Page 4 of 8 Report No. 11029568 003 Summary of testing: Tests performed (name of test and test clause): All applicable tests as described in Test Case and Measurement Sections were performed. Tests performed on the bench (details see table 7.7 in CB report 11029568 001) Maximum ambient temperature: 0-40 C. Tested for moderate conditions. The correction factors of clearance is 1.14, specified in table A. 2 of IEC 60664-1 for altitude 3000 m Unless otherwise specified, all tests were performed on model BR500CIXXXXXXXX with PCB p/n: 640-1115 Rev. 04 to represent another model and PCB. Testing location: All tests as described in Test Case and Measurement Sections were performed at the laboratory described on page 3. Summary of compliance with National Differences List of countries addressed: Summary of compliance with National Differences (for explanation of codes see below): DK, SE DK=Denmark, SE=Sweden Copy of marking plate N/A TRF No. IEC62040_1A
Page 5 of 8 Report No. 11029568 003 Test item particulars... : Equipment mobility... : [x] movable [] stationary [ ] for building-in Connection to the mains... : [x] pluggable equipment [] permanent connection [x] detachable power supply cord [ ] non-detachable power supply cord Operating condition... : [x] continuous [ ] rated operating / resting time: Access location... : [x] operator accessible [ ] restricted access location Over voltage category (OVC)... : [ ] OVC I [x] OVC II [ ] OVC III [ ] OVC IV [ ] other: Mains supply tolerance (%) or absolute mains supply values... : Tested for IT power systems... : [x] Yes TRF No. IEC62040_1A 1) ±10% for models BR500CIXXXXXXXX, BX550CIyyyyyyyy and BX650CIyyyyyyyy with input voltage 230Vac. 2) ±5% for model BX650CIyyyyyyyy with input voltage 220-240Vac. [] No IT testing, phase-phase voltage (V)... : 230V(for Norway) Class of equipment... : [x] Class I [ ] Class II [ ] Not classified Considered current rating (A)... : 16A Pollution degree (PD)... : [ ] PD 1 [x] PD 2 [ ] PD 3 IP protection class... : IPX0 Altitude during operation (m)... : Not over 3000m Altitude of test laboratory (m)... : Not over 1000m Mass of equipment (kg)... : 5.1kg for models BR500CIXXXXXXXX, BX550CIyyyyyyyy, 6.2kg for model BX650CIyyyyyyyy Possible test case verdicts: - test case does not apply to the test object... : N/A - test object does meet the requirement... : P (Pass) - test object does not meet the requirement... : F (Fail) Testing... : Date of receipt of test item... : Mar., 2013 Date(s) of performance of tests... : Mar., 2013 - April, 2013 General remarks: The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma (point) is used as the decimal separator. Standard IEC 62040-1:2008 is to be used in conjunction with IEC 60950-1:2005, which is referred to in this TRF as "RD".
Page 6 of 8 Report No. 11029568 003 General product information: Description of change(s): 1. Add alternative source of inverter transformer for models BR500CIXXXXXXXX, BX550CIyyyyyyyy and BX650CIyyyyyyyy. 2. Add alternative source of transformer (T1) for PCB p/n: 640-1115A-Z Rev. 07 and 640-1321-Z Rev. 06 3. Correct the typo of Connection to the mains in Test item particulars in report no. 11029568 002. For the above described change(s) the following was considered to be necessary: Change Testing Comments 1. Electric Strength Test The new source of inverter transformer is similar to previous source except for manufacturer, no safety impact. For details, see appended tables. 2. Electric Strength Test The new source of transformer (T1) is similar to previous source except for manufacturer, no safety impact. For details, see appended tables. 3. N/A Un-check the permanent connection. See page 5 for details. Other comments: Factory(ies): 1. International Precision Assemblies, Inc. Lot 6, Blk 8, Phase II Peza, Rosario Cavite 4106, Philipines 2. International Precision Assemblies, Inc. Plant 2 Lot 2, Blk 17, Phase IV Peza Rosario Cavite 4106, Philippines 3. American Power Conversion (India) Pvt. Ltd. 187/3, 188/3, Jigani, Anekal, Bangalore 562106, India 4. Danam Philippines Inc Lot 1-A, Block 15, Phase III, PEZA Rosario Cavite 4106, Philippines The manufacturer's declaration, that the samples tested represent the products from each factory, is available. Definition of variable(s): Model BR500CIXXXXXXXX Variable: Range of variable: Content: X any alphanumeric, +, *, #, _, - or blank For marketing purpose used only, no any technical consider. Model BX550CIyyyyyyyy and BR650CIyyyyyyyy y any alphanumeric, +, *, #, _, - or blank For marketing purpose used only, no any technical consider. History of amendments and modifications: Ref. No. 11029568 001, dated Aug. 30, 2012 (original test report) Ref. No. 11029568 002, dated Sep. 11, 2012 (modification) Ref. No. 11029568 003, dated April 10, 2013 (modification) TRF No. IEC62040_1A
Page 7 of 8 Report No. 11029568 003 IEC 62040-1 Clause Requirement + Test Result - Remark Verdict 4.5 TABLE: List of critical components P Object/part no. Unit: Manufacturer/ trademark Type/model Technical data Standard Mark(s) of conformity 1. Inverter transformer (for models BR500CIXXXXX XXX and BX550CIyyyyyyy y) (for model BX650CIyyyyyyy y only) Transformer (T1) (for PCB p/n: 640-1115A-Z Rev. 07 and 640-1321-Z Rev. 06) Leader Electronics (Philippine Branch) Inc. Leader Electronics (Philippine Branch) Inc. Leader Electronics (Philippine Branch) Inc. 430-2091- 001XXX (X can be alphanumeric or blank) 2) 430-0683XXXXXX (X can be alphanumeric or blank) 2) 430-1314- ZXXXX, (X can be 0-9, A-Z, - or blank) 2) 105 C -- -- 105 C -- -- 105 C -- -- Supplementary information: 1. An asterisk indicates a mark which assures the agreed level of surveillance. 2. Suffix X of type designation is 0-9, A-Z, - or blank for market purpose only. 6, 8.2 and 9 TABLE: Electric strength tests, impulse tests and voltage surge tests P Test voltage applied between: Voltage shape (AC, DC, impulse, surge) Test voltage (V) Breakdown Yes / No Inverter transformer, primary windings to core AC 1500 No No Transformer(T1), primary/secondary windings to core AC 1500 No No Note(s): 1. For models and all sources of transformer. 2. Tested after humidity 30 C, 95%, 48hrs. TRF No. IEC62040_1A
Page 8 of 8 Report No. 11029568 003 List of test equipment used: Clause Measurement / testing Testing / measuring equipment / material used Range used Calibration date Supplementary information: No listing of test equipment used necessary for chosen test procedure. TRF No. IEC62040_1A