INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Similar documents
Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time

Two variable ac current, variable phase-angle sources Variable dc voltage/current source and latch timer Variable harmonic current source

which is used to shift the phase angle between the two sets of coils to produce torque.

which is used to shift the phase angle between the two sets of coils to produce torque.

Type KLF Generator Field Protection-Loss of Field Relay

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

GEI-98328J. INSTRUCTiONS DIRECTIONAL DISTANCE (REACTANCE RELAY) TYPES. GCX51A Forms 11 and up. GCXS1B Forms 11 and up GENERAL ELECTRIC

GEK-27887[f INSTRUCTIONS LOSS OF EXCITATION RELAY TYPE CEH51A. NAMI hi 15*. GE Meter and Control 205 Great Valley Parkway Malvern, PA

A. Photo #9664A14. Figure 1. Type KS-3 Out-of-Step Blocking Relay Without Case

O V E R V I E W O F T H E

Digital Interface Card DEC005000

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

Power systems Protection course

Type CVX and CVX-1 Synchro-Verifier Relays

COPYRIGHTED MATERIAL. Index

Sealed Interface Control: EC20300

815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS

Spring Return DuraDrive Proportional Actuator

! CAUTION D TABLE 1

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

Setting and Verification of Generation Protection to Meet NERC Reliability Standards

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

Generator Advanced Concepts

Synchronism Check Equipment

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET.

PEAKTRONICS AMC-103 ADDITIONAL FEATURES. AC Motor Controller, 2A AMC-103 AMC-103A AMC-103B

GEK-45441C Supersedes GEK-45441L INSTRUCTIONS MHO AND AUXILIARY RELAY. for OUT-OF-STEP PROTECTION TYPE GSY51A GENERALS ELECTRIC

AMC-100 AMC-101 AMC-100 AMC-100B AMC-100D AMC-101 AMC-101B AMC-101D AMC-100A AMC-100C AMC-100E AMC-101A AMC-101C AMC-101E. AC Motor Controllers

WD series DIN Rail or Screw Mounted Protective Relays

Built-in soft-start feature. Up-Slope and Down-Slope. Power-Up safe start feature. Motor will only start if pulse of 1.5ms is detected.

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

Type CA Percentage Differential Relay for Transformer Protection (50 and 60 Hertz)

AGASTAT E7000 Series, Nuclear Qualified Time Delay Relays

BLD75-1. Bilevel Step Motor Driver. User s Guide. #L010125

Astro-Physics Inc. 400QMD Lubrication/Maintenance Guide

400GTO Lubrication Guide

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW

Static Breaker Back-up Relay Type SBC Relay SBC231B

FEATURES OPTIONAL FEATURES

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

DR3535 DR3535-O. Hardware Reference Manual. Document Revision A7 May 16, 2018 MICROKINETICS CORPORATION

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

Thornwood Drive Operating Manual: Six-SCR General Purpose Gate Firing Board FCOG6100 Revision R

SINGLE-PHASE VSV SWITCH

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

TRANSFORMERS INTRODUCTION

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

GEK-45405G INSTRUCTIONS DIFFERENTIAL VOLTAGE RELAYS TYPE S PVD21A PVD21B PVD21C PVD2ID GENERAL ELECTRIC

J POWER SYSTEMS MANAGEMENT DEPARTMENT GENERALS ELECTRIC. Insert Booklet GEK DIRECTIO1AL DISTANCE RELAY 1YPE CEY MODEL 12CEYG51B(-)D INTRODUCTION

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

1525-BRS INFORMATION MANUAL SERV O D YN A M ICS. D y n ad r iv e Ave Crocker Suite 10 Valencia, CA

GROUND DISTANCE RELAY

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

CATALOG & INSTRUCTION MANUAL. Type LJ High Speed Auxiliary Relays

NERC Protection Coordination Webinar Series June 30, Dr. Murty V.V.S. Yalla

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

INSTRUCTIONS YASKAWA. Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain for future reference.

Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping R. Table 1:

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GE K-45307K TRANSFORMER DIFFERENTIAL RELAYS WITH

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Fisher 667 Diaphragm Actuator Sizes 30/30i 76/76i and 87

Type VDG 13 Undervoltage Relay

Generator Protection GENERATOR CONTROL AND PROTECTION

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

The object of these Operating Instructions is to assist you in the correct safe and economical use of the TORSIOMAX torque screwdriver.

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

Turret covers. Rear turret cover

BFS / BFSM SERIES Installation & Maintenance Manual

INSPECTION AND CORRECTION OF BELLHOUSING TO CRANKSHAFT ALIGNMENT

Variable Transformers Product Design & Engineering Data

SETUP and OPERATING MANUAL ADVANCED MULTI-CHANNEL VEHICLE INTERCOM SYSTEM (AMCVIS)

Potentiometer Control EC20200

BME/ISE 3511 Bioelectronics I - Laboratory Exercise #4. Variable Resistors (Potentiometers and Rheostats)

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

MIL-PRF-83536/5C 08 June 2010 SUPERSEDING MIL-PRF-83536/5B 04 December 2008 PERFORMANCE SPECIFICATION SHEET

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

ELECTRIC TOOL CORPORATION

Adjusting Backlash on Sherline handwheels

HOLE CUTTER SHARPENER ASSEMBLY & SERVICE MANUAL

System Protection and Control Subcommittee

PROTECTION of electricity distribution networks

LAMBDA EMI 405 ESSEX ROAD, NEPTUNE, NJ 07753

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

GENERALS ELECTRIC INSTRUCTIONS POWER SYSTEMS MANAGEMENT DEPARTMENT PHILADELPHIA, PA. GEK Insert Booklet GEK RESTRAINT CIRCUITS

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

Lab #2 Voltage and Current Division

Switch-on-to-Fault Schemes in the Context of Line Relay Loadability

SINGLE-PHASE VSV SWITCH

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

SPECIFICATION, CONTROLS AND ACCESSORIES

6CARRIER-CURRENT-PILOT AND MICROWAVE-PILOT RELAYS

INSTRUCTION MANUAL FOR VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G

Style FR HI Shunt Track Unit

Transcription:

CEH51A SCOPE This test procedure covers the testing and maintenance of the GE CEH51A loss of excitation relay. Refer to IL GEK-27887 for testing support information and component level identification. DESCRIPTION The GE CEH51A relay is a single phase, single zone, offset mho distance type relay. The relay is designed to detect a loss of excitation on synchronous machines. An offset mho characteristic was chosen to provide selectivity between loss of excitation and other normal or abnormal conditions that may exist on the system. A 66-83 millisecond fixed time delay auxiliary unit is employed to prevent undesired tripping due to shock, vibration, or sudden complete loss of AC potential. TOOLS, EQUIPMENT, AND MATERIALS Two variable ac voltage / current, variable phase-angle sources Variable dc current source INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it. 2. Pull the relay connecting plugs to disable the trip circuit and remove the current inputs and lift the relay out of the case. 3. Visually check the relay for any obvious problems and clean the relay thoroughly. 4. Burnish the surfaces of all contacts, making sure to remove any tarnish. 5. Check that all relay connections are tight. 6. Check that there is end play in the shaft of the rotating structure. Total end play should not be more that 0.012 inch. The lower jewel screw bearing should be screwed in firmly and the top pivot locked in place by its set screw. 7. Check that the, against the backstop, contact gap is between 1/16 and 3/32 inch. 8. Check that the moving contact arm rotates freely and that the control spring provides enough opening torque toward the right hand backstop to hold the contact definitely open. Adjust the control spring as necessary.

SETTINGS There are two settings that must be made on the CEH51A relay, the offset tap setting and the circle diameter restraint tap setting. The offset tap is made directly in terms of secondary ohms via the L and H leads on the offset tap block. Settings can be made in the range indicated on the nameplate in 0.5 ohm steps. The offset setting is equal to the difference between the two offset taps used (H L and the H tap must be on a larger tap) Example: Desired offset setting = 3.5 ohms L lead = 0.5 H lead = 4.0 The circle diameter is set via the upper and lower leads on the restraint tap block. The tap setting is expressed in percent and is a function of the basic minimum diameter of the relay and the desired ohmic diameter in secondary ohms and is adjustable from 0 to 100 percent in 1 percent steps. NOTE: The setting should never be set below 10 percent Restraint Tap Setting % = (Basic minimum diameter) * 100 / (Desired diameter) Example: Basic minimum diameter (nameplate) = 5 ohms Desired diameter = 27 ohms Restraint Tap Setting % = 5 * 100 / 27 = 18.5% Use the next lower tap = 18% Upper number one lead = tap 8 Lower number one lead = tap 10 In the above example, the restraint tap setting calculated to 18.5% and the next lower tap of 18% was selected creating a diameter of 27.8 ohms. If a closer setting is desired, adjustments to the autotransformer tap settings can fine increase the restraint tap (and fine decrease the diameter) up to 10% in one percent steps. The input tap leads are attached to the restraint tap block with hex head screws. The input tap setting is equal to the sum of the two input taps used usually set to 100% (upper lead at 10 percent and lower lead at 90 percent) Input tap % = (Restraint tap) * (Desired diameter) / (Basic minimum diameter) Example: Input tap = 18 * 27 / 5 = 97.2 % Upper lead = 7 Lower lead = 90 (this lead should not be moved) Diameter = (Basic minimum diameter) * (Input tap) / (Restraint tap) Final diameter = 5 * 97 / 18 = 26.94 ohms 2

PRE-TEST SETUP 1. Connect a variable ac current source to terminals 5 and 4 with the polarity lead going to terminal 5. 2. Jumper terminal 6 to terminal 3. 3. Connect a variable ac voltage source to terminals 7 and 8 with the polarity lead going to terminal 7. 4. Apply rated DC voltage to either terminals 1(+) and 10(-) (higher rated dc voltage) or to terminals 1(+) and 9(-) (lower rated dc voltage). Check the nameplate to determine the control voltage options. 5. Monitor contact continuity at terminals 1 and 2. 6. Initiate rated ac voltage and allow the potential coils to warm up for 15 minute prior to starting the test. 7. When choosing a test fault voltage, choose a level that will prevent an impedance over range of the test set in use and keep the test current in the order of 20 amps or less. The continuous current rating of this relay is 5 amps and the one second thermal rating is 150 amps. The CEH relay utilizes a phase to phase impedance element using the following characteristic formulas: Z = E ph to ph / (2 * I) I = E ph to ph / (2 * Z) TESTING THE MAXIMUM TORQUE ANGLE NOTE: Any adjustments made to bring the MTA into tolerance will have an affect on the characteristic diameter. Ensure that the diameter is tested after any MTA adjustments. 1. Adjust the current phase angle so that the current is leading the voltage by 90 degrees. 2. Calculate test values Choose an impedance point within the characteristic between the offset impedance and the total impedance to the outside diameter. Example Diameter Offset Total impedance to outside of diameter Midpoint of characteristic Selected voltage I pickup = 115 / 2 * 14.5 = 27 ohms = 1 ohm = 28 ohms = 14.5 ohms = 115 volts = 3.97 amps 3. Initiate voltage and current at the selected values. 3

4. Vary the current phase angle until the relay drops out in the clockwise and counterclockwise directions. The average of the two drop out angles is the maximum torque angle and should be in the range of 88 to 92 degrees. 5. If the MTA does not meet specifications the following adjustments can be made: Adjust variable reactor X21 (top adjustment screw, lower left front) in the polarizing circuit Increasing reactance (cw) will decrease the MTA Decreasing reactance (ccw) will increase the MTA Adjust variable resistor R22 (upper right) in the shading coil circuit Increasing the resistance (cw) will decrease the MTA Decreasing the resistance (ccw) will increase the MTA TESTING THE DIAMETER 1. Adjust the current phase angle so that the current is leading the voltage by 90 degrees. 2. Calculate test values The total impedance to the outside of the diameter will equal the diameter setting plus the offset setting. (see Figure 1) Example Diameter Offset Total impedance to outside of diameter Selected test fault voltage I pickup = 115 / 2 * 28 = 27 ohms = 1 ohm = 28 ohms = 115 Vac = 2.05 amps 3. Initiate voltage at the selected value. 4. Pulse initiate current below expected pickup and pulse raise until the relay just picks up. 5. If the measured pickup current varies by more than 10% (+/-) adjust variable resistor R13 (bottom adjustment screw, lower left front) in the restraint coil circuit. Decreasing resistance (ccw) will decrease the diameter Increasing resistance (cw) will increase the diameter 6. Configure a timer to start when the current is applied the relay and stop when the output contact from terminals 1 and 2 close. 7. Initiate voltage at the selected value and current at 2 times the outside diameter pickup. The time delay should range from 66 to 83 milliseconds and is designed to prevent inadvertent tripping due to shock, vibration or loss of AC potential. This is a fixed time delay in the auxiliary unit. There is no adjustment. Testing has shown that this time may as much as 100 ms at lower pickup currents and will be in tolerance with higher multiples (4 times and up) 4

TESTING THE OFFSET 1. Adjust the current phase angle so that the current is leading the voltage by 90 degrees. 2. Calculate test values The offset impedance is the point at which the inside diameter contacts the y axis. (see Figure 1) Offset impedance Selected voltage I pickup = 40 / 2 * 1 Example = 1 ohms = 40 Vac = 20.0 amps 3. Initiate voltage at the selected value. 4. Initiate current just below the expected pickup (the contacts will close), raise until the relay just drops out, then lower the current to the pickup point. 5. The measured pickup current should not be more than 10% (+/-) from the calculated current. There is no adjustment to the offset impedance. The offset taps are determined by the turns of the current transactor. CHECKING THE CLUTCH The induction cup assemblies are designed with a slipping clutch mechanism that allows the cup and shaft to slip with respect to the moving contact whenever the torque in the opening or closing direction becomes greater than 50 grams pressure. Specialty tools are required for this test. If testing or adjustments to the clutch are deemed necessary, refer to IL GEK-27887 page 19, CLUTCH ADJUSTMENT for specific instructions. TESTING THE TARGET AND SEAL IN 1. Determine whether the relay is set for 0.2 amps or 2 amps by observing the tap block in the front of the target unit. 2. Disconnect the DC voltage. 3. Close the main relay contacts manually or by applying sufficient ac voltage and current quantities. 4. Manually pickup the auxiliary unit 5. Apply DC current below the pickup setting to terminals 1-2 and ramp up until the target unit picks up. 5

6. For the 0.2 amp setting, the pickup should be between 0.14 and 0.195 amps DC. For the 2.0 amp setting, the pickup should be between 1.40 and 1.950 amps DC. 7. Open the relay contacts manually or by removing test quantities and drop out the auxiliary unit. 8. Verify that the target unit remains sealed in. 9. Determine the drop out by ramping the DC down until the seal-in contacts open. Drop out should be no lower than 30% of the seal-in tap (0.06 for the 0.2 setting, 0.6 for the 2.0 setting). 6

Figure 1 CEH51A relay characteristics with various restraint taps and one ohm offset 7

Figure 2 CEH51A internal schematic 8