SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

Similar documents
CHAPTER 2. Transformers. Dr Gamal Sowilam

86 chapter 2 Transformers

Transformer & Induction M/C

148 Electric Machines

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

Practical Transformer on Load

Chapter 2-1 Transformers

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Electrical Machines I : Transformers

PROBLEMS on Transformers

AC Power Instructor Notes

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

AUTO-TRANSFORMER. This is having only one winding; part of this winding is common to both primary and secondary.

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

TRANSFORMER THEORY. Mutual Induction

Chapter 7. Copyright The McGraw-Hill Companies, Inc. Permission required for reproduction or display.

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad ELECTRICAL AND ELECTRONICS ENGINEERING

TRANSFORMER OPERATION

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014

VALLIAMMAI ENGINEERING COLLEGE

Chapter 2: Transformers

Transformers. gpmacademics.weebly.com

Hours / 100 Marks Seat No.

CHAPTER 4. Distribution Transformers

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Basic Operating Principles of Transformers

WELCOME TO THE LECTURE

EE 340 Power Transformers

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Code No: R Set No. 1

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT B.Tech. [SEM I (EE, EN, EC, CE)] QUIZ TEST-3 (Session: ) Time: 1 Hour ELECTRICAL ENGINEE

El-Hawary, M.E. The Transformer Electrical Energy Systems. Series Ed. Leo Grigsby Boca Raton: CRC Press LLC, 2000

CHAPTER 9. Sinusoidal Steady-State Analysis

Spring 2000 EE361: MIDTERM EXAM 1

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Transformers 21.1 INTRODUCTION 21.2 MUTUAL INDUCTANCE

ECE 3600 Transformers b

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

SYNCHRONOUS MACHINES

Code No: R Set No. 1

Transformers. Dr. Gamal Sowilam

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Transformer Waveforms

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Single Phase induction Motor [1/Ch. 36]

EE 350: Electric Machinery Fundamentals

Chapter 16: Mutual Inductance

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

The power transformer

~=E.i!=h. Pre-certification Transformers

EN Assignment No.1 - TRANSFORMERS

APPLICATION NOTE - 018

UNIT 1 CIRCUIT ANALYSIS 1 What is a graph of a network? When all the elements in a network is replaced by lines with circles or dots at both ends.

Question Paper Profile

Rony Parvej s EEE. Lecture 3 & 4: Transformer. Update: 30 April, fecabook.com/ronyiut

Look over Chapter 31 sections 1-4, 6, 8, 9, 10, 11 Examples 1-8. Look over Chapter 21 sections Examples PHYS 2212 PHYS 1112

Manuals. Basic Electrical Engineering BE-104

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

EE2022 Electrical Energy Systems

REV NO EXPERIMENT NO 1 AIM: To perform open and short circuit tests on 1-phase transformer and to calculate efficiency. Apparatus required:

Transmission Line Models Part 1

An induced emf is the negative of a changing magnetic field. Similarly, a self-induced emf would be found by

ECE 241L Fundamentals of Electrical Engineering. Experiment 8 A-C Transformer, Magnetization & Hysteresis

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Downloaded from / 1

Chapter 33. Alternating Current Circuits

EQUIVALENT CIRCUIT OF A SINGLE-PHASE TRANSFORMER

ELECTRICAL ENGINEERING ESE TOPIC WISE OBJECTIVE SOLVED PAPER-II

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

, ,54 A

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

VETRI VINAYAHA COLLEGE OF ENGINEERING AND TECHNOLOGY

MILWAUKEE SCHOOL OF ENGINEERING LABORATORY SESSION 4 THREE PHASE TRANSFORMERS

Downloaded From All JNTU World

Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer

Electrical Machines (EE-343) For TE (ELECTRICAL)

For the circuit in Fig. 1, determine the current in the neutral line.

ELG2336 Introduction to Electric Machines

Hours / 100 Marks Seat No.

Table of Contents. Table of Figures. Table of Tables

Experiment No. Experiments for First Year Electrical Engg Lab

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Engineering Science OUTCOME 4 - TUTORIAL 3 CONTENTS. 1. Transformers

1. Explain in detail the constructional details and working of DC motor.

UNIT II MEASUREMENT OF POWER & ENERGY

Transformers. Objectives

PROBLEMS. Figure13.74 For Prob Figure13.72 For Prob Figure13.75 For Prob Figure13.73 For Prob Figure13.76 For Prob

Three phase transformer 1

TRANSFORMERS INTRODUCTION

Chapter 33. Alternating Current Circuits

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

SHRI RAMSWAROOP MEMORIAL COLLEGE OF ENGG. & MANAGEMENT

IV. Three-Phase Transfomers

Transcription:

SECTION 4 TRANSFORMERS Yilu (Ellen) Liu Associate Professor Electrical Engineering Department Virginia Tech University Analysis of Transformer Turns Ratio......................... 4.2 Analysis of a Step-Up Transformer.......................... 4.2 Analysis of a Transformer Connected to a Load................... 4.3 Selection of a Transformer for Impedance Matching................ 4.3 Performance of a Transformer with Multiple Secondaries............ 4.4 Impedance Transformation of a Three-Winding Transformer........... 4.5 Selection of a Transformer with Tapped Secondaries............... 4.6 Transformer Characteristics and Performance................... 4.7 Performance and Analysis of a Transformer with a Lagging Power-Factor Load......................... 4.7 Performance and Analysis of a Transformer with a Leading Power-Factor Load.............................. 4.10 Calculation of Transformer Voltage Regulation................... 4.10 Calculation of Efficiency................................ 4.11 Analysis of Transformer Operation at Maximum Efficiency............ 4.12 Calculation of All-Day Efficiency............................ 4.12 Selection of Transformer to Supply a Cyclic Load................. 4.13 Analysis of Transformer under Short-Circuit Conditions............. 4.14 Calculation of Parameters in the Equivalent Circuit of Power Transformer Equivalent Circuit Using Open- and Short-Circuit Tests................................... 4.14 Performance of a Step-Up Autotransformer (Buck/Boost Transformer in Boost Mode)..................... 4.16 Analysis of a Delta-Wye Three-Phase Transformer Bank Used as a Generator-Step-Up Transformer........................... 4.17 Performance of an Open Delta or Vee-Vee System................. 4.19 Analysis of a Scott-Connected System........................ 4.20 Bibliography....................................... 4.21 4.1

4.2 HANDBOOK OF ELECTRIC POWER CALCULATIONS FIGURE 4.1 Ideal single-phase transformer. ANALYSIS OF TRANSFORMER TURNS RATIO Compute the value of the secondary voltage, the voltage per turn of the primary, and the voltage per turn of the secondary of the ideal single-phase transformer of Fig. 4.1. 1. Compute the Value of the Secondary Voltage The turns ratio, a, of a transformer is the ratio of the primary turns, N 1, to the secondary turns, N 2, or the ratio of the primary voltage, V 1, to the secondary voltage, V 2 ; a N 1 /N 2 V 1 /V 2. Substitution of the values indicated in Fig. 4.1 for the turns ratio yields a 1000/500 2. Secondary voltage V 2 V 1 /a 120/2 60 V. 2. Compute the Voltage per Turn of the Primary and Secondary Windings Voltage per turn of the primary winding V 1 /N 1 120/1000 0.12 V/turn. Voltage per turn of the secondary winding V 2 /N 2 60/500 0.12 V/turn. Related Calculations. This procedure illustrates a step-down transformer. A characteristic of both step-down and step-up transformers is that the voltage per turn of the primary is equal to the voltage per turn of the secondary. ANALYSIS OF A STEP-UP TRANSFORMER Calculate the turns ratio of the transformer in Fig. 4.1 when it is employed as a step-up transformer. 1. Compute the Turns Ratio In the step-up transformer, the low-voltage side is connected to the input, or primary, side. Therefore, a N 2 /N 1 V 2 /V 1 ; hence, a 500/1000 0.5. Related Calculations. For a particular application, the turns ratio, a, is fixed but is not a transformer constant. In this example, a 0.5 when the transformer is used as a step-up transformer. In the previous example, a 2 when the transformer is used as a step-down transformer. The two values of a are reciprocals of each other: 2 1/0.5, and 0.5 1/2.

TRANSFORMERS 4.3 FIGURE 4.2 Single-phase transformer connected to load. ANALYSIS OF A TRANSFORMER CONNECTED TO A LOAD A 25-kVA single-phase transformer is designed to have an induced emf of 2.5 V/turn (Fig. 4.2). Calculate the number of primary and secondary turns and the full-load current of the primary and secondary windings. 1. Compute the Number of Primary and Secondary Turns N 1 V 1 /(V/turn) 2500 V/(2.5 V/turn) 1000 turns. Similarly, N 2 V 2 /(V/turn) 250/2.5 100 turns. The turns ratio a N 1 /N 2 1000/100 10:1. 2. Compute the Full-Load Current of the Primary and Secondary Windings Primary current I 1 (VA) 1 /V 1 25,000 VA/2500 V 10 A. Secondary current I 2 (VA) 2 /V 2 25,000 VA/250 V 100 A. The current transformation ratio is 1/a I 1 /I 2 10 A/100 A 1:10. Related Calculations. One end of each winding is marked with a dot in Fig. 4.2. The dots indicate the terminals that have the same relative polarity. As a result of the dot convention, the following rules are established: 1. When current enters a primary that has a dot polarity marking, the current leaves the secondary at its dot polarity terminal. 2. When current leaves a primary terminal that has a dot polarity marking, the current enters the secondary at its dot polarity terminal. Manufacturers usually mark the leads on the high-voltage sides as H 1,H 2, etc. The leads on the low-voltage side are marked X 1,X 2, etc. Marking H 1 has the same relative polarity as X 1, etc. SELECTION OF A TRANSFORMER FOR IMPEDANCE MATCHING Select a transformer with the correct turns ratio to match the 8- resistive load in Fig. 4.3 to the Thevenin equivalent circuit of the source.

4.4 HANDBOOK OF ELECTRIC POWER CALCULATIONS FIGURE 4.3 Transformer used for impedance matching. 1. Determine the Turns Ratio The impedance of the input circuit, Z i, is 5000. This value represents the Thevenin impedance of the source. The load impedance, Z L, is 8. To achieve an impedance match, the required turns ratio is a Z i /Z L 5000 /8 25 Therefore, the impedance-matching transformer must have a turns ratio of 25:1. Related Calculations. The maximum power transfer theorem (Sec. 1) states that maximum power is delivered by a source to a load when the impedance of the load is equal to the internal impedance of the source. Because the load impedance does not always match the source impedance, transformers are used between source and load to ensure matching. When the load and source impedances are not resistive, maximum power is delivered to the load when the load impedance is the complex conjugate of the source impedance. PERFORMANCE OF A TRANSFORMER WITH MULTIPLE SECONDARIES Determine the turns ratio of each secondary circuit, the primary current, I 1, and rating in kva of a transformer with multiple secondaries, illustrated in Fig. 4.4. 1. Select the Turns Ratio of Each Secondary Circuit Let the turns ratio of circuit 1 to circuit 2 be designated as a 2 and the turns ratio of circuit 1 to circuit 3 as a 3. Then, a 2 V 1 /V 2 2000 V/1000 V 2:1 and a 3 V 1 /V 3 2000 V/500 V 4:1. 2. Compute the Primary Current I 1 Since I 2 V 2 /Z 2 and I 3 V 3 /Z 3, then I 2 1000 V/500 20 A and I 3 500 V/50 10 A. The ampere turns of the primary (N 1 I 1 ) of a transformer equals the sum of the

TRANSFORMERS 4.5 FIGURE 4.4 Transformer with multiple secondaries. ampere turns of all the secondary circuits; therefore, N 1 I 1 N 2 I 2 N 3 I 3. Solving for I 1, we have I 1 (N 2 /N 1 )I 2 (N 3 /N 1 )I 3. The turns ratio is N 2 /N 1 1/a 2 and N 3 /N 1 1/a 3. Hence, I 1 I 2 /a 2 I 3 /a 3 (20 A)( ) (10 A) ( ) 12.5 A. 1 2 3. Compute the Rating in kva of the Transformer The winding ratings are kva 1 V 1 I 1 /1000 (2000 V)(12.5 A)/1000 25 kva, kva 2 V 2 I 2 /1000 (1000 V)(20 A)/1000 20 kva, and kva 3 V 3 I 3 /1000 (500 V)(10 A)/1000 5 kva. The apparent power rating of the primary equals the sum of the apparent power ratings of the secondary. As a check, 25 kva (20 5) kva 25 kva. Related Calculations. When the secondary loads have different phase angles, the same equations still apply. The voltages and currents, however, must be expressed as phasor quantities. 1 4 IMPEDANCE TRANSFORMATION OF A THREE-WINDING TRANSFORMER Calculate the impedance, Z 1, seen by the primary of the three-winding transformer of Fig. 4.4 using impedance-transformation concepts. 1. Calculate Z 1 The equivalent reflected impedance of both secondaries or the total impedance seen by the primary, Z 1, is: Z 1 Z 2 Z 3, where Z 2 is the reflected impedance of circuit 2 and a 2 3 Z 3 is the reflected impedance of circuit 3. Hence, Z 1 (2) 2 (50 ) (4) 2 (50 ) 200 800 160. 2. Check the Value of Z 1 Found in Step 1 Z 1 V 1 /I 1 2000 V/12.5 A 160. a 2 2 a 2 3 a 2 2

4.6 HANDBOOK OF ELECTRIC POWER CALCULATIONS Related Calculations. When the secondary loads are not resistive, the preceding equations still apply. The impedances are expressed by complex numbers, and the voltage and current are expressed as phasors. SELECTION OF A TRANSFORMER WITH TAPPED SECONDARIES Select the turns ratio of a transformer with tapped secondaries to supply the loads of Fig. 4.5. 1. Calculate the Power Requirement of the Primary When a transformer has multiple, or tapped, secondaries, P 1 P 2 P 3, where P 1 is the power requirement of the primary and P 2, P 3, are the power requirements of each secondary circuit. Hence, P 1 5 2 10 3 20 W. 2. Compute the Primary Input Voltage, V 1 From P 1 /Z 1, one obtains V 1 P 1 Z 1 20 2000 200 V. V 2 1 3. Compute the Secondary Voltages V 2 5 6 5.48 V, V 3 2 8 4 V, V 4 10 16 12.7 V, and V 5 3 500 38.7 V. 4. Select the Turns Ratio The ratios are a 2 V 1 /V 2 200/5.48 36.5:1, a 3 V 1 /V 3 200/4 50:1, a 4 V 1 /V 4 200/12.7 15.7:1, and a 5 V 1 /V 5 200/38.7 5.17:1. Related Calculations. A basic transformer rule is that the total power requirements of all the secondaries must equal the power input to the primary of the transformer. FIGURE 4.5 Transformer with tapped secondaries.

TRANSFORMERS 4.7 FIGURE 4.6 Three-winding transformer. TRANSFORMER CHARACTERISTICS AND PERFORMANCE Compute the number of turns in each secondary winding, the rated primary current at unity-power-factor loads, and the rated current in each secondary winding of the threewinding transformer of Fig. 4.6. 1. Compute the Number of Turns in Each Secondary Winding The turns ratio in winding 2 is a 2 V 1 /V 2 N 1 /N 2 4800/600 8:1; hence, N 2 N 1 /a 2 800/8 100 turns. Similarly, a 3 V 1 /V 3 N 1 /N 3 4800/480 10:1 from which N 3 N 1 /a 3 800/10 80 turns. 2. Compute the Rated Primary Current I 1 (VA) 1 /V 1 100,000/4800 20.83 A. 3. Compute the Rated Secondary Currents I 2 (VA) 2 /V 2 50,000/600 83.8 A and I 3 (VA) 3 /V 3 50,000/480 104.2 A. Related Calculations. This method may be used to analyze transformers with one or more secondary windings for power, distribution, residential, or commercial service. When the loads are not at unity power factor, complex algebra and phasors are used where applicable. PERFORMANCE AND ANALYSIS OF A TRANSFORMER WITH A LAGGING POWER-FACTOR LOAD Calculate the primary voltage required to produce rated voltage at the secondary terminals of a 100-kVA, 2400/240-V, single-phase transformer operating at full load. The power factor (pf) of the load is 80 percent lagging.

4.8 HANDBOOK OF ELECTRIC POWER CALCULATIONS FIGURE 4.7 Circuit model of a practical transformer. 1. Analyze the Circuit Model of Fig. 4.7 The model of Fig. 4.7 includes winding resistances, inductive reactances, and core and copper losses. The symbols are defined as follows: V 1 supply voltage applied to the primary circuit R 1 resistance of the primary circuit X 1 inductive reactance of the primary circuit I 1 current drawn by the primary from the power source I EXC exciting current I c core loss component of the exciting current; this component accounts for the hysteresis and eddy-current losses I magnetizing component of exciting current R c equivalent resistance representing core loss X m primary self-inductance that accounts for magnetizing current I 2 /a load component of primary current E 1 voltage induced in the primary coil by all the flux linking the coil E 2 voltage induced in the secondary coil by all the flux linking the coil R 2 resistance of the secondary circuit, excluding the load X 2 inductive reactance of the secondary circuit I 2 current delivered by the secondary circuit to the load V 2 voltage that appears at the terminals of the secondary winding, across the load 2. Draw Phasor Diagram The phasor diagram for the model of Fig. 4.7 is provided in Fig. 4.8. The magnetizing current, I, is about 5 percent of full-load primary current. The core loss component of the exciting current, I c, is about 1 percent of full-load primary current. Current I c is in phase

TRANSFORMERS 4.9 FIGURE 4.8 Phasor diagram for circuit of Fig. 4.7. with E 1, and I lags E 1 by 90. The power factor of the exciting current, I EXC, is quite low and lags E 1 by approximately 80. 3. Simplify the Circuit of Fig. 4.7 The exciting current is neglected in the approximate transformer model of Fig. 4.9. The primary parameters R 1 and X 1 are referred to the secondary side as R 1 /a 2 and X 1 /a 2, respectively. Hence, R EQ2 R 1 /a 2 R 2 and X EQ2 X 1 /a 2 X 2. The equivalent impedance of the transformer referred to the secondary side is: Z EQ2 R EQ2 jx EQ2. 4. Solve for V 1 Transformer manufacturers agree that the ratio of rated primary and secondary voltages of a transformer is equal to the turns ratio: a V 1 /V 2 2400/240 10 1. Z EQ2 (R 1 /a 2 R 2 ) j(x 1 /a 2 X 2 ) (0.3/100 0.003) j(1.5/100 0.015) 0.03059 78.69, but I 2 (VA) 2 /V 2 100,000/240 416.67 A. Using V 2 as a reference, I 2 416.67 36.87 A, but V 1 /a V 2 I 2 Z EQ2 240 0 (416.67 36.87 )(0.03059 78.69 ) 249.65 1.952. However, V 1 a V 1 /a 10 249.65 2496.5 V. FIGURE 4.9 Simplified version of Fig. 4.7.

4.10 HANDBOOK OF ELECTRIC POWER CALCULATIONS Related Calculations. For lagging power-factor loads, V 1 must be greater than rated value (in this case 2400 V) in order to produce rated voltage across the secondary (240 V). PERFORMANCE AND ANALYSIS OF A TRANSFORMER WITH A LEADING POWER-FACTOR LOAD Calculate the primary voltage required to produce rated voltage at the secondary terminals of the transformer of Fig. 4.7. The transformer is operating at full load with an 80 percent leading power factor. 1. Solve for V 1 With V 2 as a reference, I 2 416.67 36.87 A. Substituting, we have V 1 /a V 2 I 2 Z EQ2 240 0 (416.67 36.87 )(0.03059 78.69 ) 234.78 2.81. The magnitude V 1 a V 1 /a (10)(234.78) 2347.8 V. Related Calculations. When the load is sufficiently leading, as in this case, V 1 2347.8 V. This value is less than the rated primary voltage of 2400 V to produce the rated secondary voltage. CALCULATION OF TRANSFORMER VOLTAGE REGULATION Calculate the full-load voltage regulation of the transformer shown in Fig. 4.7 for 80 percent leading and lagging power factors. 1. Solve for the Full-Load Voltage Regulation at 80 Percent Lagging Power Factor Transformer voltage regulation is defined as the difference between the full-load and the no-load secondary voltages (with the same impressed primary voltage for each case). Expressed as a percentage of the full-load secondary voltage, voltage regulation is: VR [( V 1 /a V 2 )/ V 2 ] 100 percent. From the results of the 80 percent lagging power factor example, VR (249.65 240)/240 100 percent 4.02 percent. The phasor diagram for a lagging power-factor condition, that is illustrated in Fig. 4.10, indicates positive voltage regulation. 2. Solve for the Full-Load Voltage Regulation at 80 Percent Leading Power Factor From the 80 percent leading power-factor example, VR (234.78 240)/240 100 percent 2.18 percent. The phasor diagram for a leading power-factor condition, shown in Fig. 4.11, illustrates negative voltage regulation.

TRANSFORMERS 4.11 FIGURE 4.10 factor. Phasor diagram of transformer for lagging power FIGURE 4.11 Phasor diagram of transformer for leading power factor. FIGURE 4.12 Phasor diagram for zero transformer voltage regulation. Related Calculations. Negative regulation denotes that the secondary voltage increases when the transformer is loaded. This stems from a partial resonance condition between the capacitance of the load and the leakage inductance of the transformer. Zero transformer voltage regulation occurs when V 1 /a V 2. This condition, which occurs with a slightly leading power-factor load, is illustrated in Fig. 4.12. CALCULATION OF EFFICIENCY A 10-kVA transformer has 40-W iron loss at rated voltage and 160-W copper loss at full load. Calculate the efficiency for a 5-kVA, 80 percent power-factor load. 1. Analyze the Losses The sum of the hysteresis and eddy-current losses is called the core, or iron, loss of the transformer; this will be designated P i. The core loss is a constant loss of the transformer. The sum of the primary and secondary I 2 R losses is called the copper loss, P cu ; P cu R 1 R 2. This shows that copper losses vary with the square of the current. I 2 1 I 2 2 2. Solve for Efficiency Efficiency,, can be found from P out /P in P out /(P out losses) P out /(P out P i P cu ) (VA load )(pf)/[(va load )(pf) P t P cu (VA load /VA rating ) 2 ]. From this equation, (5000 0.8)/[5000 0.8 40 160(5000/10,000) 2 ] 0.98 or 98 percent. Related Calculations. The iron losses of a transformer are determined quite accurately by measuring the power input at rated voltage and frequency under no-load conditions.

4.12 HANDBOOK OF ELECTRIC POWER CALCULATIONS Although it makes no difference which winding is energized, it is usually more convenient to energize the low-voltage side. (It is essential to use rated voltage for this test.) The copper loss is measured by short-circuiting the transformer and measuring the power input at rated frequency and full-load current. It is usually convenient to perform the short-circuit test by shorting out the low-voltage side and energizing the high-voltage side; however, it does not matter if the procedure is reversed. Because changing the power factor of the load does not change the losses, raising the load power factor will improve the efficiency of the transformer. The losses then become a smaller proportion of the total power input. The no-load efficiency of the transformer is zero. High loads increase the copper losses, which vary with the square of the current, thereby decreasing the efficiency. Maximum efficiency operation occurs at some intermediate value of load. ANALYSIS OF TRANSFORMER OPERATION AT MAXIMUM EFFICIENCY Calculate the load level at which maximum efficiency occurs for the transformer of the previous example. Find the value of maximum efficiency with a 100 percent power-factor load and a 50 percent power-factor load. 1. Calculate the Load Level for Maximum Efficiency Maximum efficiency occurs when the copper losses equal the iron losses. Then, P i P cu (kva load /kva rating ) 2 or 40 160(kVA load /10 kva) 2. Solving, find kva load 5 kva. 2. Calculate Maximum Efficiency with 100 Percent Power-Factor Load With the copper and core losses equal, P out (P out P i P cu ) 5000(5000 40 40) 0.9842 or 98.42 percent. 3. Calculate Maximum Efficiency with 50 Percent Power-Factor Load Maximum efficiency is (5000 0.5)/(5000 0.5 40 40) 0.969 or 96.9 percent. Related Calculations. Maximum efficiency occurs at approximately half load for most transformers. In this procedure, it occurs at exactly half load. Transformers maintain their high efficiency over a wide range of load values above and below the half-load value. Maximum efficiency for this transformer decreases with lower power factors for a value of 98.42 percent at 100 percent power factor to a value of 96.9 percent at 50 percent power factor. Efficiencies of transformers are higher than those of rotating machinery, for the same capacity, because rotating electrical machinery has additional losses, such as rotational and stray load losses. CALCULATION OF ALL-DAY EFFICIENCY A 50-kVA transformer has 180-W iron loss at rated voltage and 620-W copper loss at full load. Calculate the all-day efficiency of the transformer when it operates with the following unity-power-factor loads: full load, 8 h; half load, 5 h; one-quarter load, 7 h; no load, 4 h.

TRANSFORMERS 4.13 1. Find the Total Energy Iron Losses Since iron losses exist for the entire 24 h the transformer is energized, the total iron loss is W i (total) P i t (180 24)/1000 4.32 kwh. 2. Determine the Total Energy Copper Losses Energy copper losses W cu P cu t. Because copper losses vary with the square of the load, the total-energy copper losses are found as follows: W cu (total) (1 2 620 8 0.5 2 620 5 0.25 2 620 7)/1000 6.006 kwh over the 20 h that the transformer supplies a load. 3. Calculate the Total Energy Loss The total energy loss over the 24-h period is: W loss (total) W i (total) W cu (total) 4.32 6.006 10.326 kwh. 4. Solve for the Total Energy Output W out (total) 50 8 50 5 50 7 612.5 kwh. 1 2 5. Compute the All-Day Efficiency All-day efficiency W out(total) /[W out(total) W loss(total) ] 100 percent 612.5/(612.5 10.236) 100 percent 98.3 percent. Related Calculations. All-day efficiency is important when the transformer is connected to the supply for the entire 24 h, as is typical for ac distribution systems. It is usual to calculate this efficiency at unity power factor. At any other power factor, the allday efficiency would be lower because the power output would be less for the same losses. The overall energy efficiency of a distribution transformer over a 24-h period is high in spite of varying load and power-factor conditions. A low all-day efficiency exists only when there is a complete lack of use of the transformer, or during operation at extremely low power factors. 1 4 SELECTION OF TRANSFORMER TO SUPPLY A CYCLIC LOAD Select a minimum-size transformer to supply a cyclic load that draws 100 kva for 2 min, 50 kva for 3 min, 25 kva for 2 min, and no load for the balance of its 10-min cycle. 1. Solve for the Apparent-Power Rating in kva of the Transformer When the load cycle is sufficiently short so that the temperature of the transformer does not change appreciably during the cycle, the minimum transformer size is the rms value of the load. Hence S (S 2 1t 1 S 2 2t 2 S 2 3t 3 )/[t(cycle)] (100 2 2 50 2 3 25 2 2)/10 53.62 kva.

4.14 HANDBOOK OF ELECTRIC POWER CALCULATIONS Related Calculations. When selecting a transformer to supply a cyclic load, it is essential to verify that the voltage regulation is not excessive at peak load. The method used to select a transformer in this example is satisfactory provided the load cycle is short. If the load cycle is long (several hours), this method cannot be used. In that case the thermal time constant of the transformer must be considered. ANALYSIS OF TRANSFORMER UNDER SHORT-CIRCUIT CONDITIONS A transformer is designed to carry 30 times its rated current for 1 s. Determine the length of time that a current of 20 times the rating can be allowed to flow. Find the maximum amount of current that the transformer can carry for 2 s. 1. Calculate the Time for 20 Times Rating Transformers have a definite I 2 t limitation because heat equals I 2 R EQ and R EQ is constant for a particular transformer. (R EQ represents the total resistance of the primary and secondary circuits.) Hence, I 2 rating t rating I 2 new t new 30 2 1 20 2 t new ; solving, t new 2.25 s. 2. Solve for the Maximum Permissible Current for 2 s Since 30 2 1 I 2 2, I 21.21 times full-load current. Related Calculations. The thermal problem is basically a matter of how much heat can be stored in the transformer windings before an objectionable temperature is reached. The method followed in this example is valid for values of t below 10 s. CALCULATION OF PARAMETERS IN THE EQUIVALENT CIRCUIT OF POWER TRANSFORMER BY USING THE OPEN-CIRCUIT AND SHORT-CIRCUIT TESTS Both open-circuit and short-circuit tests are made on a 50-kVA, 5-kV/500-V, 60-Hz power transformer. Open-circuit test readings from the primary side are 5 kv, 250 W, and 0.4 A; short-circuit test readings from the primary side are 190 V, 450 W, and 9 A. Calculate the parameters of the equivalent circuit (R c, X m, R 1, X 2, R 2, X 2 ), referring to Fig. 4.7. 1. Analyze the Equivalent Circuit Model in Fig. 4.7 The equivalent circuit symbols that have been used are defined on page 4.8. In order to determine all of the parameters of this equivalent circuit, we need to calculate the winding resistance, inductive reactance, the equivalent resistance representing the core loss, and the primary self-inductance that accounts for the magnetizing current.

TRANSFORMERS 4.15 FIGURE 4.13 transformer. Equivalent circuit diagram of an open-circuit test for a power 2. Calculation of the Shunt Resister (R c ) and the Magnetizing Reactance of the Transformer (X m ) by Open-Circuit Test The equivalent circuit diagram of the open-circuit test for power transformer is provided in Fig. 4.13. Since R c is much larger than R 1, we can omit the influence of R 1 when we calculate. Hence, P oc Voc 2 /R c, R c Voc 2 /P oc (5 10 3 ) 2 /250 100,000. Also, since X m is much larger than X 1, we can omit the influence of X 1 when we calculate. Then, O oc Voc 2 /X m. At first, we calculate the apparent power, S oc V oc I oc 5000 0.4 2000 VA, and the power factor, pf P oc /S oc 250/2000 0.125 (lagging). The power factor is the cosine of the angle between the voltage and current vector, so the pf angle cos 1 0.125 82.8. Then, Q oc V oc I oc sin 5,000 0.4 sin 82.8 1984 VAR. Finally, X m /Q oc (5 10 3 ) 2 /1984 12,600. V 2 oc 3. Calculation of the Coil Resistance (R 1, R 2 ) and the Leakage Reactance (X 1, X 2 ) by Short-Circuit Test of Power Transformer The equivalent circuit diagram of short-circuit test of transformer is provided in Fig. 4.14. Since the value of R c, X m is much larger than that of a 2 R 2 and a 2 X 2, we could get a simple equivalent circuit of the transformer for the short-circuit test. The equivalent circuit diagram referring to the primary side is shown in Fig. 4.15. In most cases, R 1 is very close in value to a 2 R 2, and X 1 is very close in value to a 2 X 2, thus we could assume that R 1 a 2 R 2 and X 1 a 2 X 2. Then the equivalent circuit will be simplified further to the circuit shown in Fig. 4.16. We define two parameters: R w R 1 a 2 R 2 2R 1 2a 2 R 2 and X w X 1 a 2 X 2 2X 2 2a 2 X 2. At first, we calculate the apparent power S sc V sc I sc 190 9 1710 VA, so we get Q sc S 1650 VAR. Then, R w P sc / I 2 sc 2 P 450/9 2 sc 2 1710 2 450 2 sc 5.56 ; X w Q sc / I sc 2 1694/9 2 20.4. Thus, R 1 R w /2 5.56/2 2.78. We know a 5000/500 10. So, R 2 R w /(2 a 2 ) 5.56/ (2 10 2 ) 27.8 m ; and X 2 X w /(2 a 2 ) 20.4/(2 10 2 ) 102 m. FIGURE 4.14 Equivalent circuit diagram of a short-circuit test for a power transformer.

4.16 HANDBOOK OF ELECTRIC POWER CALCULATIONS FIGURE 4.15 Equivalent circuit diagram referred to the primary side. A more simplified equivalent cir- FIGURE 4.16 cuit diagram. Related Calculations. We could get the transformer exciting current from I I oc, the magnetizing current I m V oc /X m and the current I c supplying core losses when we conduct open-circuit and short-circuit tests on the transformer. Furthermore, the core loss of the transformer is approximately equal to P oc, and the copper loss of the transformer is approximately equal to P sc. This result could be used for the calculation of the efficiency of power transformer discussed on page 4.12. PERFORMANCE OF A STEP-UP AUTOTRANSFORMER (BUCK/BOOST TRANSFORMER IN BOOST MODE) Calculate the full-load currents of the 50-kVA, 2400-V, and 120-V windings of the 2400/120-V isolation transformer of Fig. 4.17a. When this transformer is connected as a step-up transformer in Fig. 4.17b, calculate its apparent power rating in kva, the percent increase in apparent power capacity in kva, and the full-load currents. 1. Find the Full-Load Currents of the Isolation Transformer I 1 (VA) 1 /V 1 50,000/2400 20.83 A, and I 2 (VA) 2 /V 2 50,000/120 416.7 A. 2. Determine the Power Rating in kva of the Autotransformer Because the 120-V winding is capable of carrying 416.7 A, the power rating in kva of the autotransformer is VA 2 (2520 416.7)/1000 1050 kva. 3. Calculate the Percent Increase in Apparent Power Using the Isolation Transformer as an Autotransformer kva auto /kva isolation 1050/50 100 percent 2100 percent. 4. Solve for the Full-Load Currents of the Autotransformer Because the series winding (X 1 to X 2 ) has a full-load rating of 416.7 A, I 2 416.7 A. Current I 1 (VA) 1 /V 1 (1050 1000)/2400 437.5 A. The current in the common winding is I c I 1 I 2 437.5 416.7 20.8 A.

TRANSFORMERS 4.17 FIGURE 4.17 Application of an (a) isolation transformer and (b) autotransformer. Related Calculations. With the circuit as an autotransformer, the power in kva has increased to 2100 percent of its original value with the low-voltage winding operating at its rated capacity. The effect on the high-voltage winding is negligible because I c 20.8 A while I 1, with the circuit as an isolation transformer, is 20.83 A. The increase in apparent-power capacity produced by connecting an isolation transformer as an autotransformer accounts for the smaller size in autotransformers of the same capacity in kva compared with ordinary isolation transformers. However, this marked increase in capacity only occurs as the ratio of primary to secondary voltages in the autotransformer approaches unity. ANALYSIS OF A DELTA-WYE THREE-PHASE TRANSFORMER BANK USED AS A GENERATOR-STEP-UP TRANSFORMER Calculate the line current in the primary, the phase current in the primary, the phaseto-neutral voltage of the secondary, and the turns ratio of the 50-MVA, three-phase transformer bank of Fig. 4.18 when used as a generator-step-up transformer and operating at rated load. 1. Find the Line Current in the Primary I 1P S/( 3 V LP ) 50,000,000/( 3 13,000 ) 2221 A. 2. Determine the Value of the Phase Current in the Primary I line I phase / 3 2221/ 3 1282 A. 3. Calculate the Phase-to-Neutral Voltage of the Secondary V 1N V LS / 3 138,000/ 3 79,677 V. 4. Solve for the Line Current in the Secondary I 1S S/( 3 V LS ) 50,000,000/( 3 138,000) 209 A.

4.18 HANDBOOK OF ELECTRIC POWER CALCULATIONS FIGURE 4.18 transformer. Delta-wye, three-phase transformer bank used as a generator step-up 5. Compute the Transformer Turns Ratio The turns ratio is a N 1 /N 2 13,000/79,677 0.163 1:6.13. Related Calculations. The line current in the secondary is related to the line current in the primary as follows: I 1S ai 1P / 3 (0.163 2221)/ 3 209 A, which checks the value of I 1S calculated in Step 4. The voltage phasor relations (Fig. 4.19) show that the secondary voltages of the wye side lead the primary voltages of the delta side by 30. FIGURE 4.19 Voltage phasor relations for a step-up transformer with (a) delta primary at 13 kv and (b) wye secondary at 138 kv.

TRANSFORMERS 4.19 PERFORMANCE OF AN OPEN DELTA OR VEE-VEE SYSTEM Each of the delta-delta transformers of Fig. 4.20 is rated at 40 kva, 2400/240 V. The bank supplies a 80-kVA load at unity power factor. If transformer C is removed for repair, calculate, for the resulting vee-vee connection: load in kva carried by each transformer, percent of rated load carried by each transformer, total apparent power rating in kva of the transformer bank in vee-vee, ratio of vee-vee bank to delta-delta bank transformer ratings, and the percent increase in load on each transformer. 1. Find the Load in kva Carried by Each Transformer Load per transformer total kva/ 3 80 kva/ 3 46.2 kva. 2. Determine the Percent of Rated Load Carried by Each Transformer Percent transformer load (load in kva/transformer)/(rating in kva per transformer) 100 percent 46.2 kva/40 kva 100 percent 115.5 percent. 3. Calculate the Total Rating in kva of the Transformer Bank in Vee-Vee Rating in kva of vee-vee bank 3 (rating in kva per transformer) 3 40 69.3 kva. 4. Solve for the Ratio of the Vee-Vee Bank to the Delta-Delta Bank Transformer Ratings Ratio of ratings vee-vee bank/delta-delta bank 69.3 kva/120 kva 100 percent 57.7 percent. 5. Compute the Percent Increase in Load on Each Transformer Original load in delta-delta per transformer is 80 kva/3 26.67 kva per transformer. Percent increase in load (kva per transformer in vee-vee)/(kva per transformer in delta-delta) 46.2 kva/26.67 kva 100 percent 173.2 percent. Removal of transformer C from a delta-delta system results in a vee- FIGURE 4.20 vee system.

4.20 HANDBOOK OF ELECTRIC POWER CALCULATIONS Related Calculations. This example demonstrates that while the transformer load increases by 173.2 percent in a vee-vee system, each transformer is only slightly overloaded (115.5 percent). Because each transformer in a vee-vee system delivers line current and not phase current, each transformer in open delta supplies 57.7 percent of the total volt-amperes. ANALYSIS OF A SCOTT-CONNECTED SYSTEM A two-phase, 10-hp, 240-V, 60-Hz motor has an efficiency of 85 percent and a power factor of 80 percent. It is fed from the 600-V, three-phase system of Fig. 4.21 by a Scottconnected transformer bank. Calculate the apparent power drawn by the motor at full load, the current in each two-phase line, and the current in each three-phase line. 1. Find the Apparent Power Drawn by the Motor Rated output power of the motor is P o 746 W/hp 10 hp 7460 W. Active power, P, drawn by the motor at full load is P o / 7460 W/0.85 8776 W, where efficiency. Apparent power drawn by the motor at full load is S P/pf (8776 W)/0.8 10,970 VA. 2. Determine the Current in Each Two-Phase Line Apparent power per phase 10,970/2 5485 VA; hence, I S/V 5485/240 22.85 A. 3. Calculate the Current in Each Three-Phase Line I S/( 3 V) 10.970/( 3 600) 10.56 A. Related Calculations. The Scott connection isolates the three-phase and two-phase systems and provides the desired voltage ratio. It can be used to change three-phase to two- FIGURE 4.21 Scott-connected system, three-phase to two-phase or two-phase to three-phase.

TRANSFORMERS 4.21 phase or two-phase to three-phase. Because transformers are less costly than rotating machines, this connection is very useful when industrial concerns wish to retain their twophase motors even through their line service is three-phase. BIBLIOGRAPHY Anderson, Edwin. 1985. Electric Machines and Transformers. Reston, Va.: Reston Publishing Co. Elgerd, Olle Ingemar. 1982. Electric Energy Systems Theory: An Introduction, 2nd ed. New York: McGraw-Hill. Gingrich, Harold W. 1979. Electrical Machinery, Transformers, and Control. Englewood Cliffs, N.J.: Prentice-Hall. Henry, Tom. 1989. Transformer Exam Calculations. Orlando, Fla.: Code Electrical Classes & Bookstore. Hicks, S. David. 1995. Standard Handbook of Engineering Calculations, 3rd ed. New York: McGraw-Hill. Jackson, Herbert W. 1986. Introduction to Electric Circuits, 6th ed. Englewood Cliffs, N.J.: Prentice-Hall. Johnson, Curtis B. 1994. Handbook of Electrical and Electronics Technology. Englewood Cliffs, N.J.: Prentice-Hall. Kingsley, Charles, A. Ernest Fitzgerald, and Stephen Umans. 1990. Electric Machinery, 5th ed. New York: McGraw-Hill College Division. Kosow, Irving L. 1991. Electric Machinery and Transformers, 2nd ed. Englewood Cliffs, N.J.: Prentice-Hall. McPherson, George, and Robert D. Laramore. 1990. An Introduction to Electrical Machines and Transformers, 2nd ed. New York: John Wiley & Sons. Richardson, David W. 1978. Rotating Electric Machinery and Transformer Technology. Reston, Va.: Reston Publishing Co. Wildi, Theodore. 1981. Electrical Power Technology. New York: John Wiley & Sons.