Nexans AmerCable VFD CABLES Index Standard VFD Power Cable... 2-3 Low Smoke Halogen-Free VFD Power Cable.... - 5 CIR VFD Power Cable... - 7 CIR Arctic Grade VFD Power Cable - 9 RATED TC-ER-HL* MMV-VFD Power Cable... - 12 VFD Cable Selection Guide.. 12-13 n 0% EMI Containment n Highly Flexible & Durable n Four Constructions n Shortest Lead Times n Best On-Time Delivery Rate *Visit www.nexansamercable.com for today s on-time delivery rate EXTREME COLD Operating Environment? See Pages -7 CIR AG VFD RATED TC-ER-HL* www.nexansamercable.com Nexans AmerCable believes the information presented throughout this catalog to be reliable and current. All information is subject to change without notice. The information listed is approximate, and is presented only as a guide for product selection. We make no claims or warranties for the suitability of any product for any particular application. Gexol is a registered trademark of AmerCable Incorporated. Registered in the U.S. Patent and Trademark Office. 201 AmerCable Incorporated
Nexans AmerCable VFD Cables are specially engineered to provide 0% containment of EMI emissions and provide longer cable life in VFD applications. Nexans AmerCable VFD cables feature symmetrical insulated ground conductors that reduce induced voltage imbalances and carry common mode noise back to the drive. Nexans AmerCable s high strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable. Hawke Gland Types Hawke Gland Types Unarmored Armored & Sheathed Industrial & Safe Area (IP) 121 153-X Increased Safety EExe 501/21 501/53/U Explosion Proof 7 753 Class I, Div. 2 Class I, Div. 1 Class I, Zone 2 Class I, Zone 1 & 2 Flameproof 501/21 501/53/U EExd Zone 1 & 2 (2 liter or < enclosures) ICG 53/U (2 liter or > enclosures) Zone 1 & 2 e-mail: marine@nexansamercable.com 1
37-2VFD STANDARD VFD POWER CABLE GEXOL INSULATED Three Conductor 2kV Rated 1 C Power Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Insulation (2kV) Gexol cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 150 and Type X1 of UL 1309/CSA 25. Color: Gray with printed phase I.D. (Black-White-Red) Jacket A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL1309/ CSA 25 and IEEE 150. Armor (Optional) Tinned copper basket weave wire armor per IEEE 150 and UL 1309/CSA 25. Shield Overall tinned copper braid plus aluminum/polyester tape providing 0% coverage. Ratings & Approvals n 1 C Temperature Rating n American Bureau of Shipping (ABS) n Transport Canada n Det Norske Veritas (DNV) n Lloyd s Register of Shipping (LRS) n NVE: 95/19, FAL n UL Listed as Marine Shipboard Cable: (E1111) n Unarmored Cable is UL Listed as Type TC (E12329) n United States Coast Guard: November 2, 197 / 930 Other certifications pending Ground Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Gexol insulated and sized per UL 1277. Color: Green Sheath (Optional) A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 25 and IEEE 150. Note: For armored versions the braid is placed between the inner jacket and outer sheath where it serves as both the EMI shield and armor. APPLICATION A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications. FEATURES n Specially engineered cable design produces a longer cable life in VFD applications. n Overall braid plus foil shield is engineered with 0% coverage and a surface transfer impedance <50 milliohms at MHz to contain EMI. n Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive. n High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable. n Gexol s lower dielectric constant (standard XLPEs, EPRs and other Type P insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system. n 2kV insulation thickness is used to resist the potential 2-3x reflected voltages experienced in 00V VFD applications. n Dual certified IEEE 150 Type P and UL 1309/CSA 25 Type X1. n Highest ampacity ratings: ABS 0 C, DNV 95 C, LRS 95 C, Transport Canada 95 C. n Severe cold durability: exceeds CSA cold bend/cold impact (-0 C/-35 C). n Flame retardant: IEC 332-3 Category A and IEEE 1202. n Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed). n Optional braid armor of bronze, aluminum or tinned copper. 2 Manufactured by Nexans AmerCable 00-50-973 713-9-500 Fax: 713-9-9009
Unarmored Armored & Sheathed (TS) DC Resist. AC Resist. Inductive Voltage Drop Grounding Size Nominal Weight Nominal Weight at 25 C at 90 C, Reactance at 90 C Conductor** Ampacity AWG/ Part No. Diameter Lbs./ Part No. Diameter Lbs./ Ohms/ 0 Hz Ohms/ Ohms/ Volts/Amp/ Size kcmil mm 2 37-2 Inches* 00 Ft. 37-2 Inches* 00 Ft. 00 Ft. 00 Ft. 00 Ft. 00 Ft. (AWG) 1 C 0 C 90 C 75 C 1 2.1-50VFD 0.30 19-50TSVFD 0.772 35 2.907 3.59 0.00 5.33 1 27 25 2 20 12 3.3-51VFD 0.75 22-51TSVFD 0.795 01 1.2 2.2 0.03 3.39 1 33 31 29 2 5.2-30VFD 0.750 30-30TSVFD 0.91 51 1.153 1.530 0.03 2.155 1 1 3 32 7. -309VFD 0.15 3-309TSVFD 1.000 73 0.70 0.90 0.037 1.339 1 5 52 1 12.5-3VFD 0.9 570-3TSVFD 1.1 5 0.5 0.590 0.033 0.52 12 75 70 5 5 21-312VFD 1.0 925-312TSVFD 1.22 113 0.300 0.399 0.031 0.5 12 99 92 3 70 2 3-31VFD 1.235 121-31TSVFD 1.392 1512 0.1 0.2 0.029 0.3 131 122 111 93 1 3-315VFD 1.30 1517-315TSVFD 1.509 151 0.17 0.195 0.029 0.301 153 13 131 1 1/0 5-31VFD 1.50 103-31TSVFD 1.15 213 0.117 0.15 0.029 0.2 17 1 150 12 2/0 70-317VFD 1.50 2120-317TSVFD 1.792 20 0.093 0.125 0.02 0.202 201 1 173 15 3/0-31VFD 1.750 227-31TSVFD 1.959 329 0.07 0.0 0.02 0.17 23 21 200 1 /0 9-319VFD 1.900 31-319TSVFD 2.1 3 0.05 0.00 0.027 0.139 270 252 232 19 22 132-320VFD 2.050 2-320TSVFD 2.25 1 0.0 0.07 0.027 0.120 315 29 273 22 313 159-321VFD 2.130 55-321TSVFD 2.353 5325 0.00 0.05 0.02 0.5 3 321 29 29 373 19-322VFD 2.275 5521-322TSVFD 2.3 7 0.03 0.07 0.025 0.092 37 31 332 277 227-323VFD 2.25 0-323TSVFD 2.3 99 0.02 0.01 0.025 0.03 0 11 32 319 535 273-32VFD 2.3 757-32TSVFD 2.931 77 0.02 0.035 0.02 0.075 9 3 07 30 32-32VFD 2.920 91-32TSVFD 3.17 9 0.020 0.030 0.02 0.0 553 51 7 39 777 39-327VFD 3.2 909-327TSVFD 3.5 1103 0.01 0.02 0.025 0.02 02 52 51 31 *Cable diameters are subject to a +/- 5% manufacturing tolerance **3 Grounding Conductors Green Insulated Stranding Profile: See Page 5 Standard VFD Cable Ampacity Ratings Based on IEEE Std. 5 with a 5 C ambient and arranged in a single bank per hanger. For those instances where cable must be double banked, the ampacities should be multiplied by 0.. GEXOL is a registered trademark of AmerCable Incorporated Gexol-HF is flexible and has a low capacitance for superior performance in VFD applications! www.nexansamercable.com e-mail: marine@nexansamercable.com 3
37-3VFD LOW SMOKE HALOGEN-FREE VFD POWER CABLE Three Conductor 2kV Rated 90 C Gexol -HF Insulation Power Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Insulation (2kV) GEXOL -HF low smoke halogen-free flame retardant cross-linked polyolefin, meeting the requirements for Type LSE or LSX of IEEE 150. Color: Gray with printed phase I.D. (Black-White-Red) Armor (Optional) Tinned copper basket weave wire armor per IEEE 150. Ground Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Gexol -HF insulated and sized per UL 1277. Color: Green Shield Overall tinned copper braid plus aluminum/ polyester tape providing 0% coverage. Jacket A black low smoke halogen-free flame retardant polyolefin, meeting IEEE 150. Sheath (Optional) A black low smoke halogen-free flame retardant polyolefin, meeting IEEE 150. Note: For armored versions the braid is placed between the inner jacket and outer sheath where it serves as both the EMI shield and armor. Ratings & Approvals n 90 C Temperature Rating n American Bureau of Shipping (ABS) n UL Listed as Marine Shipboard Cable: (E1111) n Transport Canada n Det Norske Veritas (DNV): pending n Lloyd s Register of Shipping pending Other certifications pending APPLICATION A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications where a low smoke halogen-free insulation is required. FEATURES n Low Smoke and Halogen-Free. n Specially engineered cable design produces a longer cable life in VFD applications. n Overall braid plus foil shield is engineered with 0% coverage and a surface transfer impedance <50 milliohms at MHz to contain EMI. n Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive. n High strand count conductors and braid shield design is much more flexible and easier than IEC 0092-350 series cables to install. n Gexol-HF s lower dielectric constant (standard HFXLPE, HFEPR insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system. n 2kV insulation thickness is used to resist the potential 2-3x reflected voltages experienced in 00V VFD applications. n Severe cold durability: exceeds CSA cold bend/cold impact (-0 C/-35 C). n Flame retardant: IEC 332-3 Category A and IEEE 1202. n Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed). n Optional braid armor of bronze, aluminum or tinned copper. Manufactured by Nexans AmerCable 00-50-973 713-9-500 Fax: 713-9-9009
Strand Profile: Standard & LSHF Closest Equivalent Uninsulated Size Number IEEE 5 Metric Size Conductor AWG/kcmil of Strands Std. Size (mm2) Dia. (inches) 1 12 2 1 1/0 2/0 3/0 /0 22 313 373 535 777 Unarmored 19 19 37 37 1 209 2 32 1 532 777 925 11 2 1591 192 1 2 1 3 1 212 22 313 373 535 777 Armored & Sheathed (TS) DC Resist. AC Resist. Inductive Voltage Drop Size Nominal Weight Nominal Weight at 25 C at 90 C, 0 Hz Reactance at 90 C Grounding Ampacity AWG/ Part No. Diameter Lbs./ Part No. Diameter Lbs./ Ohms/ Ohms/ Ohms/ Volts/Amp/ Conductor** kcmil mm 2 37-3 Inches* 00 Ft. 37-3 Inches* 00 Ft. 00 Ft. 00 Ft. 00 Ft. 00 Ft. Size (AWG) 90 C 75 C 0 C 1 2.1-50VFD 0.7 270-50TSVFD 0.00 31 2.907 3.35 0.00 5.073 1 2 20 15 12 3.3-51VFD 0.9 30-51TSVFD 0.22 31 1.2 2.23 0.03 3.199 1 29 2 1 5.2-30VFD 0.77 01-30TSVFD 0.9 51 1.153 1.1 0.03 2.032 1 3 32 23 7. -309VFD 0.32 90-309TSVFD 1.000 72 0.70 0.5 0.037 1.23 1 1 29 12.5-3VFD 0.912 7-3TSVFD 1.12 921 0.5 0.55 0.033 0.0 12 5 5 39 21-312VFD 1.120 95-312TSVFD 1.2 113 0.300 0.37 0.031 0.552 12 3 70 50 2 3-31VFD 1.25 1290-31TSVFD 1.22 1597 0.1 0.230 0.029 0.3 111 93 7 1 3-315VFD 1.3 1592-315TSVFD 1.595 1915 0.17 0.1 0.029 0.25 131 1 79 1/0 5-31VFD 1. 19-31TSVFD 1.701 235 0.117 0.17 0.029 0.23 150 12 91 2/0 70-317VFD 1.592 230-317TSVFD 1.19 2719 0.093 0.117 0.02 0.192 173 15 5 /0 9-319VFD 1.91 3325-319TSVFD 2.151 392 0.05 0.075 0.027 0.132 232 19 11 22 132-320VFD 2.077 201-320TSVFD 2.25 73 0.0 0.03 0.027 0.115 273 22 15 313 159-321VFD 2.15 92-321TSVFD 2.33 522 0.00 0.053 0.02 0.0 29 29 11 373 19-322VFD 2.302 550-322TSVFD 2.5 155 0.03 0.05 0.025 0.0 332 277 201 227-323VFD 2.52 579-323TSVFD 2.0 727 0.02 0.039 0.025 0.00 32 319 231 535 273-32VFD 2.70 72-32TSVFD 3.020 9007 0.02 0.033 0.02 0.072 07 30 27 32-32VFD 2.97 9311-32TSVFD 3.213 325 0.020 0.02 0.02 0.05 7 39 27 777 39-327VFD 3.12 2-327TSVFD 3.17 1225 0.01 0.025 0.025 0.00 51 31 313 *Cable diameters are subject to a +/- 5% manufacturing tolerance **3 Grounding Conductors Green Insulated 2.0 3.29 5.23 7.57 12.9 21.11 33.51 2.79 5.5 70.01 5.57.91 132.25 159.0 19.3 227.23 272. 325.70 393.7 0.07 0.093 0.113 0.13 0.175 0.25 0.32 0.31 0.07 0.1 0.5 0.575 0.5 0.720 0.75 0.0 0.91 1.029 1.132 GEXOL is a registered trademark of AmerCable Incorporated LSHF VFD Cable Ampacity Ratings Based on IEEE Std. 5 with a 5 C ambient and arranged in a single bank per hanger. For those instances where cable must be double banked, the ampacities should be multiplied by 0.. Gexol-HF is flexible and has a low capacitance for superior performance in VFD applications! www.nexansamercable.com e-mail: marine@nexansamercable.com 5
37-2 CIRVFD CIR (CRUSH & IMPACT RESISTANT) TYPE VFD POWER CABLE UL LISTED AS TYPE TC-ER Three Conductor Gexol Insulated 2kV Rated 90 C Power Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Insulation (2kV) Gexol cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 150 and Type X1 of UL 1309/CSA 25. Color: Gray with printed phase I.D. (Black- Red-Blue) Jacket A black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoplastic compound meeting UL 1309/CSA 25 and IEEE 150. Also available in Arctic Grade thermoset CPE jacket (see page ) CIR VFD Ratings & Approvals Ground Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Gexol insulated and sized per UL 1277. Color: Green Shield Overall tinned copper braid plus aluminum/ polyester tape providing 0% coverage. Safer to Handle CIR has no sharp metal armor edges that imperil worker s hands during splicing and installation of connectors n 90 C temperature rating n UL Listed as Marine Shipboard Cable (E1111) n UL Listed as Type TC-ER n American Bureau of Shipping (ABS) n Flame Retardant IEEE 1202 n Suitable for use in Class I, Div 2 and Zone 2 environments n Sunlight resistant n Direct burial APPLICATION A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications. FEATURES n Specially engineered cable design produces a longer cable life in VFD applications. n Overall braid plus foil shield is engineered with 0% coverage and a surface transfer impedance <50 milliohms at MHz to contain EMI. n Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive. n High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable. n Gexol s lower dielectric constant (standard XLPEs, EPRs and other Type P insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system. n 2kV insulation thickness is used to resist the potential 2-3x reflected voltages experienced in 00V VFD applications. n Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Gas & vapor tight impervious to water and air n Smaller bend radius (up to 0% smaller) than Type MC n Reduced tray fill (up to 35% less) compared to Type MC n Considerably more flexible than Type MC n Reduced installation time and cost compared to Type MC n Glands for this product cost up to 50% LESS than those for Type MC Manufactured by Nexans AmerCable 00-50-973 713-9-500 Fax: 713-9-9009
DC Resist. AC Resist. Inductive Voltage Drop Green Size Nominal Weight @ 25 C @ 90 C, 0 Hz Reactance @ 90 C Insulated IEEE NEC IEEE NEC AWG/ Part No. Diameter (Lbs./ (Ohms/ (Ohms/ (Ohms/ (Volts/Amp/ Grounding Ampacity Ampacity Ampacity Ampacity kcmil mm 2 37-2 Inches* 00 Ft.) 00 Ft.) 00 Ft.) 00 Ft.) 00 Ft.) Size (AWG) 90 C 90 C 75 C 75 C 1 2.1-50CIRVFD 0.7 297 2.907 3.35 0.00 5.073 1 2 15 20 15 12 3.3-51CIRVFD 0.792 37 1.2 2.23 0.03 3.199 1 29 20 2 20 5.2-30CIRVFD 0. 92 1.153 1.1 0.03 2.032 1 3 30 32 30 7. -309CIRVFD 0.92 50 0.70 0.5 0.037 1.23 1 55 1 50 12.5-3CIRVFD 1.051 2 0.5 0.55 0.033 0.0 12 5 75 5 5 21-312CIRVFD 1.093 95 0.300 0.37 0.031 0.552 12 3 95 70 5 2 3-31CIRVFD 1.225 129 0.1 0.230 0.029 0.3 111 130 93 115 1 3-315CIRVFD 1.31 2 0.17 0.1 0.029 0.25 131 15 1 130 1/0 5-31CIRVFD 1.7 190 0.117 0.17 0.029 0.23 150 170 12 150 2/0 70-317CIRVFD 1.5 227 0.093 0.117 0.02 0.192 173 195 15 175 /0 9-319CIRVFD 1.7 330 0.05 0.075 0.027 0.132 232 20 19 230 22 132-320CIRVFD 2.031 200 0.0 0.03 0.027 0.115 273 297 22 22 313 159-321CIRVFD 2.130 77 0.00 0.053 0.02 0.0 29 32 29 292 373 19-322CIRVFD 2.257 53 0.03 0.05 0.025 0.0 332 3 277 322 227-323CIRVFD 2.00 0.02 0.039 0.025 0.00 32 02 319 355 535 273-32CIRVFD 2.705 753 0.02 0.033 0.02 0.072 07 30 39 32-32CIRVFD 2.9 93 0.020 0.02 0.02 0.05 7 9 39 3 777 39-327CIRVFD 3.2 11137 0.01 0.025 0.025 0.00 51 5 31 3 *Cable diameters are subject to a +/- 5% manufacturing tolerance NEC ampacities are based on Table 3.15 (B) (1) of the National Electrical Code (NEC) for conductors rate 90 C, in a multi-conductor cable, at an ambient temperature of 30 C. The 75 C column is provided for additional information. The ampacities shown apply to open runs of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is in accordance with NEC Table 3.15 (B) (3) (a). The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.0. Closest Equivalent Uninsulated Size Number IEEE 5 Metric Size Conductor AWG/kcmil of Strands Std. Size (mm2) Dia. (inches) 1 12 2 1 1/0 2/0 3/0 /0 22 313 373 535 777 Strand Profile: CIR 19 19 37 37 1 209 2 32 1 532 777 925 11 2 1591 192 1 2 1 3 1 212 22 313 373 535 777 2.0 3.29 5.23 7.57 12.9 21.11 33.51 2.79 5.5 70.01 5.57.91 132.25 159.0 19.3 227.23 272. 325.70 393.7 0.07 0.093 0.113 0.13 0.175 0.25 0.32 0.31 0.07 0.1 0.5 0.575 0.5 0.720 0.75 0.0 0.91 1.029 1.132 www.nexansamercable.com e-mail: marine@nexansamercable.com 7
37-2 CIRVFDA ARCTIC GRADE CIR TYPE VFD POWER CABLE UL LISTED AS TYPE TC-ER & TYPE TC-ER-HL* Three Conductor Gexol Insulated 2kV Rated 90 C Power Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Insulation (2kV) Gexol cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 150 and Type X1 of UL 1309/CSA 25. Color: Gray with printed phase I.D. (Black- Red-Blue) Jacket A black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset CPE meeting UL 1309/CSA 25 and IEEE 150. CIR Ratings & Approvals Ground Conductors (x3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Gexol insulation sized per UL 1277. Color: Green Shield Overall tinned copper braid plus aluminum/polyester tape providing 0% coverage. Safer to Handle CIR has no sharp metal armor edges that imperil worker s hands during splicing and installation of connectors n 90 C temperature rating n UL Listed as Marine Shipboard Cable (E1111) n UL Listed as Type TC-ER n UL Listed as TC-ER-HL (cables up to 1 in diameter) n American Bureau of Shipping (ABS) n Flame Retardant IEEE 1202 n Suitable for use in Class I, Div 2 and Zone 2 environments n Suitable for Class 1, Div 1 and Zone 1 environments (cables less than 1 in OD) *Cables up to 1 in OD APPLICATION A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications. FEATURES Specially engineered cable design produces a longer cable life in VFD applications in severe cold environments. Exceeds CSA cold bend/cold impact (-0 C/-35 F) Brittlepoint as per ASTM D 7-07 exceeds -5 C for Jacket and -75 C for insulation Overall braid and foil shield provides 0% coverage containing VFD EMI emissions. Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive. High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable. Gexol s lower dielectric constant (standard XLPEs, EPRs and other Type P insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system. 2kV insulation thickness resists the repetitive 2x voltage spikes from 00V VFDs and reduces drive over current trip problems due to cable charging current. Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL Gas & vapor tight impervious to water and air Smaller bend radius (up to 0% smaller) than Type MC Considerably more flexible than Type MC Reduced installation time and cost compared to Type MC Glands cost up to 50% less Manufactured by Nexans AmerCable 00-50-973 713-9-500 Fax: 713-9-9009
TC-ER-HL Size Nominal Weight DC Resist. AC Resist. Inductive Voltage Drop Green Insulated IEEE NEC IEEE NEC AWG/ Part No. Diameter Per @ 25 C @ 90 C, 0 Hz Reactance @ 90 C Grounding Ampacity Ampacity Ampacity Ampacity kcmil 37-2 Inches* 00 Ft. (Ohms/1k ft) (Ohms/1k ft) (Ohms/1k ft) (Volts/Amp/1k ft) Size (AWG) 90 C 90 C 75 C 75 C 1-50CIRVFDA 0.72 23 2.907 3.35 0.00 5.073 1 2 15 20 15 12-51CIRVFDA 0.15 37 1.2 2.23 0.03 3.199 1 29 20 2 20-30CIRVFDA 0.71 73 1.153 1.1 0.03 2.032 1 3 30 32 30-309CIRVFDA 0.93 553 0.70 0.5 0.037 1.23 1 55 1 50-3CIRVFDA 1.093 797 0.5 0.55 0.033 0.0 12 5 75 5 5-312CIRVFDA 1.225 929 0.300 0.37 0.031 0.552 12 3 95 70 5 2-31CIRVFDA 1.31 127 0.1 0.230 0.029 0.3 111 130 93 115 1-315CIRVFDA 1.7 157 0.17 0.1 0.029 0.25 131 15 1 130 1/0-31CIRVFDA 1.5 21 0.117 0.17 0.029 0.23 150 170 12 150 2/0-317CIRVFDA 1.733 21 0.093 0.117 0.02 0.192 173 195 15 175 /0-319CIRVFDA 1.7 3131 0.05 0.075 0.027 0.132 232 20 19 230 22-320CIRVFDA 2.031 375 0.0 0.03 0.027 0.115 273 297 22 22 313-321CIRVFDA 2.130 709 0.00 0.053 0.02 0.0 29 32 29 292 373-322CIRVFDA 2.257 5209 0.03 0.05 0.025 0.0 332 3 277 322-323CIRVFDA 2.00 3 0.02 0.039 0.025 0.00 32 02 319 355 535-32CIRVFDA 2.705 7193 0.02 0.033 0.02 0.072 07 30 39-32CIRVFDA 2.9 9217 0.020 0.02 0.02 0.05 7 9 39 3 777-327CIRVFDA 3.2 30 0.01 0.025 0.025 0.00 51 5 31 3 *Cable diameters are subject to a +/- 5% manufacturing tolerance Ampacities are based on Table 3.15 (B) (1) of the National Electrical Code (NEC) for conductors rated 90 C, in a multi-conductor cable, at an ambient temperature of 30 C. The 75 C column is provided for additional information. The ampacities shown apply to open runs of cable, installation in any approved raceway. Derating for more than three current carrying conductors within the cable is in accordance with NEC Table 3.15 (B) (3) (a). The ampacities shown also apply to cables installed in cable tray in accordance with NEC Section 392.0. Gexol and CIR are registered trademarks of AmerCable Incorporated See Page 7 for Stranding Profile www.nexansamercable.com e-mail: marine@nexansamercable.com 9
37-5VFD MARINE MEDIUM VOLTAGE MMV-VFD POWER CABLE Three Conductor: kv 15kV % Insulation Level Rated 90 C Conductors (3) Soft annealed flexible stranded tinned copper per IEEE 150 Table 11. Insulation Extruded thermosetting 90 C Ethylene Propylene Rubber (EPR), meeting UL 1309 (Type E), IEEE 150 (Type E) and UL 72. Insulation Shield Composite shield consisting of 0.012" tinned copper braided with nylon providing 0% copper Shielded coverage meeting UL 1309, IEEE Std. 150, and UL 72. The nylon is colored for easy phase identification (three conductor = black, blue, red) without the need to remove the shield to find an underlying colored tape. Low smoke halogen-free jacket available on request. Conductor Shield A combination of semi-conducting tape and extruded thermosetting semi-conducting material meeting UL 1309, IEEE 150 and UL72. Insulation Shield Semi-conducting layer meeting UL 1309, IEEE 150 and UL 72. Symmetrical Insulated Grounding Conductors (3) Soft annealed flexible stranded tinned copper conductor per IEEE 150 Table 11. Gexol Insulation sized per Table 23.2 of UL72. Color: Green Jacket A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/ CSA 25, IEEE 150, and UL 72. This jacket allows for isolation between the insulation shields and overall shield. Shields can then be terminated on opposite ends to minimize circulating currents. Armor/EMI Shield Overall tinned copper braid plus aluminum/ polyester tape provides 0% coverage. This braid serves as both an armor and EMI shield meeting both IEEE 150 and UL 1307/CSA 25. Sheath (optional) A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 25, IEEE 150, and UL 72. Colored jackets for signifying different voltage levels are also available on special request (orange = kv and red = 15kV). Ratings & Approvals n UL Listed as Marine Shipboard Cable (E1111) n American Bureau of Shipping (ABS) n Det Norske Veritas (DNV) Pending n Lloyd s Register of Shipping (LRS) Pending n 90 C Temperature Rating n Voltage Rating kv to 15kV (25kV available on request) APPLICATIONS A flexible, braid and foil shielded, power cable specifically engineered for use in medium voltage variable frequency AC drive (VFD) applications. FEATURES n Flexible stranded conductors and braided shields. Suitable for applications involving repeated flexing and high vibration. n Small minimum bending radius (x OD) for easy installation. n Insulation has a very low dielectric constant. This allows for longer output cable distances and minimizes common mode current. n Overall braid plus foil shield is engineered with 0% coverage and a surface transfer impedance <50 milliohms at MHz to contain EMI. n Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive. n High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable. n Severe cold durability: exceeds CSA cold bend/cold impact (-0 C/-35 C). n Flame retardant: IEC 332-3 Category A and IEEE 1202. n Suitable for use in Class I, Division 1, and Zone 1 environments. Manufactured by Nexans AmerCable 00-50-973 713-9-500 Fax: 713-9-9009
THREE CONDUCTOR TYPE MMV-VFD MARINE MEDIUM VOLTAGE KV % INSULATION LEVEL Single Inductive Voltage Green Insulated Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop Grounding AWG/ Part No. Diameter (Lbs./ Air in Trays at 25 C at 90 C, 0Hz (Ohms/ (Volts/Amp/ Conductor (3x) kcmil mm2 37-5 (Inches) 00 Ft.) (Amps) (Amps) (Ohms/00 Ft.) (Ohms/00 Ft.) 00 Ft.) 00 Ft.) Size (AWG) 2 1 1/0 2/0 3/0 /0 22 313 373 535 12.5 21 3 3 5 70 9 132 159 19 227 273-332TSVFD -333TSVFD -33TSVFD -335TSVFD -33TSVFD -337TSVFD -33TSVFD -339TSVFD -30TSVFD -31TSVFD -32TSVFD -33TSVFD -3TSVFD 1.7 1. 2.071 2.11 2.22 2.31 2.9 2.31 3.57 3.030 3.1 3.319 3.92 13 207 225 3022 3373 32 11 5093 5993 7 7 55 9905 Ampacity 11 152 175 201 232 2 30 3 3 29 55 52 75 99 129 19 171 197 22 20 29 32 35 37 9 0.5 0.300 0.1 0.17 0.117 0.093 0.07 0.05 0.0 0.00 0.03 0.02 0.02 0.55 0.37 0.230 0.1 0.17 0.117 0.09 0.075 0.03 0.053 0.05 0.039 0.033 0.0 0.03 0.00 0.03 0.037 0.03 0.035 0.033 0.032 0.032 0.031 0.030 0.030 0.20 0.5 0.359 0.29 0.22 0.199 0.1 0.139 0.121 0. 0.09 0.05 0.07 THREE CONDUCTOR TYPE MMV-VFD MARINE MEDIUM VOLTAGE 15KV % INSULATION LEVEL Ampacity Single Inductive Voltage Green Insulated Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop Grounding AWG/ Part No. Diameter (Lbs./ Air in Trays at 25 C at 90 C, 0Hz (Ohms/ (Volts/Amp/ Conductor (3x) kcmil mm2 37-5 (Inches) 00 Ft.) (Amps) (Amps) (Ohms/00 Ft.) (Ohms/00 Ft.) 00 Ft.) 00 Ft.) Size (AWG) 2 1 1/0 2/0 3/0 /0 22 313 373 3 3 5 70 9 132 159 19 227-357TSVFD -35TSVFD -359TSVFD -30TSVFD -31TSVFD -32TSVFD -33TSVFD -3TSVFD -35TSVFD -3TSVFD 2.03 2. 2.59 2.71 2.75 3.02 3.20 3.33 3.500 3.52 3231 2959 090 15 530 131 707 777 703 9912 15 17 205 23 29 309 352 39 32 5 151 17 199 229 23 299 331 37 3 0.1 0.17 0.117 0.093 0.07 0.05 0.0 0.00 0.03 0.02 0.230 0.1 0.17 0.117 0.09 0.075 0.03 0.053 0.05 0.039 0.00. 030.01 0.0390. 03 0.037 0.035 0.03 0.03 0.033 0.3 0.299 0.2 0.203 0.170 0.12 0.12 0.9 0.097 0.00 MMV-VFD Stranding Profile: See Page 12 Ordering Type MMV-VFD Medium Voltage Cables Example: 3 conductor MMV-VFD power cable 15kV #2 AWG 37 5 357TSVFD AmerCable Type MMV-VFD Prefix Specific Cable Number (from charts) www.nexansamercable.com e-mail: marine@nexansamercable.com 11
MMV-VFD Power Cable MMV-VFD Stranding Profile Size Number Closest Equivalent Uninsulated AWG/ of IEEE 5 Metric Size Conductor kcmil Strands Std. Size (mm2) Dia. (inches) 2 1 1/0 2/0 3/0 /0 22 313 373 535 1 209 2 32 1 532 777 925 11 2 2 1 3 1 212 22 313 373 535 12.9 21.11 33.51 2.79 5.5 70.01 5.57.91 132.25 159.0 19.3 227.23 272. 0.175 0.25 0.32 0.31 0.07 0.1 0.5 0.575 0.5 0.720 0.75 0.0 0.91 Hawke Gland Types Industrial & Safe Area (IP) 153-X Increased Safety 501/53/U Explosion Proof 753 Class I, Div. 1 Class I, Zone 1 & 2 Flameproof 501/53/U (2 liter or < enclosures) EExd ICG 53/U (2 liter or > enclosures) Zone 1 & 2 MMV-VFD Bend Radius IEEE 5 IEC 0092-352 X Diameter 9X Diameter MMV-VFD Ampacities& Electrical Data Ampacities are based on API RP 1F (July 200) Table 3 for multi-conductor cables. The notes to these tables are also applicable. Ampacities are also based on a 90 C conductor temperature and a 5 C ambient temperature. Inductive reactance and voltage drop values are based on a 90 C conductor temperature and 0 Hz operation. Cable Selection Guide for VFD Applications The circuit of a typical voltage source PWM drive is shown in Figure 1. Each part of the equipment is bonded to the safety earth system to ensure personnel safety if faults occur. All parts have capacitance to ground shown by: CM for the motor windings. CC1 and CC2 for the power converter circuits. CT for the transformer s secondary winding to the transformers screen. The IGBT switches are in constant operation at high frequency and this produces an inverter output voltage with a PWM wave shape as shown by the voltage V1(Figure 1). This IGBT switches also cause a motor line to ground voltage V2 (Figure 1), normally called a common mode voltage. The common mode voltages cause short high-frequency pulses of common mode current to flowin the safety earth circuits, shown by currents I1 and I2 Figure 1), unless the design includes cable features to stop this from happening. It is essential that the common mode currents return to the inverter without causing EMC - EMI problems in other equipment, and this means that the common mode currents I1 and I2 must not flow in the safety earthing system. For the motor, this is achieved by connecting a set of wires from the motor to the inverter that run with the main power cables. These are called symmetrical insulated grounding conductors, see Figure 2. These conductors have a very low impedance compared with the other return path via the safety earthing system. The three symmetrical insulated grounding conductors and overall shields are connected as shown in Figure 3. This 30 connection is essential. The common mode currents I1 and I2 now flow in the symmetrical insulated grounding conductors. This happens because the symmetrical insulated grounding conductors are close to the power conductors giving a low impedance route for the currents I1 and I2 compared with the safety earthing system. 12
Transformer Shield Earth Bond CT Inverter Line to Line Voltage V1 l2 Power Converter Diodes IGBT Switches CC1 Earth Bond Safety Earth System Motor Ground Current I1 CC2 As I1 and I2 flow near the power conductors this avoids creating external EMC - EMI problems. l1 V1 V2 Motor CM Earth Bond Motor Line to Ground Voltage V2 If symmetrical insulated grounding conductors and an overall EMI shield are not used, EMC - EMI problems are very likely to occur. For cables used with voltage source PWM drives, a number of features are required to ensure correct operation, avoid overheating and achieve longer service life. The essential features of a medium Power Converter Grounding Conductors voltage cable for PWM drives are: Insulation designed to withstand the transients produced by the PWM Insulation with a dielectric constant no greater than 3.0 to minimize capacitance Voltage rating of 3x the operating voltage to prevent corona Three symmetrical insulated grounding conductors. Some cables only have one grounding conductor. This is not acceptable as it produces circulating currents in the earth system Extremely fine strands to carry the harmonic currents without overheating (i.e. the inductance of fine stranded conductors is less than 7, 19, 37 strand conductors) Overall shield to stop the radiation of voltage EMI fields Correct termination at both ends Semi-conducting shield around each insulation layer Metallic layer around each semiconducting shield to earth the semi-conducting shield Transformer Motor Inverter Shield CT l2 CC1 CC2 l1 CM Earth Bond Earth Bond Safety Earth System F I G U R E 2 Earth Bond Figures 1-3 courtesy of Converteam F I G U R E 3 13
VFD Cables Nexans AmerCable is an ISO 9001 certified cable manufacturer that combines leading-edge manufacturing technology, innovative thinking, and high quality service to deliver the finest VFD cable products available. Nexans AmerCable s professional field engineers and sales force work with you to create innovative, cost effective project solutions. Nexans AmerCable s manufacturing facility in El Dorado, Arkansas. WHAT CAN YOU EXPECT FROM NEXANS AMERCABLE? n Shortest Lead Times in the Industry n Best at On-Time Delivery n Professional Sales, Support and Service n Global Cable Management The industry standard for flexible, high performance marine cables. Precision engineered cable assemblies for hazardous and industrial applications. Crush and Impact Resistant without external armoring. Type MC-HL Cables Top Drive Service Loops Low smoke halogen-free fire resistant or flame retardant marine cables. 33 West Little York Building #1 Suite #150 Houston, TX 7701 00-50-973 713-9-500 Fax: 713-9-9009 e-mail: marine@nexansamercable.com www.nexansamercable.com 201, AmerCable Incorporated _1