Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model RFT9739 Transmitters

Similar documents
Installation Instructions P/N MMI , Rev. AA July ATEX Installation Instructions for Micro Motion Model 3500 Transmitters

ATEX Installation Instructions for Micro Motion CMF400 Sensors with Booster Amplifier

ATEX Installation Drawings and Instructions

Micro Motion Model 5700 Transmitter IECEx Zone 2/22 Installation Instructions EPL Gc and EPL Dc

Micro Motion Model 5700 Transmitter ATEX Zone 2/22 Installation Instructions II 3 G or II 3 (2) G/EPL Gc & II 3 D/EPL Dc

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Micro Motion Specific Gravity Meters (SGM)

Micro Motion Model RFT9739

Micro Motion Specific Gravity Meters (SGM)

2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

Micro Motion Model RFT9739 Flow and Density Transmitter

Mass and Volume Flow Transmitter

Power supply. Calibration. Surface finishing. Seal. Process connection

INSTRUCTION MANUAL (ATEX / IECEx)

Micro Motion Compact Density Meter (CDM)

DPharp Differential Pressure and Pressure Transmitters

Installation guide 873 SmartRadar Control Unit & Antenna Unit

Mass Flow and Density Transmitter

Model RFT9709 Transmitter Instruction Manual

Installation guide 971 SmartRadar LTi

Installation guide 877 FDI Field Display & Interface

User's Manual Model SE14 Magnetic Flow Converter

Micro Motion Compact Density Meters

IP26 Series Current to Pneumatic Converter

Installation guide 970 SmartRadar ATi

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

Series 1000 and 2000 Transmitters with MVD TM Technology

Installation guide 970, 971 and 973 series SmartRadar

Description. Annexe to: IECEx CML X Issue 1. Isolating Amplifier D461

SET Installation and Operating Instructions. Level switch for two sensors

Rosemount 148 Temperature Transmitter

Micro Motion LF-Series Low Flow Sensor and Transmitter

Rosemount 5408 and 5408:SIS Level Transmitters

New! Micro Motion CNG050 Compressed Natural Gas Mass Flowmeter with MVD Technology. Product Data Sheet PS EU February 2001

Attachment to Certificate IECEx PTB X

D1035S INSTRUCTION MANUAL. Frequency-Pulse Isolating Repeater DIN Rail Model D1035S. D Frequency-Pulse Isolating Repeater

Installation guide 854 XTG Level Gauge

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

User's Manual. ROTAMASS Total Insight Coriolis Mass Flow and Density Meter Explosion Proof Type Manual IECEx IM 01U10X02-00EN-R

Ex instruction manual. Rotamass Coriolis mass flow meter. IECEx. IM 01U10X02-00EN-R_002, 2nd edition,

Alphaline Temperature Transmitters

ProcessMaster / HygienicMaster

Micro Motion Model 1500 Transmitter with the Filling and Dosing Application

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Ex instruction manual. Rotamass Coriolis mass flow meter ATEX. IM 01U10X01-00EN-R_002, 2nd edition,

Annex 1 to Certificate of Conformity IECEx KEM X Issue No. 8 Rota Yokogawa Rotamass 3 Series Coriolis Mass Flowmeter

Micro Motion Model 2400S Transmitters with MVD Technology

Specifications. Specifications. Transfer Characteristics Accuracy at 20 C (68 F) Temperature Drift

Expert 1400 / Expert 3400 Submersible Hydrostatic Level Transmitters

IECEx Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

Mid-West. Instrument. Model 140 Electrical Installation and Operating Instructions. Gauge Front ELECTRICAL

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

Rosemount 5400 Series Radar Level Transmitter

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

Proline Promass 40. Safety Instructions. NEPSI Zone 1, Zone 21

D1061S INSTRUCTION MANUAL. RS422/RS485 Fieldbus Isolating Repeater Din-Rail Model D1061S. D RS422 / RS485 Fieldbus Isolating Repeater

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6005 Series Remote Mount Digital Valve Controllers

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Model 144H NEW. PC-Programmable Temperature Transmitter. Product Data Sheet

INSTRUCTION MANUAL. SIL 3 - SIL 2 Digital Output Loop/Bus Powered DIN-Rail Models D1040Q, D1041Q, D1042Q, D1043Q, D1040Q - D1041Q - D1042Q - D1043Q

CSA Hazardous Area Approvals Fisher FIELDVUE DVC6200 Series Digital Valve Controllers

Micro Motion Series 1000 and 2000 Transmitters

FLEX Ex Power Supplies

Micro Motion LF-Series Low Flow Flowmeter

Positioner with HART Communication Type 3780

GS.No.GBN062E-5. GENERAL SPECIFICATIONS Sensor unit

... for hydraulic and general applications in hazardous areas

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

} Max. Load Resistance : 750Ω when power supply voltage is 24V DC (Max. load resistance (Ω) = 50x Power Supply Voltage -450 ).

R88000 T (including ATEX)

Rosemount 148 Temperature Transmitter

Rosemount 148 Temperature Transmitter

[ Rosemount 648 Wireless Temperature Transmitter. Rosemount 648 Wireless. Quick Installation Guide , Rev CA August 2011

CERTIFICATE OF COMPLIANCE

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

INSTALLATION AND OPERATION MANUAL

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

Certificate of Compliance

Micro Motion Fork Viscosity Meters

Mass Flow and Density Transmitter with FOUNDATION fieldbus

Magnetic Inductive Flowmeter

Rosemount 5600 Series Radar Level Transmitter with HART and Foundation fieldbus protocol

Sarasota CM200 Sarasota HME900 Density Converter Electronics

Rosemount 3101, 3102, and 3105

Safety Instructions Proline Promag 500

A9000Px Power/Signal Adapter Installation Drawing for Emerson Transmitters

Resistance Thermometers Model Series TR7X0, Sheathed Design

Rosemount 148 Temperature Transmitter

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

User s Manual. Manual Change No V-E. Please use the attached sheets for the pages listed below in IM 01F06F00-01EN (7th).

Universal Intelligent 2-wire DIN Rail Transmitters

FLEX Ex V ac In/Quad-Ex dc Out Power Supply

SALES SERVICE +358 (0)

SINEAX / EURAX 2I1 Passive DC signal isolator

Safety Instructions Proline Promass 300

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the Soliwave M microwave barrier

The T6000 Series Electro-Pneumatic Transducer converts a DC current or voltage input signal to a directly proportional pneumatic output.

Liquid Level Sensors. M-Series Magnetostrictive Sensors

Transcription:

Installation Instructions P/N MMI-20011709, Rev. AA July 2009 ATEX Installation Instructions for Micro Motion Model RFT9739 Transmitters

Note: For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply. Information affixed to equipment that complies with the Pressure Equipment Directive can be found on the internet at www.micromotion.com/library. If you require the information given in this manual in a different language, please contact Micro Motion Customer Service. 2009, Micro Motion, Inc. All rights reserved. ELITE and ProLink are registered trademarks, and MVD and MVD Direct Connect are trademarks of Micro Motion, Inc., Boulder, Colorado. Micro Motion is a registered trade name of Micro Motion, Inc., Boulder, Colorado. The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co. All other trademarks are property of their respective owners. Reference no. EB-3007099 Rev. D

ATEX Drawings and Installation Instructions For installing the following Micro Motion transmitters with 9-wire connections: - Model RFT9739R - Model RFT9739D/E Subject: Equipment type Transmitter type RFT9739**E**** Manufactured and submitted for examination Address Micro Motion, Inc. Boulder, Co. 80301, USA Standard basis EN 50014:1997 +A1-A2 General requirements EN 50018:2000 EN 50020:1994 Flameproof enclosure d Intrinsic safety i Code for type of protection EEx d [ib] IIC T6 [EEx ib] IIC EC Type Examination Certificate DMT 02 ATEX E 051 X ATEX Installation Instructions 1

1) Subject and type Transmitter type RFT9739**E**** The options denoted by * are as follows: R F T 9 7 3 9 * * E * * * * Letter for factory options Language Letter for conduit connections Approval Y = ATEX intrinsically safe sensor outputs W = ATEX intrinsically safe sensor outputs flameproof transmitter (only for RFT9739E) Power rating 1 = 110/115 VAC (only for RFT9739R) 2 = 220/230 VAC (only for RFT9739R) 3 = 12 30 VCD (only for RFT9739R) 4 = 85 250 VAC (only for RFT9739D and E) 5 = 12 30 VCD (only for RFT9739D and E) Type D = Field-mount transmitter with display E = Field-mount transmitter without display R = Rack-mount transmitter 2) Description The transmitter is, in combination with a sensor, used for measurement of mass flow and data transmission. The electrical circuitry of the transmitters is mounted inside a flameproof metal enclosure type RFT9739E. The RFT9739D and RFT9739R are not flameproof enclosures. 2 ATEX Installation Instructions

3) Parameters 3.1) Mains circuit (See document EB-3007165 or EB-3008013 for terminals) Voltage AC/DC 12 250 V Max. voltage Um AC/DC 250 V 3.2) Intrinsically safe circuits type of protection EEx ib IIC / EEx ib IIB The circuits designed for connecting sensors are classified initially in Group IIC. However, when certain sensors are connected, they can also be assigned to Group IIB. Drive circuit (1) Pick-off circuits (1) Temperature circuit (1) Voltage Umax 11,4 Vdc 7,6 Vdc 14 Vdc Current Imax 1,14 A 4,75 ma 7 ma Power Pmax 1,2 W 18 mw 25 mw Internal resistance RI 10 Ω Nominal fuse 250 ma Group IIC IIB IIC IIB IIC IIB Max. external inductance Lo 27,4 μh 109 μh 1,5 H 6,3 H 725 mh 2,9 H Max. external capacitance Co 1,7 μf 11,7 μf 10,4 μf 160 μf 0,73 μf 4,6 μf Max. inductance/resistance ratio Lo/Ro 10,9 μh/ω 43,7 μh/ω (1) See document EB-3007165 or EB-3008013 for terminals. For drive circuit terminals, the maximum external inductance L (sensor coil) can be calcualted with the following term: Ri + Ro L = 2 E --------------------- 1,5 Uo 2 Where: E = 40 μj for group IIC and E = 160 μj for group IIB Ro = Total resistance (coil resistance + series resistance) 3.3) Ambient temperature range RFT9739R*E**** Ta 20 C to +55 C RFT9739(D or E)*E**** Ta 30 C to +45 C or Ta 40 C to +45 C (routine test required, only for RFT9739E*EW***) ATEX Installation Instructions 3

4) Marking II 2 G or II (2) G 20 C Ta +55 C for RFT9739R 30 C Ta +45 C for RFT9739(D or E)*E**** or 40 C Ta +45 C (routine test required, only for RFT9739E*EW***) - type - type of protection RFT9739E*EW*** EEx d[ib] IIC T6 RFT9739E*EY*** [EEx ib] IIC RFT9739D*EY*** [EEx ib] IIC RFT9739R*EY*** [EEx ib] IIC 5) Special conditions for safe use / Installation instructions for RFT9739E*EW***. 5.1) For the application of the transmitter in an ambient temperature of less than 20 C suitable and entries or conduit entries certified for this condition shall be used 5.2) If certified conduit entries are used for the connection of the transmitter enclosure, the associated stopping boxes shall be installed immediately at the enclosure. 5.3) The transmitter shall only be installed within the intended hazardous area if metal entries (with 3/4" 14 NPT threading) are used which are classified as EEx d IIC and are for enclosures with >2dm 3 and are certified by an authorized test station. 5.4) Entry holes which are not being used must be sealed with blanking plugs and which are classified as EEx d IIC and are certified by an authorized test station. 5.5) For installation outside the hazardous area, it is allowed to use entry fittings that are not flameproof. 5.6) To achieve potential equalization, the conductor for the transmitter grounding terminal must be connected to the appropriate grounding terminal inside the hazardous area using a potential equalizing line. 5.7) The non-intrinsically safe end of the transmitter must only be connected to devices where there are no voltages higher than 250V. 5.8) After de-energizing the flameproof RFT9739, delay 5 minutes before opening the cover. 6) Special conditions for safe use / Installation instructions for RFT9739(R or D or E)*EY***. 6.1) The transmitter must be installed outside the hazardous area in such a way that it meets a degree of protection of at least IP20 according to EN60529. 6.2) To achieve potential equalization, the conductor for the transmitter grounding terminal must be connected to the appropriate grounding terminal inside the hazardous area using a potential equalizing line 6.3) The non-intrinsically safe end of the transmitter must only be connected to devices where there are no voltages higher than 250V. 4 ATEX Installation Instructions

Model RFT9739 installation drawings Figure 1: Rack Mount Model RFT9739R transmitter to sensor with junction box COMBINE TH DRAWING WITH ONE OF FIGURE 3, 4, OR 5 Voltage label Equipment ground barrier ground For installation in safe area: [EEx ib] IIB / IIC AC + AC 100/115 220/230 12 30 VAC VAC VDC L L1 N L2 Model RFT9739R in safe area GND DC DC + CN2-D32 CN2-Z32 Non-intrinsically safe outputs Red B2 Yellow B4 Orange B6 White B8 Gray B10 Z2 Brown Z4 Black Z6 Violet Z8 Green Z10 Blue Special conditions for safe use/installation instructions for RFT9739R The transmitter must be installed outside the hazardous area to meet at least IP20 requirements according to IEC529. To achieve potential equalization, the conductor for the transmitter grounding terminal must be connected to the appropriate grounding terminal inside the hazardous area using a potential equalizing line. The non-intrinsically safe end of the transmitter must not connect to devices with voltages higher than 250V. B32 Z32 Intrinsically safe outputs 9-wire 300m maximum length Reference no. EB-20001047 Rev. D ATEX Installation Instructions 5

Figure 2: Field Mount Model RFT9739D or RFT9739E to sensor with junction box COMBINE TH DRAWING WITH ONE OF FIGURE 3, 4, OR 5 Without module installed Equipment ground barrier ground The non-intrinsically safe end of the transmitter must not connect to devices with voltages higher than 250V. Equipment ground White Violet Green Orange Brown Intrinsically safe terminals Module removed from housing External equipment ground To achieve potential equalization, the conductor for the transmitter grounding terminal must be connected to the appropriate grounding terminal inside the hazardous area using a potential equalization line. 85 250 VAC 50/60 HZ L N 12 30 VDC + CAUTION: Power supply voltage must agree with the voltage stated. For installation in Hazardous Area EExd [ib] IIC T6 Note: Prepare per RFT9739 transmitter prep instructions provided with the sensor Gray Blue Yellow Red Black 9-wire (RFT9739E with flameproof glands) When ambient temperature is less than 20 o C, and entries or conduit entries certified for this condition shall be used. To prevent ignition of hazardous atmospheres, disconnect from supply circuit before opening enclosure. Keep tightly closed when circuits are alive. If certified conduit entries are used, the associated stopping boxes shall be installed immediately at the transmitter enclosure. The transmitter shall only be installed within the intended hazardous area if metal entries (with 3/4" NPT threading) are used and are for enclosures with > 2dm 3 which are classified as EEx d II C and are certified by an authorized test station. Unused entry holes must be sealed with blanking plugs that are classified as EEx d II C and certified by an authorized test station. POWER NON- OR MODEL RFT9739 POWER NON- MODEL RFT9739 For installation in Safe Area [EEx ib] IIC (RFT9739D without flameproof glands) (RFT9739E without flameproof glands) For installation outside the hazardous area, entry fittings that are not flameproof are allowed. Reference no. EB-20001046 Rev. E 6 ATEX Installation Instructions

Figure 3: CMF, D (except D600), DL, F, H, and T sensor with junction box COMBINE TH DRAWING WITH ONE OF FIGURE 1 OR 2 Hazardous Area EEx ib IIB / IIC Hazardous Area EEx ib IIB / IIC Refer to sensor tag for complete hazardous area classification 20 m. maximum length 9-wire Refer to sensor tag for complete hazardous area classification 9-wire 20 m. maximum length Sensor junction box Chassis ground Violet Yellow Orange Green White Brown Blue Gray Red Chassis ground Sensor junction box Brn Red Orn Yel Grn Blu Vio Gry Wht Model CMF T F H Supplied as intrinsically safe Model D, DL (EXCEPT D600) Supplied as intrinsically safe Reference no. EB-20001074 Rev. D Figure 4: D600 with junction box COMBINE TH DRAWING WITH ONE OF FIGURE 1 OR 2 Hazardous Area EExde [ib] IIB Installation method Conduit Cable Fitting required EEx d IIB conduit seal EEx d IIB gland Per EN60079 14 Conduit or EEx e increased safety Cable O.D. must be suitably sized to gland. Conduit seal required within 18" of enclosure. To be sealed after wiring (customer supplied). 1/2 14 NPT or M20 1.5 adapter supplied as ordered VAC For remote mount booster amplifier wiring refer to EB-3007062. Power Ground chassis To drive coil located in sensor Violet Yellow Orange 20 m maximum length Intrinsically safe terminals Green White Brown CAUTION: To maintain intrinsic safety, the intrinsically safe wiring must be installed according to EN 60079-14. Transmitter and sensor must be properly grounded. Blue Gray Red Micro Motion mass flowmeter system connection for intrinsically safe operation To achieve potential equalization the ground terminal must be connected to the appropriate ground terminal within the hazardous area using a potential equalizing line. Reference no. EB-20000849 Rev. B ATEX Installation Instructions 7

Figure 5: DT with junction box COMBINE TH DRAWING WITH ONE OF FIGURE 1 OR 2 Hazardous Area EEx ib IIb Special conditions for safe use: For the sensor types DT065, DT100, and DT150 the following applies: The minimum medium temperature is +32 C. 20 m maximum length 9-wire DT sensor wires must be connected to using customer supplied terminal block and junction box. Earth ground DT sensor wires DT sensor wire terminations to DT sensor wire # color 1 Brown 2 Red 3 Orange 4 Yellow 5 Green 6 Blue 7 Violet 8 Gray 9 White Models: DT65, DT100, DT150 Micro Motion mass flowmeter system connection for intrinsically safe operation Reference no. EB-20000799 Rev. B 8 ATEX Installation Instructions

2009, Micro Motion, Inc. All rights reserved. P/N MMI-20011709, Rev. AA *MMI-20011709* For the latest Micro Motion product specifications, view the PRODUCTS section of our web site at www.micromotion.com Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado 80301 T +1 303-527-5200 +1 800-522-6277 F +1 303-530-8459 Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556 Micro Motion United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181 Micro Motion Asia Emerson Process Management 1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6777-8211 F +65 6770-8003 Micro Motion Japan Emerson Process Management 1-2-5, Higashi Shinagawa Shinagawa-ku Tokyo 140-0002 Japan T +81 3 5769-6803 F +81 3 5769-6844