SIMULATION OF D-STATCOM IN POWER SYSTEM

Similar documents
Performance of DVR & Distribution STATCOM in Power Systems

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Performance of DVR under various Fault conditions in Electrical Distribution System

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Power Quality Improvement in Distribution System Using D-STATCOM

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Power Quality enhancement of a distribution line with DSTATCOM

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

A Review on Improvement of Power Quality using D-STATCOM

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

ISSN: ; e-issn

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

Power Control Scheme of D-Statcom

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads

Voltage Sag Mitigation of DVR using Matlab Simulation

SIMULATION OF DSTATCOM FOR POWER FACTOR IMPROVEMENT

Improvement of Power Quality Using a Hybrid Interline UPQC

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Enhancement of Power Quality in Distribution System Using D-Statcom

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Power Quality Improvement using Hysteresis Voltage Control of DVR

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

D-STATCOM FOR VOLTAGE SAG, VOLTAGE SWELL MITIGATION USING MATLAB SIMULINK

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Simulation and Implementation of DVR for Voltage Sag Compensation

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

Analysing the performance of D-Statcom in mitigating transients from distribution system

Power Quality and the Need for Compensation

Design and Development of DVR model Using Fuzzy Logic Controller for Voltage Sag Mitigation

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

COMPARITIVE STUDY ON VOLTAGE SAG COMPENSATION UTILIZING PWM SWITCHED AUTOTRANSFORMER BY HVC

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

Improvement of Dynamic Voltage Restorer (DVR) Using Proportional Integral (PI)Controller for Mitigation of Voltage Sag

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Improvement of Power Quality Considering Voltage Stability in Grid Connected System by FACTS Devices

Mitigation of Voltage Sag and Voltage Swell by Using D-STATCOM and PWM Switched Autotransformer

FUZZY LOGIC CONTROL BASED DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY IMPROVEMENT IN DISTRIBUTION SYSTEM

Protection from Voltage Sags and Swells by Using FACTS Controller

Investigation of D-Statcom Operation in Electric Distribution System

Mitigation of Faults in the Distribution System by Distributed Static Compensator (DSTATCOM)

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

ISSN Vol.03,Issue.11, December-2015, Pages:

Voltage Correction Methods in Distribution System Using DVR

Designing Of Distributed Power-Flow Controller

Implementation of SPWM Technique in D-STATCOM for mitigating Power Quality Problem - Voltage Sag and Swell

STATCOM BASED ON REDUCTION OF PQ ISSUES IN MICRO GRID APPLICATION SYSTEMS

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

IJREE - International Journal of Research in Electrical Engineering ISSN:

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

Manjeet Baniwal 1, U.Venkata Reddy 2, Gaurav Kumar Jha 3

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

International Journal of Advance Engineering and Research Development

Designing and Control of Converters used in DPFC for Mitigation of Voltage Sag and Swell In Transmission Line

A DSTATCOM-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System for Balanced and Unbalanced Non linear Loads

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

ISSN Vol.07,Issue.21, December-2015, Pages:

Study of Different Fault Conditions using D-STATCOM Employing Diesel Generator-Based Isolation Generation System

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Volume I Issue VI 2012 September-2012 ISSN

Mitigation of Power Quality Problems Using DVR in Distribution Network for Welding Load

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Direct and Indirect Control Strategies of DSTATCOM Power Factor Controller

Transcription:

IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) SIMULATION OF D-STATCOM IN POWER SYSTEM Akil Ahemad 1, Sayyad Naimuddin 2 1 (Assistant Prof. Electrical Engineering Dept., Anjuman college of Engg. & Tech. Nagpur, India) 2 (Associate Prof. Electrical Engineering Dept., Anjuman college of Engg. & Tech. Nagpur, India) ABSTRACT : A Power quality problem is an occurrence manifested as a nonstandard voltage, current or frequency that results in a failure or a mis-operation of end user equipments. Utility distribution networks, sensitive industrial loads and critical commercial operations suffer from various types of outages and service interruptions which can cost significant financial losses. With the restructuring of power systems and with shifting trend towards distributed and dispersed generation, the issue of power quality is going to take newer dimensions. In developing countries like India, where the variation of power frequency and many such other determinants of power quality are themselves a serious question, it is very vital to take positive steps in this direction.the present work is to identify the prominent concerns in this area and hence the measures that can enhance the quality of the power are recommended. This work describes the techniques of correcting the supply voltage sag interruption in a distributed system. At present, a wide range of very flexible controllers, which capitalize on newly available power electronics components, are emerging for custom power applications A D-STATCOM injects a current into the system to correct the voltage sag, interruption. Results are presented to assess the performance of device as a potential custom power solution. The validity of proposed method and achievement of desired compensation are confirmed by the results of the simulation in MATLAB/ Simulink. Keywords: D-Statcom,, voltage dips, interruption, power quality, VSC. I. INTRODUCTION The name power quality has become one of the most productive concepts in the power industry since late 198s. Power Quality concept mainly deals with three factors namely Reliability, Quality of Supply and Customer service. Power quality may be defined as the Degree to which both the utilization and delivery of electric power affects the performance of electrical equipment. Power quality in electric networks is one of today s most concerned areas of electric power system. The power quality has serious economic implications for consumers, utilities and electrical equipment manufactures. Modernization and automation of industry and increasing use of computers, microprocessor and power electronics system such as adjustable speed drive. Integration of non-conventional generation technologies such as fuel cells, wind turbines and photo-voltaic with utility grids often requires power electronic interfaces. The power electronic system also contributes to power quality problem. Under the deregulated environment, in which electric utilities are expected to compete with each other, the customer satisfaction becomes very important. The impact of power quality problems is increasingly felt by customers industrial, commercial and even residential. The power quality problems can be solving by considering two approaches. According to first approach the solution to the power quality problems can be done from the utility side. This approach is called as load conditioning, in which the equipment is considered less sensitive to power disturbances, allowing the operation even under significant variation distortion. In second approach, install line conditioning system that suppresses the power system disturbances. In this approach the compensating devices is connect to low and medium voltage distribution system in shunt. Shunt power filters operate as a controllable current source. The scheme is implemented with voltage source PWM inverters, with a dc source having a reactive element such as a capacitor. Apart from this there are many approaches to nullify the problems, but in this paper we are solving the problem using shunt controller only. To solve the power quality problem, custom power devices used here is D-STATCOM. D-STACOM is the most efficient and effective modern customs power device used in power distribution networks. In a three-phase system, unbalanced voltages also are a power quality problem. Among them, two power quality problems have been identified to be of major concern to the customers are voltage sags and harmonics, but this paper will be focusing on voltage sag. International Conference on Advances in Engineering & Technology 214 (ICAET-214) 1 Page

IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) 1. D-STATCOM: The D-STATCOM is basically one of the custom power devices. It is nothing but a STATCOM but used at the Distribution level. The key component of the D-STATCOM is a power VSC that is based on high power electronics technologies. Basically, the DSTATCOM system is comprised of three main parts: a VSC, a set of coupling reactors and a controller. The basic principle of a D-STATCOM installed in a power system is the generation of a controllable ac voltage source by a voltage source converter (VSC) connected to a dc capacitor (energy storage device). The ac voltage source, in general, appears behind a transformer leakage reactance. The active and reactive power transfer between the power system and the D-STATCOM is caused by the voltage difference across this reactance. The D-STATCOM is connected in shunt with the power networks at customer side, where the voltage-quality problem is a concern. All required voltages and currents are measured and are fed into the controller to be compared with the commands. The controller then performs feedback control and outputs a set of switching signals to drive the main semiconductor switches (IGBT s, which are used at the distribution level) of the power converter accordingly. The basic diagram of the D-STATCOM is illustrated in Fig 1.& in Fig.1.1. The ac voltage control is achieved by firing angle control. Ideally the output voltage of the VSC is in phase with the bus voltage. In steady state, the dc side capacitance is maintained at a fixed voltage and there is no real power exchange, except for losses. Statcom. Fig. 1Block diagram of D-Statcom. Fig. 1.1 Principal of D- 1.2 PRINCIPLE OF VOLTAGE REGULATION 1.2.1 Voltage regulation without D-Statcom Consider a simple circuit as shown in fig. 1.2. It consists of a source voltage V th, V L is the load voltage and load current I L. Without a voltage compensator the load voltage drop caused by the load current I L. The change in load voltage is V. V=V th- V L =Z th *I L I L = PL jql VL V=(Rth+jXth)*( PL jql ) VL International Conference on Advances in Engineering & Technology 214 (ICAET-214) 2 Page

IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) V= Vr + Vx So, the voltage change has a component Vr in phase with Vth and component Vx having lagging phase difference. Fig. 1.2 Schematic diagram of D-Statcom Fig.1.2.1 Phasor diagram of uncompensated. 1.2.2 Voltage regulation with DSTATCOM Now consider a compensator connected to the system. It is as shown in Fig 1.2.1 shows vector diagram with voltage compensation. By adding a compensator in parallel with the load, it is possible to supply voltage =Load voltage by controlling the current of the compensator. Is =Ish + I L Fig.1.2.1 Phasor diagram of compensated. II. CONTROLLER A controller is required to control or to operate both D-Statcom a during the fault condition only. Load voltage is sensed and passed through a sequence analyzer. The magnitude of the actual voltage is compared with reference voltage i.e Vref. Pulse width modulated(pwm) control system is applied for inverter switching so as to generate a three phase 5Hz sinusoidal voltage at the load terminals. Switching frequency in the range of few KHz. The IGBT Inverter is controlled with PI controller in order to maintain 1p.u voltage at the load side. An advantage of proportional pulse integral controller is an actuating signal which is the difference between the reference voltage and feedback load voltage. Output of the controller is in the form of an angle δ, which introduces additional phase-lag/lead in the three-phase voltage. The output of error detector is the missing voltage. The controller output when compared at PWM signal generator hence, the result in the desired firing sequence. International Conference on Advances in Engineering & Technology 214 (ICAET-214) 3 Page

Voltage(KV) IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) Fig.2.1 Schematic of PI controller The sinusoidal signal V control phases modulated by means of the angle δ are, V A =Sin (ωt + δ ) V B =sin (ωt + δ -2π/3) V C =sin (ωt + δ+2π/3) This modulated signal is compaired with triangular signal and generates the switching signals for the converter valves. The main parameters of the sinusoidal PWM scheme are the amplitude modulation index of signal, and the frequency modulation index of the triangular signal. The modulating angle is applied to the PWM generator in phase A. the angles for Phase B and phase C are shifted by 12º and 24º lagging respectively. The speed of response is clearly shown in the simulation result shown. 8 6 4 2-2 -4-6 -8 Fig. 2.2 output of proposed two level voltage source converters. III. PARAMETERS OF D-STATCOM TEST SYSTEM The test system consists of 23KV, 5Hz transmission line (considered to be source). This source, feeding two transmission lines feed two distribution network through a three winding transformer connected in Y/ / 23/11/11 KV. TABLE system parameters Sr. No. System Quantities Standards 1 Source 23KV, 5Hz 1MVA 2 Three winding transformer 1MVA,Y/Y/Y 23/11/11 KV 3 Load on bus1 P=1.776MW, Q= 65.26MVAR(highly inductive) 4 Load on bus2 P=385.124KW Q=2MVAR(highly inductive) 5 Injection transformer 1MVA, 5Hz, /Y 11/11KV 6 Inverter parameters IGBT based, 3 arms, 6 pulse, carrier Frequency=18Hz SINGLE LINE DIAGRAM OF THE D-STATCOM TEST SYSTEM: International Conference on Advances in Engineering & Technology 214 (ICAET-214) 4 Page

Voltage(P.U) IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) Fig. 3 single line diagram of test system for D-statcom. IV. SIMULINK MODEL OF TEST SYSTEM AND RESULTS 4.1 Simulation of test system without fault and without D-STATCOM This simulink model present the test system without any fault and no connecting custom device like D- STATCOM. Fig.4.1. simulink mode without fault and without D-STATCOM. 4.2 Simulation Results without fault and without D-STATCOM The following results shows the system when considering no fault and no connection of D-STATCOM rms value of Voltage in p.u, instantaneous voltages and line to line voltage of the simulation result shown in the following fig.4.2.1 and 4.2.2 respectively. The line to line voltage is 11KV is measured. 1.9.8.7.6.5.4.3.2.1 Figure 4.2.1 Voltage Vrms( p.u) at load side. International Conference on Advances in Engineering & Technology 214 (ICAET-214) 5 Page

Voltage(P.U) Voltage(P.U) IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) 1.5.5 -.5-1.5 2 x 14 1-1 -2 Figure 4.2.2 line to line voltage (KV) at load side. 4.3 Simulation of test system with fault but without D-STATCOM In this simulink model we have system in which source is connect to primary side of tertiary transformer as shown. The load is connected to the secondary sides of 11KV.the sag is create here by providing the switching for the interval of.4-.6 sec. Fig. 4.3 simulation test system without D-STATCOM 4.4 Simulation Results with fault but without D-STATCOM From the following results it is observed that during the fault time i.e.4-.6 sec, the voltage sag to some finite value. The sag during the fault at the load side is nearly 1-15%, and measured the line to line voltage value during fault time is 1.25KV. Such observation can be found on the following fig.4.4 1.5.5 -.5-1 -1.5 2 x 14 1-2 4.5 Simulation of test system with D-STATCOM Fig. 4.4 line to line voltage (KV) at load side. In this simulink model we have system which fed the load through secondary winding of tertiary transformer as shown. Out of two parallel loads, sag is created by providing the switching on one of load. The D-STATCOM is connected to one of the secondary winding of tertiary transformer.the system is shown in following fig.4.5. International Conference on Advances in Engineering & Technology 214 (ICAET-214) 6 Page

Voltage(KV) IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) Fig.4.5 simulation test system with D-STATCOM 4.6 Simulation Results with fault and with D-STATCOM From the following results it is clear that the D-STATCOM compensate the voltage sag during the fault time.4-.6 sec. the compensated results of sag with respective line to line voltage is shown in fig.4.6. The battery voltage is found to be 28KV. 1.5.5 -.5-1.5 2 x 14 1-1 -2 Figure 4.6 line to line voltages (KV) at load side. with fault and with D-STATCOM V. FUTURE SCOPE The following point can be consider for future extension of work The control circuit can be change. The other controller like fuzzy, PQ technique and adaptive PI fuzzy controller may employ in the compensation scheme. Result can be improve by considering the operation with multi-level inverter Both custom devices can be established for active loads like wind turbine and solar source. VI. CONCLUSION The paper presented the study and simulation model of custom power equipment, namely D- STATCOM. and applied them for power quality problem such as voltage sag. The highly develop graphic facilities available in MATLAB is used to conduct all the aspect of model implementation and to carry out extensive simulation studies. A controller which is based on closed loop technique is used which generate error signals and this signals are used to trigger the switches of inverter using pulse width modulation (PWM) scheme in the D-STATCOM. This PWM control scheme only requires voltage measurements. The simulations are carried out for both sag on 11KV feeder using both D-Statcom. as custom power devices and it has been found that D-Statcom provide excellent voltage regulation capabilities. International Conference on Advances in Engineering & Technology 214 (ICAET-214) 7 Page

IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) REFERENCES [1] N.G.Hingorani, Flexible AC Transmission, IEEE Spectrum, vol. 3, pp.4-44,1993. [2] N.G.Hingorani, Introducing Custom Power, IEEE Spectrum, vol. 32 pp.41-48,1995. [3] Anaya-Lara O, Acha E., Modeling and analysis of custom power system by PSCAD/EMTDC, IEEE Transactions on Power Delivery, Vol.17, and Issue: 1, Jan. 22. Pp.266-272. [4] M.J.H.Bollen, Voltage sags in three-phase system Power Engineering Review, IEEE, Vol.21 Issue:9, Sept.21.pp.8-11. [5] Haque. M.H, Compensation of distribution system voltage sag by DVR and D-STATCOM. Power Tech. proceeding. 21IEEE Porto, vol.11, Issue: Sept. 21 pp.1-13 [6] Arindam Ghosh, Performance Comparision of VSC-Based Shunt and Series Compensators Used for Load Voltage Control in Distribution System.IEEE Transaction on power delivery, vol.26, No.1, Jan, 211. pp.268-278. [7] Arindam Ghosh, Copensation of Distribution System Voltage Using DVR. IEEE Transaction on power delivery, vol.17, No.4, Oct. 22. pp.13-136. [8] H.P Tiwari and Sunil Kumar Gupta Dynamic Voltage Restorer against Voltage Sag International of Innovation, Management and Technology vol.3, pp. 232-237,21. [9] C.S Chang, Y.S Ho, The Influence of Motor Load on the Voltage Restoration Capability of Dynamic Voltage Restorer. Power System Technology, Proceedings, Power Con, International Conference, vol.2,pp. 637-642,2. [1] M.H. Rashid, Power Electronics 2 nd edition, Elsevier, Inc, Publication, Californial, U.S.A 27. [11] Rakosh Das Begamudre, Extra High Voltage AC Transmission Engineering, 2nd Edition, New Age International Limited, New Delhi 199. [12] Majid Moradlou and Hamid R. Karshenas, Design Strategy for Optimum Rating Selection of Interline DVR IEEE, VOL. 26, NO. 1, Jan, 211. International Conference on Advances in Engineering & Technology 214 (ICAET-214) 8 Page