GE Multilin technical note

Similar documents
Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ISSN: Page 298

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Evaluating the Impact of Increasing System Fault Currents on Protection

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Bus Protection Fundamentals

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Switch-on-to-Fault Schemes in the Context of Line Relay Loadability

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears

Transformer Protection

{40C54206-A3BA D8-8D8CF }

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

Protective Relaying of Power Systems Using Mathematical Morphology

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

Beyond the Knee Point: A Practical Guide to CT Saturation

RCTrms Technical Notes

Evaluating the Impact of Increasing System Fault Currents on Protection

Design of Differential Protection Scheme Using Rogowski Coil

Harmonic Distortion Impact On Electro-Mechanical And Digital Protection Relays

Arc Flash Calculation Methods

CURRENT TRANSFORMER SELECTION TECHNIQUES FOR LOW-VOLTAGE MOTOR CONTROL CENTERS

System Protection and Control Subcommittee

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

Protection Introduction

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Solutions to Common Distribution Protection Challenges

Power System Protection Manual

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

g GE POWER MANAGEMENT

Impact of Incipient Faults on Sensitive Protection

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

Relay Types and Applications Dr. Sasidharan Sreedharan

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

IV/IV B.Tech (Regular) DEGREE EXAMINATION. Electrical &Electronics Engineering

Distance Relay Response to Transformer Energization: Problems and Solutions

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

Motors and drives. Module B- Introduction to input measurements

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

1% Switchgear and Substations

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET.

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Protecting Large Machines for Arcing Faults

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Phase Comparison Relaying

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Use of Advanced Monitoring Technology to Detect Incipient Failure of Line Equipment

Impact of Incipient Faults on Sensitive Protection

How to maximize reliability using an alternative distribution system for critical loads

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Protective Relays Digitrip 3000

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1. Modified_103007

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Commissioning Process and Acceptance Test of a Sub-harmonic Protection Relay

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

889 Advanced Generator Protection Technical Note

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Artificial Neural Networks approach to the voltage sag classification

Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

2015 Relay School Bus Protection Mike Kockott March, 2015

Webinar: An Effective Arc Flash Safety Program

Power Delivery to Subsea Cabled Observatories

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

Reprinted from IEEE PCIC CONFERNECE, SEPTEMBER 2005, PAPER 32. This material is posted here with permission of the IEEE.

Introduction to Harmonics and Power Quality

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

The Problem of Interference

High-Density Computing:

Low Quiescent Current Surge Stopper: Robust Automotive Supply Protection for ISO and ISO Compliance

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Busbars and lines are important elements

PROTECTION of electricity distribution networks

g GE POWER MANAGEMENT

Defining and Measuring the Performance of Line Protective Relays

Experiment 9. PID Controller

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

Redundant Bus Protection Using High-Impedance Differential Relays

Volume I Issue VI 2012 September-2012 ISSN

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Power systems Protection course

Electrical Protection System Design and Operation

CT Analyzer. Revolution in current transformer testing and calibration

Transformer Protection

Transcription:

GE Digital Energy Multilin GE Multilin technical note GE Multilin releases fast and dependable short circuit protection enhanced for performance under CT saturation GE publication number: GER-4329 GE Multilin releases fast and dependable short circuit protection enhanced for performance under CT saturation Dependability of protection under heavy saturation Short circuit protection in industrial applications by means of instantaneous overcurrent function (IOC) has gained significant interest in the last few years. It is possible that relatively low-ratio current transformers (CTs) are applied for protective relaying of small loads fed from switchgear or motor controllers of relatively high shortcircuit capacity. Assume the worst-case scenario of 64 ka available fault current from bus feeding a small motor load rated below 50 A. In theory, CTs rated as lows as 50:5 and relay class C10 may be applied for protection purposes. Recognizing that 64 ka of fault current is more than a thousand times the rated current of the 50:5 CT, the magnitude of the problem is evident. Protection class CTs are designed to work in the linear range, with reasonable errors and waveform distortions only up to 20 times the rated nominal current. Well-established practices have been developed for engineering CT/relay installations under such conditions. This engineering practice is of little help here: A CT fed with a primary current hundreds of times its rated current will saturate severely - only relatively short duration peaks of limited current will be observed from the secondary of the CT. These peaks can be as low as 5 to 10% of the ratio current, and will last for short times, down to 1 to 2 ms in extreme cases. As a result, only a very small portion of the actual ratio current is presented to protective relays fed from such severely saturated CTs. In terms of the true RMS value, the secondary current may be as low as 1 to 2% of the ratio RMS current. The following concern arises the fault current is so high compared with the CT rated that it virtually stops the CT from passing the signal to the relay. The relay does not see enough proportional secondary current during severe faults to operate its short circuit protection, and fails to trip. The upstream relays, using CTs of a much higher ratio, measure the same fault current more accurately and trip. Zone selectivity is lost because the low-ratio CT blinded the relay. In practical terms, however, the problem is not frequent as CTs are being selected reasonably well, and most relays especially those responding to the true RMS value retain ability to trip on heavily saturated waveforms. GE MULTILIN TECHNICAL NOTE FAST AND DEPENDABLE SHORT CIRCUIT PROTECTION 1

Figure 1: Example of a current waveform as seen by a typical microprocessor-based relay short lasting peaks of current do not carry enough energy to activate a high-set IOC function. 100 50 0 time Current (ka) 50 100 150 200 818964A1.CDR Users demand deterministic and guaranteed response from protective relays. Application of IOC functions under heavy CT saturation is beyond the standard engineering practice that normally predicts the worst-case performance by utilizing relay and CT specifications. Therefore, help is needed from relay manufacturers to quantify the problem better by educating users on relay performance during CT saturation, or by enhancing relays to ensure dependable and fast operation under such extreme conditions. Relay design for heavily saturated CTs The goal is to provide short circuit protection via an IOC function that is both dependable and secure. Dependability is defined as ability to respond to faults even under severe CT saturation within a specified period of time. Failure to trip or a slow trip would cause mis-coordination of the protection system. From this perspective the relay algorithm needs to respond to waveforms as illustrated in figure 1 - short lasting peaks of current are measured and must be interpreted through the intelligence of a microprocessor-based relay as a legitimate fault condition. On the other hand the relay must be immune to sporadic current spikes that may be induced by transients and other non-fault events such as contactor bounce and arcing in vicinity of the relay and its wiring. As a result the algorithm design is a challenging task. GE Multilin is introducing an enhanced algorithm that provides dependability for conditions as severe as 64 ka of short circuit current with a 75:5 C10 CT with settings as high as a typical 16 times rated IOC pickup, without jeopardizing security of protection. With reference to figure 2, three typical CTs have been exposed to 64 ka of short circuit current. A number of relays have been tested for dependability and speed with a common pickup setting of 16 times rated. The relay performed exceptionally well even when fed from a 75:5 C10 CT. The relay is dependable and responds within 25 ms in most cases. 2 GE MULTILIN TECHNICAL NOTE FAST AND DEPENDABLE SHORT CIRCUIT PROTECTION

Figure 2: Trip times for a set of tested relays fed from three typical CTs under 64 ka of fault current. The IOC functions were set at 16 times rated. 64 ka 1 2 3 cyc 10 20 30 40 50 ms 75:5 C10 150:5 C20 600:5 C100 818965A1.CDR Performance verification of IOC functions under extreme fault conditions is not a trivial task either. The secondary CT currents reach hundreds of Amperes, well above capabilities of a typical test set. In addition accurate modeling of CTs can be a challenging exercise for a typical engineering staff rendering testing via waveform playback impractical. High power testing with actual CTs and relays is, therefore, a necessity. Figure 3 depicts a typical test setup for such type tests. It is prudent to contact a relay manufacturer regarding high power tests for applications with low-ratio CTs and extremely high fault current. GE MULTILIN TECHNICAL NOTE FAST AND DEPENDABLE SHORT CIRCUIT PROTECTION 3

Figure 3: Typical test setup in a high power lab 818966A1.CDR Short-circuit protection speed considerations Historically, overcurrent protection responding to faults in the range of 50 ms was sufficient in industrial applications. Recently, however, expectations for faster operating times have risen, driven by arc flash considerations, impact of fault current on primary equipment such as generators, and overall protection coordination. Speed of operation without security and dynamic accuracy is problematic, and relay designs need to balance speed, security and accuracy. With this in mind GE Multilin has enhanced IOC algorithms further in order to provide for ultra fast operation under typical fault currents with no or mild CT saturation. Figure 4 presents the IOC trip times from fault inception till closure of a trip rated output of the relay. The response time depends on the ratio between the fault current and the applied setting and varies from 16 ms for high multiples of pickup to 25 ms for a multiple of pickup of 1.2. For comparison, figure 5 provides trip times for other brands of relays tested under identical conditions. 4 GE MULTILIN TECHNICAL NOTE FAST AND DEPENDABLE SHORT CIRCUIT PROTECTION

Figure 4: Operating speed of short-circuit protection the relay 30 25 20 Trip time (ms) 15 10 Maximum Average Minimum 5 0 0 2 4 6 8 10 Current as multiple of pickup 818967A1.CDR Figure 5: Operating speed of short-circuit protection and reference 35 30 Maximum trip time (ms) 25 20 15 0 0 2 4 6 8 Current as multiple of pickup 818968A1.CDR GE MULTILIN TECHNICAL NOTE FAST AND DEPENDABLE SHORT CIRCUIT PROTECTION 5

Summary The computational capabilities of microprocessor-based relays allow the development of sophisticated overcurrent algorithms. These algorithms ensure dependable and fast operation of short circuit protection even under severe saturation of current transformers. This eliminates the need for impractical engineering of such applications, and increases confidence levels in cases with relatively well-rated CTs that do not experience extreme saturation but are exposed to currents much higher than the conventional 20 times rated. Speeding up protection functions and improving their response to severely impaired input signals exposes them, however, to security concerns. The users are advised to inquire about rigorous relay type tests including high power tests with physical CTs and relays before deciding to shift toward greatly underrated CTs while relying on protective relays to work with impaired input signals. The presented test results for the relay illustrate the level of performance in terms of speed and dependability under severe CT saturation that is safely achievable. The relay is dependable and fast under CT saturation conditions. In addition, in properly sized CT/relay applications it provides a 1-cycle trip time for fault current levels of 4 times the pickup, and a 1.5-cycle trip time at lower currents. This performance meets the present and future needs of industrial applications. 6 GE MULTILIN TECHNICAL NOTE FAST AND DEPENDABLE SHORT CIRCUIT PROTECTION