NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

Similar documents
A3-102 PCB ROGOWSKI COILS HIGH PRECISION LOW POWER SENSORS. Ljubomir A. Kojovic * Cooper Power Systems USA

Design of Differential Protection Scheme Using Rogowski Coil

ROGOWSKI coil current sensors are transformers that

Accurate Current Measurement Transducer for Relaying Purpose

BUS2000 Busbar Differential Protection System

Catastrophic Relay Misoperations and Successful Relay Operation

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Transformer Protection

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Busbars and lines are important elements

Light measures current

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Electrical Protection System Design and Operation

CP CU1. Coupling unit for line and ground testing

Back to the Basics Current Transformer (CT) Testing

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

Transformer protection IED RET 670

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

ARC FLASH HAZARD ANALYSIS AND MITIGATION

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Notes 1: Introduction to Distribution Systems

Webinar: An Effective Arc Flash Safety Program

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

How to maximize reliability using an alternative distribution system for critical loads

Unit Protection Differential Relays

LFR: flexible, clip-around current probe for use in power measurements

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Non-conventional instrument transformers and power quality aspects an overview

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

AN OVERVIEW OF ROGOWSKI COIL CURRENT SENSING TECHNOLOGY

2015 Relay School Bus Protection Mike Kockott March, 2015

GE Multilin technical note

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Bus Protection Fundamentals

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

RCTrms Technical Notes

High-Impedance Differential Applications With Mismatched CTs

MVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Application of Low-Impedance 7SS601 Busbar Differential Protection

Rogowski Coil Based Digital Energy Meter

PROTECTION of electricity distribution networks

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Powered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

Practical Tricks with Transformers. Larry Weinstein K0NA

Line Frequency Transformer

TECHNICAL BULLETIN 004a Ferroresonance

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

Measurement and Analysis for Switchmode Power Design

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

INSTITUTO TECNOLÓGICO Y DE ESTUDIOS SUPERIORES DE MONTERREY MONTERREY CAMPUS GRADUATE PROGRAM IN ENGINEERING AND INFORMATION TECHNOLOGIES

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

CP Cu1. Advanced Test Equipment Rentals ATEC (2832) Multi-purpose coupling unit for CPC 100. Measurement System for

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Deploying Current Transformers in Applications Greater Than 200 A

results at the output, disrupting safe, precise measurements.

Transformer Waveforms

PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

Distribution/Substation Transformer

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

20 - Arc Guard Systems

EMI AND BEL MAGNETIC ICM

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

ELECTRICAL POWER ENGINEERING

Exercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers

N. TEST TEST DESCRIPTION

Application Information

UNIT-4 POWER QUALITY MONITORING

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

Power systems 2: Transformation

Using Optical Isolation Amplifiers in Power Inverters for Voltage, Current and Temperature Sensing

Centralized busbar differential and breaker failure protection function

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

Improved power transformer protection using numerical relays

FERRORESONANCE SIMULATION STUDIES USING EMTP

Enhanced Quality with a Touch of Style

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Table of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

CURRENT TRANSFORMER SELECTION TECHNIQUES FOR LOW-VOLTAGE MOTOR CONTROL CENTERS

SECTION AUTOMATIC TRANSFER SWITCH

N. TEST TEST DESCRIPTION

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Solid state electric field sensor

Data Isolation Cards. 2-Wire HDSL/56KBS Isolation Card P Wire HDSL/56KBS Isolation Card P30050

Transcription:

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture steel from scrap, the furnace transformer is one of the most critical pieces of electric power equipment in the plant. Failures in the furnace transformer or its buswork interrupt production and require costly and timeconsuming repairs. Traditional overcurrent protection is often applied at the circuit breaker that supplies the cable serving the furnace transformer. This protection is normally set to reach into the furnace transformer primary winding for faults in the winding but may not have sufficient sensitivity to reach through the transformer into the secondary winding or into the secondary leads. Faults that occur in the secondary bus work, water cooled leads, or in the conducting arms above the furnace are not detected by the upstream overcurrent protection and are normally interrupted only after personnel manually open the circuit breaker. The damage due to the extended fault duration can result in long or costly outages. Differential protection schemes are not typically applied on EAF transformers due to the difficulty in providing current transformers (CTs) of sufficient rating for the secondary leads carrying currents of 60 ka or more. Some modern EAF transformers are rated to deliver a steady state secondary current of 80 ka. In some cases, a CT is built into the transformer that monitors the current in only one secondary winding. This current signal might be used for metering or regulator control purposes, and the magnitude is calculated externally with a scale factor assuming the current in each winding is the same. The accuracy of this technique is not sufficient for a reliable differential protection system. New protection concepts presented in this paper make EAF transformer differential protection schemes possible. TRADITIONAL PROTECTION SCHEMES Traditional power transformer differential protection is shown in Figure 1. This scheme requires careful engineering to overcome some of the inherent issues that result in less sensitivity in the protection system. CT saturation problems require sloped restraint characteristics that de-sensitize the relay scheme for true faults in the zone of protection. These schemes have not been applied on EAF transformers due to the lack of commercially available current transformers for the secondary leads and CT saturation problems due to the high current magnitudes. I 1P I 1s CT1 operating coil Power Transformer r Differential Relay CT2 restraint coils r = r I diff I 1s I 2s Figure 1. Traditional Power Transformer Differential Protection Scheme PCB ROGOWSKI COILS Rogowski coils (RCs) consist of a wire wound on a nonmagnetic core. The coil is placed around the conductors whose currents are to be measured. Strict design criteria must be followed to obtain a coil immune from nearby conductors and independent of conductor location inside the coil loop. To prevent influence of nearby conductors carrying high currents, RCs must be designed with twowire loops connected in electrically opposite directions. This cancels all electro-magnetic fields coming from outside the coil loop. One or both loops can consist of wound wire. If only one loop is made of wire wound on a non-magnetic core, then the other loop can be formed by returning the wire through the center of the winding. If both loops have wound wire, then the second winding must be wound in the opposite direction. In this way, the voltage induced in the RC from the inside conductor will be doubled. The RC output voltage is proportional to the rate of change of measured current. To obtain measured current, coil output voltages must be integrated. The traditional method of coil construction uses flexible cores such as coaxial cables or straight rods to obtain higher measurement accuracy [1-3]. Patent [2] describes a RC consisting of two wound coils implemented on a pair of printed circuit boards (PCBs) located next to each other (Figure 2). For measurements of residual currents to embrace all three-phase conductors or to embrace parallel conductors carrying the same phase currents, PCB Rogowski coils have been designed in an I 2s I 2P CPS_Kojovic_B1 Session 3 Paper No 53-1 -

oval shape [1, 2]. The considered PCB Rogowski coil design has the following characteristics: measurement accuracy reaching 0.1 %; wide measurement range (the same coil can measure currents from 1 to over 100,000 amps); linear frequency response up to 700 khz; unlimited short-circuit withstand resulted from the window-type design; galvanic isolation from the primary conductors (like current transformers); possible encapsulation and location around bushings or cables, avoiding the need for high insulation. EAF transformer, two sets of RCs are needed. To protect the EAF transformer and the secondary leads, three sets are needed. Figure 3 shows a single-line diagram of the differential scheme employing three sets of RCs and one multifunction relay. RCs can be designed as split-core style for installation without the need to disconnect a primary or secondary conductor. I1 P EAF Transformer RC #1 RC #2 I2 P RC #3 I1 S Tap Position I2 S Water Cooled Leads Algorithms for Three Independent Protection Zones EAF Multifunction Relay Figure 3. Protection of Arc Furnace Transformers and Secondary Leads Figure 2. PCB Rogowski Coil The RC output voltage is in the milli-volt to several-volt range and can reliably drive digital devices designed to accept low power signals. Integration of the signals can be performed in the relay itself (by using analog circuitry or digital signal processing techniques) or immediately at the coil. Connections to relays can be by wires or through fiber-optical cables. New current and voltage sensors and intelligent electronic devices (IEDs) make possible high-level integration of protection, control, and metering systems in substations. Technical committees worldwide are actively working on standardizing low power current and voltage sensor output levels as well as interfaces between sensors, relays, and IEDs. For example, IEEE C37.92 Standard for Low Energy Analog Signal Inputs to Protective Relays standardizes analog interface links; IEC 61850-9-1 Specific Communication Service Mapping: Sampled analog values over serial unidirectional multidrop point to point link and IEC 61850-9-2 Sampled analog values over ISO 8802-3 standardize communication methods of digitized sampled values over an Ethernet network specified by the IEEE 802.3 group of standards. The goal is to obtain interoperability between IEDs and sensors of different technologies and suppliers. The PCB Rogowski coil designs considered in this paper meet the new standard and protection system requirements. EAF TRANSFORMER PROTECTION PCB Rogowski coils and multifunction relays can provide reliable EAF transformer protection. To protect only the An external signal can be supplied to the relay to indicate the operating tap of the transformer. With suitable delays, the relay can be programmed to ride through an on-load tap change when the current mismatch will change with fixed ratio sensors. The ability of the scheme to adjust to actual transformer operating conditions reduces the main sources of error that force higher percentage differential settings in conventional schemes. The tap position can be supplied to the relay in analog or digital formats. The concept shown in Figure 3 provides three protection zones. Zone 1 covers all electrical equipment between RC1 and RC2, Zone 2 covers all electrical equipment between RC2 and RC3, and Zone 3 covers all electrical equipment between RC1 and RC3. The multifunction relay employs three different and independent algorithms for each zone, providing independent protection of the arc furnace transformer, secondary leads, and combined transformer with secondary leads. For Zone 2 sensing faults in the secondary leads, there is no need for transformer tap position information, which simplifies the protection algorithm and allows the relay to be set more sensitively. Figures 4 and 5 show installations of RCs and the RC designs. RC1 set can be located in the switchgear close to the primary circuit breaker, protecting also the entire cable between the circuit breakers and EAF by Zones 1 and 3. It is very common for EAF transformers that, due to dust, faults occur outside the transformer, between secondary terminals X1 through X6 (Figure 4). These types of faults conventional overcurrent protection cannot detect since fault current levels are equal to the rated current, causing high damage to the transformer. However, the presented protection system will also protect these types of faults by Zones 1 and 3. CPS_Kojovic_B1 Session 3 Paper No 53-2 -

High Voltage Side Arc Furnace Side B A C Switchgear RC1 H1 X5 H3 H2 X4 X6 X1 X3 X2 RC2 A B C To RC3 and EAF Figure 4. Rogowski Coil Installations on the EAF Transformer Primary and Secondary Sides RC3 To EAF measured the fault current. RC4 and RC5 were located 4 inches from the primary and secondary conductors to measure the influence of the nearby conductors. Their output signal was amplified 100 times to obtain visible waveform on the recording. Primary Conductor RC1 Relay RC2 Secondary Leads Figure 5. PCB Coil Designs for EAF Transformer Protection Results To determine accuracy and sensitivity, five RCs were tested in the Cooper Power System s (CPS) high power laboratory under actual conditions. The test setup is shown in Figure 6. To test the extreme application conditions, no shielding was applied to RCs and no integration or signal conditioning of RC output signals were performed. Secondary current, representing an arc furnace load current, was 60 ka, while the primary test current was approximately 2.5 ka. Fault current was initiated by switch SW. The results were compared to the laboratory current sensors (current transformers CT1, CT2, and a shunt that was used to measure 60 ka current). RC1 and RC2 measured primary and secondary transformer currents. RC3 Figures 7, 8, 9 and 10 show results with a fault current of approximately 10% load current. Figure 7 shows waveforms from all tested current sensors. The results show the favorable comparison of the RC1 (integrated signal) with CT1, RC2 with the shunt, and RC3 with CT2. The results also confirmed that the influence of nearby conductors on the RC4 and RC5 was very small, bellow 0.2%. Figure 8 shows overlapped RC1 scaled by the transformer ratio and RC2 output non-integrated waveforms. Transient recorder channel to which RC1 was connected experienced some noise, which is visible even before the test ed. However, this did not impact the results. The difference between magnitudes of the primary and secondary signals is noticeable when the fault was initiated. Figures 9 shows calculated RMS values for both nonintegrated waveforms. The magnitudes between the primary and secondary signals are almost identical during normal operation. The difference in the magnitudes between the primary and secondary signals when the fault was initiated is clearly visible. The differential current, shown in Figure 10, was obtained by digital subtraction of the primary and secondary currents. The small differential signal that exists before the test ed is due to the noise in the transient recorder CPS_Kojovic_B1 Session 3 Paper No 53-3 -

channel. When the test ed, differential signal was almost zero during the normal operation as expected since both RC1 and RC2 output signals are equal. When the fault was initiated, differential signal increased, in this case to 0.7 V, initiating relay operation. The presented test results correspond to fault currents of 10% rated current. However, the tests were also performed at lower fault currents, and the results confirmed that the proposed scheme reliably operates for faults of 5% rated current. Greater sensitivity is likely to achieve, but requires further investigation. G R, X Ip Ratio 23 SW Is 60 ka Switch to initiate fault currents Resistor for current limitation CT1 RC1 RC3 CT2 Shunt RC4 RC2 RC5 a) Rogowski Coils RC1 and RC2 tested in differential mode. x100 x100 b) Rogowski Coil RC3 measured differential current for comparison with Coils RC1 and RC2. c) Rogowski Coils RC4 and RC5 used to determine influence of external conductors with high currents. 1 2 3 4 5 6 7 8 Transient Recorder d) Laboratory current transformers CT1, CT2 and shunt used for reference. Figure 6. Setup for Rogowski Coil ing in the Cooper s High Power Laboratory Figure 7. Rogowski Coil Results: Fault current 10% of Load Current CPS_Kojovic_B1 Session 3 Paper No 53-4 -

In conclusion, the PBC Rogowski coils are linear, accurate, reject well the influence of external electromagnetic field, and yield a strong differential signal providing reliable relaying. 8 6 4 RC Output Signal [V] 2 0-2 -4-6 -8 Is -10-12 Normal operation Fault Ip - referred to the secondary 0.05 0.1 0.15 0.2 0.25 0.3 Time [s] Figure 8. Rogowski Coil Results: Primary and Secondary Currents, Fault Current 10% of Load Current 7 6 Ip referred to the secondary RC Output Signal [V] 5 4 3 Normal operation Fault Is 2 1 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 Time [s] Figure 9. Rogowski Coil Results: RMS Values of the Primary and Secondary Currents, Fault Current 10% of Load Current CPS_Kojovic_B1 Session 3 Paper No 53-5 -

0.8 0.7 0.6 Differential Current RC Output Signal [V] 0.5 0.4 0.3 0.2 0.1 Normal operation Fault end 0 Fault duration 0.05 0.1 0.15 0.2 0.25 0.3 0.35 Time [s] Figure 10. Rogowski Coil Results: Calculated Differential Current, Fault Current 10% of Load Current CONCLUSIONS The PCB Rogowski coils presented in this paper make EAF transformer differential protection schemes possible. To determine accuracy and sensitivity, RCs were tested in a high power laboratory. To test the extreme application conditions, no shielding was applied to RCs and no integration or signal conditioning of RC output signals were performed. Secondary current, representing an arc furnace load current, was 60 ka, while the primary test current was approximately 2.5 ka. This paper presented test results for fault current of 10% rated current. However, the test results also proved that the proposed scheme reliably operates for faults of 5% rated current and even smaller. PCB Rogowski coils are linear, accurate, very well reject influence of external electro-magnetic field, and yield a strong differential signal providing reliable relaying. REFERENCES [1] Lj. A. Kojovic, PCB Rogowski Coils Benefit Relay Protection, Computer Application in Power, IEEE Magazine, July 2002. [2] Lj. A. Kojovic, V. Skendzic, S. E. Williams, High Precision Rogowski Coil, Patent Number: 6,313,623; Date of Patent: November 6, 2001. [3] Lj. A. Kojovic, Rogowski Coils Suit Relay Protection and Measurement, Computer Application in Power, IEEE Magazine, July 1997. Impact of nearby conductors carrying high currents on the RCs was also tested. The results show very small influence, bellow 0.2%. CPS_Kojovic_B1 Session 3 Paper No 53-6 -