MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Similar documents
Insulation Co-ordination For HVDC Station

High voltage engineering

Slide 1. New Delhi India Oct CIGRE AORC Meeting New Delhi October 2017

Tab 8 Surge Arresters

Electric Stresses on Surge Arrester Insulation under Standard and

Utility System Lightning Protection

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Transformers connected via a cable Overvoltage protection

GIS Disconnector Switching Operation VFTO Study

Analysis of lightning performance of 132KV transmission line by application of surge arresters

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Selection of MO surge arresters Overvoltage protection

ABSTRACTS of SESSION 6

Lightning performance of a HV/MV substation

Modeling insulation in high-voltage substations

Tab 2 Voltage Stresses Switching Transients

Energy Division. Bowthorpe LV/MV Surge Arresters

EE 1402 HIGH VOLTAGE ENGINEERING

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

G. KOEPPL Koeppl Power Experts Switzerland

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Earthing of Electrical Devices and Safety

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

Fixed Series Compensation

AORC Technical meeting 2014

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

Transmission of Electrical Energy

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Prepared by Mick Maytum

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

Overvoltage Protection of Light Railway Transportation Systems

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

DC current interruption tests with HV mechanical DC circuit breaker

Lightning overvoltage and protection of power substations

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

In power system, transients have bad impact on its

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

INTERNATIONAL STANDARD

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

(2) New Standard IEEE P (3) Core : (4) Windings :

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

TECHNICAL REPORT. Insulation co-ordination

Disclosure to Promote the Right To Information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

HIGH VOLTAGE Insulation Coordination

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

APPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems

B2-301 IMPROVING DOUBLE CIRCUIT TRANSMISSION LINE RELIABILITY THROUGH LIGHTNING DESIGN

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Metal-Oxide Surge Arresters in High-Voltage Power Systems

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Protection against unacceptable voltages in railway systems

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

EXPERIMENTAL ISSUES OF OVERVOLTAGE COORDINATION

Choosing the right Pico Technology active differential probe

TECHNICAL SPECIFICATION

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

Power Quality and Reliablity Centre

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Index. b back-flashover 245 biomass 207 breakers 74 buchholz protection 235 busbar sectionalizer 193 business enterprises 18

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

HV AC TESTING OF SUPER-LONG CABLES

Table 1: Results with standard impluse current 8/20 s applied to check for the residual voltage of V-MOV-ZnO

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Problems connected with Commissioning of Power Transformers

In order to minimise distribution (11 and 22 kv) feeder breaker

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Effective February 2017 Supersedes January 2012 (CP1122)

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Lightning transient analysis in wind turbine blades

Transcription:

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral AB Sweden klaus.winter@swedishneutral.se ABSTRACT Several grid operators around the world intend to convert the method of neutral treatment from solid to resonant grounded neutral, especially since the recent development of residual fault current compensation schemes made this classic grounding concept fit also for cable grids. It eliminates safety risks and offers a superior solution for fault management with minimum customer outages. However, the insulation coordination of the existing equipment has to be reviewed. At this, surge arresters installed for overvoltage protection of the line transformers are of particular interest. Considering a 24.5kV distribution system, four different options are studied with special regard to insulation coordination and thermal overloading of existing arresters. The first option a series connection of the hitherto installed arrester with a spark gap is not suited, as it cannot sufficiently protect the transformer due to the formation time of the spark gap. The second option is to simply replace the existing arresters by arresters rated for resonant earthed systems. The third option is to add additional arresters in series with the existing ones to to obtain the max. continuous voltage required for resonant earthed systems. Due to the series connection the residual voltage of this arrangement is also increased, which reduces the overvoltage protection performance. But transformers with 125kV (BIL) can still be sufficiently protected. The fourth option is to add one smaller arrester in the common grounding of the existing ones - the so called Neptune connection. The overvoltage performance of this cost efficient solution is the same as with option 3. For the last option the temporary overvoltage (TOV) capability of the arresters have to be checked. According to available specifications, possible operation with full rated voltage is confirmed up to 10000s. The thermal stability of some field aged arrester was successfully checked in a separate verification test. INTRODUCTION Resonance grounding has become popular again, especially since the recent development of residual fault current compensation schemes has made this classic grounding concept fit also for cable grids. The systematic elimination of residual fault currents can also solve some remaining safety issues with traditional resonance grounding in overhead grids [1]. High impedance faults can cause step voltages which constitute a serious safety risk to the public and can initiate fires. A fast and complete compensation of the remaining fault current in case of single phase earth faults now possible with the GFN Ground Fault Neutralizer (Figure 1) can eliminate these risks [2]. Figure 1: GFN basic approach for residual fault current compensation Furthermore, resonance grounding combined with residual current compensation offers a superior solution for line fault management with minimum or no interruptions to customer power supplies. Grid SAIFI and SAIDI figures will impove significantly. Finally the ongoing development work for a new GFN based online PD monitoring, aiming to facilitate the early detection of cable faults and to support CBM, adds further advantages to this novel grounding concept [3]. However, the phase-to-earth voltage of the healthy phases rises to the level of phase-to-phase voltage in case of a single-phase earth fault. This requires the resizing of the insulation coordination and the equipment in question. At this, arresters installed for overvoltage protection of transformers are of particular interest. To adopt the coordination withstand voltage of the arresters in case of temporary overvoltages (TOV) under earth fault conditions four options are studied with special regard to insulation coordination issues [4] and thermal overloading of the arresters previously installed. OVERVOLTAGES IN SYSTEMS WITH RESONANT GROUNDED NEUTRAL In case of an earth fault the phase voltage of the healthy phases turns from phase-to-earth to phase-to-phase voltage The TOV amounts to 3 pu, i. e. 1.73 pu. If the resonant grounded system is operated in the continuous mode, this situation can last for hours, till the fault is cleared. CIRED 2015 1/5

Beside these steady state fault conditions the transient voltage characteristic when a fault is initiated has to be considered. The transient overvoltage may achieve up to 2.5 pu. After the decay of this transient process the TOV of 1.73 pu is obtained. ARRESTERS IN SERIES WITH SPARK GAPS (OPTION 1) Required overvoltage performance of the overvoltage protection device The overvoltage protection device consisting of spark gap in series with arrester has to limit the lightning overvoltages at the terminals of the transformers. Assuming that the fast front overvoltage leads to a flashover of the spark gap, the arrester in series becomes active and is limiting the overvoltage equivalent to the characteristic of the arrester. In case of an earth fault the arrester has to remain separated from the phase voltage. That means, neither the transient nor the continuous overvoltage must cause a flashover of the spark gap. A flashover of the spark gap would connect the arrester to the earth-fault voltage which corresponds to the phase-to-phase voltage. As the system voltage is 25 kv and the rated continuous voltage of the arrester is 19.5 kv or 21 kv depending on the type of arrester installed, the arresters would thermally be overloaded.. Overvoltage characteristic of the spark gap The spark gap in series to the arrester has to withstand the continuous earth-fault overvoltage, but also the transient overvoltage. This slow front transient overvoltage amounts up to 2.5 x 2x25/ 3 kv = 51 kv and the continuous earth-fault overvoltage 2 x 25 kv = 35.4 kv. The lightning (fast front) withstand voltage of a rod spark gap can be derived from IEC 60071-1 [4], but for slow front overvoltages like earth fault overvoltages a conversion factor between fast front and slow front overvoltage according to IEC 60071-2, Table 2 [5] has to be taken into account. Furthermore, different atmospheric conditions and altitudes have to be regarded by a correction factor which is assumed to be 1.1. Thus a gap distance of 90 mm has to be chosen (Figure 2). In case of lightning overvoltage the spark gap has to flashover to connect and to activate the arrester installed for overvoltage protection of the transformer. The flashover voltage u b of the spark gap is given by the voltage time curve which can be estimated from the gap distance d gp [6]: 400 710. The 90% flashover voltage of the 90 mm spark gap is presented in Figure 3. Figure 2: Fast front and slow front withstand voltages for a rod-rod spark gap in dependence of gap distance The MV lines in question are subjected to direct lightning. More than 90% of the strokes have a peak current of at least 10 ka [7]. The lightning current pulses are characterised by certain steepness parameters. According to [8] the steepness between 30% and 90% of the crest value amounts to S 30/90 = 3.2 I 0.25 at which I is the crest value of the lightning current pulse. Thus the overvoltage at the strike location will exceed 2000 kv with a steepness of 1140 kv/ s. The amplitude of this fast front overvoltage is limited to about 400 kv by a flashover the next line insulator. But nevertheless, the transformer is subjected by an overvoltage of 1140 kv/ s steepness. As shown in Figure 2 this steepness leads to a flashover voltage of 260 kv and a time to breakdown of 0.25 / s. That means after 0.25 / s the arrester is connected to the line and could limit the overvoltage. Figure 3: Voltage-time characteristic of a 90 mm spark gap, 90% flashover voltage at a steepness of 1140 kv/ s CIRED 2015 2/5

Consequences for overvoltage protection of transformers connected to the system In contrast to air gaps the typical transformer insulation arrangements do not show a formation time. There is only a small increasing trend at steep front overvoltages which can be neglected when regarding the withstand capability at steep front overvoltages and the rated lightning impulse withstand voltage for power transformers can be assumed [9]. In consequence power transformers rated for a highest voltage for equipment of 24 kv and for a lightning impulse withstand voltage of 125 kv cannot be protected by a protection device consisting of a spark gap in series with previously installed arresters rated for a solidly earthed system. REPLACEMENT BY ARRESTERS DESIGNED FOR RESONANT EARTHED SYSTEMS (OPTION 2) The ratings of arresters for a system under consideration with a maximum system voltage of 24.5 kv can be derived from IEC 60099-5 [10]. In Table B4 the following characteristic values of metalloxid arresters in resonant earthed systems are given (Table 1): Max. system voltage Max. continuous voltage Rated voltage Max. resid. volt. at rated dischar. current 24 24 30 80 Table 1: Characteristic values of metalloxid arresters in resonant earthed system, system voltage 24kV As shown in Table 2 the residual voltage of these arresters is the same as those installed up to now and rated for 24 kv. Thus the protection level is also the same. Only compared to arresters rated for 21 kv the protection level is somewhat lower. Type 1 Type 2 IEC60099-5 Rated voltage 21 24 30 Max. resid. voltage 69 79 80 Table 2: Max. residual voltage of installed arresters and arrester suited for resonant earthed systems, system voltage 24 kv SERIES CONNECTION OF EXISTING AR- RESTER WITH ADDITIONAL ARRESTER (OPTION 3) To obtain the maximum continuous voltage of 24 kv or the rated voltage of 30 kv respectively for resonant earthed systems according to IEC 60099-5 [10], an additional arrester A2 has to be connected in serious with the existing one A1 (Figure 4). Due to the series connection of the two arresters the residual voltage is also increased which has consequences with regard to the protection level. Figure 4: Series connection of the existing arrester A1 with an additional arrester A2 Table 3 shows the continuous voltage, rated voltage and residual voltage at 10 ka discharge current of two arresters in series. As to be seen from Table 3, the residual voltage of the two arresters in series is increased by about 20%. Therefore the protection level is worse compared to the situation of today and it has to be clarified, if the protection level is sufficient. Two arresters A1 & A2 in series rated voltage U r1 21 24 kv rated voltage U r2 9 6 kv Ʃ rated voltage U r1,2 30 30 kv max. continuous voltage U c1 17 19.5 kv max. continuous voltage U c2 7.65 5.1 kv Ʃ max. continuous voltage U c1,2 24.65 24.6 kv max residual voltage U res1 : 10 ka, 8/20 s 69.3 79.2 kv U res2 : 10 ka, 8/20 s 29.7 19.8 kv ƩU res1,2 : 10 ka, 8/20 s 99.0 99.0 kv Table 3: Electrical data of arresters A1 and A2 connected in series Assuming a rated lightning withstand level of the transformer of 125 kv the following protective ratio defined as rated lightning impulse withstand voltage to residual voltage at rated discharge current (U rliwv / U res (10 ka)) can be determined (Table 4). U r LIWV U c LIWV U rliwv /U res (10 ka) ; modified arrester arrangement up to now U cliwv /U res (10 ka) accord. IEC (resonant earthing) 125 1.26 1.80 1.56 109 1.10 U rliwv rated lightning impulse withstand voltage U cliwv coordination lightning impulse withstand voltage Table 4: Protective ratio for different arrester arrangements depending on lightning impulse withstand voltages The protective ratio of the arresters in series connection is considerably worse compared to the single arrester in accordance with IEC for resonant earthed systems [10]. If a certain ageing of the transformer is taken into account, as it is done in the insulation coordination procedure by CIRED 2015 3/5

means of a safety factor of 15% 1 [5], the limiting voltage of the arrester is just above the coordination lightning impulse withstand voltage (ratio in red). That means, additional voltage drops on the supply leads have to be avoided in any case. Consequently the arrester has to be installed very near by the transformer with very short supply leads. ARRESTER ARRANGEMENT WITH FOUR ARRESTERS, NEPTUNE DESIGN (OPTION 4) The adoption of the arresters to the maximum continuous voltage of 24 kv can also be realized by a four arrester arrangement according to the so called Neptune design (Figure 5). Table 6 presents the capacitance C 4 of arrester A4 related to capacitance C 1 for the two types of installed arresters, assuming that U c1 /U c4 = C 4 /C 1 and C 1 = C 2 = C 3, as explained above. U c1 17 19.5 kv U c4 7.65 5,1 kv C 1, C 2, C 3 1 1 C 1 C 4 2.22 3.82 C 1 Table 6: Capacitance C 4 of arrester A4 related to capacitance C 1 The characteristic of the arrester arrangement in Neptune design in case of an earth fault in phase L1 is illustrated in Figure 6. In this case the capacitance C 1 is in parallel to C 4 resulting in a voltage component U 2 at C 2 given in Table 7. Figure 5: Four arrester arrangement according to "Neptune design" At this, the installed arresters A1 A3 are connected together at the lower arrester terminals and connected to earth via an arrester A4. The arrester A4 has to be rated in such way that under earth fault conditions the maximum continuous voltage of the series connected arresters A1 or A2 or A3 respectively and arrester A4 is greater or equal the maximum system voltage of 24.5 kv. Under consideration of the two types of arresters installed the values given in Table 5 can be assumed. The overvoltage protection efficiency of this arrester arrangement is the same as at option 2, as the ratings of the series connected arresters are the same. max. continuous voltage U c1,2,3 17 19.5 kv max. continuous voltage U c4 7.6 5.1 kv Ʃ max. continuous voltage U c 24.6 24.6 kv Table 5: Rating of the arrester A4 in the Neptune design arrangement As long as the voltage at the arrester is smaller or equal as the maximum continuous voltage U c the arresters behave in a capacitive manner (dotted in Figure 5). Since the capacitances C 1 C 4 are quantitatively not known, it is assumed that the capacitance of the arrester is inversely proportional to the maximum continuous voltage U c (C ~ 1/U c ). This assumption is plausible, as U c is depending on the number of metalloxid (MO) elements connected in series and the elements connected in series acts as a capacitance. If the U c1 equals U c4 the capacitances C 1 and C 4 would be the same. Figure 6: Characteristic of the arrester arrangement in Neptune design in case of an earth fault in phase L1 As to be seen from Table 7, due to the capacitive voltage distribution in case of an earth fault in phase L1 the voltage component at the previously installed arresters A2 and A3 is greater than the maximum continuous voltage U c. U r1, 2, 3 21 24 kv U c1, 2, 3 17 19.5 kv U c4 7.65 5.1 kv C 4 2.22 3.82 C 1 C 4 // C 1 3.22 4.82 C 1 C 4 + C 1 + C 2,3 4.22 5.82 C 1 U m 24.5 24.5 kv U 2,3 18.7 20.3 kv Table 7: Voltage component at U 2 and U 3 respectively at arrester A2 and A3 respectively Earth capacitances in parallel to C 4 which may enhance this miss-grading are disregarded. Therefore a thermal overloading of these arresters cannot be excluded in case of longer lasting earth faults. Hence the overvoltage (TOV) capability of the arresters has to be checked correspondingly. The overvoltage (TOV) characteristic provided by a manufacturer is presented in Figure 7 [11]. It shows the TOV capability depending on time related to the rated voltage of the arrester. For long lasting earth faults the TOV factor for 10 000 s has to be chosen which is 0.93 with prior duty and 1.02 without prior duty. 1 U cliwl = UrLIWL /1.15 CIRED 2015 4/5

Figure 7: Overvoltage (TOV) characteristic of arresters type according to [11] The TOV capability for the two types of arresters under consideration is given in Table 8. Even in case of a prior duty a thermal overloading or runaway of the arresters is not to be expected. U r 21 24 kv U c 17 19.5 kv 1) TOV (10 000 s) related to U r 0.93 0.93 pu TOV (10 000 s) 1) 19.5 22.3 kv U m 24.5 24.5 kv U 2,3 18.7 20.3 kv 1) with prior duty acc. to IEC 60099-4 Table 8: TOV capability of arresters A2 (U 2 ) & A3 (U 3 ) in case of an earth fault in phase L1 VERIFICATION OF TOV CHARACTERISTIC BY LABORATORY TESTS The results gained by theoretical considerations were verified by laboratory investigations. The tests comprised continuous operation of the arrester arrangements at 24.5 kv with full neutral displacement, followed by ten single phase-to-ground faults covering the transient overvoltage pre-stress. During a period of 4 5 hours under earth fault conditions the voltage and current at arrester A4 as well as the temperatures of the different arresters A1 A4 were observed. The test results do not show any indication of thermal overloading or runaway of the arresters applied. Therefore, the arrester arrangement of the Neptune design using these types of arresters is suited when a conversion of the method of neutral treatment from solidly earthed neutral to resonant grounded neutral is intended. If other types are installed, the TOV capability has to be proven by means of the TOV characteristic of the type of arrester in question. At this the pre-stress to which the arrester is subjected in practice has to be taken into account. CONCLUSIONS When converting the method of neutral treatment from solidly earthed neutral to resonant grounded neutral, the arresters have to be adopted regarding their rated voltage and continuous operating voltage correspondingly. Furthermore, an adequate overvoltage protection of the transformers by the modified arrester arrangement has to be proven. With this regard four options are considered. The most economic option is an arrester arrangement in the Neptune design at which the previously installed arresters are connected to earth via a fourth arrester. Due to the capacitive voltage distribution in case of an earth fault the voltage component at the arresters in the two sound phases can be greater than the maximum continuous voltage of the arresters. Therefore, the overvoltage (TOV) capability of these arresters in case of long lasting earth faults has to be checked correspondingly. The overvoltage protection efficiency of this arrester arrangement is somewhat worse compared with the previous one. But transformers with standard rated lightning impulse withstand level are sufficiently protected, if installed very near to the transformer via short leads. REFERENCES [1] K. Winter: The RCC Ground Fault Neutralizer a Novel Scheme for Fast Earth Fault Protection. Proceedings of the 18th Internat. Conf. on Electricity Distribution, CIRED, Turin/Italy June 2005 [2] Victorian Bushfires Royal Commission; Powerline Bushfire Safety Taskforce: Final Report Chapter 3.4.1. GFN Rapid Earth Fault Current Limiter, Melbourne /Victoria 2011 [3] Winter K. et al: On-line Partial Discharge Detection on MV cable networks with GFN CIRED, Stockholm/ Sweden, June 2013 [4] IEC 60071-1: Insulation Co-ordination. Part 1: Definitions, principles and rules. 2006, 2010. [5] IEC 60071-1: Insulation Co-ordination. Part 2: Application Guide. 1996. [6] IEEE Fast Front Transients Task Force, Modelling and Analysis of System Transients. Working Group: Modelling Guidelines for Fast Front Transients, IEEE Trans. on Power Delivery, Vol. 11, No. 1, pp. 493-506, 1996. [7] CIGRE Working Group C4.4.02: PROTECTION OF MV AND LV NETWORKS AGAINST LIGHTNING. PART 1: COMMON TOPICS. CIGRE Brochure 287. February 2006. [8] CIGRE Working Group C4.407: Lightning Parameters for Engineering Applications. CIGRE Brochure 549. August 2013. [9] IEC 60076-3: Power transformers. Part 3: Insulation levels, dielectric tests and clearances in air. 2000 [10] IEC 60099-5: Surge arresters Part 5: Selection and recommendations. 1996, modified + A1: 1999. [11] BALESTRO: Overvoltage (TOV) capability Balestro 10 ka surge arrester. Mogi Mirim, Feb. 2011. CIRED 2015 5/5