Harmonics study of common low wattage LED lamps

Similar documents
22.0 Harmonics in Industrial Power Systems

Power Quality in modern lighting: comparison of LED, microled and CFL lamps

Investigation of Harmonic Generation from Low Wattage LED Lamps

Understanding Power Quality

ACOUSTICAL RESONANCE AVOIDANCE FOR METAL HALIDE LAMPS

ABB n.v. Power Quality Products, October 2014

Harmonic Analysis to Improve Power Quality

Understanding Harmonics

Performance Evaluations and Comparative Electromagnetic Compatibility Measurements on Compact Fluorescent Lamps

Analysis of Harmonic Distortion in Non-linear Loads

BENCHMARK LIGHTING: COST SAVING TECHNOLOGIES

Harmonics White Paper

Dimmable LED Lamps: analysis of the harmonic content introduced in the power network

Power Quality implications of new residential appliances. EEA Conference & Exhibition 2010, June 2010, Christchurch

WHITE PAPER THERMAL PERFORMANCE COMPARISON: HALOGEN REPLACEMENT VERSUS LEGACY INCANDESCENT LAMPS

Published in: Proceedings of the 10th International Conference on Power Quality and Utilization (EPQU 2009), Lodz, Poland

Preventing on-board power supply problems

HIGH EFFICIENCY LLC RESONANT CONVERTER WITH DIGITAL CONTROL

ON THE TRANSIENTS OPTIMIZATION AND THE POWER FACTOR CORRECTION OF THE STATIC CONVERTERS

Performance Analysis of Electric Lamps and its Power Quality Issues

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

A. Harmonics. non-linear loads. are. required)

ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK

Increasing the Performance of PFC and LED Driver Applications

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Investigation of Passive Filter for LED Lamp

Appropriate methods to analyse Power Conversion Harmonics

Measurements and analysis selected power quality parameters in systems with LED light sources

Low Pass Harmonic Filters

Power Factor Correction of LED Drivers with Third Port Energy Storage

Product Specification

A DISTRIBUTED MEASUREMENT SYSTEM FOR POWER QUALITY MONITORING

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

The effects on radial distribution networks caused by replacing incandescent lamps with compact fluorescent lamps and LEDs.

Increasing the Performance of PFC and LED Driver Applications

2WT Tu-Wire 120V 32W T8 Ballast

SINGLE STAGE LOW FREQUENCY ELECTRONIC BALLAST FOR HID LAMPS

POWER FACTOR CORRECTION OF ELECTRONIC BALLAST FOR FLUORESCENT LAMPS BY BOOST TOPOLOGY

Experimental Analysis of Advanced System for Reducing the Energy Consumption of Public Street Lighting Systems

Differences in the performance between CFL and LED lamps under different voltage distortions

Harmonic Distortions Produced by Compact Fluorescent Lamps in Distribution Networks

ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF RESIDENTIAL LOAD

SERIES K: PROTECTION AGAINST INTERFERENCE

Effective Harmonic Mitigation with Active Filters

Philips Essential LEDtube 600, 1200mm

Emission on the low voltage grid: measurements in an urban area

Study of Energy Efficient Electronic Ballast

Philips MASTER LEDtube 600 mm High Output

BENEFITS OF SELS LED LIGHTING

Power Factor Improvement of LED by Using Buck-Boost Converter for Residential Load

AN INNOVATIVE METHOD FOR LOW-EMI PWM GENERATION IN INVERTERS

EMRP ENG05 Metrology for Solid State Lighting. D2.1.1 Comparison Report on Measurement of Electrical Quantities of Selected SSL Lamps

Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost Regulator

High Frequency Measurements and their Applications in Distribution Network. Contents. Power Line Communication. Background.

see your world in a new light

Automatic Control of a Dual-SMA Actuator System

ENERGY SAVING LIGHTS

EMC Aspects of Power Quality

Researches Regarding the Pollution with Harmonics by the Frequency Converters

Power Quality Improvement for Fluorescent Lighting

Feasible Series Compensation Applications using Magnetic Energy Recovery Switch (MERS)

SYSTEM OF CONTROLLING THE PROCESS OF STEEL ELABORATION IN DC ELECTRIC ARC FURNACES

LED Driver Constant voltage. Udriver LCA 100W 24V one4all SC PRE PREMIUM series

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

AC : THE EFFECT OF FLUORESCENT LIGHTS ON RFID SYSTEMS OPERATING IN BACKSCATTER MODE

Lamp Locator (continued)

TD - Power Supply LP DALI&Switch Dim Mono PRE (CV) MM-IP20 User Manual

Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed

Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development

Smart Grid Where We Are Today?

Round 11 Retailer Synopsis

Reliable power onboard and offshore

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

An Experimental Study of the Effect of Current THD to kwh Meter s Energy Measurement

Biax T/E. Triple Biax Compact Fluorescent Lamps Non-Integrated 13W, 18W, 26W, 32W and 42W. GE Lighting. Product description.

EXPERIMENT Electronic Ballast. Electronic Ballast for Fluorescent Lamps

100ft Temporary Construction String Light - Ten LED Work Lamps Watt LED Stringer

Potential Impacts of khz Harmonic Emissions on Smart Grid Communications in the United States

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

BOOST PFC WITH 100 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS

Energetic Analysis of the Drying Process of Current Transformers from 110 kv Ciungetu Power Station

Electromagnetic Harmonic Filters Technical Guide

A Single Phase Single Stage AC/DC Converter with High Input Power Factor and Tight Output Voltage Regulation

TECHNOLOGY INFORMATION SHEET

Transmit filter designs for ADSL modems

A PROTOCOL TO TEST THE SENSITIVITY OF LIGHTING EQUIPMENT TO VOLTAGE FLUCTUATIONS

HARMONIC ANALYSIS OF LIGHTING TECHNOLOGY APPLICATION CASE STUDY IN DISTRIBUTION NETWORK: SMART CITY BUZIOS

Harmonics Elimination Using Shunt Active Filter

Smart Street Light System using Embedded System

Saturation of Active Loop Antennas

Bridgelux Vesta Series Tunable White 9mm Array. Product Data Sheet DS152

WITH THE development of high brightness light emitting

DDA55 DISCONTINUOUS DISTURBANCES ANALYSER

Load Isolation Transformers

Bridgelux V13 Array. Product Data Sheet DS44. BXRE-27x2000

FUZZY CONTROLLER FOR A SHUNT ACTIVE POWER FILTER

1C.4.1 Harmonic Distortion

This is to attest that

Compact Fluorescent Lamps

Transcription:

Ioan Dragoş Deaconu, Alexandru Anghel, Aurel Ionuţ Chirilă, Valentin Năvrăpescu Harmonics study of common low wattage LED lamps This article presents experimental data on Light Emitting Diode (LED) lamps of low wattage that are commonly found both in commercial and residential applications. A comparison with the existing regulations is performed. The measurements are performed using power and energy quality analyzer intended also for avionic and military systems. Keywords: LED lamps, Harmonics, THD, Power Quality in vessels electrical installations. 1. Introduction This study has been commenced due to global tendency to use as lighting devices the LED (Light Emitting Diode). This trend is clearly underlined in many market studies, such as [1]-[6]. The LED lamps become more popular especially due to their advantages, such as: high energy efficiency reaching up to 110 Lm/W, longer life time, reaching up to 50000 hours of operation. In comparison with present common lighting equipment, i.e. CFL (Compact Fluorescent Lamps), LEDs are three times more energy efficient and the life time is also three to four times longer than CFLs. When compared to incandescent lamps, the LED lamps are ten times more efficient [7][8]. An example of commercial application is the lighting of transportation vehicles, such is the case of vessels. In [9] it is presented a case study for replacement of fluorescent lamps with LED lamps. Also, the energy savings obtained in the case of 6500 TEU container vessel is 4% for the power supplied by the electric generator. The cost savings per year are increasing to about 10% year on year (during 5 years after the investment). Even though the marine industry has oriented to electric drives and other equipment, there is an important issue that has to be considered. This is the power quality concern, as shown in [10]. 1

The harmonic content is an important issue both for voltage and current waveforms. The presence of harmonics implies power loss, i.e. the equipment supplied with a distorted voltage has additional losses. The equipment also includes that cables between the power source and the load. These additional losses represent in fact an overloading of the electronic and electric devices along with the distribution cables. The overloading leads directly to additional heating and thus the malfunction of the equipment is inherent or the operation is not safe. Moreover, some equipment that has been designed for a sinusoidal proper operation, when supplied with non-sinusoidal wave forms, might become a source of electromagnetic interference, which can harm near by sensitive electronic equipment, such as telecommunication modules [11]. The distortion degree is defined by the Total Harmonic Distortion factor [12]: THD X n 2 X h h 2 2 X1, (1) where: X is the electrical quantity ( RMS voltage or current) for which the distortion is computed, h is the harmonic number. Reverting to the performed study, the LED lamps from two manufacturers (Philips and Total Green) have been analyzed regarding the harmonic content and the total harmonic distortion of the absorbed current. 2. Standard of harmonic distortion limits In order to maintain the quality of the AC power supply system, especially in vessels power electrical installation [10], regulatory standards should be met. For LED lamps the applicable directives are found in IEC 61000-3-2 which sets the limits for lighting equipment under 25W. In Table 1 are provided the harmonic limits found in IEC 61000-3-2 Class C limits for lighting equipment. Table 1 Harmonics [order] Class C [% of fundamental] 3 30 x Cos 5 10 7 7 9 3 11 3 13 3 15 39 3 Also, IEC 61000-3-2 draws voltage distortion limits which isn t allow to exceed 5% for supply voltage Total Harmonic Distortion (THDv). 2

3. Measurements and results Technical characteristics of the measured LED lamps are given in Table 2. Table 2 LED lamp manufacturer Rated Power [W] cos [-] Color temp. [K] Philips Total Green 4 0.69 2700 6 0.71 2700 9.5 0.62 2700 10.5 0.6 6400 13.5 0.68 2700 8 0.58 2700 13 0.62 2700 16 0.65 2700 The experimental setup is depicted in Figure 1 and it contains a power quality and energy analyzer Fluke 437 series II, an oscilloscope Tektronix TPS 2024B, a laptop, a lamp tester and a voltage divisor for the oscilloscope. The power analyzer is compliant with IEC 61000-4-30 Class-A standard. Figure 1. Experimental setup 3

Before performing the final measurements each lamp has been kept on for 5 minutes for stabilization. The THD values of the voltage (THDu) and current (THDi) have been computed by the power analyzer. The instantaneous waveforms have been recorded using the oscilloscope. The oscilloscope has acquired data for 5 ms with a 0.002 ms step, i.e. 2500 points. In Figure 2 and Figure 3 are presented the wave shapes of the absorbed currents by the measured Total Green and Philips LED lamps respectively. Figure 2. Total Green LED lamps current waveforms Figure 3. Total Green LED lamps current waveforms 4

In Figure 4 is presented a comparison in time domain of the current waveform for similar LED lamps (about 13W ) from the two providers. The shape is similar and the 13.5W lamp has a current with greater amplitude. Figure 4. Philips versus Total Green LED lamps current waveforms A better analysis is in frequency domain. Thus, in Figure 5 and Figure 5 are depicted the screenshots from the power analyzer for the Total Green 13 W and Philips 13.5W Led lamps respectively regarding the current harmonic content and THDi factor. Figure 5. Total Green 13W LED lamp - (THDi=146 %, THDu=1.7 %). 5

Figure 6. Philips 13.5W LED lamp - (THDi=126.6 %, THDu=1.1 %). Results regarding the harmonic content and THD values are given in Table 3 and Table 4 for Total Green and Philips LED lamps respectively. LED Power [W] TOTAL GREEN LED lamps 6 Harmonics [%] Table 3 Fund. 3 rd 5 th 7 th 9 th 11 th 13 th 15 th THDi 8 100 87.1 68.4 51.5 44.4 41.1 34.9 28.35 149.12 13 100 85.81 67.47 49.83 39.08 34.28 29.84 23.55 146.00 16 100 88.31 70.13 51.24 41.05 35.74 30.79 23.84 144.14 LED Power [W] PHILIPS LED lamps Harmonics [%] Table 4 Fund. 3 rd 5 th 7 th 9 th 11 th 13 th 15 th THDi 4 100 88.13 71.9 55.12 42.79 35.72 30.41 23.98 149.84 6 100 88.43 71.78 55.92 46.3 40.6 34.32 26.24 154.92 9.5 100 84.15 62.29 45.34 36.87 29.01 19.31 15.11 131.34 10.5 100 87.89 69.98 53.25 43.25 37.03 29.52 20.35 147.82 13.5 100 83.73 60.29 42.17 34.46 27.18 17.53 13.31 126.60 To be noted that THDi is about the same for both brands. All measured LED lamps generate a high level of harmonic distortion that does not comply with IEC 61000-3-2 standard (comparison of data found in Table 2, Table 3 and Table 4 versus Table 1).

The main reason for the harmonic distortion seems to be the lack of an input low-pass filter before the AC/DC converter. The PCB of a measured LED lamp is depicted in Figure 7. Figure 7. PCB board of a measured LED lamp. 4. Conclusion The paper presents experimental data regarding the behavior of low wattage LED lamps, commonly found within commercial and residential lighting applications. The data is presented in two formats: time domain and frequency domain, i.e. harmonic content analysis and current total harmonic distortion ( THDi). The results show that for the measured LED lamps the THDi does not comply with the IEC 61000-3-2 Class C limits for lighting equipment. As the future trend is to design the lighting installation with LED lamps, in cases of sensitive applications regarding the THD factors, harmonic content mitigation methods are required. A solution for this issue is to mount low-pass filters within the lighting installation. Acknowledgement This work has been funded by University Politehnica of Bucharest, through the Excellence Research Grants Program, UPB GEX. Identifier: UPB EXCELENȚĂ 2016 Efficient solutions for energy flows within electrical vehicles, Contract number 78/26.09.2016 (acronym: EFENVE). References [1] Transparency Market Research Pvt. Ltd., Smart Lighting Market is Expected to Reach USD 56.62 billion in 2020; [2] Technavio, Global LED General Lighting Market 2014-2018; 7

[3] P&S Market Research, GLOBAL INDUSTRY INSIGHT: Outdoor Lighting Market Size, Share, Development, Growth and Demand Forecast to 2020; [4] BIS Research, Global Smart Light Fixture (LED, HID), Control (Sensor, Ballast, Relays and Switches) & Services Market: 2015-2020; [5] Philip Smallwood - Strategies Unlimited / PennWell, LED Lighting Global Market Trends; [6] http://www.ledsmagazine.com/articles/print/volume-9/issue- 9/features/led-lighting-market-holds-steady-in-2012-magazine.html; [7] Forbes, LED vs. CFL: Which Bulb is Best? (http://www.forbes.com/sites/trulia/2014/04/25/led-vs-cfl-which-bulb-isbest/#74fd03ab6ead); [8] Magazinul de leduri, Comparatie intre becurile incandescente, economice si LED (https://www.magazin -leduri.ro/comparatia-intre-becurilorincandescente-economice-si-led/) [9] Navgathi Marine, Energy saving by lighting - 6500 TEU Container Vessel (http://www.navgathi.com/wp-content/uploads/2015/06/9-energy- Saving-by-Lighting-6500-TEU-Container-Vessel.pdf); [10] Evans I. C., Hoevenaars A. H., Eng P., Meeting Harmonic Limits on Marine Vessels, IEEE Electric Ship Technologies Symposium, 2007. ESTS '07; [11] Hortopan Gh., Principii şi tehnici de compatibilitate electromagnetică, Editura Tehnică, Bucureşti, 2005; [12] Brown B., P.E., Square D Engineering Services, Section 11: Power Quality Considerations. Addresses: Lect. Dr. Eng. I. Dragoş Deaconu, Politehnica University of Bucureşti, Splaiul Independenţei nr. 313, 060042,Bucureşti, dragos.deaconu@gmail.com Eng. Alexandru Anghel, Politehnica University of Bucureşti, Splaiul Independenţei nr. 313, 060042, Bucureşti, anghel.nicu.alexandru@gmail.com Lect. Dr. Eng. Aurel I. Chirilă, Politehnica University of Bucureşti, Splaiul Independenţei nr. 313, 060042, Bucureşti, aurel.chirila@gmail.com Prof. Dr. Eng. Valentin Năvrăpescu, Politehnica University of Bucureşti, Splaiul Independenţei nr. 313, 060042, Bucureşti, valentin.navrapescu@upb.ro 8