SIMULATION OF NON-LINEAR LOAD

Similar documents
ELECTROMAGNETIC EMISSIONS OF AC HIGH-VOLTAGE CORONA

AC Theory and Electronics

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

Danfoss Harmonic Calculation Software 2.0 Handbook Basic Level

Harmonics Analysis Of A Single Phase Inverter Using Matlab Simulink

Wireless Communication

EDUCATION STRATEGY REGARDING THE ELECTROMAGNETIC COMPATIBILITY AT LOW-FREQUENCY

Physics 115 Lecture 13. Fourier Analysis February 22, 2018

ELEC3242 Communications Engineering Laboratory Amplitude Modulation (AM)

INDUCTION COILS: VOLTAGE VERSUS CURRENT OUTPUT

Systematical measurement errors

CHAPTER 5 SWITCH MODE POWER SUPPLIES

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Caution - leakage currents! Leakage currents in fault-current protected environments

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Effective Harmonic Mitigation with Active Filters

NJWA - Harmonics and Drives Proper System Design

Keywords Cascaded Multilevel Inverter, Insulated Gate Bipolar Transistor, Pulse Width Modulation, Total Harmonic Distortion.

UNDERSTANDING POWER QUALITY

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

CAPACITIVE EARTH-FAULT CURRENT IN DISTRIBUTION NETWORKS OPERATED WITH THE ISOLATED NEUTRAL POINT

Reduced PWM Harmonic Distortion for a New Topology of Multilevel Inverters

EFFECT OF THE FEEDER CABLE AND TRANSFORMER IMPEDANCE ON THE MECHANICAL OUTPUT CHARACTERISTIC OF THE INDUCTION MOTOR

Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch

Description of a Function Generator Instrument

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality

22.0 Harmonics in Industrial Power Systems

Volume I Issue VI 2012 September-2012 ISSN

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

Practical aspects of PD localization for long length Power Cables

Harmonic Requirements

Power Quality Analysis in Power System with Non Linear Load

Chapter 2 Shunt Active Power Filter

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

Harmonics White Paper

UNIVERSITI MALAYSIA PERLIS

FDM- FREQUENCY DIVISION MULTIPLEXING

ECE 2006 University of Minnesota Duluth Lab 11. AC Circuits

2.0 AC CIRCUITS 2.1 AC VOLTAGE AND CURRENT CALCULATIONS. ECE 4501 Power Systems Laboratory Manual Rev OBJECTIVE

Signal Characteristics

Nicolò Antonante Kristian Bergaplass Mumba Collins

Development of a Compact Matrix Converter J. Bauer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Dry Type Distribution Transformers NON-LINEAR TRANSFORMER PRESENTATION

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

14. DC to AC Converters

Reducing Total Harmonic Distortion with Variable Frequency Drives

Frequency Modulation KEEE343 Communication Theory Lecture #15, April 28, Prof. Young-Chai Ko

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering

PHY 351/651 LABORATORY 5 The Diode Basic Properties and Circuits

PREDICTIVE CONTROL OF INDUCTION MOTOR DRIVE USING DSPACE

POWER FACTOR CORRECTION AND ITS PITFALLS

Lab 10 - INTRODUCTION TO AC FILTERS AND RESONANCE

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Dynamic Generation of DC Displacement AN 13

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Understanding Input Harmonics and Techniques to Mitigate Them

Current Rebuilding Concept Applied to Boost CCM for PF Correction

CHOICE OF HIGH FREQUENCY INVERTERS AND SEMICONDUCTOR SWITCHES

Sound is the human ear s perceived effect of pressure changes in the ambient air. Sound can be modeled as a function of time.

3. Diode, Rectifiers, and Power Supplies

The quality of the transmission signal The characteristics of the transmission medium. Some type of transmission medium is required for transmission:

A Novel Four Switch Three Phase Inverter Controlled by Different Modulation Techniques A Comparison

Study and analysis of THD and content of Harmonics in Three Phase PWM Inverter with Filters.

Theory and praxis of synchronised averaging in the time domain

Comparison of integrated and composed step-down converter in terms of EMC

MODELLING OF ATTENUATION AND CROSSTALK OF CASCADED TRANSMISSION LINES

INTRODUCTION TO AC FILTERS AND RESONANCE

Resonant Controller to Minimize THD for PWM Inverter

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Jitter analysis with the R&S RTO oscilloscope

Study of Power Factor Correction in Single Phase AC-DC Converter

CHAPTER 6 THREE-LEVEL INVERTER WITH LC FILTER

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

CHAPTER 4 FUZZY BASED DYNAMIC PWM CONTROL

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Sheet 2 Diodes. ECE335: Electronic Engineering Fall Ain Shams University Faculty of Engineering. Problem (1) Draw the

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

VOLD-KALMAN ORDER TRACKING FILTERING IN ROTATING MACHINERY

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Rayleigh Pulse Forming Network. Part II Assessment of sensitivity

Lecture 19 - Single-phase square-wave inverter

An Innovative Option for Electrical Energy Conservation with a Step-Up DCto-DC Power Converter Based Grid Tie Inverter

DC and AC Circuits. Objective. Theory. 1. Direct Current (DC) R-C Circuit

Environmental Exposures to ELF Georg Neubauer

Power Factor Improvement with Single Phase Diode Rectifier in Interior Permanent Magnet Motor

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

CHAPTER 2 GENERAL STUDY OF INTEGRATED SINGLE-STAGE POWER FACTOR CORRECTION CONVERTERS

What does Power Factor mean?

2. TELECOMMUNICATIONS BASICS

Single Phase Bridgeless SEPIC Converter with High Power Factor

Electromagnetic Harmonic Filters Technical Guide

Standby Power. Primer

Generator Advanced Concepts

Transcription:

Intensive Programme Renewable Energy Sources June 2012, Železná Ruda-Špičák, University of West Bohemia, Czech Republic SIMULATION OF NON-LINEAR LOAD Vladislav Síťař ABSTRACT This paper introduces one possible way to create of nonlinear loads in DYNAST program. Processes that are carried out when doing this creation are described. Next, the paper approaches possible faults that occur when creating particular network elements in DYNAST. At the end, harmonics current waveforms for two chosen nonlinear loads with the evaluation of their influence on supply voltage and current are described. Keywords Nonlinear load, current waveform, harmonics, voltage distortion, DYNAST INTRODUCTION There is a broad range of electric elements in households, institutions or industrial companies. These appliances consume a variety of large currents with different shapes when supplied from the harmonic power source. Some of them consume sinusoidal currents of frequency 50 Hz (so-called nominal frequency), that has some amplitude and phase angle compared to supply voltage. Other appliances consume currents of frequencies higher than 50 Hz. These currents are called harmonics and they are consumed by nonlinear loads. A Consumed frequency is not usual only one. They consume currents of higher frequencies higher than 50 Hz that are the whole multiple of nominal frequency. Harmonics are transmitted into the power system from the loads and therefore consumed non-harmonic current occurs in the supply system. An occurrence of harmonics is undesirable. Harmonics cause additional voltage drops on individual impedances in the power system. These voltage drops lead to the distortion of voltage waves with ideal sinusoidal waveform and therefore they decrease the quality of supply voltage. They also cause heating of cable insulations, transformers and other devices of the electric power system which results in higher power losses. Moreover, they influence protections action, generate noise and thus can affect nearby telecommunication and other electronic devices. INPUT DATA FOR NONLINEAR LOAD SILMULATIONS It is possible to use a several approaches for simulating of nonlinear load. The first of them can be applied when V-A characteristic of the specific load is known. This way is almost unrealizable because no company usually specifies such information about their products. The next possibility is to know consumed harmonics spectrum. This information is also very difficult to obtain since again producers do not publish these data. The last way is usage of real waveforms of consumed currents that are indicated by individual measurements with appropriate data processing. In Fig. 1, measured current waveform for harmonic sinusoidal voltage of television set is presented. From current waveform is evident that consumed current is approximately zero within a certain time interval. In the remaining time section, the waveform is almost sinusoidal with higher frequency and zero, 83

respectively. The whole procedure and model creation is performed for this appliance in program DYNAST. Figure 1 Current and voltage waveforms of television set NONLINEAR WAVEFORM SIMULATION First, it is necessary to create similar waveform of transmitted current under sinusoidal voltage supply. Created waveform has to correspond to the shape of the current curve and ensure its limitation around time instants when the waveform is approximately zero. All requirements are ensured by means of transformed limited sinusoidal function with appropriate frequency. This function enables us to create the waveform that will have given magnitude, period, shape and time instants for its zero value and derivation for ensuring zero waveform before and after appropriate times. In the case, that this waveform can not be created using only one function, it is necessary to assemble together more similar functions that will correspond to the next time intervals or second half period of voltage time function. u=230*sqrt(2)*sin(2pi*50*time); f1 /SIN/ B=25, C=2PI*150, L=13.333m, U=16.666m, SL=0, SU=0, P=20m; f2 /SIN/ B=-25, C=2PI*150, L=3.333m, U=6.666m, SL=0, SU=0, P=20m; These limited functions are necessary to be assigned to other variables that are dependent on the time. Resulting function is only the sum of particular functions (Fig. 2). i1(t)=f1(time); i2(t)=f2(time); i(t)=i1(t)+i2(t); Figure 2 Non-harmonic current created by the transformed function 84

DATA EXPORT For nonlinear load creation, when consumed current is dependent on the supply voltage, it is necessary to export the data into suitable program, where this dependence is detectable. One such suitable program is MS Excel, where the V-A characteristics can be suitably constructed. The advantage of MS Excel is that individual values of current and voltage correspond to concrete value of time when performing simulations in DYNAST. Therefore, there are no time shifts or no time consuming hand values rewriting. An accuracy of V-A characteristic creation depends on the amount of exported data, i.e. on chosen time step size of the calculation in DYNAST. X... time [s] 1... i=f(t) 2... u=f(t) X 1 2 0.000000e+000-1.554504e-011 0.000000e+000 4.000000e-005-1.554504e-011 4.087337e+000 8.000000e-005-1.554504e-011 8.173939e+000 1.200000e-004-1.554504e-011 1.225922e+001......... 3.760000e-003 9.790482e+000 3.008932e+002 3.800000e-003 1.065047e+001 3.024217e+002 3.840000e-003 1.149534e+001 3.039024e+002 3.880000e-003 1.232388e+001 3.053352e+002 There are several ways for creating of V-A characteristics in Excel program. Suitable projection type is the line graph with displayed regression equation. This regression can be variable with the shape of the power function. The most appropriate is the linear dependence because it is the simplest (Fig. 3). It is very important to continually update the values from which the regression equation is created because otherwise obtained function may not correspond to the actual waveform. Mistakes occur especially in the initial and final points of the current waveform. Moreover, small errors arise influence of linear regression. It affects especially the current amplitude. 30 25 y = 0,5898x - 167,28 20 I (A) 15 10 5 V-A characteristic Linear (V-A characteristic) 0 280 285 290 295 300 305 310 315 320 325 330 V (V) Figure 3 - Load characteristic with linear regression NON-LINEAR CHARACTERISTIC CREATION 85

In DYNAST program, is necessary to create the transformed limited linear function which will respect obtained current for certain voltage value. Time instants, up to which the waveform is zero, are necessary to be specified using the derivations of function (Fig. 4). These functions must be assigned to other functions that are dependent on voltage at the given point (for this case in point A). Resulting dependence is given by the sum of individual linear functions that are voltagedependent. g1 /LIN/ A=-167.28, B=0.5898, L=283.621568, SL=0, U=350; g2 /LIN/ A=167.32,B=0.5898,L=-350, U=-283.689388, SU=0; b1(u)=g1(a); b2(u)=g2(a); icelk=b1(u)+b2(u); Figure 4 - Voltage-dependent current waveform This created voltage-dependent current function is assigned to a current source. Actual current magnitude corresponds to the actual voltage in the connection point of the current source. In the cases, where the voltage is lower at input terminal of current source, the magnitude of consumed current is also lower. SIMULATED WAVEFORMS In Fig. 5, there are showen two waveforms of non-harmonic currents that are created as an example in DYNAST program. The first current waveform corresponds to a device with one-phase rectifier and smoothing capacitor. These currents are consumed by TVs, PCs assemblies, monitors, DVDs and others. The second current waveform is typical for devices with six-pulse rectifier and smoothing capacitor. The corresponding currents consume for example frequency converters for three-phase motors of variable units. a) b) Figure 5 Non-harmonic current waveforms for devices containing a) one-phase rectifier and smoothing capacitor, b) six-pulse rectifier and smoothing capacitor Curves created in DYNAST program are showen in Fig. 6. The magnitude of x A is chosen for the first simulated non-linear load and y A for the second one. Their magnitudes correspond to the connection of several appliances with the same consumed current from one phase. It may be for example 50 elements of PC assemblies for the first non-harmonic type. EXAMPLE OF THE NON-LINEAR CIRCUIT 86

For evaluating the effects of current harmonics on the supply voltage, it is necessary to assembly the circuit that is composed by voltage source, conductor and variable loads. The loads are set to consume either sinusoidal or harmonics currents. This sample circuit is showen in Fig. 7. It contains above introduced elements, such as source of sinusoidal voltage, power cable, two nonlinear loads and three linear loads. Figure 6 Simulated non-harmonic waveform Figure 7 Linear and nonlinear load circuits Final current waveforms flowing through the cable are showen in Fig. 8 a). Loading magnitudes are chosen in this simulation so that the influence of harmonics on the total current and voltage in the point of loads connection was visible. Waveforms of voltage source and connection point are showen in Fig. 8 b). There is obvious a small voltage drop on a longitudinal impedance and also harmonics effect. In the times instance with fast changes of flowing current, voltage distortion occurs. It is also visible, that the voltage at the connection point is slightly phase shifted (cable inductance is chosen negligible for no effect on voltage phase shift). 87

a) b) Figure 8 a) load currents, b) voltage distortion in the connection point of nonlinear load CONCLUSIONS Development of nonlinear load models is very complicate issue. It is needed to utilize several programs for ensuring the best current waveforms of harmonics. DYNAST program enables to make these simulations and also identifies effects of harmonics on the supply voltage and total current. Intensive creation of non-harmonic currents is a huge disadvantage. Furthermore, subsequent identification of this current dependence on supply voltage by means of mathematical functions is also very inconvenient. REFERENCES [1] Mann, Heřman; Ševčenko, Michal: Snadné počítačové modelování dynamických soustav. ČVUT. Praha 2008. [2] Kůs, Václav: Vliv polovodičových měničů na napájecí soustavu. BEN. Praha 2002. [3] Tůma, Jiří a kol.: Security, quality and reliability of electrical energy. Conte. Praha 2007. ACKNOWLEDGEMENT This work has been supported by student science project SGS-2012-047. Author: Ing. Vladislav Síťař University of West Bohemia Department of Electrical Power Engineering and Environmental Engineering Univerzitní 8, 306 14 Plzeň, Czech Republic E-mail: vsudlice@kee.zcu.cz 88