A Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique

Similar documents
COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

UNDERSTANDING SUB-HARMONICS

Grid Impact of Neutral Blocking for GIC Protection:

ELEMENTS OF FACTS CONTROLLERS

Planners Perspective on Series Compensated Transmission Lines

A NEW MONITORING SPECTRAL TECHNIQUE FOR SUB- SYNCHRONOUS ELECTRICAL TORQUE FREQUENCIES

Sub-synchronous Electrical Torque Frequencies Monitoring before the SSR Presence.

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

A Direct Power Controlled and Series Compensated EHV Transmission Line

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay

Artificial Island Open Window Concerns re: Dominion Proposal 1A

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ABB Inc. April 1, 2016 Slide 1

Study of Subsynchronous Resonance in Power Systems

Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

IJSER. Fig-1: Interconnection diagram in the vicinity of the RajWest power plant

Wind and Solar (PV) Sub harmonic Interactions with Power Systems

Dynamic Phasors for Small Signal Stability Analysis

Generation Interconnection Study Data Sheet Synchronous Machines

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Central East Voltage and Stability Analysis for Marcy FACTS Project Phase I

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

Phase Angle Monitoring:

Integration of Wind Generation into Weak Grids

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Merchant Transmission and the Reliability of the New York State Bulk Power System Part I: Thermal Transfer Limit Analysis

Tanu Sharma al. International Journal of Recent Research Aspects ISSN: , Vol. 1, Issue 3, Dec 2014, pp

Grid Code Review Panel. Information Required to Evaluate Subsynchrononous Resonance on the Transmission System

Damping of Sub synchronous Resonance Using SSSC Based PWM Hysteresis Controller

Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

4 Series Capacitor Compensation Requirements

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Study on the Improvement of the Special Protection Scheme (SPS) in the Korean power system

International Journal of Advance Engineering and Research Development

EH2741 Communication and Control in Electric Power Systems Lecture 2

Power System Stability. Course Notes PART-1

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Design and Control of Small Scale Laboratory Model of a Thyristor Controlled Series Capacitor (TCSC) to Improve System Stability

ECE 692 Advanced Topics on Power System Stability 5 - Voltage Stability

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

I. INTRODUCTION. Keywords:- FACTS, TCSC, TCPAR,UPFC,ORPD

Interline Power Flow Controller: Review Paper

Stability Improvement for Central China System

Three-Phase/Six-Phase Conversion Autotransformers

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM

Ferroresonance Experience in UK: Simulations and Measurements

ENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER

Stability Issues of Smart Grid Transmission Line Switching

Identification of weak buses using Voltage Stability Indicator and its voltage profile improvement by using DSTATCOM in radial distribution systems

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

VSC Based HVDC Active Power Controller to Damp out Resonance Oscillation in Turbine Generator System

Design and Simulation of Passive Filter

IJSER. Rajasthan power system power map is placed in Fig-1. Fig-1: Rajasthan Power System

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

Code No: R Set No. 1

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Development of Dynamic Test Cases in OPAL-RT Real-time Power System Simulator

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Transmission Line Models Part 1

POWER SYSTEM OSCILLATIONS

Volume I Issue VI 2012 September-2012 ISSN

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

GSR018: Sub-Synchronous Oscillations (SSO) Workgroup Report

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Testing and Implementation of a Source Locating method at ISO New England

A PSCAD case study of the main factors influencing the level of subsynchronous torsional interaction caused by HVDC

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

GSR018/GC0077: Sub-Synchronous Oscillations (SSO)

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Voltage Control and Power System Stability Enhancement using UPFC

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

HISTORY: How we got to where we are. March 2015 Roy Boyer 1

Improving Passive Filter Compensation Performance With Active Techniques

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Appendix D Fault Levels

Chapter 10: Compensation of Power Transmission Systems

Initial Application Form for Connection of Distributed Generation (>10kW)

Testing model data usability Excitation Systems PSS Limiters

Commissioning Process and Acceptance Test of a Sub-harmonic Protection Relay

SYNCHRONOUS MACHINES

SUBSYNCHRONOUS TORSIONAL OSCILLATIONS AND RESONANCE MITIGATION IN HVDC SYSTEM AND STATCOM COMBINATION

AORC Technical meeting 2014

Optimal Voltage Regulators Placement in Radial Distribution System Using Fuzzy Logic

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Available online at ScienceDirect. Energy Procedia 53 (2014 ) 86 94

SRI VIDYA COLLEGE OF ENGG AND TECH

NERC Protection Coordination Webinar Series June 30, Dr. Murty V.V.S. Yalla

ELG2336 Introduction to Electric Machines

Transcription:

A Comprehensive Approach Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy 1, Member, IEEE, and Carlos Grande Moran 2, Senior Member, IEEE Abstract: The paper presents a comprehensive approach sub-synchronous resonance (SSR) screening analysis using a developed frequency scanning tool capable of handling power s with hundreds of buses. PTI s software packages like PSS/E and IPLAN programs were used development of SSR tool. The frequency scanning technique scans sub-synchronous frequency range between 5 Hz to 59 Hz to determine system driving point impedance (as a function of frequency) viewed from neutral point of generating unit under study. The proposed approach was applied to analyze SSR phenomenon on several steam and gas driven turbine-generator plants in norrn part of Western System Coordinating Council (WSCC) control area where several 5kV-transmission lines include series capacitor compensation. As a part of study, credible contingencies that may lead to a topology susceptible to SSR phenomenon are identified proposed plants considered in study. Key Words: Capacitor Compensated Transmission Lines, Sub-synchronous resonance. I. Introduction Series capacitor compensation has been used widely in AC transmission systems [1] as an economical alternative different purposes such as increasing transfer capability through a particular interface, controlling load sharing among parallel lines, and enhancing transient instability [2]. However, ir presence in system may lead to SSR phenomenon especially nearby generating plants that have a direct or a near radial connection to series capacitor compensated line(s). Turbine-generator shaft failure and electrical instability at oscillation frequencies lower than normal system frequency result from SSR. The two shaft failures at Mohave Generating Station in Sourn Nevada [3] led to advancements in understanding SSR phenomenon as well as explaining interaction between series capacitor compensated lines and torsion mode of steam turbinegenerators. IEEE Sub-Synchronous Resonance Working Group report [4] presented basic ory, problem definition, analytical tools, testing, and countermeasures mitigating SSR effects. The report also discussed some related problems not caused by series capacitors such as device dependent synchronous oscillation (SSO) resulting from interaction of a turbine-generator with fast acting controllers of power system components. In an attempt to analyze SSR phenomenon, several techniques were discussed in [5] to simulate and analyze SSR phenomenon. The most common techniques are eigenvalue analysis, transient torque analysis, and frequency scanning. Eigenvalue analysis deals with self-excitation and accurately provides all natural modes and damping or undamping of coupled electrical and mechanical system. However, eigenvalue studies are relatively expensive and suited a rar small size. Transient torque analysis deals with transient shaft torque due to SSR. The frequency scanning technique involves determination of driving point impedance over defined frequency range of interest as viewed from neutral bus of generator under study. Frequency scanning studies are relatively inexpensive large s involving hundred of buses. As it was indicated in [5], frequency-scanning approach is an effective way to screen out system conditions that are potentially hazardous from an SSR standpoint. In this regard, this paper presents a comprehensive approach SSR screening analysis using a developed frequency-scanning tool capable of handling power s with hundreds of buses. The developed tool utilizes PTI s software packages such as PSS/E and IPLAN. The tools was used to analyze SSR phenomenon on several steam and gas driven turbine-generator plants in norrn part of WSCC control area where several 5kVtransmission lines include series capacitor compensation. The results of analysis are presented and discussed II. Frequency Scanning Approach The frequency scanning-based approach SSR analysis consists of two major modules as shown in Figure 1. 1 M. Elfayoumy is a consultant with Power Technologies, Inc., NY 1231 USA (e-mail: Mahmoud.elfayoumy@shawgrp.com 2 C. G. Moran is an executive consultant with Power Technologies, Inc., NY 1231 USA (e- mail: Carlos.Grande@shawgrp.com

Module 1: Data manipulation and Network Reduction Module Since effects of SSR are attenuated over distance, it is desirable to develop an equivalent of outside area of which study is to be permed. This will also decrease computational time required to perm frequency scanning in second modules. Network reduction is only necessary analysis of a large interconnected system. However, tool is capable of analyzing whole system if necessary. PSS/E package is used in this module. Module 1 Module 2 Start Start Read Read Base-Case Base-Case LF LF and and define define study study Model Model components components Network Network Reduction Reduction Perm Perm reduction reduction s s outside outside of of interest interest For first plant i=1 For first plant i=1 For first contingency j=1 For first contingency j=1 Perm Perm frequency frequency scanning scanning to to determine determine R ij (f) and ij (f) and analyze to check if SSR conditions ij (f) and X exist ij (f) and analyze to check if SSR conditions exist j=j+1 j=j+1 NO NO Last Cont. YES Last Cont. YES Stop Stop Figure 1. Frequency scanning-based SSR Analysis Scheme Several assumptions are made when modeling different components as follows: 1. Generators are modeled as constant voltage source behind generator armature resistance and sub-transient reactance. An X/R ratio of 125 is used in estimating armature resistance if this data is not available. 2. Loads and shunt compensating elements are modeled as frequency-dependent admittances. 3. Transmers are represented as short equivalent lines, i.e. by lumped resistance and reactance between two buses. 4. Transmers phase shift angles are set to zero; any transmer impedance, which is a function of phase shift, is set to its nominal value. 5. Transmission lines are represented as long lines (piequivalents) that include effect of line charging currents. The reactive component of series impedance in transmission line model includes both inductive and capacitive (series capacitors) elements. 6. The HVDC stations and FACTS devices are not generally considered because y provide a limited amount of damping and do not modify electrical resonant frequencies. The exclusion of HVDC terminals, n, provides conservative SSR results in that SSR instability would be reduced slightly by its inclusion. 7. Bus voltages are set to 1 p.u and zero phase angles. With se assumptions, reduced outside of under study is built and ready frequency scanning in second module. Module 2: Frequency scanning Module In this module, each plant i and every contingency j, frequency scanning of sub-synchronous frequency range between 5 Hz to 59 Hz determines system driving point impedance (Z ij (f)), as a function of frequency, viewed from neutral point of generator unit under study. The next step is to check Induction Generator Effect and Torsional Interaction [5]. The condition of induction generator effect may occur when electrical, as viewed from neutral of unit under study, exhibits a series resonant condition at an electric frequency f e, and system resistance as seen from neutral of unit under study (R ij (f)) is smaller than rotor resistance at per unit slip frequency s given by fe 6 s = ( pu ) (1) fe Note that this per unit frequency will always be a negative number because f e is a sub-synchronous electric frequency. Thus, rotor resistance (calculated based on unit I base MVA and voltage) as seen from neutral of i th generator will be negative and equal to r ri s 2 ( r s (2) r 2i 1i ) Where, r 2i is per unit negative sequence generator resistance r 1i is per unit armature generator resistance Torsional interaction may occur when a natural torsional frequency of spring-mass torsional model of turbinegenerator unit under study is very near (+1 Hz) to a electric resonant frequency. This is a sufficient but not necessary condition torsional instability to occur. Torsional instability would occur if re is not sufficient electrical damping in machine to damp out SSR oscillations. Thus, points in frequency scanning plot of system reactance that identify configurations with SSR problem are those where reactance is zero (series resonant point). III. Case Study The developed tool was applied to analyze SSR phenomenon on several steam driven turbine-generator plants in norrn part of Western System Coordinating Council (WSCC) area where several 5kV-transmission lines have series capacitor compensation. The study was permed to evaluate SSR credible contingencies that may lead to a topology susceptible to SSR phenomenon. For purpose of including only those components that are of importance to SSR screening study, a study system was created to include HV and EHV transmission in under study and control areas with direct ties to that

. After Network reduction, study system includes 712 buses, 147 loads, 1269 branches, 246 generators, 6 control areas and no HVDC terminals. The generation dispatch specified in original LF base case was kept in SSR screening study. However, as part of methodology used in frequency scanning method a few number of units were set off-line to study sensitivity of electrical resonant frequencies to number of units in study system being out of service. Three proposed power plants were screened SSR: two are combined cycle plants: Plant 1 and Plant 2; third plant (Plant 3) is a steam plant. The number of generating units in Plant 1and Plant 3 is two while number of units at Plant 2 is four. The operating transmission voltages in study system are 5 kv, 345 kv, 23 kv and 115 kv. Branches at lower voltage levels were not included in study system because y present a high impedance path to flow of SSR currents and thus y do not significantly affect study results. Network, generation and loads outside study area were reduced to short circuit static equivalents connected at boundary buses. Two contingency scenarios were considered when studying SSR phenomenon different units in three plants under study as follows: Scenario 1: considers credible double contingency outages from a set of a double contingency list. The selected credible double contingency outages are chosen based on system configurations that y create that make plant under study to some how, eir directly or near radially connected to series capacitor compensated line(s). Scenario 2: determines existence of a system configuration that may result in onset of SSR each of power plant under study. This critical configuration occurs when plant is radially connected to a series capacitor compensated line and electrical resonant frequency is highest. This system configuration yields lowest driving point impedance or highest system conductance. Thus, methodology of contingency selection would require an achievement of highest possible conductance at highest possible electrical resonant frequency. Outages of components that shunt SSR currents away from generator unit under study will reduce system conductance and have only a small effect on resonant frequency. This system configuration is observed in plants with multiples units. The more units are operated in parallel smaller is impact of SSR currents flowing to generator under study. Theree, worst operating condition SSR in plants with multiple units is one when re is only a single unit in service. The results SSR study using two contingency scenarios mentioned above three plants are presented in next sections and discussed. A. SSR Analysis Plant 1 For system configuration with contingency scenario1 and unit #1 in service, re is no indication potential of induction generator effect. The same conclusion is drawn when unit #2 is only unit in service at Plant 1. This system configuration does not show a potential torsional interaction when one unit is in service and when both units are in service. For contingency scenario 2, following results were obtained: 1. When eir unit #1 or unit #2 is on line, re is no indication induction generator effect SSR problems. 2. When unit #1 is on line, re is a significant potential torsional interaction if re is a torsional natural frequency close to 19.5 Hz. The variation of conductance as seen from neutral of unit #1 is shown in Figure 2. SYSTEM CONDUCTANCE G 2 18 16 14 12 1 8 6 4 2 Plant 1 UNIT #1 ON LINE 5 1 15 2 25 3 35 4 45 5 55 6 Figure 2. System Conductance by Unit #1 For Near Radial Connection 3. When unit #2 is on line, re is no indication a potential torsional interaction. The system conductance observed at electric frequency of 39.9 Hz is too small to indicate any strong torsional interaction between electric and unit torsional system. 4. When both units are on line, re is a small shift to higher electric frequencies as seen by units #1 and #2. The new values se frequencies are 4.7 Hz and 4 Hz, respectively. The potential torsional interaction observed single operation of unit #1 and unit #2 is higher than parallel operation since outages near and parallel to a generator will shunt SSR currents away from generator by reducing system conductance. B. SSR Analysis Plant 2 For Plant 2, Units #1 and #3, and unit #2 and unit #4 operate in a combined cycle mode. Combustion turbines are furnished units #1 and #2 while steam turbines are used in units #3 and #4. For contingency scenario 1 with unit #1 in service, re is no indication potential of induction generator effect. The same conclusion is drawn when unit #3 is only unit in service at Plant 2. As torsional interaction in this scenario, re is a potential torsional interaction at an electric

frequency of 36 Hz when only unit #1 is in service. When unit #3 is only unit in service potential torsional interaction is negligible. The operating scenario when all units are in service shifts potential torsional interaction to a higher electric frequency, 36.7 Hz, when viewed from unit #1 and no problems with torsional interaction unit #3. As contingency scenario 2, following results were obtained: 1. When only unit #1 is in service, re is a potential induction generator effect at an electric frequency of 33.7 Hz and 55.2 Hz. The system resistance values at se two electrical resonant frequencies are.24 p.u and.75 p.u, respectively. Frequency scanning results are shown in Figure 3. Plant 2 UNIT # 1 ON LINE (SYSTEM CONDUCTANCE SEEN BY UNIT #1 FOR NEAR RADIAL CONNECTION TO SCCN) System Conductance G 4 35 3 25 2 15 1 5 5 1 15 2 25 3 35 4 45 5 55 Figure 4. System Driving Point Conductance as seen from Plant 2 Unit #1, Units 2,3, and 4 are not in service. 6.3 Plant 2 UNIT # 1 ON LINE (SYSTEM IMPEDANCE SEEN BY UNIT #1 FOR NEAR RADIAL CONNECTION TO SCCN) R-918 6 G Plant 2 UNIT 3 - WORST OUTAGE SCENARIO X-918.25.2 5.15 4 IMPEDANCE P. U.1.5 F = 33.7 Hz R =.242 P. U F = 55.2 Hz R =.75 P. U 3 5 1 15 2 25 3 35 4 45 5 55 6 Electric Fequency (Hz) -.5 2 -.1 1 -.15 Figure 3. System Driving Point Impedance seen by Plant 2 unit #1 a Near Radial Connection (Units #2, 3 and 4 are not in service). 2. When only unit #3 is in service, re is no indication a potential induction generator effect because unit #3 does not see any resonant condition in subsynchronous range. 3. When only unit #1 is in service, re is a potential torsional interaction if unit #1 has natural torsional frequencies close to 26.3 Hz and 4.8 Hz. Potential torsional interaction at electric frequency of 55.2 Hz (4.8 Hz torsional) is not an issue because majority of combustion turbines exhibit sub-synchronous torsional frequencies in range between 14 Hz to 35 Hz. Figure 4 shows system conductance as a function of electrical frequency. 4. When only unit #3 is in service, re is a potential torsional interaction if unit #3 has natural torsional frequencies close to 5.9 Hz and 9.8 Hz as shown in Figure 5. 5. The operating scenario of having all four units in service causes a small shift to higher frequencies. Also, outages near and parallel to a generator will shunt SSR currents away from generator by reducing system conductance. 5 1 15 2 25 3 35 4 45 5 55 6 Figure 5. System Driving Point Conductance Plant 2 Unit #3. 6. The loss of several generators in vicinity of Plant 2 does not change appreciably electric resonant frequencies any of two system configurations and operating scenarios studied this plant. C. SSR Analysis Plant 3 For contingency scenario1 with unit #1 in service, re is no indication potential of induction generator effect. The same conclusion is drawn when unit #2 is only unit in service at Plant 3. This system configuration does not show a potential torsional interaction when one unit is in service and when both units are in service. For contingency scenario 2, re is no indication potential of induction generator effect. This system configuration, however, show a significant potential torsional interaction if eir unit #1 or unit #2 has a torsional frequency close to electric frequency of 48.4 Hz as shown in Figure 6.

.3 PLANT 3 UNIT #1 - CONTINGENCY SCENARIO 2 R-9118 X-9118 susceptible to SSR phenomenon are identified different plants considered study. D. P. IMPEDANCE P. U.25.2.15.1.5 F = 48.4 Hz R =.473 P. U 5 1 15 2 25 3 35 4 45 5 55 6 FREQUENCY (Hz) Figure 6. System Driving Point Impedance Seen by Unit #1 Plant 3 When both units are in service re is a small shift in electric frequency at which (48.5 Hz) re is potential torsional interaction as shown in Figure 7..3 Plant 3 - CONTINGENCY SCENARIO 2 R-9118 X-9118 V. References [1] Series Capacitor Controls and Settings as countermeasures to Sub-Synchronous Resonance, IEEE Sub-Synchronous Resonance Working Group of System Dynamic Permance Subcommittee, IEEE Transactions on Power Apparatus and Systems, Vol. PAS-11, No. 6 June 1982. [2] Power System Stability and Control, Prabha Kundur, EPRI Power System Engineering Series, 1993. [3] J.W. Butler & C. Concordia, Analysis of Series Capacitors Application Problem, AIEE Transactions, Vol. 56, pp. 975-988, 1937. [4] Reader s Guide to Sub-Synchronous Resonance, IEEE Committee Report, IEEE Transactions on Power Systems, VOL. 7, No. 1, Feb. 1992. [5] B. L. Agrawal, R. G. Farmer Use of Frequency Scanning Techniques Subs-Synchronous Resonance Analysis, IEEE Transactions on Power Apparatus and Systems, VOL. PAS-98, No. 2 March/April 1979. D. P. IMPEDANCE P. U.25.2.15.1.5 F = 48.5 Hz R =.341 P. U 5 1 15 2 25 3 35 4 45 5 55 6 Figure 7. System Driving Point Impedance Seen by Unit #1 Plant 3 (Both units are on-line) Outages near and parallel to a generator will shunt SSR currents away from generator by reducing system conductance. IV. Conclusion The paper presented a comprehensive approach subsynchronous resonance (SSR) screening analysis using a developed frequency-scanning tool capable of handling power s with hundreds of buses. PTI s software packages like PSS/E and IPLAN programs were used development of SSR tool. The frequency scanning technique scans sub-synchronous frequency range between 5 Hz to 59 Hz to determine system driving point impedance (as a function of frequency) viewed from neutral point of generating unit under study. The proposed approach was applied to analyze SSR phenomenon on several steam and gas driven turbine-generator plants in norrn part of Western System Coordinating Council (WSCC) control area where several 5kV-transmission lines include series capacitor compensation. As a part of study, credible contingencies that may lead to a topology VI. Biographies Dr. Elfayoumy (M 2) received his B. Sc. and M. Sc. degrees in Electrical Power Engineering from Alexandria University, Alexandria Egypt, in 1991, and 1994 respectively with a final grade of Distinction with degree of Honor. He received his Ph.D. in Electrical Power Systems from Howard University, Washington, D.C. in May 2. Currently he is a consultant at Power Technologies, Inc. working in fields of transmission analysis and modeling. His current area of focus is in interconnection planning, reliability assessment, transfer limit calculations, fatal Flaw Analysis, Substation Screening Analysis, security constrained unit commitment, and securityconstrained dispatch. Dr. Elfayoumy is a member of IEEE and PES society. He is also a member of TAU BETA PI professional engineers honor society chapter of Washington DC and a member of Sigma Xi professional Scientific Research society. Dr. Elfayoumy published over 21 IEEE (IEE) journal and conference papers. Dr. Grande-Moran (SM 1982) received a Diploma Engineer in Electrical and Mechanical Engineering from Universidad de El Salvador (UES) in 1974, a ME in Electrical Engineering (Power Systems) from Iowa State University in 1976, a ME in Systems Engineering from The University of Virginia in 1977, and a Ph.D. in Electrical Engineering (Power Systems) from Iowa State University in 1982. Currently, Dr. Grande-Moran is an Executive Consultant at Power Technologies, Inc. responsible power system dynamics and controls, testing and monitoring of electric machinery, and power system planning.. Dr. Grande-Moran has over 2 years of experience in electric s generator design, power system dynamics, EMS systems, and stability. He is a Senior Member of IEEE Power Engineering Society (PES).