ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Similar documents
! CAUTION D TABLE 1

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

Type CA Percentage Differential Relay for Transformer Protection (50 and 60 Hertz)

Type CVX and CVX-1 Synchro-Verifier Relays

INSTRUCTIONS TYPE SBF STATIC BREAKER FAILURE RELAY

Type PM Line of Relays For Pilot Wire Monitoring And Transferred Tripping R. Table 1:

A. Photo #9664A14. Figure 1. Type KS-3 Out-of-Step Blocking Relay Without Case

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

Apprentice Electrical Technician Test (ETT) Preparation Guide

Type KLF Generator Field Protection-Loss of Field Relay

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Industrial Electronics

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

DLVP A OPERATOR S MANUAL

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway. Malvern, PA TRANSFORMER DIFFERENTIAL RELAY

INSTRUCTION MANUAL FOR VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G

PRACTICAL TRANSISTOR CIRCUITS

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

TEN-TEc INSTRUCTION SHEET MODEL KRS-A

SPECIFICATION, CONTROLS AND ACCESSORIES

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

R-F Skewed Hybrids. Type H1SB and H1SB-R. & R-F Balanced Hybrids Type H1R, H3X and Type H1RB, H3XB and Type H1RB-40. System Manual CH44 VER03

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

www. ElectricalPartManuals. com Westinghouse HRU Instantaneous Overcurrent Relay with Harmonic Restraint Descriptive Bulletin Page 1

ABB Automation Products AB

3. Diode, Rectifiers, and Power Supplies

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GE K-45307K TRANSFORMER DIFFERENTIAL RELAYS WITH

GENERALS ELECTRIC INSTRUCTIONS POWER SYSTEMS MANAGEMENT DEPARTMENT PHILADELPHIA, PA. GEK Insert Booklet GEK RESTRAINT CIRCUITS

Battery Charger Circuit Using SCR

Prof. Steven S. Saliterman Introductory Medical Device Prototyping

Learn about the use, operation and limitations of thyristors, particularly triacs, in power control

Distribution/Substation Transformer

EASUN REYROLLE LIMITED

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

Type VAEM 22 Negative Potential Biasing Relay

Long Loopstick Antenna

GENERAL ELECTRIC INSTRUCTIONS In3ert Booklet GEK GEK-4530/ TRANSFORMER DIFFERENTIAL RELAY WITH PERCENTAGE AND HARMONIC RESTRAINT STD28C TYPE

SCR- SILICON CONTROLLED RECTIFIER

which is used to shift the phase angle between the two sets of coils to produce torque.

which is used to shift the phase angle between the two sets of coils to produce torque.

CATALOG & INSTRUCTION MANUAL. Type LJ High Speed Auxiliary Relays

ELECTRONICS AND ELECTRICITY

Conventional Paper-II-2011 Part-1A

Style FR HI Shunt Track Unit

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

Microprocessor Control Board Set Up Procedures (OR PLC)

GENERALS ELECTRIC I NSTRUCT IONS GEK-45312A. Insert Booklet GEK TRANSFORMER DIFFERENTIAL RELAY WITH PERCENTAGE AND HARMONIC RESTRAINT

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

PROTECTION of electricity distribution networks

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

MVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

Teccor brand Thyristors AN1001

Pre-certification Electronics Questions. Answer the following with the MOST CORRECT answer.

LBI-30398N. MAINTENANCE MANUAL MHz PHASE LOCK LOOP EXCITER 19D423249G1 & G2 DESCRIPTION TABLE OF CONTENTS. Page. DESCRIPTION...

Back to the Basics Current Transformer (CT) Testing

Maintenance Manual ERICSSONZ LBI-31552E

POWER SUPPLY MODEL XP-720. Instruction Manual ELENCO

3 Pole high impedance differential relay 7VH83

GEK-45405G INSTRUCTIONS DIFFERENTIAL VOLTAGE RELAYS TYPE S PVD21A PVD21B PVD21C PVD2ID GENERAL ELECTRIC

FMR622S DUAL NARROW BAND SLIDING DE-EMPHASIS DEMODULATOR INSTRUCTION BOOK IB

Electrical Fundamentals and Basic Components Chapters T2, T3, G4

SPAE 010, 011 High Impedance Protection Relay

Power Electronics. Prof. B. G. Fernandes. Department of Electrical Engineering. Indian Institute of Technology, Bombay.

Instructions AVC125-10: Voltage Regulator. Voltage Range. Maximum Continuous Burden. Voltage Range. Nominal Frequency

ERICSSONZ LBI-30398P. MAINTENANCE MANUAL MHz PHASE LOCKED LOOP EXCITER 19D423249G1 & G2 DESCRIPTION TABLE OF CONTENTS

A Digital Multimeter Using the ADD3501

Technician Licensing Class

MASTR II AUXILIARY RECEIVER 19D417546G7 & G8 & ANTENNA MATCHING UNITS 19C321150G1-G2. Maintenance Manual LBI-30766L. Mobile Communications

INPUT: 110/220VAC. Parallel Input Series Input Parallel Output Series Output (W/CT)

2 5 1 A Va c u u m T u b e

Basic Electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

W DC ELECTRONIC LOAD INSTRUCTION MANUAL

GEI E INSTRUCTIONS SILICON JUNCTION RECTIFIER FOR TRIPPING DUTY. Type 102L218. www. ElectricalPartManuals. com

Lecture (04) PN Diode applications II

Maintenance Manual INTERNAL BATTERY STANDBY CHARGER OPTION BC01 (9669), 9670 AND 9771 (FOR MASTR II STATIONS) Mobile Communications LBI-30869L

3 Circuit Theory. 3.2 Balanced Gain Stage (BGS) Input to the amplifier is balanced. The shield is isolated

ARN-21D Solid State Modulator - A/A mode

Unit Protection Differential Relays

SPECIFICATION, CONTROLS AND ACCESSORIES


1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3

Radar. Radio. Electronics. Television. .104f 4E011 UNITED ELECTRONICS LABORATORIES LOUISVILLE

Central Electronics Model 600L Linear Amplifier

PAPER-II (Subjective)

and UNTUNED DECODING UNITS DECODING TRANSFORMERS SERVICE MANUAL 6097 Operation, Installation and Maintenance for EL Coded Cab Signal Equipment

Two variable ac current, variable phase-angle sources Variable dc voltage/current source and latch timer Variable harmonic current source

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

AN1001. Fundamental Characteristics of Thyristors. Introduction. Basic Operation of a Triac. Basic Operation of an SCR. Basic Operation of a Diac

Practical Tricks with Transformers. Larry Weinstein K0NA

Glossary 78 LIFETIME LIMITED WARRANTY. GREENLEE Phone: (International)

Chapter 3. Electricity, Components and Circuits. Metric Units

Transformer Protection

LAMBDA EMI 405 ESSEX ROAD, NEPTUNE, NJ 07753

Transcription:

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet 41-348.1H Effective: November 1997 Supersedes I.L. I.L. 41-348.1G, Dated January 1985 ( ) Denotes Change Since Previous Issue! CAUTION In calculating the burden, use the longest one-way lead resistance from the ct to the SA-1 for distribution transformer or resistance grounded machines. Use twice the longest one-way lead resistance for reactance grounded machines. Before putting relays into service, operate the relay to check the electrical connections. Close red handle switch last when placing relay in service. Open red handle switch first when removing relay from service. 1. APPLICATION The SA-1 relay is a three-phase high-speed relay used for differential protection of ac generators and motors. With proper selection of current transformers, the relay is unaffected by dc transients associated with asymmetrical through short-circuit conditions. Current transformer burden in ohms should not exceed (N P V CL )/133; further, the burden factor, BF, should not differ by more than a 2 to 1 ratio between the two sets of ct s. The above terms are defined as: N P = proportion of total number of ct turns in use V CL = current transformer relaying accuracy class voltage (e.g. C400, V CL = 400) B F = 1000 R B --------------------- N P V CL R B = resistance of the burden, excluding ct winding resistance For example, if the 400/5 tap of a 600/5 multi-ratio ct is used, N P = 400/600 = 0.67. If this ct has a C200 rating, V CL = 200, and the burden should not exceed: N P V CL ------------------- 133 Assuming a resistance burden of R B = 0.5 ohms, the burden factor, BF is: BF The other set of ct s may than have a burden factor as high as 2 x 3.8 = 7.6, or as low as 1/2 x 3.8 = 1.9. If the other set of ct s also has a burden of 0.5 ohm, a C100, C200, or C400 rating would be satisfactory since the burden factors are 7.6, 3.8 and 1.9 respectively. 2. CONSTRUCTION 0.67 200 = --------------------------- = 1.0 ohm 133 1000 R B 1000 0.5 = -------------------- = --------------------------- = 3.8 N P V CL 0.67 200 The type SA-1 relay consists of a Restraint Circuit, Operating Circuit, Sensing Circuit, Amplifier Circuit, Trip Circuit, Indicating Circuit, Surge Protection Circuit and external reactors. The principal parts of the relay and their location are shown in Figures 1 through 8. All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.

41-348.1H 2.1. RESTRAINT CIRCUIT The restraint circuit of each phase consists of a center-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are connected in parallel. The parallel connection of rectifiers is a maximum voltage network. Hence, the voltage applied to the filter circuit is proportional to the phase current with the largest magnitude. 2.2. OPERATING CIRCUIT The operating circuit consists of a transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are connected in parallel. This parallel connection of rectifiers is a maximum voltage network. Hence, the voltage applied to the filter circuit is proportional to the phase current with the largest magnitude. 2.3. SENSING CIRCUIT The sensing circuit is connected to the output of the restraint filter circuit, the operating filter circuit and the input to the amplifier circuit. 2.4. AMPLIFIER CIRCUIT The amplifier circuit consists of a two-transistor amplifier which controls the operation of a relaxation oscillator. The amplifier circuit is connected to the sensing circuit such that it receives the difference in output of the restraint filter and the operating filter. Thus, the polarity of the input voltage to the amplifier depends upon the relative magnitude of the voltages appearing on the restraint and operating filters. When the voltage output of the operating filter is greater than the output voltage of the restraint filter, a voltage of a certain polarity appears across the input of the amplifier. To trigger the amplifier requires that the output voltage of the operating filter be greater than the output voltage of the restraint filter. 2.5. TRIP CIRCUIT The trip circuit consists of a thyristor which has an anode, cathode, and a gate. The anode of the thyristor is connected to the positive side of the dc supply and the cathode of the thyristor is connected to the negative side of the dc supply through the trip coil of a breaker. The gate of the thyristor is connected to the output of the amplifier circuit through a pulse transformer. With no gate current flowing, the thyristor acts as an open circuit to the breaker trip coil. When a gate current is applied tot he thyristor the thyristor connects the breaker trip coil to the dc supply. 2.6. INDICATING CIRCUIT The indicating circuit is triggered by a signal from the amplifier of the relay. Under normal or non-fault conditions, the indicating circuit is turned off. When a fault is applied to the relay, the amplifier will conduct to cause a signal to flow into the indicator circuit. When the indicator circuit is triggered, the lamp will turn on. This lamp will remain lit until the indicator circuit is interrupted by resetting the micro-switch. 2.7. SURGE PROTECTION CIRCUIT The surge protection circuit consists of two capacitors (C10 and C11) and a R-C network which is connected across the anode and cathode of the tripping thyristor to prevent the SCR from firing by a surge of voltage. 2.8. EXTERNAL REACTORS Three reactors are mounted on a metal plate with a separate terminal strip. The reactors are of the saturable type. 3. OPERATION The relay is connected to the protected apparatus as shown in Figure 9. On external faults, current flows through the primary winding of the restraint transformers to induce a voltage on the restraint side of the sensing circuit. If the two sets of main current transformers have different performances, some current will flow out of the mid-tap of the restraint transformers to the operating transformers. This will produce a voltage on the operating side of the sensing circuit. With the relay correctly applied, sufficient restraint voltages will exist to prevent the operating voltage from triggering the amplifier. The percentage slope characteristic of the relay limits the operating voltage on heavy external faults where the performance of the two sets of current transformers may be quite different. On internal faults, the operating coil current is the sum of the current flowing in each of the windings of the restraint transformer and sufficient operating voltage is available to overcome the restraint voltage. 2

41-348.1H 4. CHARACTERISTICS The percentage slope curves are shown in Figures 12 and 13. It will be observed that the relay operates at 5% unbalance at 5 amperes restraint (Figure 12) to provide high sensitivity for internal faults up to full load conditions. At 60 amperes restraint, the operating current required to trip the relay is 30 amperes or 50% unbalance (Figure 13). Thus, when 60 amperes through-fault current is flowing, the output of the main current transformers may vary considerably without causing incorrect operation. The minimum pickup of the relay is 0.14 ampere or 0.5 ampere for the desensitized version. The operating characteristic of the desensitized SA- 1 is shown in Figure 14. The time curve of the relay is shown in Figure 15. The frequency response characteristic of the SA-1 relay is shown in Figure 16. 5. ENERGY REQUIREMENTS Each Restraint Circuit Burden at 5 amperes is 0.25 VA Continuous rating 20 amperes 1 second rating 300 amperes Operating Circuit The burden imposed by the operating circuit on each circuit transformer is variable because of the saturating transformer and reactors. At 0.5 amperes, it is 0.37 VA, and at 60 amperes it is 170 VA. Continuous rating 10 amperes 1 second rating 200 amperes Amplifier The dc burden on the station battery is: Volts Milliamperes Watts 125 dc 48 dc 55 60 6.9 2.9 6. SETTINGS There are no taps on either transformer and, consequently, there are no settings to be made except for the choice of battery voltage level. The 48/125 Vdc relays are normally shipped for 125 volts. For 48 Vdc applications use the mid-tap on the resistor mounted at the top of the relay. The red dot on the resistor is the common point DO NOT REMOVE. 7. INSTALLATION The relay should be mounted on switchboard panels or their equivalent in a location free from moisture. Mount the relay vertically by means of the four mounting holes on the flange for semi-flush mounting. Either a mounting stud or the mounting screws may be utilized for grounding the relay. The electrical connections may be made directly to the terminals by means of screws. The external reactor assembly should be mounted and wired per interwiring Connection Drawing, Figure 11. For detailed FT case information, refer to I.L. 41-076. 8. ADJUSTMENTS AND MAINTENANCE The proper adjustments to insure correct operation of this relay have been made at the factory and should not be disturbed after receipt by the customer. 8.1. ROUTINE TEST The following check is recommended to insure that the relay is in proper working order. All checks can best be performed by connecting the relay per the test circuit of Figure 17. Due to high impedance of the external reactor, prior to saturation, the test circuit of Figure 17 should be used to test the relay only. The reactors can be checked by applying 0.2 amperes 60 hertz and reading the voltage drop across the reactor with a high impedance True RMS reading voltmeter. The voltage drop will be between 20 and 26 volts True RMS. For 0.4 amperes input, the reading should be between 29 and 31 volts True RMS. 3

41-348.1H 1. Minimum Trip Current with I R set at zero amperes, apply 0.14 ±5% (0.5 ±5% got desensitized SA-1) amperes operating current to each operating circuit of the relay. The relay should operate and the indicator lamp should light. 2. Differential Characteristic a) Apply I R of 5 amperes and adjust the operating current until the relay operates. The relay should operate and the indicator lamp should light with an operating current of 0.25 ±5% amperes (0.71 5% for desensitized SA-1). Repeat for each phase of the relay. b) Apply I R of 60 amperes and adjust the operating current until the relay operates. The relay should operate and the indicator lamp should light with an operating current of 30 ±10% amperes. Repeat for each phase of the relay. (I R = 40 amperes and I O = 24 ±10% for desensitized SA-1). 8.2. MAINTENANCE All relays should be checked once a year to detect any failures which may have occurred. The tantalum capacitors C1, C2, C3, C4 and C13 may have a common mode failure characteristic and should be checked visually for symptoms of electrolyte leakage every year and replaced if necessary. 8.3. CALIBRATION Use the following procedure for calibrating the relay if the relay adjustments have been disturbed. This procedure should not be used until it is apparent the relay is not in proper working order. 1. Minimum Trip Current Connect the relay per test circuit of Figure 17 with switch K open. Adjust the operating resistor in the rear of the relay until the relay operates with IO equal to 0.14 ampere, 0.5 ampere for desensitized SA-1. DO NOT make adjustments to the resistor unless the dc is disconnected. The indicator lamp should light when the relay operates. Repeat for each phase of the relay. 2. Percentage Slope Characteristic (Low Current). Close switch K and set I R equal to 5 amperes and adjust the restraint resistor in the rear of the relay until the relay operates with I o = 0.25 ±.010 amperes. DO NOT adjust resistor with dc applied to relay. The indicator lamp should light when the relay operates. Repeat for each phase of the relay. Percentage Slope Characteristic (High Current) Set I R equal to 60 amperes for the operating current of 30 amperes. Replace the resistor R17 if necessary. The value of R17 can be between 0 and 100 ohms. Repeat for the other two phases if necessary, replacing R18 and R19 respectively. 3. Electrical Checkpoints See Table 1. 9. RENEWAL PARTS Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be furnished to customers who are equipped for doing repair work. When ordering parts, always give the nameplate data. 10. ELECTRICAL CHECKPOINTS Connect relay per test circuit of Figure 17. All voltage readings should be made with a high resistance voltmeter. Refer to component location of checkpoints. Voltage readings are approximate. The voltage readings Input to Amplifier should not be taken with relay in service. 4

41-348.1H Table 1: (Values in Parenthesis Represent Desensitized SA-1) CIRCUIT PRIMARY CURRENT PHASE CHECKPOINTS (Typical Value) TERMINAL VALUE FUNCTION Operating 0.14A (0.5A) 1 2 3 2-7 3-6 4-5 2.5 ac 2.5 ac 2.5 ac Input to operate rectifier Input to operate rectifier Input to operate rectifier Sensing (Operating) 0.14A (0.5) Any phase + to - 23-26 24-26 24-8 8-25 25-26 2.1 dc 1.85 dc 0.55 dc 0.65 dc 0.65 dc Output to rectifier a. Output to operating sensing circuit b. Input to amplifier c. d. Output to restraint sensing circuit Ref.: a = b + c + d 30.0A Any phase + to - 24-26 51.0 dc Restraint 5.0A 1 2 3 18-13 17-14 15-16 6.0 ac 6.0 ac 6.0 ac Input to restraint rectifier Input to restraint rectifier Input to restraint rectifier Sensing (Restraint) 5.0A Any phase + to - 25-26 25-8 8-24 24-26 2.1 dc 1.2 dc 0.6 dc 0.3 dc a. Output of restraint sensing circuit b. c. Input to amplifier d. Output to operating sensing circuit Ref.: a = b + c + d 60.0A Any phase + to - 25-26 42.0 dc Amplifier 0 Minimum Trip Current +5% Any phase + to - 27-8 12-8 10-8 + to - 27-8 12-8 21-8 0.7 dc 24.0 dc 24.0 dc 0.5 dc 24.0 dc 10.0 dc 5

41-348.1H Table 2: Electrical Part List Circuit Symbol Reference Style Resistors Resistors Resistors Zener SCR Reactor UT, UM, UB LT, LM, LB R14 Z2 L1 60 Ohms, 25W 265 Ohms, 25W 1.8K, 40 W IN2986B 1875676 1725542 187A321H06 629A798H03 184A614H05 1478B98G01 SA Module Style Number 408C673G01 Sub 35 Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor Resistor R1 R2 R3, R4 R5 R6 R7 R8 R9 R10 R11 R12 R13 R17, R18, R19 270 Ohms, 1W 2K, 5% 15K, 5% 2.7K, 5% 68K, 5% 27K, 5% 2.2K, 5% 100 Ohms, 10% 220 Ohms, 5% 680 Ohms, 5% 47K, 5% 33 Ohms, 5% 184A635H06 184A763H34 184A763H55 184A763H37 184A763H71 184A763H61 184A763H35 184A763H03 184A763H11 184A763H23 184A763H67 187A290H13 Capacitor Capacitor Capacitor Capacitor Capacitor Capacitor C1, C2, C3, C13 C4 C5 C6 C7 C8, C9 25 MFD, 125V 22 MFD, 35V 0.5 MFD, 200V 2.2 MFD, 35V 2.0 MFD, 200V 0.47 MFD, 50V 184A637H01 184A661H16 187A624H03 837A241H16 187A624H05 762A680H04 Diode Diode D1 to D24 D25, D26 IN4821 IN645A 188A342H16 837A692H04 Zener SCR Transistor Transistor Transformer Z1 T1, T2 T3 TR-1 IN752A K1149-13 2N3417 2N2647 186A797H12 184A640H13 848A851H02 629A435H01 629A372H02 SPK Module Style Number 1584C21G01 Resistor Capacitor Capacitor R15 C10, C11 C12 470 Ohms, 1W 0.01 MFD, 1.5KV 2.0 MFD, 200V 187A643H19 3516A36H03 3509A33H01 NOTE: The values of R17, R18 and R19 are between 0 and 100 Ohms. They are determined in test. 6

41-348.1H Figure 1. without Case (Front View) 7

41-348.1H Figure 2. without Case (Rear View) 8

41-348.1H 629A406 Sub 15 Figure 3. Internal Schematic of Relay 48/125 Vdc 9

41-348.1H 876A613 Sub 9 Figure 4. Internal Schematic of Relay 250 Vdc 10

41-348.1H RELAY TYPE SA-1 HIGH SPEED DIFFERENTIAL FOR GENERATOR PROTECTION IN TYPE FT-32 CASE (DESENSITIZED) 877A847 Sub 8 Figure 5. Internal Schematic of Desensitized SA-1 Relay 11

41-348.1H 23 + C1 R17 762A601 Sub 9 Figure 6. Component Location for 48/125 Vdc 12

41-348.1H 867A639 * Sub 5 Figure 7. Component Location for 250 Vdc * Denotes Change 13

41-348.1H COMPONENT LOCATION 48/125 V C 1 1 C 1 0 2 1 3 5 4 R15 SPK C12 1584C01G01 C11 & C10.01 uf 3516A36H03 C12 2.0 uf 3509A33H01 R15 470 Ohm 187A643H19 COMPONENT LOCATION 250 V C 1 1 C 1 0 2 1 3 5 4 R15 6 7 SPK 1584C01G02 C11 & C10.01 uf 3516A36H03 R15 470 Ohm 187A643H19 Illustration 3532A07 Sub 2 Figure 8. Component Location of the SPK Module 14

41-348.1H 775B965 *Sub 4 Figure 9. External Schematic of Relay for Generator Protection 775B982 Sub 1 Figure 10. Reactor Outline 15

41-348.1H NOTE: A - PLACE IT. 1 TO 3 IN IT. 5 FOR SHIPPING Lead SCREW SIZE IT. L A B 1 3.00.164-32.164-32 2 4.00.164-32.190-32 3 3.00.164-32.190-32 4 13.438.164-32.190-32 A ITEM PART NAME STYLE DWG. ITEM GR. NOTE CODE ENG. REF. REQ 01 LEAD 57Z0301 616 A 63-D-653 2 02 LEAD 57Z0401 622 A 63-D-655 3 03 LEAD 57Z0301 622 A 63-D-655 1 05 BAG 836A618 H04 B 27-D-5478 1 B L ±.156 775B981 * Sub 5 Figure 11. Relay and Reactor Interconnection * Denotes Change 16

41-348.1H 3537A44 Sub 2 Figure 12. Percentage Slope characteristic at Low Value of Restraint Current 17

41-348.1H 878A742 Sub 3 Figure 13. Percentage Slope Characteristic at High Value of Restraint Current 18

41-348.1H 619406 Sub 1 Figure 14. Percentage Slope Characteristic of High Value Restraint Current for Desensitized SA-1 Relay 19

41-348.1H 477706 Sub 1 Figure 15. Typical Operation Time Characteristic 20

41-348.1H 3537A45 Sub 2 Figure 16. Typical Frequency Response Curve 184A864 Sub 4 Figure 17. Typical Frequency Response Curve 21

41-348.1H 3519A69 * Sub 4 Figure 18. Outline and Drilling Plan for the Relay in Type FT-32 Case * Denotes Change 22

41-348.1H NOTES 23

41-348.1H ABB Automation, Inc. Substation Automation & Protection Division 4300 Coral Ridge Drive Coral Springs, FL 33065 954 752-6700 800 523-2620 24 www.abb.com/papd ABB Automation, Inc. Substation Automation & Protection Division 7036 Snowdrift Road, Suite 2 Allentown, PA 18106 610 395-7333 800 634-6005