C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

Similar documents
C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

Module Title: Electrical Installation II Laboratory Sheet:

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

Licensed Electricians Practical Assessment (LEP)

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Company Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations

Licensed Electricians Practical Assessment (LEP)

Les Hampson Cert Ed FSCTE, Chairman CAI Technical Committee

APRIL 2017 Level 3 Advanced Technical Diploma in Electrical Installation (450) Level 3 Electrical Installation Theory Exam

MinorWorks/Single Circuit Electrical Certificate

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

UNIT Earthing and Earth Fault Current Protection (SCQF level 6)

power Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.

ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET

CURRENT FUTURE REGULATIONS PROPOSALS

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

Grounding and Lightning arrestors

Company Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis

17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.

PROTECTION AGAINST FAULT CURRENT

ET 51 - Electrician Theory Examination Marking Schedule

2 Grounding of power supply system neutral

FAQ ON EARTHING STANDARDS 16/08/2018

Section 3. Test Procedures

TN, TT & IT Earthing Arrangements

ET 61 - Electrician Theory Examination Marking Schedule

Installation Tester BENNING IT 130. Operating Manual

Technical Certificate in Electrical Installation Version Sample September Question Paper Pack

Installation Tester BENNING IT 115. Operating Manual

Chapter 6. WIRING SYSTEMS Safe Electrical Design

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

Options to Improve the MEN System into the 21 st Century

Reference Number PDS 07 (RIC Standard: EP SP)

QUICK SETUP GUIDE SECULIFE IP

Earthing Guidance Notes

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

INSTRUCTION MANUAL MULTI-FUNCTION TESTER KEW 6016

ET 40 - Electrician Theory Examination Marking Schedule

GOSSEN METRAWATT. Testers

Portable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No

ELECTRICAL INSTALLATION CONDITION REPORT

G SAFETY WARNINGS. LT300 High current loop tester. User guide

So, let us investigate those parts of the Wiring Regulations that need to be considered in the early stages of the design procedure.

EI HIGH VOLTAGE INSULATION TESTING POLICY

MEGGER CM300 MK II, CM400 MK II & CM500

Multi-Function Installation Tester MEGGER CM500. User Guide MEGGER

ECP HV INSULATION TESTING

Automatic disconnection of lighting circuits from dimming equipment

400 Series. User manual

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

ELECTRICAL INSTALLATION CONDITION REPORT FOR A TELECOMS INSTALLATION

ENSURING PUBLIC SAFETY THROUGH PROPER EARTHING IN LOW VOLTAGE NETWORKS

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

ECP HV INSULATION TESTING

EurotestEASI MI 3100 SE MI 3100 s Instruction manual Version 1.1, Code no

Wiring of the Main Distribution Panelboard

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

Candidate Handbook answers

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

Industrial and Commercial Power Systems Topic 7 EARTHING

, Power Industries and Communications Industry Training Board

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

Stake-less earth / ground testing

C.A 6115N. Safety at all costs. IEE 16th: Electrical installation IEC/EN I E C. Insulation RCD. Earth. Loop. Continuity.

Operating manual Installation Tester BENNING IT 110 / BENNING IT 120 B

V1.3. TBLC08 50mH AC-LISN TBLC08

Grounding Recommendations for On Site Power Systems

IMP/010/011 Code of Practice for Earthing LV Networks and HV Distribution Substations

Education & Training

INSTALLATION WARNING: BEFORE COMMENCING INSTALLATION ISOLATE YOUR MAINS ELECTRIC SUPPLY

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

EurotestXE MI 3102H BT, MI 3102 BT Instruction manual Version 1.0, Code no

Testing Manual for Electrical Equipment

Measurements on electric Installations in theory and practice Instruction manual Code:

OPERATING MANUAL FAULT LOOP IMPEDANCE METER MZC-304

-(where thenl is mutual responsibility for the design)

U ACTIVE SAT DISTRIBUTION FIELD

Analysis of transfer touch voltages in low-voltage electrical installations

SECTION PANELBOARDS

EurotestCOMBO MI 3125 / MI 3125E Short instructions Version 2.2, Code no

1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact

TT W Wireless receiver Inline Switch

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

EARTH RESISTANCE TESTER

Instruction Manual for Digital Grounding Resistance Meter

CP CU1. Coupling unit for line and ground testing

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN

Chapter F Protection against electric shocks

Choosing the right Pico Technology active differential probe

ELECTRICAL POWER TRANSMISSION TRAINER

8PK-ST1520 Digital Earth Resistance Tester

Transcription:

C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Earth Fault Loop Impedance Tests 1

Revision Inspections are made to verify that the installed electrical equipment is in compliance with Standards, and in accordance with the regulations Prior to the testing, you must check the instrument is fit for purpose. There are two methods for testing the continuity of protective conductors. It is unacceptable to simply record a result, it needs to be reasonable. The insulation resistance test is used to verify that the insulation of conductors, accessories and equipment is acceptable (has a high resistance). Site applied Insulation test is quite rare and is only carried out when insulation has been applied on site. A polarity test is carried out to determine that the line conductor only is switched, to ensure the correct operation of accessories, and to ensure that in Edison Screw lamps, the centre-contact is connected to the line conductor.

Outcomes of this Session describe the earth fault loop impedance paths for TN-S, TN-C-S and TT systems describe the methods of carrying out earth fault loop impedance tests in terms of the tests used for measuring actual earth fault loop impedance and methods of calculation of earth fault loop impedance from given data and measurement of conductor impedance explain how the results should be compared with relevant data such as Table 41.2, 41.3 and 41.4 of BS 7671.

Earth Fault Loop Impedance Regulation 612.8.1 requires that the effectiveness of the measures for fault protection by automatic disconnection of supply is verified for TN- S, TN-C-S and TT systems. This verification can be determined by measuring or calculating the earth fault loop impedance of the circuits within an installation.

Typical TN-S Supply Earth (Terre) and Neutral Separate This is the newer type of TN-S system. This is a more traditional arrangement and is found in many older installations.

Equivalent Earth Fault Loop for a TN-S Supply A TN-S system usually has an external earth loop impedance of around 0.8 Ω. quoted by the distributor for both single and three phase supplies. The external earth loop depends on many factors such as length and cross-sectional area of the cable. The external fault loop is labelled Z e and the internal earth fault loop path is labelled (R 1 +R 2 ). When combined give the overall impedance of the fault current path. Z S = Z e + (R 1 +R 2 )

Typical TN-C-S Supply Earth (Terre) and Neutral Combined through part of the System This system has a combined neutral and earth in the supply cable, but at the consumers installation they separate, and are separated throughout the rest of the installation. Examples of this type of supply arrangement are PME (Protective Multiple Earthing) or PNB (Protective Neutral Bonding)

Equivalent Earth Fault Loop for a TN-C-S supply A typical value of a external loop impedance would be a maximum of 0.35 Ω for single-phase supplies. For three-phase supplies the figures vary.

TT Supply Earth to Earth (Terre - Terre) This system has no earth provided by the distributor, just the normal current carrying conductors. The consumer must supply their own earth via an earth electrode and RCD installed to 411.5.3. A typical figure for the external earth fault loop would be 21 Ω at the distributors transformer. This value covers the resistance of the neutral to earth, the impedance of the transformer winding and the line conductor.

TT Supply TT systems are most commonly found on farms and villages and are fed from an overhead supply system. They can also be found on petrol station forecourts. The loop on the distributor s side passes via the general mass of earth.

Testing Earth Fault Loop Impedance The most common form of testing for the earth fault loop impedance is using a earth fault loop impedance tester. You can also determine the earth fault loop impedance by calculation The earth fault loop test makes sure that the protective devices operate within the required time. (anything from 0.05 s to 5 s depending on where and what you are testing) There are a number of ways in which the earth fault loop impedance can be determined. Direct measurement using an earth fault loop impedance tester Measurement of (R 1 +R 2 ) and adding to a known value of Z e Zs=Ze+(R1+R2)

Test Points for Earth Fault Loop Impedance Testing When testing sockets, all socket-outlets should be tested, and the worse case result recorded (the highest Zs value). When testing lighting circuits, the end point (furthest point) of the circuit should be tested. Again, all lights on the circuit should be tested, and the worse case result (the highest Zs value) recorded. Be aware of the increased risk to others Earth Fault Loop Impedance Testing is a live test and the requirements of EAWR Regulation14 apply.

Two-lead Instrument at a D.B Testing at the end point gives you the total loop impedance of that circuit. This is labelled Z s. You will also need to test at the intake position and at each subsequent distribution board. This is the Earth Loop Test with a two lead instrument such as a Megger. One lead is connected to the incoming feed with the other connected to the Main Earthing Terminal (MET) Earthing and main protective bonding conductors should be disconnected for the test!

Three-lead Instrument at a D.B Instrument set for Z S This is the Earth Loop Test with three leads such as a Robin/Fluke. One lead is connected to the neutral or neutral block, one to the line, and the other connected to the MET. Earthing and main protective bonding conductors should be disconnected for the test!

Guidance Note 3 does not permit testing at the terminals of a motor. You must test on the supply side of the motor. Zs Motor circuits R1 + R2 The total earth-fault-loop impedance will be a combination of the impedance readings and those from the continuity test (R1 + R2).

Testing for Zs at the end of the circuit You should also; Make sure that you are taking the power for the meter from the circuit that you are testing. Remove the main equipotential bonding conductors.

Checking the Values Once measured, the earth-fault-loop impedance should be checked; For TN systems there are a number of options: For standard thermoplastic circuits, the values in Appendix B of the On-Site Guide and Guidance Notes 3 can be used. The designers own calculated figures. Table 41.2, 41.3 and 41.4 of BS 7671, after being corrected for temperature. (20 o C 70 o C) 1.2!!!!! Using the `rule of thumb method. (80% of max.values BS7671) Remember: Read the exam paper question carefully and use the method requested as per the given scenario!!!

Rule of Thumb The IET Guidance Note 3 provides a rule of thumb to operate if you don t want to work through all the factors. This is now agreed to be 80%. This reduction is an allowance for the fact that a measured Zs value is measured at an ambient conductor temperature of 20 o C. However, when under full load, the conductor temperature may rise to a maximum operating temperature of 70 o C, raising the final actual Zs value. This is done by: Determining the new corrected maximum tabulated value and comparing with the measured value. The new corrected maximum tabulated value must be greater than the measured value (measured @ 20 o C) in order to satisfy ADS!

Earth Loop (Zs) Test problems! An Earth Loop Impedance test instrument may cause an RCD, RCBO, or a 6 A Type B circuit breaker to trip when a circuit is under test. For an RCD, there are a number of solutions to this problem: Use a meter that has No-trip setting or effective D-Lok function Replace the RCD for the duration of the test (not a preferred option) with a circuit-breaker Measure the external impedance (Z e ) and add this value to the measured value of (R 1 + R 2 ) You must not short-out the RCD!! Similar solutions can be put in place to reduce the tripping of a 6 A BS EN 60898 type B circuit-breaker.

End of chapter 6 Earth Loop Impedance (Zs) An actual measured value of Zs would generally be lower than the calculated value due to the following factors: The presence of parallel paths due to the connection of protective bonding conductors Parallel paths through the steel conduit/trunking containment system The effect of the steel wire armour being in parallel with a conductor used as a cpc.