LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS

Similar documents
The Nature of Electric and Magnetic Fields 2017

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE

KEY WORDS: conductive, clothing, live, line, maintenance, high, voltage

IZAR RADIO. A safe form of radio

6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report

Specific Equipment and Area - EAC District Office Substation

PROBLEMS on Transformers

BEMFV. Order on the procedure for providing proof as regards limiting exposure to. electromagnetic fields

CHAPTER ELECTRIC AND MAGNETIC FIELDS

Appendix 6-F: Electric and Magnetic Field Study Report

WLAN. Date: 20 October 2016

Biljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010

DEP 2008 ELECTRIC AND MAGNETIC FIELDS CHAPTER ELECTRIC AND MAGNETIC FIELDS

YARRANLEA SOLAR PROJECT. Electromagnetic Radiation Assessment. Zenviron Document: 8013-EL-R

Electromagnetic Fields, Mobile Telephones and Health

VI 3 - i TABLE OF CONTENTS

ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION

Technical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure

Reducing personal EMF exposure

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

86 chapter 2 Transformers

Magnetic Field Meter BMM-5 user instructions

A Practical Guide to Free Energy Devices

Protection of Electrical Networks. Christophe Prévé

Precautionary Principle in Health Protection Policies regarding Electromagnetic Fields (EMF)

Research Activities Plan. Appendix K Magnetic Fields from Submarine Cables

Code of Practice for Proposed Mobile Phone Base Station Installations on University Premises.

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer

Analytical Design Optimization of 765 kv Transmission Line Based on Electric and Magnetic Fields for Different Line Configurations

Loss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

INCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

Guidelines to the standard EN

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Table of Contents. Introduction... 1

VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

Magnetic Field Meter EM-191

EN 62479:2010 ASSESSMENT REPORT WIN CHANNEL ELECTRONICS (HK) CO., LTD

Human Exposure Requirements for R&TTE and FCC Approval

Regulatory Framework for RF Safety in Mauritius

Health Issues. Introduction. Ionizing vs. Non-Ionizing Radiation. Health Issues 18.1

First South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June 2016

Workplace safety for demagnetizer operators

Tap Changer Analyzer & Winding Ohmmeter RMO25TD

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Electric and magnetic field levels around Christchurch

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

DESIGN OF A 45 CIRCUIT DUCT BANK

How to maximize reliability using an alternative distribution system for critical loads

AC Magnetic Field Survey Report

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

Copper Sheathed Cable Sheath Currents

Regulation GOVERNING AMATEUR RADIO STATIONS AND THEIR USE. Issued in Helsinki on 4 November 2009

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

New Methods to Mitigate Distribution System Harmonics

EMF risk for operators mounting, adjusting and maintaining base stations

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

BEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES

Partial Discharge, Survey or Monitor?

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

I -limiter The world s fastest switching device

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

ELECTROMAGNETIC SHIELDING PRODUCTS

Low Frequency. Precision test equipment for safety in electric and magnetic fields

Safety in electromagnetic fields. EMF Directive 2013/35/EU

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13

Placement Paper For Electrical

Appendix I. Applicant s Audible Noise and EMF Calculations

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Analysis of magnetic and electromagnetic field emissions produced by a MRI device

PHYSICS VCE UNITS 3&4 DIAGNOSTIC TOPIC TESTS 2017

High Voltage Overhead Power Lines, 21 Georgiou Eikosari, Dali

TS RES - OUTSTANDING ISSUES

MAGNETIC FIELD METER Operator s Manual

Distribution Network Capacitor Resonance A Case Study

BEFORE THE NEW JERSEY BOARD OF PUBLIC UTILITIES

EXPOSURE to electromagnetic fields (EMFs) is not a

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

ELECTRICAL POWER ENGINEERING

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

EN EMF REPORT For. Two way radio Model No.: RT-5R

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

Miniature substations: What they are really capable of delivering

RF EMISSIONS COMPLIANCE REPORT. Verizon Wireless. Report Status: Verizon Wireless is Compliant

The Role of the Grounding System in Electronics Lightning Protection

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

Selective and broadband low frequency field analysis

ANALYSIS OF OPERATION MODE AND PERFORMANCE INDICATORS OF A TRANSFORMER WHEN CONTROLLING ITS VOLTAGE WITH AN ALTERNATING MAGNETIC FLUX

TECHNICAL REQUIREMENTS FOR ELECTROMAGNETIC DISTURBANCES EMITTED FROM LIGHTING EQUIPMENT INSTALLED IN TELECOMMUNICATION CENTERS

Effects of Harmonic Distortion I

Tech Byte 16: The Truths About Transformers Part 2

Alternating-Current High-Voltage Power Vacuum Interrupters Safety Requirements for X-Radiation Limits

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

I. DRAFT G E N E R A L M E A S U R E

TABLE OF CONTENT

Safety Code 6 (SC6) Measurement Procedures (Uncontrolled Environment)

Transcription:

LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS Peter Leipold, Klaus-Peter Panzlaff Bewag Aktiengesellschaft, Puschkinallee 52, D-12435 Berlin Tel.: +49 30 267 10 350 - Fax: +49 30 267 10 352 - E-mail: Panzlaff.Klaus-Peter@bewag.com ABSTRACT In 1997, a new regulation on emission protection (26 th BImSchV) (amending the Act on protection of the environment against harmful effects through air pollution, noise, vibrations and similar factors) came into effect in Federal Germany. It includes directions for compliance with maximum permissible emission levels for electrical and magnetic fields. These requirements are intended as a precaution to protect the general public against potentially harmful effects of low-frequency fields. They are so low, that only multiples of these limits could have an influence on living organism. Damages to humans is inconceivable. Investigations at secondary (h.v/) substations operated by Bewag have shown that these emission limits are, in general, not exceeded. But they are near the limit of the requirement. However, even though the legally required limits are respected, there are electromagnetic fields of much lower strengths that have an influence on PC s by reason of the kind of function of the PC. Therefore, it is recommended to make use of any available cost-effective means of reducing emissions to the lowest possible level when new secondary substations are built. This is why EMF-optimized secondary substations have been developed in conjunction with switchgear manufacturers. The improvements are described in the present report. As a result of these efforts, magnetic fields generated in newly designed stations were reduced to values which represent only a fraction of the legally prescribed standard. For example, magnetic alternating fields which are measured 3.5 m above the station floor exhibit values which exclude any impact on even older personal computers. The above-mentioned electromagnetic compatibility was achieved without any high cost increases for station equipment for new installed stations. However, where this effect is required to be built into existing facilities, the necessary reconstruction work will be quite cost intensive. magnetic field is created as soon as an electric current flows. The field strengths of both rapidly decrease as the distance to the source of their generation increases. Natural fields have always existed on earth. For example, there is electric fields in the atmosphere - the cause of thunderstorms - or the natural magnetic field of the earth. In the low-frequency range, the technically generated fields are often much stronger than those natural fields which occur in the environment. They are created when electrical energy is generated, distributed and used. Publications on the effects of electric and magnetic fields on man and electrical appliances as a result of the operation of electrical installations have caused insecurity and confusion among some people. 'Electrosmog' is the term the media frequently uses, although it is physically incorrect. According to the opinions of scientists, the fields caused by normal devices of which we are always surrounding ourselves cause no damage for humans. They are measurable by sensitive measurement devices. 2 GERMAN LEGISLATION To protect human beings from harmful effects of electric and magnetic fields, the Federal German Law on Emission Protection stipulates consent limits. They are ultimately based on the recommendation given by the ICNIRP (International Committee on Non-Ionizing Radiation Protection) that the current densities caused by fields in the human body should be lower than 2 ma/m 2. The above-mentioned precautionary base limit has been used to derive consent limits for exterior electric and magnetic field strengths at a frequency of 50 Hz for protection of the general public and the neighborhood against harmful environmental impacts. These limits are given in the above-mentioned German Emission Protection Act as follows: 1 PROBLEM DESCRIPTION Basic life has positively changed since electricity has been used in the form of mechanical work, heat or light. The use of electrical energy has brought on electrical and magnetic fields which mostly occur as alternating fields. An electric field is created under any energized electrical conductor. A

Low-frequency facilities Frequency in Hertz (Hz) Effective value of electric field strength and magnetic flux density Electric field strength in kilovolts per meter (kv/m) Magnetic flux density in micro tesla (µt) This leaves the distribution switchboard and its connection to the distribution transformer as the main magnetic field-producing component in secondary substations. It is here where the high currents occur which are necessary for the generation of strong magnetic fields. In its existing facilities, Bewag usually complies with legal requirements for magnetic field strengths of 100 T outside the station rooms even without applying any special measures. This is demonstrated in the following schematic drawing (figure 1). 50 Hz fields 16 2/3 Hz fields 5 10 100 300 max 100 µt Table 1 This ordinance defines low-frequency facilities as 'stationary installations for transformation and transmission of electrical energy at a voltage including and above 1000 V'. Commissioning of such facilities has to be reported to authorities, and compliance with consent limits has to be proven to them (table 1). h.v.- compound transformer max 100 µt After a three-year transitional period, the above-mentioned directions will also apply to existing installations already in operation. With the low limits of the German legal requirements, we have the full protection of humans. Also, these are not very high hurdles for the beneficial use of electric energy. 3 THE SECONDARY SUBSTATION AS A SOURCE OF MAGNETIC FIELDS As electric fields do not reach considerable sizes even in old secondary substations, all further observations can be restricted to magnetic fields. Figure 1 3.1 Measurement in a non-accessible substation with a 400 kva distribution transformer A magnetic field measurement, at a rated voltage of 6kV/0.231kV and a 556 A to 618 A transformer actual load current, revealed the following field distribution (table 2): A secondary substation consists essentially of three components: the high-voltage switchgear, the transformer and the low-voltage distribution. At nominal output, the individual components contribute to the emitted magnetic field in varying degrees. As a result of the high voltage in the h. v. area, the currents flowing there are relatively small. The magnetic fields found there are therefore of low intensity. The transformer similarly emits very small magnetic fields. This is due to the fact that it is built to keep down transformer losses as much as possible. To achieve this, it is necessary to chose transformer designs which generate a minimal stray field and consequently a minimum outgoing magnetic field.

0.20 m Station top view 1 2 3 4 I/A B/µT 800 80 13 14 5 magnetic field strength = µt 12 High voltage 16 17 18 19 20 15 Low voltage 6 7 1/2 of the station width 700 70 11 10 9 8 600 60 each time 1/6 of the station length actual load current = A Measuring points : 0.45 m ; 0.90 m ; 1.55 m above ground of the roof 09:57:39 09:58:39 09:59:39 10:00:39 10:01:39 10:02:39 10:03:39 10:04:39 10:05:39 10:06:39 time Figure 2 The safety of this kind of old secondary substation is not in question. It is impossible to effect people with the strength of magnetic fields of this substation. Table 2 3.2 Time characteristic of magnetic field strength and actual load current In another measurement, the time characteristic of the magnetic field strength was recorded as a function of the actual load current at measuring point no. 6 at a height of 0.9 m (figure 2). Rated voltage: Rated power: Rated current: 6 kv/0.231 kv 400 kva 38.5 A / 1000 A 4 SPECIAL MEASURES FOR REDUCING MAGNETIC FIELDS IN THE CONSTRUCTION OF NEW SECONDARY SUBSTATIONS The emission of magnetic fields can be reduced by the following measures: Prevent creation of an outgoing magnetic field (by utilizing the balancing three-phase effect), Measure type A Keep the distance between the emission source and the place of emission as large as possible, Measure type B Keep the strength of currents flowing in the electrical installations and thus the generation of magnetic fields as low as possible, Measure type C Keep the field-generating effective lengths of energized conductors as short as possible, Measure type D

4.1 Increasing the distance between the bus bar and the ceiling of the room (Measure type B) 4.3 Decrease the length of the coupling between transformer and l. v. distribution box (max 1 m) (Measure type B) The maximum height of the unit should not exceed 1.6 m. ceiling packaged design appx 75 cm h.v. compound Figure 3 appx 85cm h.v. compound station floor By way of increasing the space between the h.v. compound (emission source) and the room above of the station unit (place of emission), a lower magnetic field strength is experienced (figure 3). 4.2 Use of custom-designed transformers with connections fitted at the bottom (EMF transformer) (Measure types B and D) Figure 5 max 1 m If no EMF-optimized transformer is available, it should at least be provided for connection lines to be kept as short as possible (figure 5). 4.4 Arrange conductors of connections in such a way that the fields cancel each other as much as possible, e.g. by twisting of the individual wires (Measure types A and B (Figure 6) An EMF reduction is achieved by using an EMF transformer. max 1 m Figure 6 max 1 m Figure 4 Current-carrying wires should be fitted in a maximum possible distance from the ceiling (see 4.1). Currentcarrying connections between components, in this case the distribution and the outgoing unit of the transformer should be as short as possible. This is why the system components are put up close to each other, and the outgoing units on the l. v. side of the EMF-optimized transformer are fitted close to the bottom of the transformer rather than on the cover as usual (figure 4). 4.5 Three examples for how the distance between bus bars can be reduced (Measure type B) Figure 7

The emitted resulting magnetic field can be restricted by modifying the spatial arrangement of the bus bars of a three-phase current system on a l. v. switchboard. This effect can be best achieved by turning the bus bars through 120 and arrange them in a staggered way. The second best effect is obtained by arranging bus bars with smaller spaces between them (figure 7). 4.6 Symmetrical structure of the low-voltage distribution with central supply (Measure type C) 5 PROOF OF THE REDUCTION OF MAGNETIC FIELDS IN AN EMF-OPTIMIZED LOCAL AREA NETWORK STATION To compare, the differences are shown in the magnitude of the magnetic fields for 1) a conventional EMF Non- Optimized Network Station, 2) for an EMF Optimized Station with a Conventional Distribution Transformer and 3) for an EMF-Optimized Station with EMF- Optimized Distribution Transformer. Proportionally, EMF Optimized stations indicate significantly smaller magnetic field strengths. Transformer 800A 5.1 Non EMF-Optimized Station with a 630 kva Distribution Transformer 100A 200A 300A 400A 400A 300A 200A 100A Calculated Voltage: Calculated Current: Measuring Point Reference: 10/0,4 kv 1000 A Height of the station floor 100A 100A 100A 100A Figure 8 100A 100A 100A 100A a b c d e f g 7 + + + + + + + distribution 6 + + + + + + + Central supply to bus bars of the l. v. distribution helps at best to halve partial currents on bus bar sections (figure 8). 4.7 Arrange the most-loaded feeders directly beside the supply point (Measure types C and D) 5 + + + + + + + 4 + + + + + + + transformer 3 + + + + + + + 2 + + + + + + + Transformer 100A 350A 700A 350A 100A 1 + + + + + + + Figure 10: Measuring Points (Measured Distance = 1 m) The maximum values occur within the area of the lowvoltage distribution board at the measuring points 7/d. They are represented in Table 3 in relation to the given height over the station floor. Figure 9 Reserve 100A 250A 250A 100A Reserve When the highest-power outgoing feeders are arranged close to the supply point of the bus bar system, the length of those bus bar sections which carry heavy currents is reduced (figure 9). Height Maximum Value 1.0 m 760.5 µt 2.0 m 387.9 µt 3.0 m 170.4 µt 3.5 m 98.0 µt Table 3: Maximum Values in µt

a b c d e f g 7 14.1 30.4 60.5 98.0 60.1 30.7 15.1 6 25.4 49.1 88.2 90.0 87.9 48.9 25.4 5 16.7 30.2 57.9 87.5 58.1 30.1 17.3 4 11.2 25.7 58.4 88.5 59.2 28.4 12.1 3 8.7 22.1 46.1 58.7 45.9 22.7 9.5 2 4.0 14.8 30.7 31.5 30.4 11.2 4.3 1 2.5 3.2 7.9 18.5 8.1 3.2 2.1 Table 4: Field Distribution (µt) at 3.5 m High 5.2 EMF-Optimized Station with 630 kva Distribution Transformer Calculated Voltage: Calculated Current: Measuring Point Reference: 10/0,4 kv 1000 A Height of the station floor a b c d e f g 7 + + + + + + + 6 + + + + + + + 5 + + + + + + + EMF- 4 + + + + + + + transformer 3 + + + + + + + 2 + + + + + + + 1 + + + + + + + Figure 11: Measuring Points The maximum values occur within the area of the lowvoltage distribution board at the measuring point 4/d. They are represented in Table 5 in relation to the relative highest values of Table 3, section 5.1. The values are given in percentages. Table 5: Height Maximum Value 1.0 m 12.47 % 2.0 m 11.70 % 3.0 m 2.58 % 3.5 m 1.90 % Maximum values, in percent, as relative to Table 3 in section 5.1 5.3 EMF-Optimized Station with 630 kva EMF- Transformer Calculated Voltage: Calculated Current: Measuring Point Reference: 10/0,4 kv 1000 A Height of the station floor a b c d e f g 7 + + + + + + + 6 + + + + + + + 5 + + + + + + + EMF- 4 + + + + + + + EMF-t ransf. 3 + + + + + + + 2 + + + + + + + 1 + + + + + + + Figure 12: Measuring Points The maximum values occur within the area of the lowvoltage distribution board at the measuring point 4/d. They are represented in Table 6 in relation to the relative highest values of Table 3, section 5.1. The values are given in percentages. Table 6: Height Maximum Value 1.0 m 5.64 % 2.0 m 4.62 % 3.0 m 1.15 % 3.5 m 1.00 % Maximum values, in percent, as relative to Table 3 in section 5.1