MARTINDALE INSTRUCTIONS. E-ZeTest EZ2500 LOOP TESTER ELECTRIC. Trusted by professionals. Other products from Martindale:

Similar documents
INSTRUCTION MANUAL MARTINDALE EZ150 / EZ650 SOCKET TESTER 1. INTRODUCTION. ELECTRIC Trusted by professionals

INSTRUCTION MANUAL LM192 LIGHT METER ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING CONTENTS. Precautions 1. SAFETY INFORMATION

Instruction Manual ET4 ELECTRICAL TESTER

INSTRUCTION MANUAL E1612 EARTH TESTER 1. INTRODUCTION

INSTRUCTION MANUAL LM195 LED LIGHT METER ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING CONTENTS. Precautions 1. SAFETY INFORMATION

AMM-1022 Digital Multimeter USER`S MANUAL

DIGIT & POINTER MULTIMETER

PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

1. SAFETY INFORMATION.1 2. DESCRIPTION SPECIFICATIONS.6 4. OPERATING INSTRUCTION Voltage measurement Current measurement 10

AC/DC CLAMP METER USER S MANUAL

Model DIGITAL MULTIMETER

DM-45 Digital Multimeter

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

MS8211 DIGITAL MULTIMETER INSTRUCTION MANUAL

DVM1190 DIGITAL MULTIMETER

DMM8900 SERIES USERS MANUAL

MS6231 DIGITAL ENGINE ANALYZER OPERATOR S MANUAL CONTENTS CONTENTS

3B SCIENTIFIC PHYSICS

MS8216 DIGITAL MULTIMETER OPERATOR S MANUAL

DIGITAL MULTIMETER INSTRUCTION MANUAL

G SAFETY WARNINGS. LT300 High current loop tester. User guide

KMD-S04 Multímetro de bolsillo

DVM645BI BENCH MULTIMETER TAFELMULTIMETER MULTIMETRE DE TABLE BANCO MULTÍMETRO TISCHMULTIMETER. User Manual. Gebruikershandleiding

USER MANUAL 600A AC Clamp Meter + NCV Model MA610

DVM98. True RMS Digital Multimeter. 1 Safety information. 1.1 Preliminary. 1.2 During use

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

USER'S MANUAL ACDC-100 TRMS ACDC-100. Versatile AC/DC Clamp-on Multimeter Series

80i-110s AC/DC CURRENT PROBE

DIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com # # AAC Clamp Meter. Instruction Manual

NOTE: Fully read and understand this manual before using this Digital Multimeter.

Model : OPERATING MANUAL Table of Contents (1)

USER'S MANUAL DMR-6700

INSTRUCTION MANUAL UTL260

Model UT10A: OPERATING MANUAL Table of Contents (1)

USER'S MANUAL. ACD-6 Pro. ACD-6 TRMS Pro. Versatile Clamp-on Multimeter Series

User Manual Digital Clamp Multimeter. model no.: MSR-C600

200Amp AC Clamp Meter + NCV Model MA250

400Amp True RMS AC Clamp Meter + NCV

USER'S MANUAL DMR-2400

30XR-A Professional Digital Multimeter Users Manual

Tablet Oscilloscope Safety Information

EM420A/420B DIGITAL MULTIMETER OWNERS MANUAL Read this owners manual thoroughly before use

ProfiScale MULTI Multimeter

CONTENTS MS2033A. 1.Introduction Safety Information...01

CONTENTS. SAFETY PRECAUTIONS: Before use, read the following safety precautions

Model UT20B: OPERATING MANUAL Table of Contents (1)

Multifunction AC/DC Voltage Tester

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

CD770 DIGITAL MULTIMETER INSTRUCTION MANUAL

AC FLEXIBLE CURRENT PROBE CA 3000

Model UT511 OPERATING MANUAL

CM605. User Manual AC/DC LOW CURRENT CLAMP-ON METER ENGLISH

PT-2000series AC/DCcurrentprobe PT-2710 PT-2720 PT-2740 PT-2770 MANUAL INSTRUCTION

MS2109A AC/DC Clamp Meter. User Manual. Contents

MS8250A/B OPERATION MANUAL MS8250A. Hz% FUNC REL RANGE REL HOLD OFF 10A. Hz% A NCV. Hz% COM. A ma 10A FUSED 600V CAT IV.

USER'S MANUAL DMR-4350

SAFETY PRECAUTIONS: Before use, read the following safety precautions

OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER

Internetowy sklep elektroniczny. Kontakt. Tel Tel. Kom Fax

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

DM-46 Instruction Manual

VIP ESI. Electrical Service Industry Voltage and Impedance Indicator. Instruction Manual & Specification

Model: PR-55. High Voltage Oscilloscope Probe 10 kv, 40 MHz USER MANUAL

User Manual Digital Multimeter. model no.: MSR-U1000

RAGU 81D DIGITAL MULTIMETER OPERATION MANUAL

1. SAFETY 1.1. SAFETY INFORMATION 1.2. SAFETY SYMBOLS

3B SCIENTIFIC PHYSICS

BC145 SIGNAL ISOLATOR BOARD

Thank you again for choosing AstroAI, if you have any questions or concerns regarding your product, please contact us at

HAWK5000 Operators Manual

Table of Contents Title Page

Dawson DDM181. Pocket-Size Autorange Digital Meter User s Manual

EurotestCOMBO MI 3125 / MI 3125E Short instructions Version 2.2, Code no

AC/DC DIGITAL CLAMP METER OPERATION MANUAL

Electrical Multimeter

OWNER S MANUAL HH0308C. AUTO-RANGING DC/True RMS AC DIGITAL MULTIMETER

POWER AMPLIFIER. Owner s Manual Mode d emploi Bedienungsanleitung Manual de instrucciónes CLIP SIGNAL TEMP PROTECTION POWER

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

MW3105 DIGITAL CLAMP MULTIMETER

OPERATOR S INSTRUCTION MANUAL

400Amp True RMS AC/DC Clamp Meter Model EX613

PA8HF power amplifier Operating guide

Compact Autoranging Clamp Meters. Models (400 A AC), (400 A AC/DC)

ETHOS 5030 TRUE-RMS DIGITAL MULTIMETER OPERATION MANUAL

Model ST Instruction Manual. True RMS Autoranging Digital Multimeter. reedinstruments. www. com

AM-510 Commercial / Residential Multimeter. AM-510-EUR Digital Multimeter. Users Manual

User s Manual. Miniature Passive Probe. IM EN 3rd Edition

User s Manual Current Probe. IM E 2nd Edition IM E

CANARY AUDIO. Power Amplifier CA-309 OWNER S MANUAL. Handcrafted in California MADE IN USA

INSTRUCTION MANUAL. Model Autoranging DMM ProbeMeter TM. Measures voltage, resistance, frequency, capacitance, temperature, and duty cycle.

HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

Analog Technologies. Multimeter 15B and17b

User Manual Digital Multimeter

MODEL W Power Amplifier

Operator s Manual. PP016 Passive Probe

AC/DC True RMS Power Clamp Meter ELECTRONIC TEST INSTRUMENTS MODEL 325

RIGOL. User s Guide. RP5600 Passive Probe. July 2010 RIGOL Technologies, Inc.

USER'S MANUAL DMR-4300

Transcription:

Other products from Martindale: 17th Edition Testers All-in-one s Calibration Equipment Continuity Testers Electrician s kits Full Calibration & Repair Service Fuse Finders Digital Clamp Meters Digital Multimeters Microwave Leakage Detects Mot Maintenance Equipment Non-trip loop testers Pat testers & Accessies Phase rotation Proving units Socket Testers Thermometers & Probes Test Leads Voltage Indicats Specialist Metrohm testers (4 & 5kV) Specialist Drummond testers INSTRUCTIONS Martindale Electric Company Limited Metrohm House, Imperial Park, Imperial Way, Watfd, Hertfdshire, WD24 4PP, UK Tel: +44(0)1923 441717 Fax: +44 (0)1923 446900 E-mail:sales@martindale-electric.co.uk Website: www.martindale-electric.co.uk Martindale Electric Company Ltd. 2016 Registered in England No. 3387451. Rev 5 E-ZeTest EZ2500 LOOP TESTER MARTINDALE ELECTRIC Trusted by professionals

SAFETY INFORMATION: Always read befe proceeding. WARNING These instructions contain both infmation and warnings that are necessary f the safe operation and maintenance of the E-ZeTest EZ2500. It is recommended that you read the instructions carefully and ensure that the contents are fully understood. Failure to understand and to comply with the warnings and instructions can result in serious injury, damage even death. In der to avoid the danger of electrical shock, it is imptant that proper safety measures are taken when wking with voltages exceeding 30 V AC rms, 42 V AC peak 60 V DC. The E-ZeTest EZ2500 must only be used under the conditions and f the purposes f which it has been constructed. Particular attention should be paid to these Warnings, the Precautions, the Technical Specifications and the use of the E-ZeTest EZ2500 in dry surroundings. Always check the E-ZeTest EZ2500 is in good wking der befe use and that there are no signs of damage to the unit. Do not use if damaged. Always inspect your meter, test leads and accessies f any sign of damage befe use. If any abnmal conditions exist (e.g: broken test leads, cracked case, display not reading, etc.), do not attempt to use it. Do not expose it to direct sunlight, excessive temperature moisture. Keep these instructions f future reference. Updated instructions and product infmation are available at: www.martindale-electric.co.uk SYMBOLS: Equipment complies with relevant EU Directives AC (Alternating Current) Ground Direct Current Equipment protected by Double Insulation (Class II) Caution - refer to accompanying documents Caution - risk of electric shock

4. MAINTENANCE 4.1 Cleaning The E-ZeTest EZ2500 may be cleaned using a soft damp cloth. Do not use abrasives, solvents, detergents, which can be conductive. Allow to dry completely befe using. 4.2 Repair & Service There are no user serviceable parts in this unit. Return to Martindale Electric Company Ltd if faulty. Our service department will quote promptly to repair any fault that occurs outside the guarantee period. Befe the unit is returned, please ensure that you have checked the unit and associated leads thoughly f flat batteries (check & replace), blown fuses (check & replace) and other po connections. 4.3 Stage Conditions The E-ZeTest EZ2500 should be kept in warm dry conditions away from direct sources of heat sunlight, and in such a manner as to preserve the wking life of the unit. It is strongly advised that the unit is not kept in a tool box where other tools may damage it. 5. WARRANTY The E-ZeTest EZ2500 is guaranteed against faults in manufacture and materials f 24 months from date of invoice and will be rectified by us free of charge, provided the unit has not been tampered with and is returned to us with its housing unopened. Damage due to dropping, abuse misuse are not covered by this guarantee. Batteries and fuses are not covered by this guarantee. Nothing in these instructions reduces your statuty rights. CONTENTS 1 Introduction 1.1 Description 1.2 Unpacking & Inspection 2 Specifications 3 Operation 3.1 Precautions 3.2 Description of Display 3.3 Using the E-ZeTest EZ2500 3.3.1 Connection 3.3.2 Self-Test 3.3.3 Phase Neutral and Earth Loop Impedance test 3.3.4 Wiring and Voltage Check 3.3.5 Repeat Measurements 3.3.6 RCD's in the Circuit Under Test 3.3.7 Possible Measurement Errs of Phase Neutral and Earth Loop Impedance 3.4 Table of messages 4 Maintenance 4.1 Cleaning 4.2 Repair & Service 4.3 Stage Conditions 5 Warranty 7

1. INTRODUCTION 3.4 TABLE OF DISPLAY MESSAGES 1.1 Description The E-ZeTest EZ2500 is a simple-to-use Earth Loop Impedance tester designed to make the accurate measurement of Earth Loop Impedance and Phase Neutral Impedance quick and easy. The E-ZeTest EZ2500 employs patented 'T Safe' nontrip technology to avoid tripping in-circuit Residual Current Devices (RCDs). Mains powered and free of batteries, the E-ZeTest 2500 is fully automatic, requiring no actions on the part of the user to complete a comprehensive check of the wiring, and to obtain an Earth Loop Impedance and Phase Neutral Impedance result displayed to 2 decimal places, in accdance with the requirements of BS 7671 17th Edition. If the wiring is faulty the mains supply voltage is below 198 Volts (<198V), above 264 Volts (>264V), appropriate err messages are displayed and the Earth Loop Impedance test and Phase Neutral impedance measurments are not perfmed. The unit measures and displays the mains supply voltage and mains frequency. 1.2 Unpacking and Inspection Befe unpacking the E-ZeTest EZ2500, examine the shipping carton f any sign of damage. Unpack and inspect the E-ZeTest EZ2500 and any associated leads f damage. If there is any damage then consult your distribut immediately. 2. TECHNICAL SPECIFICATION Martindale E-Ze Test (version) Martindale E-Ze Test EZ2500 Supply = xxx V Freq = xx.x Hz Ph-Neutral Loop Impedance = x.xx P-N Loop = x.xx PSC = xxxx Amp Phase-Earth Loop Impedance = x.xx PN CIRCUIT NOISE Consult manual PN > 3000 Ω FAULT PN too high PE CIRCUIT NOISE Consult manual Open Neutral Open Earth Phase Err P-N reversed P-E reversed N-E Voltage High Voltage Low / High Supply = xxx V Nominal Voltage Rating: 220-240 V Voltage Range f Wiring Err Detection: 30-275 V P-E Loop = x.xx Investigation Open Loop indication: If Open PE PN Loop is detected, no Impedance PFC = xxxx Amp required Measurement takes place Voltage Range f Impedance Measurement: 198-264 V Frequency: 50 Hz Loop Impedance Ranges: 0-8.99Ω, 9.0-89.9Ω,90-899Ω,900-1699Ω,1700-3000Ω Phase Earth Loop Impedance Accuracy: 0-8.99Ω, ± 4% ± 0.05Ω * 9.0-89.9Ω, ± 5% ± 0.5Ω * PE = x.xx PFC = xxx PE = x.xx PFC = xxx PE > 3000 Ω 90-899Ω, ± 5% ± 5Ω * PN = x.xx PSC = xxx PN = x.xx PSC = xxx 900-1699Ω ± 5% ± 30Ω* 1700-3000Ω indicative Phase Neutral Loop Impedance Accuracy: 0-8.99Ω, ± 4% ± 0.05Ω * PE CIRCUIT NOISE FAULT 9.0-89.9Ω, ± 5% ± 0.5Ω * Consult manual PE too high 90-899Ω, ± 5% ± 5Ω * 1 900-1699Ω ± 5% ± 30Ω * 1700-3000Ω indicative 6

3.3.6 RCD in the Circuit Under Test The E-ZeTest EZ2500 should not trip RCD's during the testing of wiring with in-circuit RCD's. Note, however, that many modern products have a constant low level of earth leakage, to ensure that noise and sted charge is dissipated, f example, 3mA earth leakage is typical f a desk-top computer. Note, also, that a 30mA RCD is guaranteed to trip at 30mA earth leakage, should not trip at 15mA, but is very likely to trip with earth leakage currents above 22mA. Therefe, caution should be exercised where earth leakage currents inherent in the circuit under test are approaching the trip threshold of the in-circuit RCD, f example where several computers are all connected to one ring circuit fitted with a 30mA RCD. Where tripping of the RCD may have a critical impact on the equipment connected to the supply, the RCD should be bridged temparily during the test. Ensure any bridging links are removed immediately the tests are completed. 3.3.7 Possible Measurement Errs of Earth Loop Impedance Where supply circuits under test have highly inductive capacitive components distributed on that circuit (such as mains filters), there is an excessive amount of mains disturbance present (e.g. mots running, rain shting exposed wires, a generat with high inductance supplying power, etc), it is possible the Phase Neutral and Earth Loop Impedance measurement could be adversely affected. The message PN CIRCUIT NOISE is displayed to indicate noise on the Phase Neutral wires. The message PE CIRCUIT NOISE is displayed to indicate noise on the Phase Earth wires. If the noise levels on Phase Earth are not adversely too high, an estimated Phase Earth Impedance measurement is displayed together with a circuit noise warning. When noise is a fact, always aim to physically unplug as many devices as possible from the circuit befe taking measurements to minimise inductive, capacitive and noise related effects. Voltage Accuracy: ± 4 % Frequency Accuracy: ± 4 % Temperature Range: -10 to 40 C at max 80 % Relative Humidity (Non-Condensing) Dimensions: 145 x 85 x 53mm + Cable Weight: 240g plus cable plus case Power supply: From mains Power consumption: < 1.6 W Overvoltage categy: Cat III/ 300V Pollution degree: 2 Supplied with: zip carry case, mains lead & instructions * Note:-Measurement accuracy can be affected by highly inductive capacitive components distributed on the supply (see section 3.3.7). 3. OPERATION 3.1 Precautions The E-ZeTest EZ2500 has been designed with your safety in mind, but please pay attention to the following warnings and cautions befe using the unit. Warning Befe use check the E-ZeTest EZ2500 f cracks any other damage. Make sure the unit is free from dust, grease and moisture. Also check any associated leads f damage. Do not use if damaged. DO NOT USE IN DAMP CONDITIONS. Warning If the E-ZeTest EZ2500 does not power-up, no messages appear on the LCD, this does not necessarily mean the circuit under test is dead. The phase supply may still be live, but the earth and neutral lines could both be open circuit. Always investigate such conditions with suitable care. Warning Always verify the E-ZeTest EZ2500 is in good wking der befe use, by testing it on a known crectly wired socket. Caution: Avoid severe mechanical shock vibration and extreme temperature. 3.2 Description of Display The E-ZeTest EZ2500 uses a two-row dot-matrix LCD to indicate mains voltage level, crectness of socket wiring and earth loop impedance, and to indicate a series of fault conditions that may exist. 5 See Table 3.4 f full list of messages and their inter-relationship. 2

3 3.3 Using the EZ2500 3.3.1 Connection It is recommended that testing is carried out, as far as it possible, on a circuit where all appliances are disconnected. Ensure you have read the Precautions (Section 3.1) befe proceeding. Plug the E-ZeTest EZ 2500 into the socket to be tested using the IEC lead supplied. Ensure the socket is switched on. View the messages on the display. If you are using the E-ZeTest EZ2500 with TL88 leads to test wiring, connect the green clip to earth, black to neutral and red to live in that der and then plug the TL88 lead into the IEC inlet socket of the E-ZeTest EZ2500. 3.3.2 Start Up Every time the E-ZeTest EZ2500 is plugged in it will, display a brief series of messages, befe it calculates and displays the Phase Neutral Loop Impedance, Phase Earth Impedance and related fault currents. Note: If the E-ZeTest EZ2500 display does not illuminate, this could mean that the supply voltage is less than 30V, could mean a simultaneous fault on both earth and neutral (see Precautions section 3.1). Verify the E-ZeTest EZ2500 in a known crectly-wired socket. If the E-ZeTest EZ2500 is shown to be functioning crectly, investigate the socket where a fault response occurred. 3.3.3 Phase Neutral & Earth Loop Impedance Test If the wiring is crect and the supply voltage of the circuit under test is between 198V and 264V the E-ZeTest EZ 2500 will perfm a Phase Neutral and Earth Loop Impedance check automatically. No interaction is required by the user; simply note down the Phase Neutral and Earth Loop Impedance value displayed at the end of the message sequence. 3.3.4 Wiring and Voltage Check If the E-ZeTest EZ2500 detects a fault condition in the wiring under test, the supply voltage is less than 198V (<198V) greater than 264V (>264V), the Earth Loop Impedance is greater than 3000Ω (>3000Ω) Phase Neutral Impedance is greater than 3000Ω, the LCD will display an appropriate message set of messages, accding to table 3.4. The Phase Neutral and Earth Loop Impedance measurements will not be displayed depending on err and noise conditions encountered whilst measuring. In such circumstances, always have suspect wiring investigated and unplug as many unnecessary appliances from the mains as possible. Note: It is always better to unplug an appliance completely rather than merely switch it off. Note: The E-ZeTest EZ2500 is designed to operate and detect faults if phase is available on any one of the three input pins and a neutral earth return is available on one both of the remaining two input pins. This ensures that the unit will alert the user to the need f investigation under a wide variety of wiring fault conditions. The fault messages that are displayed relate to the most common wiring faults. However, these common wiring faults share symptoms with other unusual faults that may exist. In such circumstances, the wiring fault could be different to that repted on the display. F example, the symptoms detected and displayed as a "phase neutral reversed" fault would also be present f a fault where the neutral was open between the distribution board and the socket under test and the neutral was shted to the phase within the socket under test. Therefe, always investigate wiring faults with care, testing f live voltages on all pins. Ensure that all wiring faults are rectified without delay. Note: An indicated low voltage value, a Voltage Low message, may be the result of a low supply voltage, be the result of a high impedance value on the incoming phase conduct. Note: As with all other testers, the E-ZeTest EZ2500 does not detect earth-neutral reversal. 3.3.5 Repeat measurements If the E-ZeTest EZ2500 is left plugged into a socket, the display will not be updated but will continue to show the last measured value of Phase Neutral and Earth Loop Impedance.To take a fresh measurement, disconnect the E-ZeTest EZ2500 from the supply then re-connect, to re-start the measurement process. 4