SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

Similar documents
3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

SUPPLY NETWORK ANALYZER. CVMk SERIES. CVMk-4C SERIES INSTRUCTION MANUAL. ( M / 00 B - Manual 1 / 2 ) (c) CIRCUTOR S.A.

Computer-14d - xx - 144a

SUPPLY NETWORK ANALYZER CVM-96 SERIES

CAVA Series USER S MANUAL

SUPPLY NETWORK ANALYZER

400,440Vac Vdc V, A, W, VA, var, Hz, V, Avg. A cos phi, sin phi and phi measurement kwh, kvarh (via Pulse Output)

SUPPLY NETWORK ANALYZER

MD-5060 DIGITAL MEGOHMMETER

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

Series P. Applications

INTELLIMETER REGISTER

Operating Instruction

DEIF A/S. User s manual. Read synchroscope type RSQ-3. Precision LED synchronoscope. High immunity to harmonic distortion F (UK)

EMD-FL-C-10. Current Monitoring Relay. Data Sheet. Functions. Structure 08/2004

TC 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC PULSE COUNTER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR-MTC34ENG02

Instruction Manual TABLE OF CONTENTS 1 PRINCIPLE OF OPERATION Limitations INSTALLATION Mains connection...

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

POWER TRANSDUCERS FOR SINGLE-PHASE AND THREE-PHASE NETWORK ISO P11P, P13P and P13B mm SERVICE MANUAL

Radio to radio repeater. airrepeater INSTRUCTIONS MANUAL M A

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA


Installation and Operating Instructions. Power IT Power Factor Controller RVC

Contents. Measurement and checking equipment for transformation centers Micro-ohmmeter MH-10 Page 3. Indirect earth contact simulator TL-5 Page 5

M.3. Electrical measurement and control. Electrical energy meters for partial consumption

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

TT 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR-MTT34ENG02

SVP CONTROL AND VISUALIZATION OF VOLTAGE, PHASE AND FREQUENCY IN THREE-PHASE LINES WITH NEUTRAL

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

PRetrans Table of contents

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

Series BDF for Process

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

DATA SHEET Differential current relays, RMC-131D ANSI code 87

DIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

REV-201М OPERATING MANUAL MULTIFUNCTIONAL TWO-CHANNEL TIME DELAY RELAY. «NOVATEK-ELECTRO» Ltd Intelligent industrial electronics

OPERATION & SERVICE MANUAL FOR FC 110 AC POWER SOURCE

A1000 ALPHA and A1200 ALPHA Meter Installation Instructions. General. Installation. For A1000 ALPHA Type R, A1000 ALPHA Type C, and A1200 ALPHA Meters

Power factor correction and harmonic filtering. Automatic power factor regulators

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

E-STOP relays, safety gate monitors

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar

Protection relays and controllers. Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB

USER MANUAL. WBP314P71 active power transducer. (3-phase 4-wired)

RMV-122D, RMV-132D ANSI

MODEL 421 Over/Under Motor Load Monitor

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar

SINEAX TV 808, 2 channels Isolating Amplifier Unipolar/Bipolar

Protection relays and transformers

METERSUK. SmartLink D Y N A M i T E. EM735 S Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION.

TECHNICAL DATA SHEET. Safety and function tester GLP1-g. Standard model GLP1-g ELECTRICAL SPECIFICATION

Synchronisation meters for manual or semiautomatic synchronisation Synchronization Meters SQ0114/SQ0104 Synchronization Meters SQ0214/SQ0204

Overcurrent Protection / 7SJ45

User Guide. AC/DC Mini Clamp Meter. Model Introduction. Large 3 3/4 digit LCD display with 40 segment bargraph

Positive-guided relay outputs: 8 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

EA16, EB16, EA17, EA19, EA12 MOVING-IRON METERS Ammeters and Voltmeters

Anacon Power & Controls Relay Assembly Specialists An Anacon Electronic Sales, Inc. Company

POINTAX 6000L2 Point Recorder

DIN 22.5/17.5 Size Lineup of A Wide Range of Measuring and Monitoring Relays. Model Number Structure

Contents H3CR. DIN 48 x 48-mm Multifunctional Timer Series. Broad Line-up of H3CR Series H3CR-A. Solid-state Timer. Common to ALL Timers

Mounting Instructions / Manual MV1171

Instantaneous Overcurrent Relay

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

TCM-2 Thyristor Control Module DATA SHEET

MINI MCR-SL-UI-f(-SP)

Room Temperature Controllers. for heating and cooling systems

C-Bus 8 Channel Low Voltage Relay

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

TT 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. User Manual Cod.: ENG - Vr /05 - ISTR-MTT34E03. Index. 1.1 General description

Electromotoric actuators for valves

XUA1 - AC Voltage and phase balance relay

Model Number Structure

USER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2

Content. Monitoring relay pluggable. 1-phase current monitoring relay phase direct-current voltage monitoring relay... 5.

SAFETY PRECAUTIONS: Before use, read the following safety precautions

ISOMETER IRDH575. Approvals

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

PD30CNB25xxPS. Photoelectrics, Background suppression reflective - PointSpot. Main features. Main functions. Description

Technical Description. DCF77 Receiver-Module 4460

AC MASTER Switch mode sine wave inverter

Converter. Specifications/Instructions. General. Features. Specifications. Dimensions AB-6484

r ADDENDUM FOR REAR-OF-BOARD VERSION LFS - R

Operating Instructions

OPERATION MANUAL FOR ALLIGATOR TUMBLE STIRRER* VP 710A

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC.

06528E00. ATEX / IECEx NEC 505 NEC 506 NEC 500

Installation Instructions

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit

27/04/2015

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

AC/DC Current Oscilloscope Probe Model SL261

Type Nominal voltage (V) Code HSV V

Phase-sequence Phase-loss Relay

PEAKTRONICS AMC-103 ADDITIONAL FEATURES. AC Motor Controller, 2A AMC-103 AMC-103A AMC-103B

Transcription:

SYNCHRONISM RELAY SYNCRO-96 (Code 2 28 913-2 28 914-2 28 915) INSTRUCTION MANUAL ( M 981 196 / 99A ) (c) CIRCUTOR S.A.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 1 Synchronism relay SYNCRO-96 1.- BASIC INSTRUCTIONS 1.1.- Delivery spot check This manual is issued to help all the SYNCRO-96 users to install and use it in order to get the best from it. After receiving the unit please check the following points: (a) Does this device corresponds to your order specifications? (b) Check if any damage was done during the shipment process. (c) Verify that it includes one instruction manual. 1.2.- Connection procedures For the safe use of SYNCRO-96 is basic that people who install or handle it follow the normal safety considerations and the diverse advises related in this manual. Before connecting verify that the voltage supply of the instrument (see identificative label) corresponds to the rated phase-phase voltage of the mains where you have to connect it: Code Type Voltage supply (phase to Frequency phase) 2 28 913 SYNCRO-96 110 V 110 Va.c. 20 % 40...70 Hz 2 28 914 SYNCRO-96 230 V 230 Va.c. 20 % 40...70 Hz 2 28 915 SYNCRO-96 400 V 400 Va.c. 20 % 40...70 Hz 2.- MAIN CHARACTERISTICS

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 2 The synchronism relay SYNCRO-96 is an electronic microprocessor based instrument able to measure and control the connection of an auxiliary generator to the electrical mains. To connect an auxiliary supply to the electrical mains it is necessary the meet of the next conditions: - The generator and the main network must have the same number of phases, the same sequence and the same voltage. - Same frequency. - No phase shift between both. SYNCRO-96 only gives the synchronism order when the above three conditions are achieved.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 3 The main characteristics of the device are: - Easy visualization of all the synchronism parameters. - Synchronism relay with the possibility of adjusting the limit phase shift and the delay. - Two auxiliary generator regulation relays (one to accelerate and another one to break the auxiliary generator). The activating and deactivating time can be adjusted. - Easy use and installation. - Little size (96x96 mm). Before operating the instrument read the INSTALLATION and ADJUST chapters and choose the properly operation mode. 3.- INSTALLATION AND START-UP The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions. The instrument must not be powered and used until its definitive assembly on the cabinet s door. If the instrument is not used as manufacturer s specifications, the protection of the instrument can be damaged. When any protection failure is suspected to exist (for example, it presents external visible damages), the instrument must be immediately powered off. In this case contact a qualified service representative.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 4 3.1.- INSTALLATION Before applying AC power to the instrument, check following points : a.- Voltage supply (see identificative label): Code Type Voltage supply (phase Frequency to phase) 2 28 913 SYNCRO-96 110 V 110 Va.c. ± 20 % 40...70 Hz 2 28 914 SYNCRO-96 230 V 230 Va.c. ± 20 % 40...70 Hz 2 28 915 SYNCRO-96 400 V 400 Va.c. ± 20 % 40...70 Hz - Connection terminals: Terminals A1-A2 and B1 B2. - Instrument consumption: 7 VA. b.- Operation conditions: - Operation temperature: -20 to +70ºC. - Operation humidity: 25 to 80 % HR. - Indoor use. c.- Safety: Designed to meet protection class II as per EN 61010. Mounting: The instrument is to be mounted on a panel. All connections keep inside the cabinet.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 5 Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. Therefore, the instrument must not be used until this is completely installed. The instrument must be connected to a power supply circuit protected with gl type (IEC 269 ) or M type fuses rated between 0.5 and 2 A. This circuit should be provided with an automatic switch or any equivalent element to disconnect the instrument from the power supply network. The supply and measuring voltage circuits will be both connected through a wire with a minimum cross-section of 1 mm 2. 3.2.- SYNCRO-96 CONNECTION 3.2.1.- Connection terminals Name A1 - A2 B1 B2 Ac Co CS1 CS2 CR1 CR2 CL1 CL2 Concept Connection to the main network Auxiliary supply of the device (voltage supply depending on the model) Connection to the auxiliary generator Auxiliary supply of the device (voltage supply depending on the model) Voltage comparator input Synchronism relay (NO) output Output of the relay for increasing the frequency of the auxiliary generator (NO relay) Output of the relay for reducing the frequency of the auxiliary generator (NO relay)

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 6 3.2.2- Wiring diagrams a) Wiring diagram for a 3-phase low voltage network:

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 7 b) Wiring diagram for a 3-phase low or medium voltage network through voltage transformers:

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 8 IMPORTANT REMARKS: - Connect A1-A2 and B1-B2 inputs with the polarity shown in the picture (if you use voltage transformers, also take care of their polarity). A polarity change would cause a 180º error in the SYNCRO-96 phase shift measurement. The instrument would give the synchronism order just when the voltages are 180º shift (!). - In a three-phase network is important to know the phase sequence, since the instrument measures between two phases. The phase connected to the A1terminal input has to be the same that the one connected to the B1 terminal input and the phase connected to the A2 terminal input has to be the same that the one connected to the A2 terminal input. - In case of using voltage transformers, take into account the possible phase shift that might affect over the measurement. 4.- OPERATION MODE The device has two voltage inputs: one for the main network and another one for the auxiliary generator. The instrument measures the frequency difference and the phase shift between both signals. These parameters allows SYNCRO 96 to decide about the connection of the generator to the mains. The voltage difference between both voltages is a less critical parameter for the connection of the generator, so an acceptation signal can be given to the instrument just making a contact between the terminals Ac and Co The instrument only works if the generator and mains voltages are between the values specified in point 3.1. If one of the voltages falls SYNCRO-96 will stop. When the voltages return to the specified level the instrument will automatically start-up.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 9 4.1.- SYNCHRONICITY If the connection of a generator to a main network has to be done without any kind of disturbance (overcurrents or mechanical stress on the generator), the following conditions have to be met: a. The generator and the main network must have the same number of phases, the same sequence and the same voltage. b. No phase shift between both voltages. c. Same frequency. In the SYNCRO-96, these conditions turn to these ones: a. Ac and Co terminals have to be linked (this means that voltages has the same value). It is given as a fact that systems have the same number of phases and the same sequence (it has been verified). b. Phase shift has to be lower than the adjusted value in PHASE knob. c. Phase shift has to be lower than the adjusted value in PHASE knob for a time higher than the adjusted value in the DELAY knob. When these three conditions are met, SYNCRO-96 activates the synchronism relay (CS1-CS2). The CS1-CS2 relay keeps activated while the conditions are met. If the auxiliary supply falls, the CS1-CS2 relay will switch to open position (NO relay).

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 10 ---------------------------------------------------------------------------------------------------------------- Following, an example of the operation mode is attached: - DELAY knob adjusted to 2 s - PHASE knob adjusted to 30º ----------------------------------------------------------------------------------------------------------------

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 11 4.2.- REGULATION INDICATORS AND RELAYS The user is informed about all the synchronism parameters by means of: A circular visualization consisting of 10 LEDS, that gives information about the phase shift and the frequency difference between the two voltage (6). Several leds that indicate: - If voltages are equal (1). - Pre-synchronism and synchronism orders (2). - Status of the regulation relays (4 and 5). (2) (3) (6) (5) (1) (4)

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 12 4.2.1.- Circular display When the display indication is turning in the opposite way that a clock pointer the auxiliary generator frequency is lower than the mains frequency. When the display indication is turning as a clock pointer the auxiliary generator frequency is higher than the mains frequency. The speed of the movement is proportional to the frequency difference. In case that frequencies are equal, one LED will keep lit on indicating the approximate phase shift: Actually, when the phase shift between generator voltage and mains voltage is close to 0, the zone (3) is lit on.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 13 4.2.2.- Equality voltage indicator The indicator (1) is lit on when the Ac and Co input terminals are linked and it is lit off when they are not linked. 4.2.3.- Pre-synchronism and synchronism indicators When the following conditions are met: - phase shift lower than the set at the PHASE knob - Ac and Co input terminals linked, in other words, equality of voltages indicator (2) begins to blink (pre-synchronism indication). If the two above conditions keep for a time higher than the adjusted in the DELAY knob, indicator (2) keeps permanently lit on and the CS1-CS2 synchronism relay is activated (synchronism indication). However, if in the pre-synchronism state SYNCRO 96 is not under anyone of two above conditions, the indicator (2) turns off. This indicator will lit on again when the two conditions are met. 4.2.4.- Regulating relays operation The regulating relays give pulses proportionally to the frequency difference between the generator and the mains. These pulses allows the generator regulator to accelerate or break the generator in order to achieve the synchronism conditions.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 14 The instrument has two free of voltage output relays: CR1-CR2. This relay operates when the generator frequency is lower than the mains frequency. CL1-CL2. This relay operates when the generator frequency is higher than the mains frequency. The activation and non-activation times of the relay pulses can be adjusted by means of the T on and T off knobs (on rear side): T off is the relay non-activation time (time between pulses). This time will keep constant during all the synchronicity process. T on is the relay activation time. When the frequency difference is equal or higher than 5 Hz, the activation time keeps equal to the knob set value. When the frequency difference is lower than 5 Hz the activation time is proportional to this difference.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 15 ---------------------------------------------------------------------------------------------------------------- Examples: Adjusted times: T off = 4 s and T on = 1 s Ex. 1. Generator frequency= 42.5 Hz / Mains frequency= 50 Hz Ex. 2. Generator frequency= 45 Hz / Mains frequency = 50 Hz Ex. 3. Generator frequency= 47.5 Hz / Mains frequency= 50 Hz

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 16 Ex. 4. Generator frequency= 50 Hz / Mains frequency= 50 Hz Ex. 5. Generator frequency= 52.5 Hz / Mains frequency= 50 Hz Ex. 6. Generator frequency= 57.5 Hz / Mains frequency= 50 Hz ---------------------------------------------------------------------------------------------------------------- Different generators will need different adjusting times (T on and T off ) with the purpose of getting the more accurate connection.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 17 4.2.5.- Regulating relay operation indicators When the network frequency is higher than the generator one, the indicator (4) is lit on. CR1-CR2 relay operates and CL1-CL2 relay keeps open. Each time that the CR1- CR2 relay is activated the indicator + (5) is lit on. When the generator frequency is higher than the network one, the indicator + (5) is lit on. CL1-CL2 relay operates and CR1-CR2 relay keeps open. Each time CL1-CL2 relay is activated the indicator (4) is lit on. When there is almost no difference between frequencies, indicators & + lit on alternatively. 5.- TECHNICAL CHARACTERISTICS Auxiliary supply From the measuring circuit (A1-A2 and B1-B2 connection terminals). Measuring circuit Frequency range: from 40 to 70 Hz. Rated voltage: 110 V, 230 V or 400 Vac, depending on the type (see label). Tolerance: ± 20%. Consumption: 7 VA. Synchronism mark By means of the CS relay (CS1-CS2 connection terminals). Delay in the synchronism mark: adjustable from 0 to 3 s by means of a rear knob (DELAY). Maximum phase shift allowed: adjustable from 0 to 30º by means of a rear knob (PHASE). Accuracy at synchronism mark: ± 0,5% at 50 Hz.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 18 Voltage comparator input Ac-Co terminals: working contact (NPN). Auxiliary generator regulation By means of 2 relays (CR1 CR2: frequency increasing and CL1 CL2: frequency reducing). T on (relay activation time): adjustable from 0 to 1 s by means of a rear knob. T off (relay non-activation time): adjustable from 0 to 10 s by means of a rear knob. Output relays Relays: CS1-CS2, CL1-CL2, CR1-CR2. Type: mechanical, 2 contacts (open/closed), free of voltage, NO. Use: AC11 250 V/2 A DC11 24 V/6 A Isolating system Between A1-A2 and B1-B2 inputs: 3 kv a 50 Hz during 1 min. Between inputs and output relays: 3 kv a 50 Hz during 1 min. Working conditions Working temperature: -20 / +70ºC. Use: indoor. Constructive characteristics Case material: ABS self-extinguishing (as per UL 94 V1) and high resistance against impacts. Protection degree: Box: IP 52 / Connection terminals: IP 20 Screwed transparent cover for the adjustment knobs. Security Category II, EN-61010. Standards IEC 51-1, IEC 255-5, IEC 1010-1, EN 61010-1.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 19 Dimensions: Panel hole: 92 mm +0.8 x 92 mm +0.8 7.- SAFETY CONSIDERATIONS All installation specification described at the previous chapters named INSTALLATION AND STARTUP and SPECIFICATIONS. Note that with the instrument powered on, the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts. This instrument is factory-shipped at proper operation condition.

----- Synchronism relay SYNCRO-96 -------- M - 981 196 --- Page nº 20 8.- MAINTENANCE The SYNCRO-96 does not require any special maintenance. No adjustment, maintenance or repairing action should be done over the instrument open and powered and, should those actions are essential, high-qualified operators must perform them. Before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source. When any protection failure is suspected to exist, the instrument must be immediately put our of service. The instrument s design allow a quick replacement in case of any failure. 9.- TECHNICAL SERVICE For any inquiry about the instrument performance or whether any failure happens, contact to CIRCUTOR s technical service. CIRCUTOR S.A. Aftersales Service c / Lepanto, 49 08223 - TERRASSA (Barcelona) - SPAIN Telf. 34-93 - 745 29 00 Fax. 34-93 - 745 29 14 e-mail : central@circutor.es