Rev.8 03/08 SSRMAN-1P SERIES USERS MANUAL SSR INTELLIGENT PHASE ANGLE CONTROL MODULE COPYRIGHT 2008 NUWAVE TECHNOLOGIES, INC.

Similar documents
Rev.8.8 SSRMAN-1P SERIES USERS MANUAL SSR INTELLIGENT PHASE ANGLE CONTROL MODULE COPYRIGHT 2015 NUWAVE TECHNOLOGIES, INC.

Anacon Power & Controls Relay Assembly Specialists An Anacon Electronic Sales, Inc. Company

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC.

Anacon Power & Controls

P o w e r. C O N T R O L S A N D a t h e n a c o n t r o l s. c o m. ATHENA CONTROLS, INC Campus Drive Plymouth Meeting, PA U.S.A.

815-BR SERVO AMPLIFIER FOR BRUSH SERVOMOTORS

Product Data Sheet. Models 1022/1025/1029C/1032/3629B 3629B. Models 1022/1025/1032. Model 1029C. Model 3629B. Phase Angle Power Control

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

DynaDrive INFORMATION MANUAL SDFP(S)

TMC3 SERVO CARD For WEM/XEM Series Actuators Installation & Maintenance Manual

OVEN INDUSTRIES, INC. Model 5C7-362

PEAKTRONICS AMC-103 ADDITIONAL FEATURES. AC Motor Controller, 2A AMC-103 AMC-103A AMC-103B

MODEL 421 Over/Under Motor Load Monitor

1525-BRS INFORMATION MANUAL SERV O D YN A M ICS. D y n ad r iv e Ave Crocker Suite 10 Valencia, CA

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Mini Receiver. Off Peak System Control. Operation & Installation Guide for Power Line Carrier WARRANTY. (Applicable to Software Version

751 SERIES POWER CONTROL UNITS Single Phase, Phase Angle SCR Controller

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

Using the VR448 in place of the Marathon DVR 2000

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

Accessories Power Amplifiers

Ametek, Inc. Rotron Technical Products Division. 100 East Erie St., Suite 200 Kent, Ohio User's Guide. Number Revision F

INSTALLATION AND OPERATING INSTRUCTIONS

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

VersaMax Mixed Discrete / High-Speed Counter Module

AMC-100 AMC-101 AMC-100 AMC-100B AMC-100D AMC-101 AMC-101B AMC-101D AMC-100A AMC-100C AMC-100E AMC-101A AMC-101C AMC-101E. AC Motor Controllers

VersaMax Mixed Discrete / High-Speed Counter Module

SERIES 70. R SERVO PRO Version 3.0 OPERATION AND MAINTENANCE MANUAL. The High Performance Company

DM8010 tm. Hardware Reference Manual. Document Revision B3 May 16, 2018

An American Control Electronics Brand PCM4 SERIES USER MANUAL PCM4.

BC145 SIGNAL ISOLATOR BOARD

Power Supply Unit (550W)

AMC mA Positioner

Application Note. Applicable Product: AC Drives

ADJUST AND SET UP FOR UNIT B

Sealed Interface Control: EC20300

PART # mA Positioner

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

E3 Adjustable Speed Drive Engineering Specification

PACSystems* RX3i IC695MDL765

AF91 Adjustable Frequency Drives Series B

DigiSpeed DC-03. Isolated Control Voltage Generator User s Guide. PCB: DC-03 V3.0 Firmware: Ver: 3.0 Mach3: Ver: 1.84

Your Global Flow Control Partner. Series 70 SERVO PRO Version 3.0 Operation and Maintenance Manual

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems

CAT BOARD A CONTROL AND TRIGGER BOARD FOR 3-PHASE POWER SUPPLIES

ADVR-053. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

Series 70 Servo NXT - Modulating Controller Installation, Operation and Maintenance Manual

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

PEAKTRONICS AMI-103. AC Motor Interface AMI-103 AMI-103A AMI-103B FEATURES

Apitech Valve Drive Board

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module

Service Instructions. The Conductor Controls. Conductor DC15-A, Enclosed Unit CH15-A, Open Chasis Unit

The SSR P Series. Phase-Fired SCR Power Controllers. for resistive heating loads. Phase-Fired SCR Power Controllers AMPS VAC

Fuzzy Temperature Controllers E5AF

AD-8100 & AD-8200 Servo Amplifiers

SPECIFICATION, CONTROLS AND ACCESSORIES

µservo drive user s guide

ADVR-16. Hybrid Universal Analog Digital Voltage Regulator Operation Manual. Self Excited 16 Amp Analog / Digital Voltage Regulator

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

WD series DIN Rail or Screw Mounted Protective Relays

MULTIMETER TRAINING UNIT QUICKSTART GUIDE

PHASETRONICS. SCRPowerControlSpecialists. 1P1 Series. 20to600AmpModels SinglePhaseSCR OPERATIONANDSERVICEMANUAL MANUAL-1P REV2 REV06/13/13

Electronic regulator for PWM controlled proportional solenoid valves FABER -

SC-FI Series Frequency to Current Signal Conditioner

High Frequency Sinewave Guardian TM Filter

Microprocessor Control Board Set Up Procedures (OR PLC)

KEY FEATURES. Selectable modes of control : Phase Angle or Burst Fire (Single- Cycle/Dual-Cycle & adjustable STD Burst Firing)

DPC-100VO. Proportional Voltage Controller. Features. Applications

DPC-100LC. Proportional Valve Driver. Features. Applications

PHASE CUT SIGNAL DRIVERS

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

DST-2000C. Direction Sensing Tachometer INSTRUCTION MANUAL

FC Series Signal Conditioners

INSTALLATION AND OPERATION MANUAL IODA INPUT/OUTPUT MULTI-FUNCTION BOARD (Part No. 9668)

New Eagle PWM to Analog Converter

INSTRUCTION MANUAL. March 11, 2003, Revision 3

DPFHP451 HIGH PERFORMANCE BILEVEL STEP MOTOR / MANUAL PRESET INDEXER DRIVER PACK

Thornwood Drive Operating Manual: Two-SCR General Purpose Gate Firing Board FCRO2100 Revision H

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Electronic Circuit Breaker BASIC SMART. - Number of available output channels: 2 / 4 / 8

Thornwood Drive Operating Manual: Six-SCR General Purpose Gate Firing Board FCOG6100 Revision R

High Frequency SineWave Guardian TM Filter

Copyright 2014 by Minarik Drives

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

MicroManager. Velocity Mode PID Dancer/Loadcell Control. Instruction Manual MM3000-PID

FUJI Inverter. Standard Specifications

TECHNICAL DATA SHEET. Safety and function tester GLP1-g. Standard model GLP1-g ELECTRICAL SPECIFICATION

PRELIMINARY AVB250A060 PRELIMINARY. Servo Drive. Peak Current (10 seconds)

SPECIFICATION, CONTROLS AND ACCESSORIES

MODEL KBWD-15 Pulse Width Modulated (PWM)

LED converter Linear / area dimming. Uconverter LCAI 80 W 350 ma one4all V ECO

Cell Management Module (CMM)

GS1 Parameter Summary Detailed Parameter Listings...4 9

Transcription:

Rev.8 03/08 MAN-1P SERIES USERS MANUAL INTELLIGENT PHASE ANGLE MODULE COPYRIGHT 2008

MAN-1P Users Manual Page 2 TABLE OF CONTENTS 1. Ordering Codes... 2 2. Description... 2 2.1 Features... 3 3. Installation... 3 3.1 Mounting Instructions... 3 3.2 Electrical Connections... 3 4. Operation... 4 4.1 Power Supply... 4 4.2 24V Power Fusing... 4 4.3 Command Input... 4 4.4 PWM Command Input... 4 4.4.1 Input Fail-safe Protection... 4 4.5 Line Voltage Compensation... 4 4.6 Soft Start... 4 4.7 Voltage Limit... 5 4.7.1 Voltage Limit Adjustment Procedure... 5 4.8 Configuration Dipswitch... 5 4.9 Control Output... 6 4.10 Output LED... 7 4.11 Three Phase Operation... 7 4.11.1 Three Phase Special Wiring Considerations... 7 4.11.2 Three Phase Wiring of Command Inputs... 7 4.12 Wiring Multiple Units in Single Phase Applications... 7 4.12.1 Connecting Power & Commands In Parallel... 8 5. Electrical Specifications... 8 6. Mechanical Dimensions... 8 7. Contact Information... 9 8. WIRING DIAGRAM (4-20mA, 0-5V, 0-10V Inputs)... 9 9. WIRING DIAGRAM (Potentiometer Input)... 9 10. WIRING DIAGRAM (0-135 Ohm Input)... 10 11. WIRING DIAGRAM (PWM Input)... 10 12. WIRING DIAGRAM 3 PHASE 4 WIRE Y CONNECTION... 11 13. WIRING DIAGRAM 3 PHASE INSIDE DELTA... 12 1. Ordering Codes Part# Description Inputs MAN-1P Mount Phase Angle Control 0-10V, 0-5V, 2-10V, 1-5V, 4-20mA, 0- Module, Volts, ma Input, Pot 20mA, Potentiometer MAN-1P-VL Mount Phase Angle Control 0-10V, 0-5V, 2-10V, 1-5V, 4-20mA, 0- Module, Volts, ma Input, Pot, Voltage 20mA, Potentiometer Limit Option MAN-1P-135 Mount Phase Angle Control 0-135 Module, 0-135 Input MAN-1P-REV Reverse Acting Output Option 0-10V, 0-5V, 2-10V, 1-5V, 4-20mA, 0-20mA, Potentiometer MAN-1P-PWM Mount Phase Angle Control PWM (time proportioning logic input) MAN-1P-XSS MAN-1P-FR Module, PWM Input X Second Soft Start Time, where X is choice of 2-18 seconds Default is 20 Seconds when XSS is omitted Mount Phase Angle Control Fast Response, No LV Comp. 0-10V, 0-5V, 2-10V, 1-5V, 4-20mA, 0-20mA, Potentiometer 0-10V, 0-5V, 2-10V, 1-5V, 4-20mA, 0-20mA, Potentiometer 2. Description

MAN-1P Users Manual Page 3 The MAN-1P is a phase angle control module designed for use with standard footprint random fire s (Solid State Relays). The module mounts directly on the s input screws. The module operates by varying the firing point of the s input. The power delivered to the load is proportional to the command input signal. The MAN-1P will not operate correctly with zero cross fired s. 2.1 Features 3. Installation Provides true linear power output phase angle control Small (1.75x1.40 ) module mounts on the input terminals of an inexpensive Command input accepts 4-20mA, 0-10V, 0-5V, 0-135, Pot, PWM Configurable line voltage compensation increases stability of your process Configurable soft start for high inrush loads Automatic 50/60Hz operation Adjustable Voltage Limit (-VL) Option Drives multiple solid state relays Single phase and three phase control WARNING: FIRE HAZARD!! Even quality electronic components CAN FAIL KEEPING FULL POWER ON! Provide a SEPARATE (redundant) OVER TEMPERATURE SHUTDOWN DEVICE to switch the power off if safe temperatures are exceeded. WARNING: HIGH VOLTAGE!! This control is installed on a Solid State Relay with high voltage on it. This control must be installed in a GROUNDED enclosure by a qualified electrician in accordance with applicable local and national codes including NEC and other applicable codes. Provide a safety interlock on the door to remove power before gaining access to the device. 3.1 Mounting Instructions The MAN-1P mounts directly to the control input terminals of an. Some relays have short input screws and longer screws will required to reach through the contacts on the MAN. Be sure to observe the correct polarity when mounting the module (module should be positioned over the ). The module should sit firmly on top of the when the screws are tightened. 3.2 Electrical Connections See the WIRING DIAGRAMS at the end of this document. Make sure the module ordered is the correct module for the application before wiring. Before wiring the module all Dip Switch settings for the command input and special features should be setup properly per the Dipswitch Configuration Section

MAN-1P Users Manual Page 4 4. Operation 4.1 Power Supply The MAN-1P power requirement is 24V AC +/-15% 47-63Hz. The module will not operate from a 24VDC power supply since it relies on the supply for synchronization to the AC line. 4.2 24V Power Fusing Fusing may be accomplished by fusing each module separately or fusing groups of the modules with either primary or secondary fusing. The current draw of each MAN-1P is 65mA max. 4.3 Command Input The MAN-1P can accept 4-20mA, 0-10V, 0-5V, and Potentiometer and PWM inputs. The MAN-1P-135 can only accept 0-135 inputs and the MAN-1P-PWM can only accept PWM inputs. All command inputs are not isolated from the power Input. The type of command input can be configured via the dipswitch. The default setting is 0-5V/potentiometer. When wiring multiple MAN-1P s together, follow the guidelines in the Wiring Multiple MAN-1Ps section. Any leg of the command input can tolerate shorts to the (0V) input. Connecting the 24V AC power to the command input will cause damage to the unit. 4.4 PWM Command Input The MAN-1 s PWM Command input is designed to accept a signal from a PLC or a process/temperature controller s drive output. This logic signal is used generate a command setpoint. The MAN-1P can accept logic signals with cycle times ranging from 0.1 to 6 seconds and logic voltages from 5-30VDC. 4.4.1 Input Fail-safe Protection If the signal sent to the MAN-1P s command input should become electrically open the control output will be forced to an off state. 4.5 Line Voltage Compensation The MAN-1P s line voltage compensation keeps the power constant on the load as the line voltage changes. The line voltage is measured via the power applied to the MAN-1P module. To use the line voltage compensation feature properly, the power transformer should be fed from the same mains as the load circuit to be controlled as per the wiring diagrams at the end of this document. Line voltage compensation can be enabled or disabled using the configuration dipswitch. The default setting is enabled (switch # 6 is OFF). To disable the Line Voltage Compensation, set switch # 6 to the ON position. 4.6 Soft Start The soft start feature ramps up to the command value over a period of approximately 20 seconds. The soft start time resets if the command value goes to zero (less than 4% of the input range) or power is cycled. Soft start is useful on high inrush heaters such as Quartz, Molybdenum, Tungsten, or Graphite heaters.

Current Current MAN-1P Users Manual Page 5 Soft Start can be set on or off using the configuration dipswitch. The default setting is off. Soft Start Times below 20 seconds are available and can be ordered by adding a XSS to the ordering code where X is the time in seconds. Soft Start Period The Soft Start ramps the voltage up slowly over the soft start period. High Inrush Load Soft Start used to limit the inrush Time Time 4.7 Voltage Limit The Voltage Limit option can be ordered as MAN-1P-VL. The Voltage Limit feature is used in conjunction with the line voltage compensation feature to limit the actual voltage delivered to the load. The voltage limit is adjustable via a potentiometer located just below the input terminal block. For this feature to work properly, line voltage compensation must be turned on and the power transformer for the MAN-1P must be connected to the same mains as the load power is connected to. 4.7.1 Voltage Limit Adjustment Procedure The Voltage Limit is adjustable from 5% to 100% of the max load voltage. Setting the Voltage Limit potentiometer half way corresponds to a power limit of approximately 55% or a voltage limit of 70% of the max load voltage. The best way to set the voltage limit is using a voltmeter connected across the load. With the command input set to approximately 100% (on startup) turn the pot fully CCW. Then just turn the pot CW until the desired output voltage is achieved. For this feature to work as a true voltage limit, it is important that the Line Voltage Compensation be enabled (this is the OFF position of switch # 6). If the line voltage compensation is set to OFF the voltage limit will act as a percentage of output limit and the absolute voltage limit will change with line voltage. 4.8 Configuration Dipswitch The configuration dipswitch is used for setting up the command input, line voltage compensation and soft. Using a pen point gently push the switch up for on and down for off according to the setup outlined in the table below.

MAN-1P Users Manual Page 6 Command Input 1 2 3 5 0-5V (Default) OFF OFF OFF OFF Potentiometer OFF OFF OFF OFF 0-10V OFF OFF ON OFF 4-20mA OFF ON OFF ON 1-5V OFF OFF OFF ON 2-10V OFF OFF ON ON 0-135 * ON OFF OFF OFF PWM** OFF OFF OFF OFF *Module must be ordered as MAN-1P-135 for 0-135 input support. **Module must be ordered as MAN-1P-PWM for PWM input support Feature to Enable 4 6 Line Voltage Comp Enabled (default) OFF OFF None OFF ON Soft Start Only Enabled ON ON Soft Start & Line Voltage Comp Enabled ON OFF 4.9 Control Output The MAN-1P output drive is a DC pulsed current limited 10V/15mA (nominal) drive signal. This is more than enough current for driving most 3-32V standard s, however it is still important to review the data sheet for the you would like to use for compatibility with the MAN-1P s output drive. The control output can tolerate a momentary direct short. The following graph will allow you to verify the s compatibility with the MAN-1P over wide input voltage variations.

DRIVE CURRENT (m ADC) MAN-1P Users Manual Page 7 30 25 20 + 10% 15 (NOMINAL) -10% 10 5 0 5 10 15 20 INPUT VOLTAGE DROP (VDC) MAN-1P Output Drive Current vs. Input Voltage Drop 4.10 Output LED The MAN-1P s RED output LED will turn on when the output is on and increase in intensity as the power output is increased. Because the drive signal varies considerably to give linear power output, the LED should only be used as a rough indication of Drive and not actual power output. The output LED is wired in series with the s input. If there is a poor connection on the input terminals or a problem with the s Input, the output LED will not become energized. 4.11 Three Phase Operation Three MAN-1Ps can be used to control three poles of a three phase load for inside delta or grounded wye configurations. The Module should be wired as shown in the wiring diagrams, using one transformer for each leg to be controlled. 4.11.1 Three Phase Special Wiring Considerations The MAN-1P derives its AC synchronization from the applied power. Each transformer s primary must be connected to the corresponding leg power to be controlled by each MAN-1P. 4.11.2 Three Phase Wiring of Command Inputs The command inputs should be connected in parallel if 0-5V or 0-10V is selected and in series if 4-20mA is selected. 4.12 Wiring Multiple Units in Single Phase Applications If more than one MAN-1P is to be used from a non-isolated or common command signals: 1. A common power transformer can be shared. If the input selected is 0-10V or 0-5V, the inputs should be wired in parallel.

MAN-1P Users Manual Page 8 2. If multiple units must be powered from one power transformer and 4-20mA input is selected, one module should be set for 4-20mA and the remaining modules should be set for 1-5V. 3. If the command is 4-20mA, and the command inputs are to be wired in series, a separate power transformer for each module is required to isolate the inputs. 4.12.1 Connecting Power & Commands In Parallel When multiple MAN-1P power inputs and commands are wired in parallel, all of the 0V terminals must be connected together follows: Power: Command: 0V-----0V-----0V-----> 0V-----0V-----0V-----> 24V---24V---24V----> IN------IN-----IN------> No crossing of the power input feed or command signal is permitted. If for some reason the power should become crossed, it will cause a direct short in the system. If properly fused, the fuse will blow and the MAN-1P will not be damaged. If the command inputs are wired improperly, damage to MAN-1P can result. We do not guarantee operation of the MAN-1P with any other manufacturer's control module. Using them in the same circuit may cause either module to be damaged. 5. Electrical Specifications Command Inputs 4-20mA, 0-10V, 0-5V, 0-135, Pot, PWM Input Impedance 10K (0-10V), 250 (4-20mA), 100K (0-5V) 0-135 Excitation Current 13mA max Control Output Drive, DC pulse, nominally 10V at 15mA Response Time 100mS PWM Input Period Range 1-5 Seconds PWM Input Level 5-30VDC Output Linearity +/-2% External Potentiometer Res. 10K -25K Line Voltage Comp. Range +15%/-15% up to 100% output Regulation 2% Soft Start Period 20 Seconds to reach 100% output Voltage Limit Range 5-100% of max load voltage. Ambient Temperature Range 0 to 70 C Power Supply +15/-15%, Power consumption less than 2 Watts Line Frequency Range 47-63 Hz 6. Mechanical Dimensions

1.75" MAN-1P Users Manual Page 9 Max Height is 0.6 1.40" 7. Contact Information NuWave Technologies, Inc 866-379-3597 www.nuwaveproducts.com 8. WIRING DIAGRAM (4-20mA, 0-5V, 0-10V Inputs) MAN-1P WIRING DIAGRAM (4-20mA, 0-5V, 0-10V INPUT) AC POWER SOURCE PROCESS + - LER 4-20mA, 0-5V,OR 0-10V N L HEATER 9. WIRING DIAGRAM (Potentiometer Input)

MAN-1P Users Manual Page 10 MAN-1P WIRING DIAGRAM (POTENTIOMETER INPUT) AC POWER SOURCE N L CCW HEATER W CW POTENTIOMETER 10. WIRING DIAGRAM (0-135 Ohm Input) MAN-1P WIRING DIAGRAM (0-135 Ohm Input) AC POWER SOURCE N L HEATER 0-135 Ohm Thermostat 11. WIRING DIAGRAM (PWM Input)

MAN-1P Users Manual Page 11 MAN-1P WIRING DIAGRAM (PWM INPUT) AC POWER SOURCE PROCESS + - LER PWM OUTPUT (TIME PROP.) N L HEATER 12. WIRING DIAGRAM 3 PHASE 4 WIRE Y CONNECTION MAN-1P WIRING DIAGRAM 3 PHASE 4 WIRE Y CONNECTION L1 L2 L3 0-10V COMMAND + - HEATERS N

MAN-1P Users Manual Page 12 13. WIRING DIAGRAM 3 PHASE INSIDE DELTA L1 MAN-1P WIRING DIAGRAM 3 PHASE INSIDE DELTA CONNECTION COMMAND INPUTS: WIRED IN PARALLEL FOR 0-10V WIRED IN SERIES FOR 4-20MA HEATER3 HEATER1 L2 HEATER2 L3