Synchronous Generator Subtransient Reactance Prediction Using Transient Circuit Coupled Electromagnetic Analyses & Odd Periodic Symmetry

Similar documents
Generator Advanced Concepts

Combined analytical and FEM method for prediction of synchronous generator no-load voltage waveform

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

SYNCHRONOUS MACHINES

Contents. About the Authors. Abbreviations and Symbols

A Practical Guide to Free Energy Devices

3.1.Introduction. Synchronous Machines

VALLIAMMAI ENGINEERING COLLEGE

Cylindrical rotor inter-turn short-circuit detection

Generalized Theory Of Electrical Machines

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Code No: R Set No. 1

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Modelling of Electrical Machines by Using a Circuit- Coupled Finite Element Method

OPTIMUM DESIGN ASPECTS OF A POWER AXIAL FLUX PMSM

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Sizing Generators for Leading Power Factor

Placement Paper For Electrical

Spec Information. Reactances Per Unit Ohms

Introduction : Design detailed: DC Machines Calculation of Armature main Dimensions and flux for pole. Design of Armature Winding & Core.

CHAPTER 6 FABRICATION OF PROTOTYPE: PERFORMANCE RESULTS AND DISCUSSIONS

Model Correlation of Dynamic Non-linear Bearing Behavior in a Generator

GENERATOR DATA JANUARY 30, 2015

Finite Element Analysis of Cogging Torque in Low Speed Permanent Magnets Wind Generators

PART A. 1. List the types of DC Motors. Give any difference between them. BTL 1 Remembering

Conventional Paper-II-2013

CHAPTER 2 D-Q AXES FLUX MEASUREMENT IN SYNCHRONOUS MACHINES

GOVERNMENT COLLEGE OF ENGINEERING, BARGUR

IOCL Electrical Engineering Technical Paper

Electromagnetic and thermal model for Brushless PM motors


COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING ACADEMIC YEAR / EVEN SEMESTER QUESTION BANK

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Module 1. Introduction. Version 2 EE IIT, Kharagpur

CHAPTER 9. Sinusoidal Steady-State Analysis

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer

CHAPTER 5 CONCEPTS OF ALTERNATING CURRENT

AC Machinery. Revised October 6, Fundamentals of AC Machinery 1

Three-Phase Induction Motors. By Sintayehu Challa ECEg332:-Electrical Machine I

Beyond the Knee Point: A Practical Guide to CT Saturation

AGN 034 Alternator Reactance

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

A Practical Guide to Free Energy Devices

THE UNDER HUNG VOICE COIL MOTOR ASSEMBLY REVISITED IN THE LARGE SIGNAL DOMAIN BY STEVE MOWRY

1. Explain in detail the constructional details and working of DC motor.

AGN 005 Fault Currents and Short Circuit Decrement Curves

Rotor Structure Selections of Nonsine Five-Phase Synchronous Reluctance Machines for Improved Torque Capability

THE SINUSOIDAL WAVEFORM

CHAPTER 3 EQUIVALENT CIRCUIT AND TWO AXIS MODEL OF DOUBLE WINDING INDUCTION MOTOR

DESIGN STUDY OF LOW-SPEED DIRECT-DRIVEN PERMANENT-MAGNET MOTORS WITH CONCENTRATED WINDINGS

Motor-CAD winding temperature model verification using Finite Element Analysis

WELCOME TO THE LECTURE

EE 410/510: Electromechanical Systems Chapter 5

The synchronous machine as a component in the electric power system

1249. Development of large salient-pole synchronous machines by using fractional-slot concentrated windings

Exercise 9. Electromagnetism and Inductors EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Magnetism, magnets, and magnetic field

(2) New Standard IEEE P (3) Core : (4) Windings :

DISCUSSION OF FUNDAMENTALS

Power. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt

ELG2336 Introduction to Electric Machines

Motor-CAD Brushless PM motor Combined electromagnetic and thermal model (February 2015)

BE. Electronic and Computer Engineering Final Year Project Report

PESIT Bangalore South Campus Hosur road, 1km before Electronic City, Bengaluru -100 Department of Electronics & Communication Engineering

PART 2 - ACTUATORS. 6.0 Stepper Motors. 6.1 Principle of Operation

ENGINEERING ACADEMY X V

Single-turn and multi-turn coil domains in 3D COMSOL. All rights reserved.

Spec Information. Reactances Per Unit Ohms

Overview of IAL Software Programs for the Calculation of Electrical Drive Systems

THE UNIVERSITY OF BRITISH COLUMBIA. Department of Electrical and Computer Engineering. EECE 365: Applied Electronics and Electromechanics

Power System Dynamics and Control Prof. A. M. Kulkarni Department of Electrical Engineering Indian institute of Technology, Bombay

CHAPTER 2. Transformers. Dr Gamal Sowilam

Linked Electromagnetic and Thermal Modelling of a Permanent Magnet Motor

Lab E2: B-field of a Solenoid. In the case that the B-field is uniform and perpendicular to the area, (1) reduces to

Synchronous Machines Study Material

UNIVERSITY OF JORDAN Mechatronics Engineering Department Measurements & Control Lab Experiment no.1 DC Servo Motor

Realize Your Product Promise. Maxwell

WDG 12 - Technical Data Sheet

Analysis of Indirect Temperature-Rise Tests of Induction Machines Using Time Stepping Finite Element Method

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

ELECTRIC MACHINES MODELING, CONDITION MONITORING, SEUNGDEOG CHOI HOMAYOUN MESHGIN-KELK AND FAULT DIAGNOSIS HAMID A. TOLIYAT SUBHASIS NANDI

WDG 12 - Technical Data Sheet

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

Dhanalakshmi Srinivasan Institute of Technology, Samayapuram, Trichy. Cycle 2 EE6512 Electrical Machines II Lab Manual

WDG 13 - Technical Data Sheet

Effects of the Short-Circuit Faults in the Stator Winding of Induction Motors and Fault Detection through the Magnetic Field Harmonics

Electrical Engineering / Electromagnetics

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator

WDG 07 - Technical Data Sheet

Bakiss Hiyana binti Abu Bakar JKE, POLISAS BHAB

Meshing Challenges in Simulating the Induced Currents in Vacuum Phototriode

Back to the Basics Current Transformer (CT) Testing

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

Chapter 10: Compensation of Power Transmission Systems

Alternating Current Page 1 30

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad

ESO 210 Introduction to Electrical Engineering

Step vs. Servo Selecting the Best

Transcription:

Synchronous Generator Subtransient Reactance Prediction Using Transient Circuit Coupled Electromagnetic Analyses & Odd Periodic Symmetry Joshua Lorenz Kato Engineering Inc., North Mankato, MN John T. Fowler Kato Engineering Inc., North Mankato, MN Abstract For synchronous 3 phase electrical generator machine design, the ability to predict the subtransient reactance of a particular machine design is of prime importance. The subtransient reactance has a significant impact on the magnitude of the fault currents generated within the machine during an event such as a 3 phase short-circuit. Power system designers routinely use the generator subtransient reactance as a key parameter to aid in the design of the complete power generation system. For new generator designs the subtransient reactance is routinely tested for as part of a thorough evaluation of the generator performance characteristics. In this paper, a method is presented to calculate the subtransient reactance of a particular generator design using transient circuit coupled finite element electromagnetic analyses. The finite element modeling technique presented utilizes odd periodic symmetry along with a moving interface at the rotorstator air-gap. The use of odd periodic symmetry allows for the simulations to be accomplished with half of the model size as compared to even periodic symmetry. The calculated generator subtransient reactance from the finite element modeling technique presented is compared to generator test data as well as previous calculation methods. Other key pieces of information which may be generated throughout the process are also documented, such as calculated voltage harmonics and the open-circuit saturation curve. Introduction Kato Engineering primarily manufactures synchronous 3 phase electrical generators. The ability to predict the subtransient reactance of a particular generator design is of prime importance. Power system designers routinely use the generator subtransient reactance as a key parameter to aid in the design of the complete electrical power generation system. The subtransient reactance, X d, is the generator internal impedance element that is effective in the first cycles of a transient load event and determines the magnitude of the instantaneous fault current from the generator. The transient reactance, X d, becomes effective after approximately 6 cycles into a transient load event and determines the amount of voltage change seen at the generator terminals due to the step change in load. As stated, the reactances of a generator have a direct effect on the transient fault currents experienced in an electrical power generation system, as well as the motor starting capability of the generator. The magnitudes of the fault currents need to be calculated so that breakers, etc. can be sized accordingly. The peak magnitudes of the 3 phase fault currents are inversely proportional to the subtransient reactance of the generator. For new generator designs, the transient and subtransient reactances are routinely tested for as part of a thorough evaluation of the generator s performance characteristics. Traditional reactance prediction methods have served engineers well when new designs closely mimic previous designs which have been tested and their reactance predictions validated. From the perspective of the machine designer, an uncomfortable level of uncertainty always accompanied a new design that deviated significantly from standard form. In this paper, a method is presented to calculate the transient and subtransient reactance of a generator using transient dynamic circuit-coupled finite element electromagnetic analyses. Finite Element electromagnetic analysis offers a powerful tool to reduce the risk in new generator design.

A series of Finite Element (FE) electromagnetic simulations were performed in order to generate the following simulation data: Open-Circuit Saturation Curve Generator Voltage Signal Harmonics Generator Transient and Subtransient Reactance The open-circuit saturation curve and voltage signal harmonics were obtained from the magnetostatic model and the reactance calculations were based upon results from a transient circuit-coupled model with a moving interface at the rotor-stator air gap. The voltage signal harmonics were also calculated with the transient circuit-coupled model, for comparison. The transient circuit-coupled finite element modeling technique presented utilizes odd periodic symmetry along with a moving interface at the rotor-stator air gap. The use of odd periodic symmetry allows for the simulations to be accomplished with half of the model size as compared to even periodic symmetry. The particular generator design used for these analyses is a Kato Engineering, salient pole, 3 phase, 60 Hz, 13.8 kv synchronous generator. The generator rotor is a 4-pole rotor with a normal operating speed of 1800 RPM. The generator is rated for 4.5 MW of output power at 0.8 Power Factor with a temperature rise of 95ºC at an ambient temperature of 50ºC. The generator is approximately 7 ft wide by 10 ft tall by 11 ft long. Figure 1 shows a view of the generator assembly. One of the reasons this design was chosen for analysis was the fact there is a plethora of good test data in existence for this design. Figure 1. Generator Assembly View Model Information For all of the simulations performed, the portion of the generator assembly modeled is commonly referred to as the active region of the generator rotor and stator. The active region is comprised of the generator rotor and stator stacks along with their respective windings. The models are all 2D models with periodic

symmetry. The model covers 1 pole of a 4 pole generator (i.e. 90 degrees). The rotor shaft is included in the rotor portion of the model, and the stator portion of the model is bounded by the outer diameter of the laminated stator stack. Figure 2 shows a view of the 2D geometry which was utilized for all of the simulations. The geometry was created in Pro/Engineer and transferred to ANSYS via an IGES file transfer. The simulated length of the model was 33.5 inches. This is representative of the stack lengths for the rotor and stator. Figure 2. Generator Modeled Geometry The circuit-coupled models utilized the circuit which is shown in Figure 3. The 1-pole model encloses half of a parallel circuit for the stator windings. The stator phase windings present in the model are A+, B+, B- and C-. Therefore the circuit contains four circuit-coupled stator winding elements. For the open-circuit voltage harmonics simulation, the phase leakage inductors were effectively removed from the coupled circuit via voltage coupling constraints across each inductor. The rotor field windings are coupled to the circuit, and so are the rotor damper bars.

Figure 3. Generator Coupled Circuit The circuit construction and portions of the model building process were handled via an APDL input file which was read into ANSYS with the use of the /INP command functionality. The element, material property, and real constant specifications were all defined in the APDL file. Elements Three basic element types were used in the models. The table below shows the element types that were used and a general description of where they were used in the models Table 1. Element Type Tabular Listing ANSYS Element Type PLANE53 CIRCU124 MESH200 Where Used Rotor shaft, rotor lamination, rotor windings, rotor damper cage, air regions, stator lamination, stator windings, stator slot sticks All circuit elements For mesh controls and circuit connection dummy wires. The same element mesh was used for the magnetostatic model and the circuit-coupled models. The mesh contained 9,636 elements and 29,564 nodes (excluding the circuit elements and nodes). Figure 4 shows a

view of the element mesh (excluding the circuit elements). The mesh is not connected at a boundary arc between the rotor and stator elements. The boundary arc resides at the middle of the air-gap between the rotor and stator. Figure 4. Generator Element Mesh Material Properties For all of the simulations there were 3 unique magnetic materials, each with their own B-H curve. Figure 5 shows the B-H curves for the magnetic materials listed below: Rotor laminations 16 Gage ASTM A715 Grade 80 Stator laminations 26 Gage M27 C3 (adjusted) Rotor shaft AISI 1045 steel

Figure 5. Simulation B-H curves The B-H curve for the stator laminations was adjusted from the vendor material property data in order to account for the fact the stator core is vented. For this design the stator core has (12) integral vents. The vents have an axial width of 0.375 inches. Therefore, over the active stack length of the machine (33.5 ) the stator core only has 29 of active lamination material in the axial direction. The fraction of the stack length which is comprised of stator lamination material is 0.8657 (29/33.5). The actual stator lamination flux densities in reality are 1.155x those calculated from the 2D model (1/0.8657 = 1.155). The B-H curve of the stator lamination material is adjusted so that the correct magnetic induction (H) is required in order to produce the flux densities which would be seen in reality. The mathematical B-H curve adjustment is based solely upon the fraction of stator stack length active material (i.e. 0.8657). The open-circuit saturation curve from the magnetostatic model was developed with and without the stator vent correction in order to see how the stator vent correction affects the results. The air regions, rotor and stator winding regions, stator slot stick regions, and damper cage element regions of the model were all assumed to have a relative magnetic permeability of 1.0. For the circuit-coupled models, the winding resistances for the circuit coupled winding elements were taken from one of our in-house generator spreadsheet design programs. The program calculates expected winding resistances based upon the design input parameters of the generator. The calculated cold winding resistances were used because the generator reactance test is normally conducted on a cold generator. The fill factors of the rotor and stator coils were back-calculated based on the given winding resistance, winding length, number of turns, geometric area, and cold resistivity in order that the ANSYS calculated winding resistances match the specified winding resistances from the Kato Engineering in-house design program. The equation used by ANSYS for winding resistance based upon fill factor, number of turns, geometric area, length, and resistivity is shown below:

L turns FF R = ρ area The circuit-coupled solid conductor elements, which represent the damper bars of the generator rotor, used the cold resistivity of copper in the solid conductor element specification. Boundary Conditions & Model Details For all models, odd-periodic symmetry constraints were applied to the periodic edges of the model (i.e. the boundary lines at 45 and 135 degrees). The constraints were applied via the use of the PERBC2D command. Odd-periodic symmetry was required because the model encompasses only a single polarity for the rotor poles. A model of twice the angular span (i.e. 180 degrees and 2 rotor poles) would allow for the use of even-periodic symmetry. However, even-periodic symmetry is not required to obtain all of the necessary simulation information and the use of odd-periodic symmetry allows for more efficient models. For all models, An Az = 0 constraint was applied at the OD of the stator laminations. This constraint can also be described as a flux parallel constraint. For the magnetostatic model a uniform current density is applied to each side of the rotor field winding. A positive current density was used on the left hand side, and a negative current density was used on the right hand side (see Figure 2). Fifteen different current densities were used on the magnetostatic model in order to generate the open-circuit saturation curve. Each unique current density corresponds to a certain amount of ampere-turns of rotor field excitation. For the circuit-coupled transient dynamic models, the rotor field excitation was driven by a fixed DC voltage source connected to the circuit-coupled rotor field windings. The DC source voltage was set such that the ampere-turns generated in the rotor resulted in the nominal open-circuit voltage at the generator output terminals. The nominal open-circuit phase voltage is 7,967 Volts line to neutral (i.e. 13.8kV line to line). The circuit-coupled transient dynamic models also employ several voltage coupling equations and voltage constraints. All of the grounded nodes in the coupled circuit have a zero voltage DOF constraint. All of the nodes on the right hand side of the solid conductor elements (i.e. damper cage conductor elements) have coupled voltage DOF. A coupling equation is also used, for cosmetic purposes, to couple the fixed DC voltage source to the rotor field winding elements. The coupled circuit contains a leakage inductor for each phase of the output voltage. The leakage inductor is used in the coupled-circuit in order to account for the leakage reactance of the generator armature. The leakage reactance of a generator armature can be categorized by 4 different armature leakage flux components [1]: Slot leakage flux The flux in the stator that does not completely encompass the stator slot by crossing the stator slot. Flux leakage increases with narrower slot and deeper slot. Zig zag leakage flux The flux that zigzags across the air gap from tooth to tooth and never links the stator winding. Flux leakage increases with smaller air gap and wider teeth with respect to the slot pitch. Belt leakage flux Considered negligible in 3 phase synchronous machines. End-connection leakage flux The stator flux that is generated in air surrounding the stator end windings. Flux increases with the axial length of the coils with respect to the stack length. All but the end-connection leakage flux are accounted for in the Finite Element model. For this reason, the leakage inductors are added to each phase of the output voltage circuit in order to account for the armature end-connection leakage reactance. The inductance value used for the leakage inductors is based on a fraction of the total calculated armature leakage reactance. Inductance (L) and reactance (X) are related by the formula for inductive reactance, as shown below [2]:

X L = ω Kato Engineering s in-house design programs calculate the total armature leakage reactance based on the input design parameters of the generator. For the 3 phase short-circuit simulation the short-circuit fault is simulated by applying a zero voltage DOF constraint at the output terminals on the coupled circuit. The output terminal nodes correspond to the nodes on the right hand side of the inductor elements. For the magnetostatic model, the rotor and stator meshes are connected by the use of the CEINTF command. The CEINTF command effectively couples the Az DOF between the rotor and stator regions in the static model. For the dynamic models, the rotor/stator moving interface is dealt with via the use of a macro titled ODDSLIDE. The macro was written by the author, and is similar in functionality to the SLIDE macro which is not documented, but supported to an extent by ANSYS. The SLIDE macro does not support odd-periodic symmetry and can only be used for even-periodic symmetry models. The ODDSLIDE macro allows for the use of odd-periodic symmetry (i.e. ½ the model size) and is discussed in further detail in the next section. For all but one of the transient dynamic models a time step increment of 750 microseconds was used for the simulations. This equates to an angular step of 8.1 degrees for the 1800 RPM machine, and a sampling frequency of 1.33 khz. The time stepping used was a compromise between solution fidelity and solution run time. The period of oscillation for the output voltage and current of the machine is approximately 16.7 milliseconds (i.e. 60 Hz). Therefore, the time stepping used results in roughly 22 solutions per period of oscillation. Another iteration of the transient dynamic model was performed with a time step increment of 130.2 microseconds (i.e. 7.68 khz sampling frequency) in order to verify the open-circuit voltage signal harmonics which were calculated via the magnetostatic model. The generator voltage harmonics test data is available out to the 39 th harmonic which has a frequency of 2.34 khz. Dynamic Solution Routine In order to perform the circuit-coupled transient dynamic simulations using odd-periodic symmetry, a fairly detailed approach was used to carry out the simulation process. For all of the transient dynamic circuitcoupled simulations the solution process was started with a static solution obtained while the rotor and stator sections of the model were aligned. After the static solution, time integration was turned on and the time-stepping solution loop was carried out. The basic steps of the solution loop employed are listed below: Identify the new rotor position in absolute degrees Enter /prep7 Call the oddslide macro with the new absolute rotor position Enter /solu Set the analysis type to RESTART Define the time of the new solution Solve The basic loop shown above was repeated for each time step increment. For the short-circuit simulation the output side of the inductor nodes (on the coupled circuit) were grounded at a particular time in the simulation loop. The grounding was accomplished by constraining the node voltage DOF to zero. The simulation loop was then continued with the grounded output terminals (i.e. 3 phase short-circuit).

oddslide Macro The primary function of the oddslide macro was to provide connectivity between the rotor and stator meshes at the air-gap line, given a displaced position of the rotor. The rotor and stator mesh densities need not be identical at the interface. The dissimilar meshes are handled with the CEINTF command within the oddslide macro. Since only a single polarity of the rotor poles is included in the FE mesh, the macro must consider the absolute location of the displaced rotor in order to determine whether a positive or negative rotor pole is residing beneath the stationary portion of the FE mesh. In its simplest form, if a positive pole is residing beneath the stator mesh the mesh coupling can be described as Az = Az or even coupling. If a negative pole is residing beneath the stator mesh the mesh coupling can be described as Az = -Az or odd coupling. This latter type of odd coupling essentially reverses the polarity of the rotor pole as seen by the stator mesh. Figure 6 shows a very simplified flowchart of the process used in the oddslide macro. Figure 6. oddslide Macro Flowchart Analysis Results & Test Data Comparison All of the analyses were performed with ANSYS 10.0 on an Intel 32-bit system running Windows XP Professional. The machine was equipped with dual Xeon 3.06 GHz processors and 2.0 GB of RAM.

Open-Circuit Saturation Curve Figure 7 shows a comparison of the simulation results and test data for the open-circuit saturation curve. A series of magnetostatic simulations were run with varying field current, to obtain the simulation results shown below. The generator armature phase voltage is calculated from each of the magnetostatic simulation results via the following formula [1], where the last two quantities ([A z.2 -A z.1 ] x L s ) are equivalent to the flux per pole: PH = 4.0 f fb D P ( A Z.2 A Z.1) LS V k k N f output frequency f b form factor (1.11 for a perfect sine wave) k D winding distribution factor k P pitch (chord) factor N turns per phase (A Z.2 - A Z.1 ) difference in air-gap magnetic vector potential (per unit length) at adjacent quadrature axes L S generator stack length The output frequency, winding distribution factor, pitch factor, turns per phase, and generator stack length are all parameters which come from the Kato Engineering in-house spreadsheet design program for a given electrical machine design. The difference in air-gap magnetic vector potential at adjacent quadrature axes comes from the FE model results. The predicted field current required to produce rated voltage in the generator was 65.9 amps from the magnetostatic simulation. The actual field current required to produce rated voltage in the generator during Factory Acceptance Tests (FAT) was 66.2 amps. The percent error of the simulation prediction was - 0.45%. The predicted open-circuit field currents from the Kato Engineering in-house spreadsheet design programs were 61.4 amps and 78.6 amps. The former prediction comes from our design program which is used on most new R&D projects and the latter prediction comes from our more standard design program which employs test data correction after a design is built and tested. The R&D spreadsheet program is generally more accurate for out of the box predictions of this type.

Figure 7. Open-Circuit Saturation Curve Comparison Generator Voltage Signal Harmonics The simulation no-load voltage signal harmonics can be calculated from the magnetostatic simulation results via the use of the air-gap radial flux plot. Figure 8 shows the radial flux pattern versus path length along the air-gap of the machine, from the magnetostatic simulation results. The flux pattern is transformed from the time domain to the frequency domain via the use of a Fast Fourier Transform (FFT). The frequency domain magnitudes are normalized by the fundamental frequency (i.e. 1 st harmonic). Each flux wave harmonic fraction is then multiplied by a pitch factor, distribution factor, and skew factor in order to calculate the individual voltage harmonics, expressed in percent. For this calculation there are unique pitch, distribution, and skew factors calculated for each individual flux wave harmonic based upon the number of poles, stator slots, throw, pitch percentage, skew, and phases. The total harmonic distortion (THD) is calculated by evaluating the square root of the sum of the squares of the individual harmonics (excluding the fundamental).

Figure 8. Radial Air-Gap Flux versus Path Length The no-load voltage signal harmonics can also be calculated from the transient open-circuit simulation results by performing a Fast Fourier Transform directly on the simulation output voltage signal. The individual harmonic magnitudes from the FFT are once again normalized by the fundamental harmonic magnitude and the THD is calculated in the same manner as explained above. Figure 9 shows the transient open-circuit simulation output voltage signals.

Figure 9. Transient Simulation Open-Circuit Voltage Figure 10 shows a tabular comparison of the no-load line to neutral (L-N) phase voltage signal harmonics from the simulation predictions and from the actual test data voltage signal harmonics measured in the generator FAT. The predicted peak individual harmonic was 0.99% and 1.03% for the 5 th harmonic from the magnetostatic and transient simulations, respectively. The peak individual harmonic from the generator test data was 0.94% for the 5 th harmonic. The predicted total harmonic distortion (THD) was 1.336% and 1.490% from the magnetostatic and transient simulations, respectively. The THD from the generator test data was 1.340%. The R&D spreadsheet program predicted a peak individual harmonic of 1.105% and a THD of 1.431%.

Figure 10. Generator Voltage Harmonics Comparison Generator Transient and Subtransient Reactance Figure 11 shows a tabular comparison of the predicted and tested generator reactance values. The predicted transient reactance from the simulation was 10.0% and the transient reactance calculated from the actual test data was 11.2%. The predicted subtransient reactance from the simulation was 8.6% and the subtransient reactance calculated from the test data was 9.1%. The predicted transient and subtransient reactances from the R&D spreadsheet program were 15.3% and 12.8%, respectively. It is more convenient for electrical design engineers to express circuit values in percent or even per unit terms. To convert to actual ohmic values for the reactances, multiply the percentages (in decimal format) by the base impedance (which is derived from rated voltage and current). Figure 11. Generator Reactance Comparison For the generator FAT, the transient and subtransient reactances are calculated individually for 3 separate current traces taken from 3 unique applications of a three phase fault. The results from the 3 calculations are averaged for the final reported values. The test operators try to achieve a balanced fault current trace as this makes the calculation process more reliable. For the simulation predictions, the transient and subtransient reactances are calculated for all 3 phase current traces and the results are averaged to obtain the final values for comparison. The process of calculating the reactance values from the short-circuit phase current traces is typically fairly time consuming and definitely somewhat subjective. The author developed an automated process for

calculating the reactance values in order to reduce the time required to calculate the values based upon the short-circuit phase current trace data. The automated process was set-up and performed with the software program Mathcad. Figure 12 shows the phase current trace data from the short-circuit simulation. Figure 12. Short-Circuit Current Simulation Data Conclusions The open-circuit saturation curve predicted from the magnetostatic simulation correlates extremely well with the open-circuit saturation curve developed from the generator Factory Acceptance Tests. The predicted field current required to produce rated open-circuit voltage was within 0.5% of the actual tested field current requirement. The model does an excellent job of predicting the saturation characteristics of the machine and this capability has proven to be extremely useful. The heating in the field coil winding is proportional to the square of the current flowing in the winding, and the ability to accurately predict the current requirements has a big impact on the ability to predict the heat generation in the field coil windings, among other things. Our in-house spreadsheet design programs generally do a good job of predicting the linear behavior of the saturation curve (i.e. the air-gap line), but they tend to struggle with the actual saturation characteristics as well as the effects of the air vents in the stator stack. The excellent correlation of the FE model saturation curve essentially validates the magnetic material properties used for the analyses. The magnetostatic model and transient circuit-coupled model both do a good job of predicting the voltage signal harmonics for the generator. In this case, the predictions from the magnetostatic model were the most accurate. The peak individual harmonic prediction from the magnetostatic model was within 5.3% of the measured peak individual harmonic from the generator Factory Acceptance Tests. The Total Harmonic Distortion prediction from the magnetostatic model was within 0.3% of the measured Total Harmonic Distortion. The R&D in-house spreadsheet design program also does a reasonably good job of predicting the voltage signal harmonics. The spreadsheet predictions were within 17.6% and 6.8% for the peak individual harmonic and Total Harmonic Distortion, respectively. Note that the simulations show a higher

harmonic distortion content near the 30 th harmonic than what is found in the test data. For this generator design, the slot passing frequency for the rotor is 1.8 khz. The 30 th harmonic has a frequency of 1.8 khz. The simulation voltage signal has a 1.8 khz ripple due to the rotor passing the stator slots. This is typically reduced in reality by using a slot skew on the stator stack. This particular design has a 1 slot skew and the skew results in lesser measured distortion near the 30 th harmonic. The transient circuit-coupled simulation provides a powerful tool for predicting the transient and subtransient reactances of the generator. The subtransient reactance prediction was within 5.5% of the measured value from the generator Factory Acceptance Tests. The transient reactance prediction was within 10.7% of the measured value. The reactance calculations themselves are a bit nebulous due to the nature of how the calculations are carried out. Typically, Kato Engineering guarantees the measured reactance values within +/-20% of the predicted reactance values. The importance of the ability to predict the reactance values can be brought to light by considering the history of this particular generator design. The guaranteed subtransient reactance for this generator design was 9.3% to 12.6% (+/-15% of the standard spreadsheet design program prediction). This particular customer specification had a slightly narrower tolerance band for the allowable subtransient reactance (i.e. +/-15%). The measured subtransient reactance was 9.1% and we had to request a specification deviation from the customer in order to deliver the generator. Had we been able to use the Finite Element simulation tools presented herein for predicting the subtransient reactance we would have put forth a guaranteed range of 7.3% to 9.9%, and the measured subtransient reactance would have been well within the limits of our customer driven specification. References 1. John H. Kuhlmann, Design of Electrical Apparatus, 3 rd ed., John Wiley and Sons, New York, 1950. 2. James W. Nillson, Electric Circuits, 4 th ed., Addison-Wesley Publishing Company, 1993.