1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay status 2 Marker label A C D K E L UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC RMRS Marks a b CE C-Tick Order data Type Rated control supply voltage = measuring voltage Order code 3 x 0-500 AC 1SR 430 824 R9300 Order data - Accessories Type Description Order code ADP.01 Adapter for screw mounting 1SR 430 029 R0100 MAR.01 Marker label 1SR 366 017 R0100 CO.01 Sealable transparent cover 1SR 430 005 R0100 Application The is used to monitor three-phase mains for incorrect phase sequence and phase failure. Operating mode Signalling is made by means of the front-face LED. LED Function Output contact closed R: yellow LED ABB 1
Function descriptions/diagrams Function diagram legend G Control supply voltage not applied / Output contact open / LED off B Control supply voltage applied / Output contact closed / LED glowing Phase sequence and phase failure monitoring If all phases are present with the correct phase sequence, the output relays energize after the start-up delay t s is complete. If a phase failure or a phase sequence error occurs, the output relays de-energize instantaneously. The LED R glows when the output relays are energized. In case of motors which continue running with only two phases, the detects phase failure if the reverse fed voltage is less than 60 % of the originally applied voltage. L1, L2, L3 Measuring value 11-14 11-12 21-24 21-22 R: yellow LED t s L1, L2, L3 L1, L3, L2 L1, L2, L3 L1, L2 L1, L2, L3 L1 L1, L2, L3 t s = start-up delay fixed 500 ms L3 L2, L3 2CDC 252 013 F08 Connection diagram L1 L2 L3 L1 L2 L3 1115 2125 1216 1418 2226 2428 2226 2125 2428 1216 1115 1418 1SC 110 000 F0118 L1, L2, L3 Control supply voltage = measuring voltage 11 15-12 16 /14 18 Output contacts - 21 25-22 26 /24 28 closed-circuit principle 2 ABB
Data at T a = 25 C and rated values, unless otherwise indicated Type Supply circuit = measuring circuit L1, L2, L3 Rated control supply voltage U S = measuring voltage 3 x 0-500 AC Power consumption approx. 15 A Rated control supply voltage U S tolerance -15...+10 % Rated frequency 50/60 Hz Duty time 100 % Measuring circuit L1, L2, L3 Monitoring functions phase failure J phase sequence J Measuring ranges 3 x 0-500 AC Thresholds U min 0.6 x UN Hysteresis related to the threshold value Measuring voltage frequency 50/60 Hz Response time 500 ms Accuracy within the rated control supply voltage tolerance iu m 0.5 % Accuracy within the temperature range iu m 0.06 % / C Timing circuit Start-up delay t S fixed 500 ms Tripping t - Indication of operational states Relay status R: yellow LED Output relay energized Output circuits 11(15)-12(16)/14(18), 21(25)-22(26)/24(28) Kind of output 2 c/o (SPDT) contacts Operating principle 1) closed-circuit principle Contact material AgNi Rated operational voltage U e (IEC/EN 60947-1) 250 Minimum switching voltage / Minimum switching current - / - Maximum switching voltage 250 AC, 250 DC Rated operational current I e AC12 (resistive) 230 4 A (IEC 60947-5-1) AC15 (inductive) 230 3 A DC12 (resistive) 24 4 A DC13 (inductive) 24 2 A Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime (AC12, 230, 4 A) 0.1 x 10 6 switching cycles Max. fuse rating to achieve n/c contact 4 A fast-acting short-circuit protection n/o contact 6 A fast-acting AC rating Utilization category (Control Circuit Rating Code) B 300 (UL 508) max. rated operational voltage 300 AC max. continuous thermal current at B 300 5 A max. making/breaking apparent power at B 300 3600/360 A General data Dimensions (W x H x D) 22.5 x 78 x 100 mm (0.89 x 3.07 x 3.94 inch) Mounting DIN rail (IEC/EN 60715) Mounting position any Minimum distance to other units horizontal / vertical M 10 mm if the control supply voltage is higher than 415 Degree of protection enclosure / terminals IP50 / IP Electrical connection Wire size fine-strand with wire end ferrule 2 x 0.75-2.5 mm² (2 x 18-14 AWG) fine-strand without wire end ferrule 2 x 0.75-2.5 mm² (2 x 18-14 AWG) rigid 2 x 0.5-4mm² (2 x -12 AWG) Stripping length 7 mm (0.28 inch) Tightening torque 0.6-0.8 mm Environmental data Ambient temperature range operation / storage -..+60 C / -40...+85 C Environmental testing (IEC 68-2-30) 24 h cycle time, 55 C, 93 % rel., 96 h Operational reliability (IEC 68-2-6) 4 g Mechanical resistance (IEC 68-2-6) 6 g Isolation data Umax ABB 3
Data at T a = 25 C and rated values, unless otherwise indicated Type Rated insulation volt. between supply, measuring and output circuits (DE 0110, IEC 60947-1) 500 Rated impulse withstand voltage U imp between all isolated circuits (DE 0110, IEC 664) 4 k / 1.2-50 µs Test voltage between all isolated circuits 2.5 k, 50 Hz, 1 min. Pollution category (DE 0110, IEC 664, IEC 255-5) 3 Overvoltage category (DE 0110, IEC 664, IEC 255-5) III Standards Product standard IEC/EN 60255-6 Low oltage Directive 06/95/EC EMC Directive 04/108/EC Electromagnetic compatibility Interference emission to IEC/EN 61000-6-2 electrostatic discharge IEC/EN 61000-4-2 Level 3 (6 k/ 8 k) radiated, radio-frequency, electro- IEC/EN 61000-4-3 magnetic field Level 3 (10 /m) electrical fast transient (burst) IEC/EN 61000-4-4 Level 3 (2 k / 5 khz) surge IEC/EN 61000-4-5 Level 4 (2 k L-L) conducted disturbances, induced IEC/EN 61000-4-6 by radio-frequency fields Level 3 (10 ) Interference emission IEC/EN 61000-6-4 1) Closed-circuit principle: Output relay is de-energized if the measured value exceeds/drops below the adjusted threshold. Technical diagrams Load limit curves AC load (resistive) DC load (resistive) 300 0 100 80 60 50 40 30 2CDC 252 194 F05 300 0 100 80 60 50 40 30 2CDC 252 193 F05 10 0.1 0.2 0.5 1 2 4 6 10 I A 10 0.1 0.2 0.5 1 2 4 6 10 I A Derating factor F Contact lifetime at inductive AC load F 1.0 0.9 0.8 0.7 0.6 0.5 2CDC 252 192 F05 Switching cycles 250 resistive load 2CDC 252 148 F06 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ Switching current [A] 4 ABB
Dimensions in mm 109.5 4.31 102 4.02 22.5 0.886 78 3.07 1 0.039 100 3.94 5.5 0.216 2CDC 252 031 F0003 Dimensions - Accessories in mm 6.5 0.256 62.5 2.461 60 2.362 70 2.756 10 11.5 0.394 0.453 0.787 2CDC 252 008 F0010 3A11 0.787 8 0.315 2CDC 252 186 F0005 ADP.01 - Adapter for screw mounting MAR.01 - Marker label 22.5 0.886 7 0.275 3.5 0.138 2.70 68.5 front-to-back size 107 2CDC 252 185 F0005 CO.01 - Sealable transparent cover Further documentation Document title Document type Document number Electronic Products and Relays Technical catalogue 2CDC 110 004 C0x CM-PAS,, CM-PSS, CM-PS Instruction manual 1SC 630 510 M0000 You can find the documentation online at www.abb.com/lowvoltage R Control Products R Electronic Relays and Controls ABB 5
Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low oltage Products and Systems Document number. 2CDC 112 135 D01 (11/10) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 10 ABB All rights reserved