Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Similar documents
INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Improvement of Power Quality Using a Hybrid Interline UPQC

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Interline Power Quality Conditioner for Power Quality Improvement

Power Quality Improvement by Inter line UPQC with Fuzzy Control TechniqueBY

Compensation of Unbalanced Sags/Swells by Single Phase Dynamic Voltage Restorer

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

ISSN Vol.07,Issue.21, December-2015, Pages:

A Modified Control Method For A Dual Unified Power Quality Conditioner

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Power Quality Improvement by IUPQC with Fuzzy Control Technique

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Power Quality Improvement using Hysteresis Voltage Control of DVR

Grid-Voltage Regulation Controller: IUPQC

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Protection from Voltage Sags and Swells by Using FACTS Controller

2020 P a g e. Figure.2: Line diagram of series active power filter.

Compensation for Voltage and Current in Multifeeder System Using MC-UPQC

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

Mitigation of Voltage Sag/Swell Using UPQC

Power Quality Improvement using Active shunt Power filter using PI Controller

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Enhancement of Power Quality Using Advanced Series Active Power Filters

Self-Tuning PI Control of Dynamic Voltage Restorer Using Fuzzy Logic

Mitigation of Power system Disturbance by Using MC-UPQC with PI, ANN & FUZZY Controller Technique

Performance of DVR under various Fault conditions in Electrical Distribution System

Power Quality Improvement in Fourteen Bus System using UPQC

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

Simulation and Implementation of DVR for Voltage Sag Compensation

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Power Quality Improvement By Using DSTATCOM Controller

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Voltage Correction Methods in Distribution System Using DVR

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Dynamic Voltage Restorer for Voltage Sag Compensation Using Fuzzy Pi Controller

Fuzzy Controlled DSTATCOM for Voltage Sag Compensation and DC-Link Voltage Improvement

INTERNATIONAL JOURNAL OF PROFESSIONAL ENGINEERING STUDIES Volume V /Issue 4 /AUG 2015

A Voltage Controlled Dstatcom for Power Quality Improvement

Power Quality enhancement of a distribution line with DSTATCOM

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

SIMULATION OF D-STATCOM IN POWER SYSTEM

FUZZY LOGIC CONTROLLER BASED UPQC FOR POWER QUALITY MITIGATION IN GRID CONNECTED WIND ENERGY CONVERSION SYSTEM

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

VOLTAGE SAG COMPENSATION USING UNIFIED POWER FLOWER CONTROLLER IN MV POWER SYSTEM USING FUZZY CONTROLLER

Improvement of Power Quality Using a Hybrid UPQC with Distributed Generator

Modeling and Analysis of a Nonlinear Adaptive Filter Control for Interline Unified Power Quality Conditioner

ISSN Vol.08,Issue.01, January-2016, Pages:

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

HARMONIC COMPENSATION USING FUZZY CONTROLLED DSTATCOM

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

DC Link Capacitor Voltage of D-Statcom With Fuzzy Logic Supervision

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

A Power Control Scheme for UPQC for Power Quality Improvement

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

Downloaded from

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

Power Quality and the Need for Compensation

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

P. Sivakumar* 1 and V. Rajasekaran 2

Enhancement of Power Quality with Multifunctional D-STATCOM Operated under Stiff Source for Induction Motor Applications

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

FUZZY BASED SMART LOAD PRIMARY FREQUENCY CONTROL CONTRIBUTION USING REACTIVE COMPENSATION

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

DESIGN OF A HYBRID ACTIVE FILTER FOR HARMONICS SUPPRESSION WITH VARIABLE CONDUCTANCE IN INDUSTRIAL POWER SYSTEMS USING FUZZY

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

ISSN Vol.04,Issue.08, July-2016, Pages:

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Power Quality improvement of a three phase four wire system using UPQC

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications

A Novel Fuzzy Control Approach for Modified C- Dump Converter Based BLDC Machine Used In Flywheel Energy Storage System

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Transcription:

International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 10, Issue 7 (July 2014), PP.01-15 Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc S.Sarada 1, S.Anupama 2, and T.Siva Ram 3 1 Assistant Professor, Dept of EEE, Annamacharya Institute of Technology & Sciences, Rajampet, India 2 Assistant Professor, Dept of EEE, Annamacharya Institute of Technology & Sciences, Rajampet, India 3 PG Student, Dept of EEE, Annamacharya Institute of Technology & Sciences, Rajampet, Andhra Pradesh, Abstract: - Day by day the use of sophisticated electronic devices is increased. Unfortunately these devices are very sensitive to power quality disturbances. Power quality disturbances is an occurrence manifested as a nonstandard voltage, current, or frequency that results in tripping or failure of end use equipments. One of the major problems dealt here are power sag/swell. To solve this problem custom devices are used. Among these, the distribution static compensator, dynamic voltage restorer and unified power quality conditioner which are based on the VSC principle are used for power quality improvement. This paper mainly proposes a new connection for a interline unified power quality conditioner (IUPQC) to improve the power quality between two feeders in a distribution system. The proposed configuration of the UPQC is developed and verified for various Power quality disturbances by simulating the model using MATLB/SIMULINK. Index Terms: - Power Quality, PQ disturbances, Interline unified power flow controller (IUPQC), Unified power quality conditioner (UPQC), PI controller, Fuzzy logic controller (FLC), total harmonic distortion (THD). I. INTRODUCTION This paper mainly presents improvement of power quality between two feeders in a distribution system using IUPQC. With the development in the process control and digital electronics communications, a number of sensitive critical loads which require sinusoidal supply voltage for their proper operation are extensively used. At the same time increased use of nonlinear loads by both electric utilities and end users has been affecting the quality of electric power, by causing major power quality disturbances in the distribution system such as voltage and current harmonics, imbalances, voltage flicker, voltage sag/swell and voltage interruptions etc. As such improvement of power quality in distribution systems is a major issue for utilities. It is well established by the application of custom power controllers in distribution sector that power quality can be significantly improved. Voltage-Source Converter based Custom power devices are increasingly being used in custom power applications for improving the power quality (PQ) of power distribution systems. Devices such as distribution static compensator (DSTATCOM) and dynamic voltage restorer (DVR) are extensively being used in power quality improvement. A DSTATCOM can compensate for distortion and unbalance in a load such that a balanced sinusoidal current flows through the feeder [2, 3]. It can also regulate the voltage of a distribution bus. A DVR can compensate for voltage sag/swell and distortion in the supply side voltage such that the voltage across a sensitive/critical load terminal is perfectly regulated. A Unified Power Quality Conditioner (UPQC) can perform the functions of both D-STATCOM and DVR. The UPQC consists of two voltage source converters (VSCs) that are connected to a common dc bus. One of the VSCs is connected in series with a distribution feeder, while the other one is connected in shunt with the same feeder. The dc- links of both VSCs are supplied through a common dc capacitor [4]. It is also possible to connect two VSCs to two different feeders in a distribution system is called Interline Unified Power Quality Conditioner (IUPQC) which is the most sophisticated mitigating device for the power quality disturbances. It was firstly introduced to mitigate the current harmonics and voltage disturbances. The main aim of the IUPQC is to hold the voltages V t1 and V t2 constant against voltage sag/swell/any power disturbances in either of the feeders. Many contributions were introduced to modify the configurations and the control algorithms to enhance its performance. Control schemes of UPQC based on PI controller has been widely reported [5, 6].The PI control based techniques are simple and reasonably effective. However, the tuning of the PI controller is a tedious job. Further, the control of UPQC based on the conventional PI control is prone to severe dynamic interaction between active and reactive power flows. In this work, the conventional PI controller has been replaced by a fuzzy controller (FC). The FC has been used in APFs in place of conventional PI controller for improving the dynamic performance [7, 8]. The FC is basically nonlinear and adaptive in nature. The results obtained through FC are superior in the cases where the effects of parameter variation of controller are also taken into consideration. The FC is based on linguistic variable set theory and does not require a mathematical model. Generally, the input variables are error and rate of change of error. If the error is coarse, the FC provides 1

coarse tuning to the output variable and if the error is fine, it provides fine tuning to the output variable. In the normal operation of UPQC, the control circuitry of shunt APF calculates the compensating current for the current harmonics and the reactive power compensation. In the conventional methods, the DC link capacitor voltage is sensed and is compared with a reference value. The error signal thus derived is processed in a controller. A suitable sinusoidal reference signal in-phase with the supply voltage is multiplied with the output of the PI controller to generate the reference current. Hysteresis band is normally (most often but not always) is imposed on top and bottom of this reference current. The width of the hysteresis band is so adjusted such that the supply current total harmonic distortion (THD) remains within the international standards. II. POWER QUALITY PROBLEMS & ISSUES A recent survey of Power Quality experts indicates that 50% of all Power Quality problems are related to grounding, ground bonds, and neutral to ground voltages, ground loops, ground current or other ground associated issues. Electrically operated or connected equipment is affected by Power Quality. Determining the exact problems requires sophisticated electronic test equipment [9]. The following symptoms are indicators of power quality problems: Piece of equipment mis operates at the same time of day. Circuit breakers trip without being overloaded. Equipment fails during a thunderstorm. Automated systems stop for no apparent reason. Electronic systems fail or fail to operate on a frequent basis. Electronic systems work in one location but not in another location. The commonly used terms those describe the parameters of electrical power that describe or measure power quality are Voltage sags, Voltage variations, Interruptions Swells, Brownouts, Blackouts, Voltage imbalance, Distortion, Harmonics, Harmonic resonance, Inter harmonics, Notching, Noise, Impulse, Spikes (Voltage), Ground noise, Common mode noise, Critical load, Crest factor, Electromagnetic compatibility, Dropout, Fault, Flicker, Ground, Raw power, Clean ground, Ground loops, Voltage fluctuations, Transient, Dirty power, Momentary interruption, Over voltage, Under voltage, Nonlinear load, THD, Triples, Voltage dip, Voltage regulation, Blink, Oscillatory transient etc., Solutions to power quality problems: There are two approaches to the mitigation of power quality problems. The solution to the power quality can be done from customer side or from utility side. First approach is called load conditioning, which ensures that the equipment is less sensitive to power disturbances, allowing the operation even under significant voltage distortion. The other solution is to install line conditioning systems that suppress or counteract the power system disturbances. Currently they are based on PWM converters and connect to low and medium voltage distribution system in shunt or in series. Series active power filters must operate in conjunction with shunt passive filters in order to compensate load current harmonics. Shunt active power filters operate as a controllable current source and series active power filters operate as a controllable voltage source. Both schemes are implemented preferable with voltage source PWM inverters, with a dc bus having a reactive element such as a capacitor. However, with the restructuring and dispersed generation, the line conditioning systems or utility side solutions will a play a major role in improving the inherent supply quantity. III. CONTROL SCHEME Sinusoidal PWM-Based Control Scheme: In order to mitigate the simulated voltage sags in the test system of each mitigation technique, also to mitigate voltage sags in practical application, a sinusoidal PWM-based control scheme is implemented, with reference to IUPQC. The aim of the control scheme is to maintain a constant voltage magnitude at the point where sensitive load is connected, under the system disturbance. The control system only measures the rms voltage at load point, in example, no reactive power measurements is required. The VSC switching strategy is based on a sinusoidal PWM technique which offers simplicity and good response. Since custom power is a relatively low-power application, PWM methods offer a more flexible option than the fundamental frequency switching (FFS) methods favoured in FACTS applications. Besides, high switching frequencies can be used to improve the efficiency of the converter, without incurring significant switching losses. 2

Figure: 1 PWM based control scheme IV. SYSTEM DESCRIPTION The IUPQC shown in Figure consists of two VSCs (VSC-1 and VSC-2) that are connected back to back through a common energy storage dc capacitor. Let us assume that the VSC-1 is connected in shunt to Feeder-1 while the VSC-2 is connected in series Feeder-2. Each of the two VSCs is realized by three H-bridge inverters. In this structure, each switch represents a power semiconductor device (e.g., IGBT) and an anti-parallel diode. All the inverters are supplied from a common single dc capacitor C dc and each inverter has a transformer connected at its output. The secondary (distribution) sides of the shunt-connected transformers (VSC-1) are connected in star with the neutral point being connected to the load neutral. The secondary winding of the series-connected transformers (VSC-2) are directly connected in series with the bus B-2 and load L-2. The ac filter capacitors C f and C k are also connected in each phase to prevent the flow of the harmonic currents generated due to switching. The six inverters of the IUPQC are controlled independently. The switching action is obtained using output feedback control. In this figure, the feeder impedances are denoted by the pairs (R s1, L s1 ) and (R s2, L s2 ). It can be seen that the two feeders supply the loads L-1 and L-2. The load L-1 is assumed to have two separate components an unbalanced part (L-11) and a non-linear part (L-12). The currents drawn by these two loads are denoted by i l1 and i l2, respectively. We further assume that the load L-2 is a sensitive load that requires uninterrupted and regulated voltage. The shunt VSC (VSC-1) is connected to bus B-1 at the end of Feeder-1, while the series VSC (VSC-2) is connected at bus B-2 at the end of Feeder-2. The voltages of buses B-1 and B-2 and across the sensitive load terminal are denoted by V t1, V t2, and V l2, respectively. 3

Figure 2: Typical IUPQC connected in a distribution system The aim of the IUPQC is two-fold: To protect the sensitive load L-2 from the disturbances occurring in the system by regulating the voltage V l2 ; To regulate the bus B-1 voltage V t1 against sag/swell and or disturbances in the system. In order to attain these aims, the shunt VSC-1 is operated as a voltage controller while the series VSC-2 regulates the voltage across the sensitive load. The length of Feeder-1 is arbitrarily chosen to be twice that of Feeder-2. The shunt VSC (VSC-1) holds the voltage of bus B-1 constant. This is accomplished by making VSC-1 to track to a reference voltage across the filter capacitor Cf. It is assumed that the dc capacitor is initially charged and both the feeders along with the IUPQC are connected at time zero. Once the three-phase B-1 voltages become balanced, the currents drawn by Feeder-1 also become balanced. The load L-2 bus voltages are also perfectly sinusoidal with the desired peak as the converter VSC-2 injects the required voltages in the system. The bus B-2 voltages will have a much smaller magnitude. V. FUZZY LOGIC CONTROLLER Fuzzy control system is a control system based on fuzzy logic a mathematical system that analyzes along input values in terms of logical variables that take on continuous values between 0 and 1. Controllers based on fuzzy logic give the linguistic strategies control conversion from expert knowledge in automatic control strategies. In the fuzzy control scheme, the operation of controller is mainly based on fuzzy rules, which are generated using fuzzy set theory. Fuzzy controller plays an important role in the compensation of PQ problem the steps involved in fuzzy controller are fuzzification, decision making, and defuzzification. Fuzzification is the process of changing the crisp value into fuzzy value. The fuzzification process has no fixed set of procedure and it is achieved by different types of fuzzifiers. The shapes of fuzzy sets are triangular, trapezoidal and more. Here, a triangular fuzzy set is used. The fuzzified output is applied to the decision making process, which contains a set of rules. Using the fuzzy rules, the input for bias voltage generator is selected from FIS. Then, the defuzzification process is applied and the fuzzified calculated voltage (V dc ) is determined. The structure of designed FLC is illustrated as follows. And the steps for designing FLC are pointed below. Fuzzification strategy Data base building Rule base elaboration Interface machine elaboration Defuzzification strategy 4

Figure 3: Fuzzy Logic Controller In addition, design of fuzzy logic controller can provide desirable both small signal and large signal dynamic performance at same time, which is not possible with linear control technique. The development of fuzzy logic approach here is limited to the design and structure of the controller..the inputs of FLC are defined as the voltage error, and change of error. Fuzzy sets are defined for each input and output variable. There are seven fuzzy levels (NB-negative big, NM-negative medium, NS-negative small Z-zero, PS-positive small, PMpositive medium, PB-positive big) the membership functions for input and output variables are triangular. The min-max method interface engine is used. The fuzzy method used in this FLC is center of area. The complete set of control rules is shown in Table.1. Each of the 49 control rules represents the desired controller response to a particular situation. Fig.2 shows the block diagram of a fuzzy logic controller.the block diagram presented in Fig 3.shows a FLC controller in the MATLAB simulation. The simulation parameters are shown in Table1. The performance of degree of member ship functions are shown in Fig 4. W w Prime Error NL NM NS ZE PS PM PL NL NL NL NL NL NM NS ZE NM NL NL NL NM NS ZE PS NS NL NL NM NS ZE PS PM ZE NL NM NS ZE PS PM PL PS NM NS ZE PS PM PL PL PM NS ZE PS PM PL PL PL PL ZE PS PM PL PL PL PL 5

Table.1 Fuzzy Rules Figure 4: The block diagram presented in Figure above shows a FLC controller in the MATLAB simulation Figure 5: Performance of Membership Function (i) Error Voltage, (ii) Change of Error Voltage and (iii) Output Voltage. 6

VI. IMULATION RESULTS Simulation circuit and corresponding waveforms of voltage sag: A. MITIGATION OF VOLTAGE SAG: A 3-phase supply voltage (11kv, 50Hz) with impulsive sag of 0.5 p.u magnitude and the duration about 0.5 to 30 cycles is taken. With the system operating in the steady state, 15 cycle impulsive voltage sag of 0.5 p.u magnitudes is occurring at 0.3 msec for which the peak of the supply voltage reduces from its nominal value of 10kv to 5kv. 7

With PI controller: 8

With Fuzzy controller: 9

10

Figure 5: Simulation results- Mitigation of voltage sag for PI controller & Fuzzy controller equipped with IUPQC (a) Instantaneous source voltage (kv) (b) Instantaneous load voltage (kv) (c) Three phase load and source r.m.s voltage (d) Voltage injected by UPQC (kv) (e) Load current (KA) (f) Source and load active powers (MW) (g) Source and load reactive powers (MVAR). Simulation circuit and corresponding waveforms of voltage swell: B. MITIGATION OF VOLTAGE SWELL: A 3-phase supply voltage (11kv, 50Hz) with momentary swell of 0.26 pu magnitude and the duration about 0.5 to 30 cycles is taken. With the system operating in the steady state, a 21 cycle momentary voltage swell of 0.26 p.u magnitude is occurring at 0.3 msec for which the peak of the supply voltage raises from its nominal value of 10kv to 12.6kV. In order to supply the balanced power required to the load, the DC capacitor voltage raises as soon as the swell occurs. 11

With PI controller: 12

13

With Fuzzy controller: Figure 6: Simulation results-mitigation of a voltage swell for PI controller & Fuzzy controller equipped with IUPQC 14

(a) Instantaneous source voltage (kv) (b) Instantaneous load voltage (kv) (c) 3-Ф load and source r.m.s voltage (pu) (d) Voltage injected by UPQC (kv) (e) Load current (ka) (f) Source and load active powers (MW) (g) Source and load reactive powers (MVAR Reduction of Voltage Imbalance in a two Feeder Distribution System Using IUPQC The IEEE standard is that it should be below 5%. The current obtained when UPQC is in the operation with the proportional integral controller the THD is 0.90 and 1.11 which is quite low and satisfy the IEEE standard. And when the UPQC is in operation with the Fuzzy logic controller the THD is 0.45 and 0.90 which much more less than the pi controller. Comparison of Pi and Fuzzy results Pi results THD fuzzy results THD Currents1 currents currents1 currents Voltage sag 0.90 0.04 0.45 0.04 Voltage swell 1.11 0.04 0.90 0.04 VII. CONCLUSION A new custom power device named as IUPQC mitigate current and voltage harmonics, to compensate voltage sag/swell and to improve voltage regulation. The compensation performance of shunt and a novel series compensator are established by the simulation results on a two-feeder, two bus distribution system. After simulation the results compensates the input voltage harmonics and current harmonics caused by non-linear load effectively by the control strategy. From the results it is observed that the THD of the source current at 0.15 s is 0.90 in the case of the PI controller while it is 0.45 in the case of the fuzzy logic controller scheme. Similarly, the THD of the source current at 0.25 s is 1.11 in case of the PI controller while it is 0.90 in case of the fuzzy logic controller scheme. Thus by seeing the result obtained through the simulation of IUPQC with both the controller PI and Fuzzy logic Controller it can be conclude that for the same load the THD obtained is less as compared to the conventional PI controller. REFERENCES [1]. R.N.Bhargavi, Power Quality Improvement Using Interline Unified Power Quality Conditioner published in 2011 IEEE. [2]. G. Ledwich and A. Ghosh, A flexible DSTATCOM operating in voltage and current control mode, Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 149, no. 2, pp. 215 224, 2002. [3]. M. K. Mishra, A. Ghosh, and A. Joshi, Operation of a DSTATCOM in voltage control mode, IEEE Trans. Power Del., vol. 18, no. 1, pp.258 264, Jan. 2003. [4]. A. Ghosh and G. Ledwich, A unified power quality conditioner (UPQC) for simultaneous voltage and current compensation, Elect Power Syst. Res., vol. 59, no. 1, pp. 55 63, 2001. [5]. Wang H. F., Jazaeri M. and Cao Y. J., Operating modes and control interaction analysis of unified power flow controller, IEE Proc. Gener. Transm. Distrib., vol. 152, no. 2, pp. 264-270, 2005. [6]. Basu M., Das S. P. and Dubey G. K., Comparative evaluation of two models of UPQC for suitable interface to enhance power quality, Elect. Power Syst. Res., vol. 77, no. 7, pp. 821-830, 2007. [7]. Jain S. K., Agrawal P. and Gupta H. O., Fuzzy logic controlled shunt active power filter for power quality improvement, IEE Proc. Electrical Power Appl., vol. 149, no. 5, pp. 317-328, 2002. [8]. G.K. Singh., A. K. Singh and R. Mitra., A simple fuzzy logic based robust active power filter for harmonics minimization under random load variation, Electrical Power Systems. Res., vol. 77, 8, pp.1101-1111, 2007. [9]. Understanding Power Quality Problems, Voltage Sags and Interruptions by Math. HJ. Bollen. 15