Reference Number PPS 05 - (RIC Standard: EP SP)

Similar documents
Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved

Reference Number PDS 07 (RIC Standard: EP SP)

Status Date Prepared Reviewed Endorsed Approved

Reference Number PCP 02 (RIC Standard: EP SP)

Title Operating Work - Low Voltage Distribution System. Reference Number POP 06 - (RIC Standard: EP SI)

Title Lightning/ Surge Protection - Power Inductors. Reference Number SPS 37 - (RIC Standard: SC SP)

Reference Number PDS 04 (RIC Standard: EP SP)

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Status Date Prepared Reviewed Endorsed Approved

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

General Electricity Company of Libya

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

AS/NZS :2013 (IEC , , MOD)

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

K Factor Power Transformers

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

Collection of standards in electronic format (PDF) 1. Copyright

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

SECTION TRANSFORMERS

Design Guide for Hot Dip Galvanizing best practice for venting and draining

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Cast resin transformers HARMONY TM

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

CONTINUING EDUC ATION

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank

Metroll. Purlins & Girts. C Section Purlins. C Section Purlins are manufactured from Galvaspan steel and are roll formed into C Section.

ISO INTERNATIONAL STANDARD. Fasteners Hot dip galvanized coatings. Éléments de fixation Revêtements de galvanisation à chaud

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz

POTENTIAL TRANSFORMER

Network Standard NS

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Standard Specification for Carbon and Alloy Steel Nuts [Metric] 1

CSEE UM71 AF Jointless Track Circuits Set-up, Test and Certification

Title Common Requirements for Electric Power Equipment. Reference Number PDS 12 - (RIC Standard: EP SP)

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

1 Scope. 2 Normative references. 3 Dimensions. Page 2 DIN :

Standard. Extra High Voltage (EHV) Current Transformer Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

OIL-IMMERSED ARC-SUPPRESSION COILS

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

No. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS

Article 250 Grounding & Bonding

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

80 kva Isolation Transformer - 480V AC Primary - 20V AC Secondary - NEMA 3R - Single Phase

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

SECTION METAL FABRICATIONS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

500 kva Isolation Transformer - 480V Delta Primary - 400Y/231 Wye Secondary - NEMA 3R

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

Australian/New Zealand Standard

015 : 1993 CEB STANDARD

AGILITY. ROTA WEB CLIMBER 3.3m PROD. CODE SIZE AGE RANGE F/ FALL HEIGHT HEAVIEST PART TOTAL WEIGHT ROTAWEB33. 8 TO mm 73kg 115kg

225 kva Autotransformer - 240V Delta Primary Voltage - 220V Delta Secondary Voltage - NEMA 3R

WB&S FS2500 AF Jointless Track Circuits Set-Up, Test and Certification

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

Full Height Ladder Safety Gate

HPS Universal BUCK-BOOST TRANSFORMERS

Capacitive voltage transformers

Government Recognized Export House OHSAS 18001:2007 ISO 14001:2004 PED Approved Company.


TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

SECTION PANELBOARDS

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

TS RES - OUTSTANDING ISSUES

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

Transcription:

Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards and Systems Refer to Reference Number Signalling Standards Engineer T Moore GM Infrastructure Strategy & Performance M Owens Safety Committee Refer to minutes of meeting 24/01/05

Disclaimer Australian Rail Track Corporation has used its best endeavors to ensure that the content, layout and text of this document is accurate, complete and suitable for its stated purpose. It makes no warranties, express or implied, that compliance with the contents of this document shall be sufficient to ensure safe systems of work or operation. Australian Rail Track Corporation will not be liable to pay compensation in respect of the content or subsequent use of this document for any other purpose than its stated purpose or for any purpose other than that for which it was prepared except where it can be shown to have acted in bad faith or there has been willful default. Document Approval The technical content of this document has been approved by the relevant ARTC engineering authority and has also been endorsed by the ARTC Safety Committee. Document Supply and Control The Primary Version of this document is the electronic version that is available and accessible on the Australian Rail Track Corporation Internet and Intranet website. It is the document user s sole responsibility to ensure that copies are checked for curency against the Primary Version prior to its use. Copyright The information in this document is Copyright protected. Apart from the reproduction without alteration of this document for personal use, non-profit purposes or for any fair dealing as permitted under the Copyright Act 1968, no part of this document may be reproduced, altered, stored or transmitted by any person without the prior written consent of ARTC. March 2005 Page 2 of 20

About This Standard This document details the design, manufacture and whole of life performance requirements for single and three phase low voltage isolating transformers for use in the Australian Rail Track Corporation electrical network. The transformers described in this document are associated with Local Electricity Distributor supplies, the 120V signalling system and supplies to buildings or structures in contact with the Australian Rail Track Corporation 1500 V system. The intention of this document is that the transformers will be dry-type. Oil filled transformers will not be acceptable. March 2005 Page 3 of 20

Document History Primary Source RIC Standard EP 17 00 00 11 SP Version 2.0 List of Amendments ISSUE DATE CLAUSE DESCRIPTION 1.1 05/01/2005 Reformatted to ARTC Standard 1.2 11/03/2005 Disclaimer Minor editorial change March 2005 Page 4 of 20

Contents About This Standard...3 Document History...4 1 Scope and Application...7 2 References...7 2.1 Australian Standards...7 2.2 Australian Rail Track Corporation Documents...8 3 Definitions and Abbreviations...8 4 Functional Characteristics...9 4.1 General...9 5 Performance Characteristics...9 6 Technical Characteristics...10 6.1 General...10 6.2 Core...10 6.3 Protective Screen...10 6.4 Internal Connections...11 6.5 Terminals...11 6.6 Transformer Case...11 6.6.1 Indoor Type...11 6.6.2 Outdoor Type...12 6.6.3 Mounting...12 6.6.4 Lifting and Lashing Attachments...12 6.6.5 Surface Finish...12 6.7 Nameplate...12 6.8 Tolerances...13 6.9 Temperature Rise Limits...13 6.9.1 Sound Level...13 7 Maintenance Concept...13 8 Tests...14 March 2005 Page 5 of 20

8.1 Routine Tests...14 8.2 Type Tests...15 9 Data Set associated with the Equipment...15 9.1 Equipment Manuals...15 9.2 Drawings and Information...15 9.3 Test Results...15 9.4 Life Cycle Costing...16 9.5 Technical Schedule...16 Appendix 1 Technical Schedule...17 A1.1 Transformer Details...17 A1.2 Overall Dimensions...18 A1.3 Mass...18 A1.4 Terminals...19 A1.5 Reliability Data...19 A1.6 Departure from Standard...20 Appendix 2 Request for Tender Checklist...20 March 2005 Page 6 of 20

1 Scope and Application This document details the design, manufacture and whole of life performance requirements for single and three phase low voltage isolating transformers for use in the Australian Rail Track Corporation electrical network. The transformers described in this document are associated with Local Electricity Distributor supplies, the 120V signalling system and supplies to buildings or structures in contact with the RailCorp1500 V system. The design is suitable for transformers rated at 25 kva and larger. It is encouraged that 25 kva be specified as a minimum size unless a smaller size is required by special circumstances. The intention of this document is that the transformers will be dry-type. Oil filled transformers are not acceptable. The requirements of this document apply to all new single and three phase low voltage isolating transformers. Existing isolating transformers purchased under the former SRA specification A-844 should meet the basic double insulation requirements. 2 References 2.1 Australian Standards The following Australian Standards are either referenced in this document or can provide further information. AS 1627.4, 2002 AS 1939, 1990 AS 2374.1, 1997 AS 2374.5, 1982 AS 2374.6, 1994 AS 2700, 1996 AS 2735, 1984 AS/NZS 3000, 2000 AS/NZS 3100, 2002 AS/NZS 3108, 1994 AS/NZS 3750.15, 1998 Metal finishing - Preparation and pre-treatment of surfaces, - Abrasive blast cleaning Degrees of protection provided by enclosures for electrical equipment (IP Code) Power transformers - General requirements Power transformers - Ability to withstand short-circuit Power transformers - Determination of transformer and reactor sound levels Colour standard for general purposes Dry-type power transformers Electrical installations (known as the Australian/New Zealand Wiring Rules Approval and test specification - General requirements for electrical equipment Approval and test specification - Particular requirements for isolating transformers and safety isolating transformers Paint for steel structures - Inorganic zinc silicate paint March 2005 Page 7 of 20

AS/NZS 4680, 1999 Hot-dip galvanised (zinc) coatings on fabricated ferrous articles AS/NZS 61558.2.4, 2001 Safety of power transformers, power supply units and similar - Part 2.6: Particular requirements for isolating transformers for general use 2.2 Australian Rail Track Corporation Documents The following Australian Rail Track Corporation documents are either referenced in this document or can provide further information. PDS 16 PDS 07 PDS 08 EP 12 30 00 01 SP SPS 23 Transformer Loss Evaluation Low Voltage Distribution Earthing Low Voltage Installations Earthing Electrolysis From Stray DC Current (RailCorp publication) Single Phase Air Cooled, Isolating Transformer for Signalling Applications 3 Definitions and Abbreviations For the purpose of this specification the definitions specified in the referenced Australian Standards apply. The following definitions should particularly be noted: Dry-Type Transformer: Isolating Transformer: Primary Winding: Principal Tapping: Secondary Winding: Protective Separation: Protective screening: A transformer of which the core and windings are not immersed in an insulating liquid (from AS 2735-1984). A transformer with protective separation between the input and output windings. The winding that receives the active power from the supply system. Is the 0% tapping position. It is also the tapping to which the rated quantities are related. The winding that delivers the active power to the load circuit. Denotes separation between circuits by means of basic and supplementary protection (basic insulation plus either supplementary insulation or protective screening) or by an equivalent protective provision (for example, reinforced insulation). Denotes separation from live parts by means of an interposed conductive screen, connected to the means of connection for an external protective conductor. March 2005 Page 8 of 20

4 Functional Characteristics 4.1 General Isolating transformers are used in the Australian Rail Track Corporation network to ensure separation of different earth systems for electrolysis mitigation purposes and IT system of earthing, in particular: Provide galvanic isolation between the local electricity distributor s MEN earth system and Australian Rail Track Corporation s earth system. Australian Rail Track Corporation s earthing system has been designed for a dc traction environment. Provide for the unearthed 120 V ac signalling IT system of earthing. Supplies to buildings or structures in contact with Australian Rail Track Corporation s 1500 V traction system. For further information on the background for these requirements refer to PDS 07 - Low Voltage Distribution Earthing, PDS 08 - Low Voltage Instalations Earthing and RailCorp publication EP 12 30 00 01 SP Electrolysis from Stray DC Curent. 5 Performance Characteristics Number of phases..1 or 3. Frequency. 50 Hz. Type.. Dry, suitable for either indoor or outdoor use Type of cooling. Air natural Isolation Transformer complying with AS 3108 Rated voltage...415 V (3 phase), 240 V (single phase) Tapping on primary winding. Full kva tappings on the primary winding at ±2.5% and -±5% of the principal tapping Secondary winding The secondary windings of the single phase transformers shall be arranged in two equal sections, each rated at 120 V, suitable for operation in series at 240 V or in parallel at 120 V by external connections. Tap-changing device.refer to Section 6.5 System highest voltage..1.1 kv Connection symbol Dyn1 (for 3-phase transformers) March 2005 Page 9 of 20

Insulation. Windings double insulated from earth Rated insulation level. 5 kvrms Reference temperature for determination of impedance voltage 115 C Impedance voltage at rated current at reference temperature.. As per Table 1 of AS 2374.5 6 Technical Characteristics 6.1 General Each transformer shall be so constructed as to be unaffected by normal handling during transport, installation, inspection and repair. Due to the type of usage of the isolating transformers in the Australian Rail Track Corporation electrical network the following factors are considered important and should influence the design characteristics of the transformer. These aspects will be assessed as part of the technical schedule: Voltage regulation; Insertion loss; Protection coordination; Lightning protection. 6.2 Core The core of the transformer is to be isolated from the external metal parts of the transformer with an insulation level of at least 5 kv. A test point for the application of high voltage test and insulation resistance test is to be provided on the core. Insulators shall be used to mount the core onto the frame of the transformer. All nuts used in the construction of the core shall be adequately locked by means of spring washers, locknuts, or other approved locking devices. 6.3 Protective Screen Each transformer shall be provided with a protective screen of copper or aluminium at least 0.5 mm in thickness with an insulation level of at least 5 kvrms, located between the primary and secondary windings. The protective screen is to be connected to a special insulated terminal (5 kv insulation level) in the same enclosure as the primary terminals of the transformer. The protective screen shall be arranged to prevent leakage from any part of the primary windings to any part of the secondary windings of the transformer. The protective screen shall withstand a 5 kv voltage test applied for one minute between the screen terminal and primary and secondary windings. March 2005 Page 10 of 20

The insulation level between the protective screen and the core and the frame shall be 5 kv for one minute. For further information on the connection of the screen, refer to PDS 07 Low Voltage Distribution Earthing for supplies from a Local Electricity Distributor or PDS 08 Low Voltage Instalations Earthing for Signaling supplies or supplies to buildings or structures in contact with the Australian Rail Track Corporation 1500 V system. 6.4 Internal Connections The leads between the windings and the terminals (including protective screen terminal) shall be double insulated, in accordance with the requirements of the Clause covering Double Insulation in AS/NZS 3000 2000. The leads shall be secured to prevent contact with the transformer casing if the connection becomes loose or breaks away from the terminal. The method of securing the leads shall be detailed in appendix A1.4. Flexible leads shall be provided between the windings and terminals where the cross sectional area of the leads are less than 25 mm ². 6.5 Terminals The primary and secondary windings of the transformer shall be terminated onto screwed terminal studs suitably sized for the power rating of the transformer. The hardware used shall provide secure cable connections, locked against loosening, for example by the use of star washers and nickel plated brass nuts. The terminals shall be arranged so that all required interconnections of windings and adjustments of taps can be accomplished by the alteration of accessible tinned copper bolted links. The links shall be rated at the full transformer kva rating. Access to the terminals and adjustment of links shall only be possible by the use of appropriate tools. The links shall be supplied with the transformer. The primary and secondary terminals must be located within individual weatherproof polycarbonate enclosures. The polycarbonate enclosures are to be suitably sized to accommodate the appropriate installation of the terminals, links, glands and cables fitted with crimp lugs. The degree of protection to be provided from the exterior environment by the polycarbonate enclosure is to comply with AS 1939-1990 Table II and Table III as IP56. Removal of the terminal enclosure cover shall only be possible by the use of appropriate tools. 6.6 Transformer Case 6.6.1 Indoor Type The terminal enclosures shall be mounted on opposite sides of the transformer outside, and close to the top, of the transformer casing. The casing shall be fabricated from galvanised steel sheet, minimum 2 mm thick and must comply with AS 1939-1990 Table II and Table III as IP33. March 2005 Page 11 of 20

This design is for use indoors, such as within a traction substation or signalling hut, or within a fibreglass padmount structure. 6.6.2 Outdoor Type The terminal enclosures shall be located within the transformer casing, which must comply with AS 1939-1990 Table II and Table III as IP56. Cable entry shall be provided on the primary and secondary sides of the transformer enclosure to allow for external cable connection within the primary and secondary terminal enclosure. The screwed holes shall be plugged using heavy-duty PVC plugs to maintain IP56 rating. The casing shall be vermin, insect and vandal resistant. 6.6.3 Mounting The transformer case shall be fitted with suitable hot dipped galvanised mounting brackets suitable for floor mounting. The bracket design shall include 15 mm diameter mounting holes that are accessible when the transformer is floor mounted against a wall. When specified wall mounting brackets shall be provided. The design shall allow for mounting without the removal of the transformer cover. The mounting design must ensure that the clearance between the transformer enclosure and the mounting surface allows for sufficient ventilation to meet the heat rise requirements. Refer to clause 8.2 for heat rise tests. A minimum of clearance of 50 mm is required. 6.6.4 Lifting and Lashing Attachments Suitable lifting lugs for attaching lashings shall be provided external to the transformer enclosure. They shall be affixed near the top of the transformer enclosure for securing it to a transport vehicle and for lifting the transformer. 6.6.5 Surface Finish All external surfaces shall have welds made smooth, rough edges rounded and weld splatter removed. The transformer shall remain corrosion free for the life of the transformer. All external steelwork shall be hot-dipped galvanised to AS/NZS 4680-1999. Alternatively for indoor transformers, the transformer casing may be powder coated after fabrication to colour 631 transformer grey (colour code N41 to AS 2700 or 631 to BS 381C). 6.7 Nameplate The nameplate shall meet the requirements of AS 2374.1-1997, Clause 7, and shall include a diagram of connections including the primary tappings. The nameplate shall also indicate that a protective screen is fitted between the primary and secondary windings. A terminal marking plate complying with the requirements of AS 2374.1-1997, Appendix ZC, Clause ZC7 shall also be attached to the transformer. The plates shall not be attached to a removable cover. March 2005 Page 12 of 20

As the transformer is a double insulated isolating transformer complying with AS/NZS 3108-1994, the labelling shall include the following marking: DOUBLE INSULATED ISOLATING TRANSFORMER TO AS/NZS 3108 DO NOT EARTH If the transformer has an actual design rating exceeding the rating ordered, the nameplate shall show the actual design rating and not the rating ordered. 6.8 Tolerances The tolerances provided in Table 1 of AS 2374.1-1997, shall apply to the load loss and no-load loss. The tolerances applying to the voltage ratio and regulation shall comply also with Table 1. 6.9 Temperature Rise Limits The transformer shall be capable of continuous operation at rated power without exceeding the maximum temperature-rise limits as specified in Table 3.3 of AS 2735-1984. 6.9.1 Sound Level The mean audible sound level of the transformer shall not exceed the value specified in Appendix AA of AS 2374.6-1994, when measured in accordance with that Standard. 7 Maintenance Concept The transformer shall be designed and constructed to require no maintenance. March 2005 Page 13 of 20

8 Tests 8.1 Routine Tests Routine tests as listed in AS 2374.1 clause 10.1.1 shall be carried out on each transformer. The routine test of clause 5.1.6 and clause 5.1.7 shall also be carried out on each transformer. These tests shall be carried out in conjunction with the following requirements: 1 2 3 4 5 6 7 Test No. Input Winding Output Winding Core Protective Screen (Frame) External Metal Parts Applied HV Test 1 minute (kv) Min. 500 V insulation resistance (Megohms) 1 HV E F F E 5.0 100 2 E HV F F E 5.0 100 3 E E F HV E 2.5 10 4 E E HV F F 2.5 10 5 F F HV F E 5.0 10 6 F F E HV E 5.0 100 Notes: a) HV indicates that the high voltage test or the insulation resistance test is to be applied to the part. b) E indicates that the part is to be connected to earth during the high voltage test and the insulation resistance test. c) F indicates that thepart is not to be connected to any supply or earth, ie, to be floating during the high voltage test and the insulation resistance test. d) If the core is to be connected to the external metal parts (frame) delete Test Nos. 4 and 5 and Column 3. The protective screen shall withstand a 2.5 kv voltage test applied for one minute between the screen terminal and primary and secondary windings. (Test 3) The insulation level between the protective screen and the core and the frame shall withstand 5 kv applied for one minute. (Test 5) March 2005 Page 14 of 20

8.2 Type Tests Temperature rise type tests shall be carried out on one transformer of each type and rating in accordance with Clause 5.1.10 of AS 2735-1984. The method of loading is to be either by the direct loading method (described in AS 2735-1984, Clause 5.1.10.2) or by the back-to-back method (described in Clause 5.1.10.3). The simulated load method (described in Clause 5.1.10.4) is not acceptable by Australian Rail Track Corporation. The winding temperature rise is to be determined by the change of resistance method. The resistance is to be determined by d.c. volts/amps in which the current is to be substantial (ie greater than 10% of the current rating of the winding). Type test certificates for each of these tests will be accepted where it can be demonstrated that the transformer supplied is of a similar design to a previously type tested transformer. 9 Data Set associated with the Equipment The following data shall be supplied by the manufacturer and maintained for the isolating transformers. This data will remain the property of Australian Rail Track Corporation. 9.1 Equipment Manuals No Equipment Manual is required for Isolating Transformers. 9.2 Drawings and Information The following drawings are required. Outline Drawing, with external dimensions Nameplate drawing Terminal arrangement drawing 9.3 Test Results The results of all tests, including routine, type, periodic and corrective maintenance tests, shall be recorded and maintained. Routine Tests certificates showing the results of each test performed shall be supplied in duplicate and electronically, in English, and maintained for the life of the transformer. Type Tests certificates showing the results of each test shall be supplied in duplicate and electronically, in English, and maintained for the life of the equipment. March 2005 Page 15 of 20

9.4 Life Cycle Costing All the data and assumptions pertaining to the determination of the whole-of-life cost calculations shall be recorded, including transformer loss calculations as detailed in PDS 16. 9.5 Technical Schedule The information listed in the technical schedule of Appendix A, supplied by the manufacturer, shall be maintained for each isolating transformer. March 2005 Page 16 of 20

Appendix 1 Technical Schedule The Tenderer, shall supply the information listed in this Technical Schedule at tender stage, for each isolating transformer. A1.1 Transformer Details Model/Type number.... Type of transformer (eg Air cooled/cast resin, suitable for indoor or outdoor use or both).... IP Rating of transformer casing.... Rated primary voltage.... V Primary voltage tappings....% Rated secondary voltage Rated power.... V.... kva Number of phases.... Connection symbol.... Maximum temperature rise of windings.... C Impedance voltage at rated curent and 115 C (expressed as....% percentage of rated voltage).... C Regulation, no-load to full-load at 115 C and unity power....% factor.... C Efficiency, full-load at 115 C and unity power factor....%.... C No-load current with rated voltage applied to the principal tapping (expressed as percentage of rated current)....% No-load current with 110% of rated voltage applied to the principal tapping (expressed as percentage of rated current)....% Maximum value of in-rush current.... A Describe the design features that have been used to reduce the in-rush current and provide any recommendations to coordinate protection settings including choice of circuit breakers.......... March 2005 Page 17 of 20

No-load loss Load loss... Watts... Watts Type of core steel - (hot or cold rolled)... Brand of trade name and grade of core steel... Flux density based on net cross-section of steel with rated voltage at rated frequency applied to the principal tapping (a) Limbs (b) Yoke Mean audible sound level (to AS2374.6-1994)... T... T... db Type of material used for windings - (copper or aluminium)... Type of insulating material used for windings... Temperature class of winding insulation... Type and size of material used for protective screen... Terminal details... Core insulator details (manufacturer and catalogue No)... Describe the design enhancements for reducing the prospective damage due to lighting strikes and list any recommended external components.......... A1.2 Overall Dimensions (a) Length (b) Width (c) Height... mm... mm... mm A1.3 Mass Mass of windings only Mass of transformer core and windings only Total mass of transformer...kg...kg...kg March 2005 Page 18 of 20

A1.4 Terminals Power frequency voltage test, which the windings and terminals will withstand without puncture or flashover Tests in accordance with Clause 21 and Table 1 of AS 1265. Primary terminals (a) Lighting impulse withstand voltage (b) Power frequency withstand voltage... kvp...kvms Secondary terminals (a) Lighting impulse withstand voltage... kvp (b) Power frequency withstand voltage... kvrms Terminals, minimum clearance in air: Between phases (a) Primary... mm (b) Secondary... mm Phase to earth (a) Primary... mm (b) Secondary... mm (c) Heat-shrink material provided on the terminals? (YES/NO)... Describe the method to be used for securing the leads (clause 6.4 Internal Connections)......... A1.5 Reliability Data Design Life Failure Modes (for Early, Normal Life, & Wear Out periods)... Years a)... b)... c)... Mean Operating Hours Between Failures: a)... b)... c)... March 2005 Page 19 of 20

Time to Repair a)... b)... c)... A1.6 Departure from Standard Are there any departures from the requirements of this Standard? * YES / NO Appendix 2 Request for Tender Checklist Where this standard is used as the basis for procurement of isolating transformers for a particular location, in addition to the general requirements in this standard the following information will need to be supplied related to the particular site: Number of isolating transformers required; Power rating (preferred minimum value of 25 kva); Number of phases (single or 3 phase); Indoor / Outdoor Use; Maximum enclosure size (height x width x depth); Type of mounting (wall or floor); Any site specific limitations on size or arrangement; Limitations due to access or transport; Any exceptional service conditions. March 2005 Page 20 of 20