Siemens Switzerland Ltd HVAC Products. SIEMECA Electronic Heat and Cooling Meters

Similar documents
Electronic Heating Energy Meters

Q water 5.5. Electronic water meter. Data sheet DST1-QWA5-EN0 WMEAP / V 2.1

SONOMETER TM 1100 Ultrasonic compact energy meter

RAY MECHANICAL COMPACT METER. 4 MID approved class 2 from ND 15 mm qp 0,6 m3/h up to ND 40 mm qp 10 m3/h

SonoMeter 31 Energy Meters

RAY MC COMPACT ENERGY METER MECHANICAL

Heat meter Q heat 5 US

RAY MC COMPACT ENERGY METER MECHANICAL

SONOMETER TM 1100 Ultrasonic compact energy meter

SonoSelect 10 and SonoSafe 10 Energy Meters

RAY COMPACT ENERGY METER MECHANICAL

EW447-EW452 Series Mechanical Heatmeters FOR HEATING AND COOLING APPLICATIONS

SHARKY 775 ULTRASONIC COMPACT METER. 4 Approved according EN 1434 and MID in class 2 with dynamic range of 1:250 (qi:qp) in class 2

HDU-SF (Horizontal Distribution Units - Single Flat)

SHARKY 775 ULTRASONIC COMPACT METER. 4 Approved according EN 1434 and MID in class 2 with dynamic range of 1:250 (qi:qp) in class 2

Brunata Optuna H. Properties. Counter

Magnetic Inductive Flow Sensor induq

SVM F27 / C27. Ultrasonic BTU meter for heating or cooling. Data sheet

SVM F27 Compact. Ultrasonic heatmeter. Data sheet

Digital flow transmitter for continuous flow measurement

ph or ORP Transmitter

Infocal 9 Energy calculator

WATER METERS M SERIES WATER METERS INSTALLATION, OPERATION AND MAINTENANCE GUIDE METAL M SERIES WATER METER PLASTIC M SERIES WATER METER

ULTRAHEAT / ULTRACOLD T330. The Evolutionary. Ultrasonic Heat Meter / Cooling Meter. Ultrasonic Heat Meter / Cooling Meter.

SHARKY 775 ULTRASONIC COMPACT METER. 4 Approval with dynamic range up to 1:250 (qi:qp) MID in class 2 (depends on meter size), standard 1:100

ULTRAHEAT / ULTRACOLD T330. The Evolutionary. Ultrasonic Heat Meter / Cooling Meter. Ultrasonic Heat Meter / Cooling Meter.

Size : Connection End : Min Temperature : Max Temperature : Materials : Cast iron body

Digital flow ELEMENT transmitter for continuous flow measurement

Brunata Optuna H Ultrasonic energy meter Type 775 Installation Guide Edition 1.2

MULTICAL 302 DATA SHEET

Electromotoric actuators

Price list 2018 Devices

INFOCAL 8 Energy calculator

Digital flow ELEMENT transmitter for continuous flow measurement

SONOMETER TM 1000 Ultrasonic compact heat meter

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Conductivity Transmitter

Applications. Features RESIDENTIAL ULTRASONIC WATER METER. Revenue metering Residential submetering Commercial buildings.

QAC910. Meteo Sensor. Synco living

Ultrasonic level transmitter, non-contact

Outside Temperature Sensors

User s Manual. F2 Calculator. A metering component for thermal energy applications

SVM F22. Calculator for heating or cooling applications. Data sheet

ultego III smart plus

ENCORE 300 SERIES INSTALLATION AND OPERATING INSTRUCTIONS

INLINE flowmeter for continuous flow measurement

The innovative way forward symphonic sensor net radio system

Instruction. INFOCAL 8 Energy calculator. 1.0 Table of contents. 2.0 Safety notes and product information

SONOMETER 2000 Ultrasonic heat meter

MULTICAL Energy meter TS PTB. Application

microclima Single Jet SENSOSTAR 2/2+ DE-07-MI004-PTB025 (MID, heat)

Installation and Operating Instructions Compact Heat Meter Compact Heat / Cooling Meter Amtron

Instruction. SONOMETER 1100 Ultrasonic compact energy meter. 1.0 Table of contents. 2.0 Safety notes and product information

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

Portfolio. and ULTRAWATER. Ultrasonic Static Meters. Ultrasonic Meters Residential and District Heating/ Cooling Water Measurement

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Diesel Pile Hammer D30-32 Part # 66508

INLINE flowmeter for continuous flow measurement

installation instructions

Valve Island with Electronic I/O

Magnetic-Inductive flow Meter fmi

Absolute Encoders Multiturn

Measuring and Controlling Unit Multronic OC

Absolute Encoders - Singleturn

ED701 General Industry Pressure Transmitter

Kiosk Solution W1000. Installation and Assembly Instructions July 2015 Edition

ULTRAHEAT T230 ULTRACOLD T230

SECTION COMMON WORK RESULTS FOR HVAC

Overview of types. Technical data

Installation & User Guide. Multical 402. (Heating & Cooling) Supplied by. .com. Call us on +44 (0)

JUMO Wtrans E01. Measuring probe for humidity, temperature, and CO 2 with wireless data transmission. Brief description. Universal Wtrans receiver

Absolute Encoders Multiturn

Metering systems 0474EN April 2018 Domestic water meter

SONO 1500 CT Ultrasonic flow sensor

Mx-D15 Intelligent Valve Actuator

SVM F2 Calculator. A small competent calculator for compact or wall montage. Users manual

MODEL 1500, 2500 & 2700 MANUAL CONTROLS. Service Manual

Applications. Features RESIDENTIAL ULTRASONIC WATER METER. Revenue metering Residential submetering Commercial buildings.

WESAN WP E ELECTRONIC METER WOLTMAN

installation instructions WC Frame 1180mm with Dual Flush Cistern

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Operating Instructions for Flow Indicator. Model: DAZ

INLINE flowmeter for continuous flow measurement

L40. Pneumatic linear slide L40

ULTRASONIC D. Compact ultrasonic heat meter

1. Fasten press to bench or work surface using the mounting holes provided (Item 3).

Ultrasonic heat and cooling energy meters

EFC 3600 Frequency converter for higher energy efficiency and improved process control

Digital flowmeter for continuous flow measurement

FMG90 Series Electromagnetic Flow Meter

MJK Expert 700 / 800 / 900 / 1100 / 2100 MJK Expert 1400 / 3400

JARVIS. Model25CL-4,5,6 Hock Cutter and Loin Dropper. 25CL--5 Front Legs and Horns. 25CL--4 Hind Legs and Horns. 25CL--6 Loins

Single phase meter with direct connection and pulse or Modbus RS485 output

Directional valves Electrically operated Series 563, 565, 567. Brochure

Hexa Multi Module 366HMM. Introduction. Design Specifications. Key Features

FMG70B Series Magnetic Inductive Flow Sensor

Device Manual Chapter 4.1-R optosonic u 3 radio net

Self contained servo drive CLDP Technical data sheet

Electromagnetic Flow Transmitter

Absolute Encoders Singleturn

Transcription:

5 338 SIEMECA Electronic Heat and Cooling Meters WFR WFN Electronic, mains-independent meters to acquire the heat and cooling energy consumption in autonomous heating, cooling and domestic hot water plants. Storage and display of the cumulated consumption values on a selectable set day. Available as single-jet meters in «combined» all-in-one or split version Nominal flow rates of single-jet meters 0.6 m 3 /h, 1.5 m 3 /h or 2.5 m 3 /h. The electronic Siemeca heat and cooling meter is a component of the Siemeca AMR, the Siemeca Radio Metering and the Siemeca M-Bus Metering Systems. Use The electronic Siemeca heat and cooling meters are used for measuring heat and cooling energy. Their major field of use are central heating and cooling plants, where heat and cooling energy are delivered individually to several consumers. Plants of this type are used in buildings such as multi-family houses office and administrative buildings Typical users are: Private building owners Property associations Building maintenance companies Housing estate agents CE1N5338E 25.10.2004 Siemens Switzerland Ltd HVAC Products

Functions Ascertains heat and cooling energy consumption by measuring flow and temperature difference Aggregates consumption values Records cumulative consumption values on reference date Displays consumption values Displays main operating data Self-monitoring with error display Data transmission by M-bus and radio Type summary List of heat and cooling meters M-Bus-Versions Nominal flow rate q p Mounting Temperature s Cable Immersion Return temp. Communication Type reference** 0.6 m 3 /h 110 mm 1.5 m directly integrated via M-bus* WFN21.B111 1.5 m 3 /h 110 mm 1.5 m directly integrated via M-bus* WFN21.D111 2.5 m 3 /h 130 mm 1.5 m directly integrated via M-bus* WFN21.E131 0.6 m 3 /h 110 mm 2.5 m directly integrated via M-bus* WFN21.B112 1.5 m 3 /h 110 mm 2.5 m directly integrated via M-bus* WFN21.D112 2.5 m 3 /h 130 mm 2.5 m directly integrated via M-bus* WFN21.E132 1.5 m 3 /h 80 mm 1.5 m directly not integrated via M-bus* WFR21.D081 1.5 m 3 /h 80 mm 2.5 m directly not integrated via M-bus* WFR21.D082 1.5 m 3 /h 110 mm 1.5 m indirectly integrated via M-bus* WFN21.D115 2.5 m 3 /h 130 mm 1.5 m indirectly integrated via M-bus* WFN21.E135 1.5 m 3 /h 110 mm 2.5 m indirectly integrated via M-bus* WFN21.D116 2.5 m 3 /h 130 mm 2.5 m indirectly integrated via M-bus* WFN21.E136 * Prepared for communication via M-bus ** Short-form Radio 433MHz-Versions Nominal flow rate q p Mounting Temperature s Cable Immersion Return temp. Communication Type reference** 0.6 m 3 /h 110 mm 1.5 m directly integrated via radio 433 MHz WFN22.B111 1.5 m 3 /h 110 mm 1.5 m directly integrated via radio 433 MHz WFN22.D111 2.5 m 3 /h 130 mm 1.5 m directly integrated via radio 433 MHz WFN22.E131 0.6 m 3 /h 110 mm 2.5 m directly integrated via radio 433 MHz WFN22.B112 1.5 m 3 /h 110 mm 2.5 m directly integrated via radio 433 MHz WFN22.D112 2.5 m 3 /h 130 mm 2.5 m directly integrated via radio 433 MHz WFN22.E132 1.5 m 3 /h 80 mm 1.5 m directly not integrated via radio 433 MHz WFR22.D081 1.5 m 3 /h 80 mm 2.5 m directly not integrated via radio 433 MHz WFR22.D082 1.5 m 3 /h 110 mm 1.5 m indirectly integrated via radio 433 MHz WFN22.D115 2.5 m 3 /h 130 mm 1.5 m indirectly integrated via radio 433 MHz WFN22.E135 1.5 m 3 /h 110 mm 2.5 m indirectly integrated via radio 433 MHz WFN22.D116 2.5 m 3 /h 130 mm 2.5 m indirectly integrated via radio 433 MHz WFN22.E136 ** Short-form 2/10

Pulse Output-Versions Nominal flow rate q p Mounting Temperature s Cable Immersion Return temp. Communication Type reference** 0.6 m³/h 110 mm 1.5 m directly integrated Pulse Output WFN24.B111 1.5 m³/h 110 mm 1.5 m directly integrated Pulse Output WFN24.D111 2.5 m³/h 130 mm 1.5 m directly integrated Pulse Output WFN24.E131 0.6 m³/h 110 mm 2.5 m directly integrated Pulse Output WFN24.B112 1.5 m³/h 110 mm 2.5 m directly integrated Pulse Output WFN24.D112 2.5 m³/h 130 mm 2.5 m directly integrated Pulse Output WFN24.E132 1.5m³/h 80mm 1.5m directly not integrated Pulse Output WFR24.D081 1.5m³/h 80mm 2.5m directly not integrated Pulse Output WFR24.D082 1.5 m³/h 110 mm 1.5 m indirectly integrated Pulse Output WFN24.D115 2.5 m³/h 130 mm 1.5 m indirectly integrated Pulse Output WFN24.E135 1.5 m³/h 110 mm 2.5 m indirectly integrated Pulse Output WFN24.D116 2.5 m³/h 130 mm 2.5 m indirectly integrated Pulse Output WFN24.E136 ** Short-form Radio 868 MHz-Versions Nominal flow rate q p Mounting Temperature s Cable Immersion Return temp. Communication Type reference** 0.6 m 3 /h 110 mm 1.5 m directly integrated via radio 868 MHz WFN26.B111 1.5 m 3 /h 110 mm 1.5 m directly integrated via radio 868 MHz WFN26.D111 2.5 m 3 /h 130 mm 1.5 m directly integrated via radio 868 MHz WFN26.E131 0.6 m 3 /h 110 mm 2.5 m directly integrated via radio 868 MHz WFN26.B112 1.5 m 3 /h 110 mm 2.5 m directly integrated via radio 868 MHz WFN26.D112 2.5 m 3 /h 130 mm 2.5 m directly integrated via radio 868 MHz WFN26.E132 1.5 m 3 /h 80 mm 1.5 m directly not integrated via radio 868 MHz WFR26.D081 1.5 m 3 /h 80 mm 2.5 m directly not integrated via radio 868 MHz WFR26.D082 1.5 m 3 /h 110 mm 1.5 m indirectly integrated via radio 868 MHz WFR26.D115 2.5 m 3 /h 130 mm 1.5 m indirectly integrated via radio 868 MHz WFR26.E135 1.5 m 3 /h 110 mm 2.5 m indirectly integrated via radio 868 MHz WFR26.D116 2.5 m 3 /h 130 mm 2.5 m indirectly integrated via radio 868 MHz WFR26.E136 ** Short-form Scope of delivery of heat and cooling meters Item 80 mm Temperature s, and immersion 110 mm, directly 110 mm, indirectly 130 mm, directly 130 mm, indirectly Packing Flow measuring section Box Electronic unit Box Temperature with fitting Box Bracket Box Protective cap 2 2 2 2 2 Box Mounting instructions Box Commissioning and operating instructions Box Flat seal 2 2 2 2 2 Bag 1 Sealing wire 3 2 2 2 2 Bag 1 Self-lock seal 3 2 2 2 2 Bag 1 (Adhesive seal) Bag 1 Fischer dowel S6 2 2 2 2 2 Bag 2 Screws C 4.2 25 2 2 2 2 2 Bag 2 3/10

List of mounting kits Scope of delivery, description For 80 mm mounting, both s directly immersed, flow temp. in ball valve For 80 mm mounting, return temp. s directly immersed, flow temp. in ball valve For 110 mm mounting, return temp. s directly immersed, flow temp. in ball valve For 110 mm mounting, return temp. indirectly immersed, flow temp. protection pocket For 110 mm mounting, return temp. directly immersed, flow temp. ball valve For 110 mm mounting, return temp. indirectly immersed, flow temp. protection pocket For 130 mm mounting, return temp. directly immersed, flow temp. ball valve For 130 mm mounting, return temp. indirectly immersed, flow temp. protection pocket For 130 mm mounting, return temp. directly immersed, flow temp. ball valve For 130 mm mounting, return temp. indirectly immersed, flow temp. protection pocket Type reference WFZ.E80 WFZ.E80G3 WFZ.E110-I WFZ.E110-IT WFZ.E110G3-I WFZ.E110G3-IT WFZ.E130-I WFZ.E130-IT WFZ.E130G1-I WFZ.E130G1-IT Scope of delivery of mounting kits Accessory E80 E80G3 E110-I E110-IT E110G3-I E110G3-IT E130-I E130-IT E130G1-I E130G1-IT Spacer Ball valve, internally threaded ½", for use in return pipe, cap nut * ¾", with thread for, flat seal ¾" Ball valve, internally threaded ½", for use in return pipe, cap nut* ¾", flat seal ¾ Ball valve, internally threaded ¾", for use in return pipe, fitting ¾" with cap nut 1", flat seal 1" Ball valve, internally threaded ½", for use in flow pipe, with thread for Ball valve, internally threaded ¾", for use in flow pipe, with thread for Ball valve, internally threaded 1", for use in flow pipe, with thread for T-piece, internally threaded ½", for use in flow pipe T-piece, internally threaded ¾", for use in flow pipe T-piece, internally threaded 1", for use in flow pipe WFZ- 2 2 2 2 2 2 2 2 Protection pocket M10x1 * Cap nut integrated in ball valve (cannot be removed) List of accessories Accessory Description, scope of delivery Type reference Spacer For mounting 80 mm (¾" male) WFZ.R80 Spacer For mounting 110 mm (¾" male)) WFZ.R110 Spacer For mounting 130 mm (1" male) WFZ.R130 Ball valve Connecting thread ½", with thread for WFZ.K15 4/10

Accessory Description, scope of delivery Type reference Ball valve Connecting thread ¾", with thread for WFZ.K18 Ball valve Connecting thread 1", with thread for WFZ.K22 T-piece Internally threaded ½", with protection pocket M10x1 WFZ.T16 T-piece Internally threaded ¾", with protection pocket M10x1 WFZ.T19 T-piece Internally threaded 1", with protection pocket M10x1 WFZ.T22 Covering plate IV Chromium-plated WFZ.B4 M-bus connection kit 1 plug with cable (1 m long;1 adhesive label) WFZ.MBUSSET Functions Ordering Technical design Acquisition of heat and cooling energy consumption based on the measurements of flow rate and temperature differential Cumulation of the consumption values Storage of the cumulated consumption values on the set day Display of the consumption values Display of the key operational data Self-supervision, with fault indication Data transmission via M-bus or radio When ordering, please give type reference according to «Type summary». The electronic Siemeca heat and cooling meter comes standard with an M-bus output. If the heat and cooling meter is connected to a SYNERGYR M-Bus Metering System, the M-bus connection kit is required. For the pulse output version the M-bus connection kit is also required. If a set day other than 31 December is required, the desired month is to be added to the type reference when ordering (normally, the last day of the month is the set day). Ordering example for a heat and cooling meter, 130 mm mounting, set day 30 April: WFN21.E131, set day: April Measurement principle Acquisition of heat consumption Storage of consumption values The meter operates based on the single-jet measurement principle where the water jet hits the impeller tangentially. The impeller's speed is sensed electronically without producing a magnetic field. The temperatures in the flow and return pipes are measured with immersion type platinum sensing elements (Pt500). The heat and cooling meter is designed for mounting in the return pipe. The electronic unit measures the flow continuously and the flow and return temperatures at least once in four minutes. A microprocessor in the electronic unit determines the temperature differential which the microprocessor uses, along with the mean flow rate and the heat coefficient, to calculate the amount of heat consumed (or, with the cooling coefficient, to calculate the amount of cooling energy consumed). The heat and cooling energy consumption values are continuously cumulated. At 23.59 hours of the next set day, the actual meter reading will be stored. The set day is factory-set, the standard setting being 31 December (also refer to «Ordering»). At the time the annual consumption values are stored, the meter calculates a verification code. Tenants who make their own reading need to give this code to the billing centre, along with the set day reading. This enables the billing centre to verify the reading. The stored set day value will be retained for one year. 5/10

Display Fault messages The meter has three display levels which show the following values and variables: (One display level is missing in the Radio 868 MHz-Versions) Cumulated heat and cooling energy consumption since the last set day Segment test Actual heat and cooling output Actual flow rate Actual flow temperature Actual return temperature Actual temperature differential Meter's number of operating hours since it was first installed Set day and set month Stored heat and cooling energy consumption of previous year Stored heat and cooling energy consumption of the last 13 months (is missing in the Radio 868 MHz-Versions) Verification code Cumulated heat and cooling energy consumption since the meter was first installed Indication of faults (also refer to section below) The units displayed are C or K, kwh (or GJ on request), m 3 /h, kw, and hours. Standard display is the cumulated heat consumption. The meter monitors itself and can display faults it has detected. It differentiates between two categories of faults: Temporary faults: they have no impact on the correct functioning of the meter. Severe functional faults: the measurements have been stopped. In that case, the display alternates between error code and date the fault occurred for the first time. The values that have been cumulated until the fault first occurred remain stored. Mechanical design The heat and cooling meter is comprised of flow measuring section, electronic unit and two temperature s. The flow measuring section is mounted in the piping with the help of fittings. It is made of nickel-plated brass and contains the measuring chamber with the single-jet impeller. The inlet has a strainer to retain larger dirt particles. The meter is supplied as a compact all-in-one unit, but the electronic unit can be detached if required (split version). Electronic unit Temperature s The electronic unit houses the electronics and the eight-digit LCD. The operating voltage of DC 3 V is supplied by a lithium battery. Below the display, there is a button for advancing the display. The electronic unit on the flow measuring section can be swiveled through 270 and tilted by 90. The temperature s are immersion type s. They are immersed either indirectly or directly. The temperature s consist of an immersion rod the end of which carries the sensing element (Pt500), the threaded nipple, and the shielded silicon cable which establishes the connection to the electronic unit. The temperature s are designed for fitting in ball valves (direct immersion) or protection pockets (indirect immersion). The s used are ready mounted, approved, mounted as pairs, and certified. 6/10

Sizing p 1,0 Q p 0,6 m 3 /h Q Q p 2,5 m 3 p 1,5 m 3 /h /h 0,5 0,4 0,3 0,2 0,1 0,05 0,04 0,03 0,02 0,01 0,2 0,3 0,4 0,5 0,6 1,0 1,2 1,5 2 2,5 3 4 5 6 Q 5333D01 Pressure drop characteristic p Pressure drop in bar Q Flow rate in m 3 /h Mounting notes The local regulations for the use of heat and cooling meters (mounting, sealing, operation, etc.) must be complied with The heat and cooling meter must be mounted in the return pipe between two shutoff valves. To facilitate readout and service work, it should be easily accessible A settling path is required just upstream of the meter: 150 mm with the mounting s of 80 mm and 110 mm 200 mm with the mounting of 130 mm If the meter is only used at the time of commissioning, it is possible to fit the spacer first Prior to mounting the meter, the piping must be thoroughly flushed; for this purpose, the spacer is required When mounting the meter, the direction of flow (indicated by an arrow on the body) must be observed If T-pieces of other manufacture are used, it must be ensured that they are compliant with EN 1434 The electronic unit can be mounted away from the flow measuring section (split version). If the hole in the wall is too large for the unit, it can be mounted with the help of the mounting cover. If required, a chromium-plated covering plate can be used The electronic unit should be positioned such that it is easy to read After mounting, the required test pressure must be applied to the plant The electronic unit, the two temperature s and the fittings must be sealed to ensure protection against tampering. If required, the M-bus service interface must also be sealed The piece of piping where the temperature s are located should be lagged Operating notes For recalibration, the local regulations must be observed 7/10

Technical data Measurement accuracy class 3 to EN 1434 Environmental class A to EN 1434 Unit of energy Standard On request Max. heat output that can be measured Flow rates Min. flow rate q i (Q min ) H / V Nominal flow rate q p (Q nenn ) Max.flow rate q s (Q max ) Starting flow, horizontal Max. perm. operating pressure KWh GJ 300 kw 0.6 m 3 /h 1.5 m 3 /h 2.5 m 3 /h 6 / 12 l/h 15 / 30 l/h 25 / 50 l/h 600 l/h 1500 l/h 2500 l/h 1200 l/h 3000 l/h 5000 l/h 1.2 l/h 3 l/h 5 l/h 16 bar Range of use of flow measuring section 1 90 C Temperature measurement Heating: Cooling: Measurement range temp. s 20 110 ºC 1 19,4 ºC Temperature differential 3 90 K from 0.6 K Output signal under measuring conditions in test mode Behavior in the event of excessive flow flow rate = 2 q s flow rate > 2 q s Perm. ambient temperature Transport und Storage Operation Battery life optional M-bus (EN 1434) optional M-bus (EN 1434) optional voltage pulses (DC 3 V) Linear constant 5 55 C max. 55 C >10 years Connections and weight Pipe connection (inlet and outlet) Mounting Weight Temperature s Sensing element Connecting cable 0.6 m 3 /h 1.5 m 3 /h 1.5 m 3 /h 2.5 m 3 /h ¾ ¾ ¾ 1 110 mm 80 mm 110 mm 130 mm 0.73 kg 0.65 kg 0.71 kg 0.8 kg Pt 500 Ω to EN 60751 1.5 bzw. 2.5 m 8/10

90 5333M01 26 46 10 1500/2500 13,5 85 71,5 137 Additional technical data (only for pulse output meters WFx24 ) Pulse output open collector + protection resistor 2440 Ω ±10 % Ppolarity reversal not possible Pulse 100ms Pulse pause 100ms Max. voltage <30 V Current 0.1mA Impedance to ground (water pipe) 10nF (50 V) Pulse valency 1 kwh per pulse (cooling energy) Advice: The service tools (ACS210, AZS210 and ABS210) can not be used with the pulse output meter! Dimensions R 74 79 360 19 12 G ¾ 50 SW19 67 5 M 10x1 110 Mounting 110 mm, direct immersion of R 74 79 90 360 71,5 85 137 19 G ¾ 50 67 46 1500/2500 5 110 12 13,5 5333M02 Mounting 110 mm, indirect immersion of 9/10

90 90 R 74 79 360 1500/2500 17 73 90 142 14 14 24,5 SW13 G1 50 67 46 10 26 5 M 10x1 130 5333M03 Mounting 130 mm, direct immersion of R 74 79 360 1500/2500 17 90 73 142 14 14 24,5 G1 50 46 67 5 130 5333M04 Mounting 130 mm, indirect immersion of R 74 79 90 360 1500/2500 13,5 71,5 85 137 19 G ¾ 10 50 48 67 26 SW13 5 M 10x1 80 5333M05 Mounting 80 mm, direct immersion of s This Data Sheet only contains general descriptions and technical features which, in the case of specific applications, may not necessarily apply, or which may change due to further development of the product. Technical details and features are binding only if explicitly agreed upon at the time of contract closure. 10/10 2002 Siemens Building Technologies Subject to alteration