Past CIGRE and Emerging IEEE Guide Documents on FCLs

Similar documents
Standards Developments for Fault Current Limiters

Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, Strombegrenzerkonzepte im Vergleich

DEVELOPMENT OF A TEST PROTOCOL FOR A 15 KV CLASS SOLID-STATE CURRENT LIMITER

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

DEVELOPING TESTING PROCEDURES FOR HIGH VOLTAGE INNOVATION TECHNOLOGIES

Saturated Core Fault Current Limiters: successful testing/ service performance

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

TRANSIENT AND DESIGN OPERATION ASSESSMENT OF RFCL IN BULK POWER SYSTEMS

Recent Development of SFCL in the USA

Roadmap For Power Quality Standards Development

Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC

Fault Current Limiter Selection Considerations for Utility Engineers

PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS

N. TEST TEST DESCRIPTION

Superconducting Fault Current Limiter Modules for Power Transmission / Distribution

N. TEST TEST DESCRIPTION

OLD BUSINESS

Fixed Series Compensation

AORC Technical meeting 2014

Insulation Co-ordination For HVDC Station

EE 1402 HIGH VOLTAGE ENGINEERING

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

EDS FAULT LEVELS

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Copyright 2008 IEEE.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

ABSTRACT I. INTRODUCTION

Shunt Reactor Switching

MEDIUM & HIGH VOLTAGE

TS RES - OUTSTANDING ISSUES

Harmonic filter design for IEC compliance

FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION

Tab 2 Voltage Stresses Switching Transients

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

I -limiter The world s fastest switching device

Sub-cooled SFCL Device and Modules for Power Transmission / Distribution

Simulation of HTS saturable core-type FCLs for MV distribution systems

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

Electric Power Quality: Voltage Sags Momentary Interruptions

MV network design & devices selection EXERCISE BOOK

Mosca-Genova: SMART CITY futuro o realtà?

Keywords: Solid state fault current limiter, Distribution system, Distributed generation, Recloser-fuse coordination.

LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards.

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Protection of Electrical Networks. Christophe Prévé

CVVOZE Power Laboratories (CVVOZEPowerLab)

FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Using Fault Current Limiting mode of a Hybrid DC Breaker

HARMONIC FILTERS Design for IEC compliance

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids

Impact of SFCL on the Four Types of HVDC Circuit Breakers by Simulation

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

Power Quality Basics. Presented by. Scott Peele PE

DC VACUUM CIRCUIT BREAKER

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

SERIES ACTIVE power filters have proved to be an interesting

NEMA Standards Publication ICS Adjustable Speed Electrical Power Drive Systems

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Multimeter 500CVD21 RTU500 series

Table of Contents. Introduction... 1

(2) New Standard IEEE P (3) Core : (4) Windings :

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

StarSine Power Quality Products

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

UNIT-4 POWER QUALITY MONITORING

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Prepared by Mick Maytum

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

Harmonic control devices. ECE 528 Understanding Power Quality

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

Harmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.

International Journal of Engineering Technology and Scientific Innovation

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Development and performance analysis of a saturated core high temperature superconducting fault current limiter

PTTS series. Power Transformer Test System. Scope of Work:

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Immunity Testing for the CE Mark

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Design and Simulation of superconducting fault current limiter

DEPARTMENT OF EEE QUESTION BANK

ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Phase Shifting Transformers. Presented by

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

VI 3 - i TABLE OF CONTENTS

Control of Power Converters for Distributed Generation

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Stabilized Differential Relay SPAD 346. Product Guide

Transcription:

Past CIGRE and Emerging IEEE Guide Documents on FCLs Michael Mischa Steurer Leader Power Systems Research Group at FSU-CAPS Email: steurer@caps.fsu.edu, phone: 850-644-1629 Presented by W. Hassenzahl Advanced Energy Analysis 11th EPRI Superconductivity Conference Oct 29, 2013, Houston, TX

Why FCLs? Design trade off in power systems High short-circuit capacity during normal operation (low short-circuit impedance) - Low voltage drops - High power quality - High steady-state and transient stability - Low system pertubations Low short-circuit capacity during fault conditions (high short-circuit impedance) - Low thermal and mechanical strain - Reduced breaker capacity Optimal solution FCL - Low impedance during normal operation - Fast and effective current limitation - Automatic and fast recovery 2

History of CIGRE s Work on FCLs CIGRE WG 3.10, 1996 2003, 15 members from 9 countries TB 239 Fault Current Limiters in Electrical Medium and High Voltage Systems First international group to look at FCLs initial technology overview Started to define FCL behavior in the grid CIGRE WG 3.16, 2003 2008, 11 members from 8 countries TB 339 Guidelines on the Impacts of Fault Current Limiting Devices on Protection Systems General systematic to assess the impact on system protection Technology independent - FCL as black box CIGRE WG 3.23, 2008 2012, 25 members from 11 countries TB 497 Application and Feasibility of Fault Current Limiters in Power Systems Comprehensive FCL technology overview Examples of FCL applications TB = Technical Brochure 3

Fault Current Limiting Measures PC37.302 adopted from CIGRE TB 497 Permanent impedance increase during nominal and fault conditions Splitting into sub grids Introducing a higher voltage range Splitting of bus bars Old term: passive High impedance transformers Current limiting reactors Sequential tripping Fault Current Limiters Condition based impedance increase Small impedance at nominal load fast increase of impedance at fault Fuse based devices (< 36 kv) Stand alone HV fuse (< 1 ka) Commutating Current Limiters (< 5 ka) Old term: active Emerging Concepts Superconductors Solid-State Devices Magnetic Effects Hybrid Systems Scope of IEEE PC37.302 Topological measures Apparatus measures Topological measures Fault Current Limiting Devices Apparatus measures & FCL must limit the first peak 4

IEEE WG PC37.302 Guide for Fault Current Limiter Testing Established: June 2010, PAR expires Dec 2014 Recognizing the need for general guidance on FCL testing to ease market introduction Sponsors: IEEE Switchgear (PE/SWG) Committee Power & Energy Society/Substations (PE/SUB) Power Electronics Society/Standards Committee (PEL/SC) Balloting planned for Dec 2013 Register and ballot via IEEE Standards Association Contact: Mischa Steurer steurer@caps.fsu.edu, 850-644-1629 Chair of IEEE WG PC37.302 Former member of CIGRE WG A3.16, A3.23 5

IEEE WG PC37.302 Guide for Fault Current Limiter Testing Follows template/structure of other equipment testing standards with clauses 3. Definitions 4. Introduction 5. Specification 6. Design Tests 7. Production (Routine) Tests 8. Field Tests Does not prescribe any specific value Major effort to develop general framework which maintains FCL technology independence Provides parameter definitions for fully describing any FCL behavior References numerous other IEEE and IEC standards for applicable procedures, test setups, etc. 6

C37.302 Clause 3 Definitions Fault Current Limiter (FCL) A device which limits the prospective peak and/or RMS fault current in an alternating current power system to the specified value by providing condition-based increase in resistive and/or reactive impedance between normal conducting mode and current limiting mode. The FCL may consist of discrete functionally integrated, spatially separated equipment Provides parameter definitions to fully describe FCL behavior Needed to substantially expand parameter set given by CIGRE TB 497 to meet the needs of the FCL testing guide No definition of FCL existed previously This is the consensus in WG PC37.302 7

C37.302 Clause 3 Definitions FCL modes C mode: normal conducting the FCL is in its low impedance state CL mode: current limiting generally, the FCL is in its high impedance state some technologies may constantly transition between high and low impedance during the current limiting phase I mode: interruption the FCL has interrupted the fault current flow (if applicable) Transitions to and from other modes: IC, CLI, ICL C mode 2 2 *I R i p,max i p,lt t LT t k,cl CL mode I mode Prospective current Limited current 2 2 *I k,max 8

C37.302 Clause 4 FCL Technical Principles Treats FCL as black box Refers to CIGRE TB 497 for technology overview in open literature FCL types consistent with TB 497 A1: behavior with a current waveform that can be accurately described by power frequency and DC components after transitioning into CL mode A2: current waveform, which after transitioning into CL mode, requires additional parameters or information during each current loop besides power frequency and DC components in order to be accurately described B: A1 or A2 but with interruption by FCL Example: Air core reactor parallel with solid state switch Example: Saturated iron core type 9

Example: Type A1 Resistive Behavior Current through FCL Fault inception Fault clearing by circuit breaker AND Voltage across FCL waveforms are parameterized 10

Example: Type A2 Current through FCL Fault inception Fault clearing by circuit breaker AND Voltage across FCL waveforms are parameterized 11

C37.302 Clause 5 Specifications Provides parameter descriptions (no values) by which FCLs may be specified & rated Electrical Prospective fault current, Rated power frequency, Rated steady-state voltage drop, Rated losses, etc Physical and Operational Footprint, Height, Weight, Cryogenic system maintenance, etc. Environmental Proper thermal performance, Temperature regulation for electronics, Transport conditions, Storage, etc. Safety Lifespan 12

C37.302 Clause 5 Specifications Recovery Process FCL in C mode Partial recovery process Provides guidance on how to parameterize the fault current limitation and recovery process Technology independent; applicable to all types of FCLs A1, A2, B FCL in C mode ready to limit Fault inception FCL in CL mode limiting fault current t pr Fault cleared FCL is CL mode recovered FCL in CL mode, ready to limit rated fault current and ready to carry below rated continuous current FCL is CL mode rated recovered and ready to carry up to rated continuous current FCL is C mode recovered FCL in C mode, ready to limit rated fault current and enter CCL transition and ready to carry below rated continuous current FCL is fully recovered and ready to carry up to rated continuous current t prr t da t r t k,cl t rr with load current with fault current without load current with load current Time 13

C37.302 Clause 6 Design Tests Voltage Withstand: Power Frequency, Lightning Impulse, Switching Impulse, Chopped-Wave, Partial Discharge Current Withstand: Continuous, Surge, Short-Time and Peak Withstand Harmonic Distortion EMC, Audible Sound, Seismic, Visual Inspection Short-circuit current limitation Recovery FCL Technology-Specific Similar to other equipment FCL specific 14

Short-Circuit Current Limitation Test Test Circuit G Generator Line CB PT CT FCL External bypass CB PT Load Digital recorder Short Circuit CB Test number Applied current condition Duration Remark 1 Rated continuous current of FCL (I r ) 2 Rated maximum prospective short-circuit current of FCL (i p,max, i k,max ) 3 Rated continuous current of FCL (I r ) 4 Rated maximum prospective short-circuit current of FCL (i p,max, i k,max ) 3 sec. minimum To verify the expected insertion impedance 10 cycles To verify the rated limited short circuit withstand current of the FCL during peak and RMS current limiting action twice the expected recovery time 10 cycles To repeat test 2 To verify the recovery time. The duration should be long enough to ensure recovery. Example of test Sequence 15

Conclusions CIGRE TB 239, 339, and 497 provide very good overview on FCL technologies, applications, and power system impact IEEE C37.302 will provide the first guide for testing Substantially expanded the definitions of waveforms and associated parameters to adequately describe FCL behavior Defines a framework for FCL recovery Maintains technology independence Possible topic for next WG Guide for Application of FCLs in Power Systems 16