potentially the most damaging. causes: (i) contaminated insulation (ii) physical damage to insulation, (iii) transient or continuous over-voltages. typical arc voltages in LV systems: ~ 100V. arcing fault currents << bolted-fault current.

6 SYSTEMS OF EARTHING IN LOW-VOLTAGE INSTALLATIONS

Direct earthing system: system relies on current flow through the ground thus requires low earth resistivity and good earth electrode. Not always possible. MEN system is preferred as it utilizes supply utilities neutral to provide an additional earth return path.

MEN system: earth connections to neutral at consumer s installation and along route to supply substation neutral provides the return path while in direct earth system the metallic path is provided by water pipes, cable sheaths or by special earthing connections if provided balancing of load to utilize phase current cancellation in return neutral to minimize voltage drop

neutral conductor must be earthed at substation and at other locations as necessary to ensure that total impedance between neutral and earth does not exceed 10 ohms conductors used to earth neutral conductor of distribution system must have a cross-section area of at least 20% that of the smallest size of neutral used in system

CMEN system: Common Multiple Earthed Neutral extension of MEN system high voltage and low voltage equipment is bonded (via a neutral conductor) to a single common earth impedance to ground of this interconnected system of earthing is very low, typically 1 ohm or less.

7 TYPES OF EARTHING SYSTEMS IN CONSUMER S INSTALLATIONS

TN systems TT systems IT systems TN-C TN-S TN-C-S In practice, only TT and TN systems are commonly used.

1st letter (I or T) gives relationship of supply to earth T (terra): direct connection of one point of supply system to earth I (insulation): all live parts of supply isolated from earth or one point connected to earth through an impedance

2nd letter (T or N) gives relationship of exposed conductive parts of the general installation to earth T (terra): direct connection of exposed conductive parts to earth, independent of earthing of supply system N (neutral): direct connection of exposed conductive parts to earthed point of supply (neutral point).

TN systems: one point directly earthed, exposed conductive parts connected to that point by protective conductor (PE) TN-S system: separate neutral (N) and PE throughout TN-C system: N and PE combined into a single conductor throughout TN-C-S system: N and PE combined into a single conductor in a part of the system

TN-S TN-CS TN-C

TT system: one point directly earthed, exposed conductive parts connected to earth via separate earth electrode, no direct connection between live parts and earth, exposed conductive parts connected to earth

IT system: no direct connection between live parts and earth, exposed conductive parts connected to earth

8 EARTHING FOR COMPUTER SYSTEM AND EQUIPMENT

Earthing systems for data links

9 EARTH RESISTANCE OF BURIED ELECTRODES

Earth resistance determined by: shape of electrode(s) extent of electrode(s) electrical resistivity of the soil

10 EQUIVALENT HEMISPHERE MODEL OF AN EARTH ELECTRODE

most common form of earth electrode is a driven rod or pipe or a complex distributed mesh in the ground. not simple for analytic calculation determine equivalent hemisphere and then used for potential distribution calculations

Example:

11 USE OF EQUIVALENT HEMISPHERE MODEL TO CALCULATE TOUCH, STEP, TRANSFERRED POTENTIALS

V(r) = ground potential w.r.t earth electrode

12 EARTH RESISTANCE OF CLOSELY-SPACED IDENTICAL ELECTRODES

separate earth electrodes buried close to one another earth potential fields around these electrodes when current flows to earth will interact earth resistance of combined system higher than that of parallel combination isolated electrode system

13 MEASUREMENT OF EARTH RESISTANCE

Three-electrode method

Fall-of-potential method potential probe remote current probe

14 EARTH RESISTIVITIES

not a good conductor as compared with metals. variable depending upon physical nature and chemical composition heavily influenced by moisture content and dissolved salts.

Rule of thumb Mud (compressed coal): Wet soil: Moist soil: Dry soil: Rock: 1 Ωm, 10 Ωm, 100 Ωm, 1000 Ωm, 10000 Ωm.

15 ELECTRIC SHOCK EFFECTS

body resistance foot contact resistance ρ = soil resistivity Equivalent circuits for touch and step potentials

Assume bare feet or conducting footwear:

Tolerable touch and step potentials

Thank you

Unused slides

In distribution substations, the buried grid system will determine the earth resistance. The maximum recommended resistance is 5Ω or even 1Ω.

Step voltage means the prospective or open circuit voltage that may appear between any two points (1 metre apart) on the surface of the ground. Touch voltage means the prospective or open circuit voltage that may appear between any point of contact with conductive parts (that are located within 2.4 metres of the ground) and any point on the surface of the ground with a horizontal distance of one metre from the vertical projection of the point of contact with the conductive part.

Transferred earth potential Although a line may be "earthed " there may be a dangerous voltage or potential between the line and the earth point, including a concrete pole or a steel tower, at the work site. For example, where a line is under access at a remote substation, a fault not directly associated with the line under access can cause a dangerous voltage rise on the substation earth grid. That voltage rise is transferred through the line to the work site, where it can create a hazard to workers on the site.

In 1924, South Australian James Stobie invented a steel and concrete pole to carry electricity and telephone lines, due to SA s lack of suitable timber. A particular impetus for their invention was the need for a reliable supply of poles for the expansion of electricity into the countryside. Stobie Poles have other advantages too they re termite proof and have a life span of around 50 years. All Stobie Poles end at the SA border, with most other States preferring wooden telegraph poles.

Ref: AS61000.4.8-2002: Electromagnetic compatibility