Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator

Similar documents
Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

A Software Tool for Real-Time Prediction of Potential Transient Instabilities using Synchrophasors

Phasor Measurement Unit (PMU) Performance Test Report for TESLA 4000

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System

Critical analysis of PMU testing procedures for step response evaluation

Phasor Measurement Unit and Phasor Data Concentrator test with Real Time Digital Simulator

Dynamic PMU Compliance Test under C aTM-2014

Comparative Testing of Synchronized Phasor Measurement Units

Synchrophasors: Definition, Measurement, and Application

Engineering Thesis. The use of Synchronized Phasor Measurement to Determine Power System Stability, Transmission Line Parameters and Fault Location

New Standards for Test and Calibration of Phasor Measurement Units

Automated Testing Of PMU Compliance

Phasor Measurement Unit Testing

PMU Implementation Issues

Enhanced DFT Algorithm for Estimation of Phasor by PMU under Power Quality Events

Synchrometrology and PMU Testing at NIST

MANY protective relaying functions use the phasors

CONVERT ERLPhase TESLA DMEs TO PHASOR MEASUREMENT UNITS (PMUs)

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Estimation of the Short Circuit Ratio and the Optimal Controller Gains Selection of a VSC System

A Hybrid Method for Power System Frequency Estimation Jinfeng Ren, Student Member, IEEE, and Mladen Kezunovic, Fellow, IEEE

Sub/super-synchronous harmonics measurement method based on PMUs

Algorithms for the synchrophasor measurement in steady-state and dynamic conditions

Testing and Validation of Synchrophasor Devices and Applications

Measurement tools at heart of Smart Grid need calibration to ensure reliability

Development of DFT Based MATLAB and LABVIEW Models for Phasor Measurements

Characterizing dynamic behavior of PMUs using step signals z

Modelling of Phasor Measurement Unit and Phasor Data Realisation with 2 Bus System

6135A/PMUCAL Phasor Measurement Unit Calibration System

PHASOR MEASUREMENT UNIT: - A Revolution in Power System

FREQUENCY TRACKED PHASOR ESTIMATION ALGORITHM FOR PMU DURING OFF-NOMINAL FREQUENCY VARIATIONS

Steady-State PMU Compliance Test under C a-2014

A Novel Adaptive Algorithm for

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying

Traceable Synchrophasors

Evaluation of Steady-State and Dynamic Performance of a Synchronized Phasor Measurement Unit

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

A P + M Phasor Measurement Unit

A Novel Detection and Classification Algorithm for Power Quality Disturbances using Wavelets

Synchronized Phasor Measurement in Protective Relays for Protection, Control, and Analysis of Electric Power Systems

NOWADAYS, there is much interest in connecting various

The Virginia Tech Calibration System

PRECISE SYNCHRONIZATION OF PHASOR MEASUREMENTS IN ELECTRIC POWER SYSTEMS

Jean-Pierre Braun obtained the B.E. degree from the Ecole d'ingénieurs de Genève, Switzerland, in 1980; the M.E.M. degree from the University of

The Effect of Delays on Wide-Area Damping Control of Electromechanical Oscillations

Test Suite Specification

Application of a MW-Scale Motor-Generator Set to Establish Power-Hardware-in-the-Loop Capability

Dynamic Phasors for Small Signal Stability Analysis

Florida State University Libraries

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Phasor Measurement: A Short History of the Technology and the Standards. Harold Kirkham Pacific Northwest National Laboratory

Implementation and Evaluation of a Labscale Synchrophasor Model and Applications

SYNCHRONIZED PHASOR MEASUREMENT TECHNIQUES. A.G. Phadke

PMU (algorithm) Testing to C (a) in software. Dr. Andrew Roscoe

Experiences with Steady-State PMU Compliance Testing using Standard Relay Testing Equipment. In:

Performance Evaluation and Operation of PMUs in Power System

FOURIER analysis is a well-known method for nonparametric

A New Fault Locator for Three-Terminal Transmission Lines Using Two-Terminal Synchronized Voltage and Current Phasors

Use of Synchronized Phasor Measurements for Model Validation in ERCOT

1392 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

Lavopa, Elisabetta (2011) A novel control technique for active shunt power filters for aircraft applications. PhD thesis, University of Nottingham.

THE core component of a phasor measurement unit (PMU)

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Integration of Phase-Locked Loop Based Real-time Oscillation Tracking in Grid Synchronized Systems

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

Wide Area Monitoring with Phasor Measurement Data

Distance Relay Response to Transformer Energization: Problems and Solutions

Verifying Interoperability and Application Performance of PMUs and PMU-Enabled IEDs at the Device and System Level

A Faster Method for Accurate Spectral Testing without Requiring Coherent Sampling

Synchrophasors for Distribution Applications

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

Development of Dynamic Test Cases in OPAL-RT Real-time Power System Simulator

Direct Harmonic Analysis of the Voltage Source Converter

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

THE basic frequency is an important operating parameter

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

METHODS TO IMPROVE DYNAMIC RESPONSE OF POWER FACTOR PREREGULATORS: AN OVERVIEW

A New Control Method for the Power Interface in Power Hardware-in-the-Loop Simulation to Compensate for the Time Delay.

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

Prepared by Tony Weekes Husam Al Hadidi Brian Archer

Testing and Calibration of Phasor Measurement Units

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

Practical PMU Applications for Utilities

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

POWER SYSTEM BACKUP PROTECTION USING SYNCHRONIZED PMU

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Spoofing GPS Receiver Clock Offset of Phasor Measurement Units 1

Performance Analysis of Matrix Converter Fed Induction Motor with Different Switching Algorithms

Employment of Interpolated DFT-based PMU Algorithms in Three-Phase Systems

Introduction to Phase Noise

Adaptive-window PMU algorithms using cascaded boxcar filters to meet and exceed C (a) requirements. Dr. Andrew Roscoe

Stability Issues of Smart Grid Transmission Line Switching

Algorithms to Improve Performance of Wide Area Measurement Systems of Electric Power Systems

PMU-based Voltage Instability Detection through Linear Regression

PMU based Wide Area Voltage Control of Smart Grid: A Real Time Implementation Approach

Synchrophasors and the Smarter Grid

Protective Relay Synchrophasor Measurements During Fault Conditions

Transcription:

Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Dinesh Rangana Gurusinghe, Dean Ouellette, and Athula D. Rajapakse Abstract-- Many commercial phasor measurement units (PMUs extract phasors using the standard discrete Fourier transform (DFT that has some inherent drawbacks such as leakage and picket fence effects. The standard DFT based PMUs employ additional filtering to overcome these effects, but the smart DFT ( algorithm is capable achieving the required accuracy with minimum or no additional filtering. The benefits of can outweigh the additional computational complexity in real-time implementation. This paper investigates the implementation of a based PMU model in a real-time simulator. Various aspects relevant to real-time implementation such as data sampling, time synchronization, and measurement streaming according to C37.118 format are addressed. Performances of the developed PMU model are evaluated according to the latest IEEE synchrophasor standard and compared with the reference M-class algorithm [1]. Keywords: Discrete Fourier Transform (DFT, Smart DFT, Phasor Estimation, Phasor Measurement Unit, Real-time Digital Simulator. P I. INTRODUCTION HASOR measurement unit (PMU is the core component in synchrophasor based wide area monitoring, protection and control (WAMPaC systems. PMUs provide phasor values of the voltage and current waveforms as well as the frequency and the rate of change of frequency. The measurements are time synchronized, and dispatched to the synchrophasor network at a specified reporting rate, with a timestamp indicating the measurement time. Many power utilities all over the globe install PMUs at suitable locations on the network, targeting various applications ranging from simple monitoring algorithms to advanced response based WAMPaC systems. It is important to test and verify these synchrophasor based WAMPaC applications before they are deployed in the field. It is practically difficult to evaluate the performance of a given synchrophasor application on a real power system, as some of the test conditions cannot be created without disrupting the normal operation of the power system. The more feasible solution for validation of real-time performance is to use realtime power system simulators. Some of the real-time simulators such as RTDS have provided emulated software/hardware models of PMUs. The ability of these PMU D. R. Gurusinghe and D. Ouellette are with RTDS Technologies Inc., Winnipeg, MB, R3T 2E1, Canada (e-mail of corresponding author: dinesh@rtds.com, dean@rtds.com. A. D. Rajapakse is with the Department of Electrical and Computer Engineering, University of Manitoba, Winnipeg, MB, R3T 5V6, Canada (email: Athula.Rajapakse@umanitoba.ca. Paper submitted to the International Conference on Power Systems Transients (IPST217 in Seoul, Republic of Korea June 26-29, 217 models to output synchrophasor data streams through a network connection, similar to a real PMU, make them extremely useful for testing WAMPaC applications. These reference P- class and M-class PMUs are implemented according to the current IEEE synchrophasor standards C37.118.1-211 [1] and C37.118.1a-214 [2]. Many commercial PMU devices extract phasors using the standard discrete Fourier transform (DFT. The DFT based phasor estimation techniques are accurate when the sampling process is coherent with the fundamental tone s frequency. However, in reality, the system frequency can deviate from its nominal value, leading to erroneous phasor estimates caused by the leakage effect. In addition, the presence of noise and harmonics as well as power system dynamic events can further reduce the accuracy of the DFT algorithm. These effects can be mitigated by utilizing window functions and backend performance class filters [1]. However, implementation of these additional filtering requires storing of a large number of signal samples; thus, computationally expensive specifically for real-time implementations [3]. In this paper, recent research to enhance the accuracy and computational efficiency of a real-time PMU model is presented. The paper specifically examines the application of a novel phasor estimation algorithm referred to as smart DFT (. The algorithm proposed in [4]-[6] appears to be a better alternative for the commonly used standard DFT algorithm to estimate phasors in the presence of off-nominal frequencies, noise and harmonics. The algorithm requires additional computational steps compared to the standard DFT, but the benefits of reduced filtering requirements can outweigh the additional computational burden. Use of algorithm for implementing a PMU or a PMU model has not been previously reported, as per the authors knowledge. The objective of this paper is to implement a based PMU model in a real-time simulator, which is an electromagnetic transient (EMT simulation based platform, and to evaluate its performances according the current synchrophasor standards [1], [2]. The main contribution of this paper is the adaption of to calculate synchrophasors defined according to IEEE C37.118.1-211 [1]. This includes data sampling, time synchronization, and measurement streaming according to C37.118 formats defined in IEEE C37.118-25 [7] and IEEE C37.118.2-211 [8]. These aspects are not addressed in the original proposals of [4]-[6]. In the synchrophasor standard [1], the frequency is defined as the rate of change of estimated phase angles, in contrast, relies on accurately estimated system frequency for phasor estimations, thus reconciliation is necessary. In addition, the paper will highlight the challenges in implementing in a real-time

environment. The simulations are performed to highlight the performances of the developed PMU model in comparison to the reference M-class PMU model in the RTDS simulator. Finally, an application of the developed PMU model is demonstrated by simulating a PMU network installed on the New England 1-machine 39-bus benchmark power system. II. SMART DFT ( BASED PMU ALGORITHM A. Standard Algorithm A pure sinusoidal signal sampled at discrete instants in the time-domain can be represented as, x(k = X m cos ( 2πfk + φ (1 where X m is the signal amplitude, f is the signal frequency, φ is the initial phase angle, f is the nominal system frequency (5 or 6 Hz, and N is the sampling rate in samples/cycle. The signal can be expressed as, x(k = 1 2 [X me j(2πfk + φ + Xm e j(2πfk + φ ] (2 = 1 j2πfk [x e + x e j2πfk ] 2 where x = X m e jφ and x denotes the complex conjugate of x. The fundamental frequency component within the DFT of x(k, evaluated at the r th sample, is given by, N 1 x r = 2 x(k + r e j2πk N (3 N k= Let consider the system frequency deviation is Δf; thus, f = f + Δf (4 By performing some algebraic manipulations after substituting (2 into (3, it is possible to show that [4]-[6]: x r = A r + B r (5 where, A r = x 2π(f + Δfr sin ( πδf N ej e jπ(n 1Δf f sin ( πδf (6 B r = x 2π(f + Δfr N e j e jπ(n 1(f + Δf sin ( π(f + Δf f sin ( π(f + Δf Define the exponential kernel in (6 and (7 as, Let, a = e j2π(f + Δf (8 w = a + a 1 = 2 cos ( 2π(f + Δf (9 Then, the frequency deviation, Δf is given by, Δf = 2π cos 1 (R ( w 2 f (1 where R( denotes the real part of a complex number. If w is known, then the system frequency can be estimated. From (6-(8, we can find the following relations. (7 A r = aa r 1 (11 B r = a 1 B r 1 Consider three consecutive DFT fundamental components based on (5, x r = A r + B r = aa r 1 + a 1 B r 1 x r 1 = A r 1 + B r 1 x r 2 = A r 2 + B r 2 = a 1 A r 1 + ab r 1 Then, w can be estimated as, (12 w = x r + x r 2 (13 x r 1 The phasor can be estimated by rearranging (6 as, A r = X sin ( πδf m f N sin ( πδf e j(2π(f + Δfr + π(n 1Δf + φ (14 Then, X m = A r N sin ( πδf sin ( πδf f (15 π(n 1Δf (16 φ = angle (A r In (16, the phasor rotates when the data window advances by one sample. Therefore, the phasor angle should be corrected to obtain a stationary phasor. π(n 1Δf φ = angle (A r 2π N m (17 where m is a counter varies from to (N 1. Then, solve (9 to obtain, a = w 4 w2 ± 2 2 From (12, A r = a2 x r ax r 1 a 2 1 B. Extension of for Synchrophasor Estimation (18 (19 A new phasor is calculated at every sampling point; however, all of them are not reported since the PMU reporting rate is always less than the sampling rate. The number of samples between two consecutive reportings is known as decimation factor, M and is given by, M = F s (2 where F s is the PMU reporting in frames/s. Then, every M th phasor is reported as a PMU measurement. Investigations revealed that estimated phasors show a numerical oscillation especially when the nominal system frequency is 6 Hz where the sampling interval is an irregular value. Therefore, it is proposed to filter the estimate w obtained from (13 using a mean filter with an order of 1.5N. Thus, (2.5N + 1 data samples are required to estimate a phasor. The time tag was set at the middle of this data window, resulting in a measurement delay of only 5N samples. When compared to the delay of 164 samples (N = 16

Magnitude (V and F s = 6 frames/s as an example of the reference M-class algorithm [1], [2], this is a significant improvement achieved with a less amount of memory and computational resources. well below to the error limits specified in the standards [1], [2] as shown in Fig 1(c. Therefore, both PMU models show satisfactory performances under frequency range test. III. MODEL VALIDATION The new PMU model was implemented in the RTDS simulator. First, the simulated waveforms (7 V nominal are internally fed to the PMU model, which has fixed sampling rate of 16 samples/cycle. Then, phasors are estimated based on the algorithm discussed in Section II. Performances of the proposed PMU model were evaluated under a variety of conditions that are specified in [1], [2]. In this paper, signal frequency range, linear frequency ramp, measurement bandwidth, and step response tests are presented to demonstrate compliance of the PMU model in a real-time simulation environment. Steady-state compliance tests such as signal magnitude (voltage/current, harmonic distortion and out-ofband interference tests were also performed; the PMU passed all stead-state tests but detailed results are omitted due to space limitation. Power system frequency was selected as 6 Hz for the demonstration purpose, but the PMU model proves similar performances for 5 Hz power system as well. PMU reporting rate was selected as 6 frames/s. Errors of the PMU model were expressed in terms of total vector error (TVE [1] and compared with the reference M- class model in the RTDS simulator. The automated PMU test setup proposed in [9] was used to test the proposed PMU model. The test setup has been developed around the RTDS simulator and capable to execute a series of tests, collects measurements, calculates errors, and checks conformity (pass/fail assessment as per the synchrophasor standard [1], [2] and the IEEE synchrophasor measurement test suite specification guidelines [1] with minimal user interaction. A. Signal Frequency Range The signal frequency range test demonstrates a deviation of frequency in the power system. In this test, the signal frequency is varied from 55 Hz to 65 Hz. When the frequency is deviating from the nominal frequency of 6 Hz the magnitude measured in the model shows slightly better performance. For example, if the signal frequency is set to 55 Hz the magnitude measured in the model is 69.998 V whereas measured value in the M-class model is 69.947 V as shown in Fig 1(a. Phase angle measurements of both models very closely follow the reference value as shown in Fig 1(b. The corresponding TVEs are.3% and.174% respectively and 7.6 7.4 7.2 7. 69.98 69.96 69.94 69.92 69.9 69.88 Fig. 1. Signal frequency at 55 Hz 28 24 2 16 12 8 4-4 -8-12 -16-2 B. Ramp of Signal Frequency A sudden loss of large generation or load results a power system imbalance and then, system frequency ramps from its nominal value. The ramp can either be positive or negative. The ramping rates specified in [1], [2] are +1 Hz/s and 1 Hz/s and the ramping range is 55 Hz to 65 Hz. As shown in Fig. 2 both PMU models show satisfactory performances and again the model shows slightly better accuracy. The reference M-class algorithm is design to operate within the ramping range of 55 to 65 Hz. Occasionally, extreme imbalance situations may result to deviate the system frequency even beyond that range and the M-class PMU model shows poor performances if the system frequency deviates beyond 55-65 Hz. As shown in Fig. 3 if the ramping range is expanded to 6-7 Hz, the magnitude measured in the M-class model shows significant deviation from the reference value. Thus, the TVE exceeds the specified limit of 1% around 67.3 Hz. It was observed that the TVE of the M-class model reaches to 6% at 7 Hz. However, the model shows better performances even at 7 Hz with a TVE of.35%. Similar results were observed if the ramping range is expanded to 5-6 Hz. Therefore, the model is appropriate to measure phasor quantities over a wide range of frequencies. C. Measurement Bandwidth The measurement bandwidth test demonstrates oscillations in the power system. This test includes two tests; magnitude modulation and phase angle modulation [1], [2]. In the magnitude modulation test, 1% modulation signal is added to the signal magnitude and modulation frequency is varied over the range of.1 to 5 Hz. The phase angle modulation test is similar, but 1% modulation signal is applied to the phase angle. Fig. 4 and Fig. 5 compare the performances of two PMU models when the modulation frequency is set to 5 Hz. As seen in the figures, both PMU models satisfy the specified error limits of the standards [1], [2]. The model shows a slight oscillation in phase angle when magnitude is modulated. If phase angle is modulated, the model shows a slight oscillation in magnitude. These oscillations cause maximum TVE to reach.54%, but it is well within specified limit of 3% [1], [2]. The M-class model shows better performances compared to the model in this particular test.. 1.6 1.4.8.6.4.2

Magnitude (V Magnitude (V Magnitude (V Magnitude (V 7.1 7. 69.99 69.98 69.97 69.96 69.95 69.94 6 61 62 63 64 65 28 24 2 16 12 8 4-4 -8-12 -16-2 6 61 62 63 64 65 1.6 1.4.8.6.4.2. 6 61 62 63 64 65 Fig. 2. Ramp of signal frequency from 6 Hz to 65 Hz 7.5 7. 69.5 69. 68.5 68. 67.5 67. 66.5 66. 65.5 6 61 62 63 64 65 66 67 68 69 7 28 24 2 16 12 8 4-4 -8-12 -16-2 6 61 62 63 64 65 66 67 68 69 7 4. 3.5 3. 2.5 2. 1.5.5. 6 61 62 63 64 65 66 67 68 69 7 Fig. 3. Ramp of signal frequency from 6 Hz to 7 Hz 82 78 74 7 66 62-89.6-89.7-89.8-89.9-9. -9.1-9.2-9.3 4.5 4. 3.5 3. 2.5 2. 1.5.5. Fig. 4. Magnitude modulation at 5 Hz 7.14 7.1 7.6 7.2 69.98 69.94 69.9-8. -82. -84. -86. -88. -9. -92. -94. -96. 4.5 4. 3.5 3. 2.5 2. 1.5.5. Fig. 5. Phase angle modulation at 5 Hz

Magnitude (V Magnitude (V 78 77 76 75 74 73 72 71 7 69 -.8 -.4..4.8 Fig. 6. Magnitude step response 7.8 7.6 7.4 7.2 7. 69.8 69.6 Fig. 7. Phase angle step response 69.4 -.8 -.4..4.8-89.5-89.6-89.7-89.8-89.9-9. -9.1-9.2-9.3-9.4-9.5 -.8 -.4.4.8-78 -8-82 -84-86 -88-9 -92 -.8 -.4.4.8 -.8 -.4..4.8 7 6 5 4 3 2 1 16 14 12 1 8 6 4 2 -.8 -.4..4.8 D. Step Response The step response test demonstrates the power system switching events. This test also includes two tests; magnitude step and phase angle step responses [1], [2]. In the magnitude step, ±1% step is applied to the signal magnitude whereas ±1 step is applied to the signal phase angle under the phase angle step. The step is initiated by a signal at a precise time, which allows determining response time, delay time, and maximum overshoot/undershoot [1]. Since PMU response time and delay time are small compared to the PMU reporting interval it is difficult to characterize the response of a single step. Therefore, the equivalent sampling approach explained in [11] should be used to achieve the required resolution. Fig. 6 and Fig. 7 show the magnitude and phase angle step responses respectively. Table I provides the response time, delay time, and maximum overshoot/undershoot of both PMU models under magnitude and phase angle step responses. The test results show that both PMU models satisfy the standards [1], [2], however, the model shows better performances compared to the M-class model. Influence Quantity Magnitude step Phase angle step TABLE I STEP RESPONSE PERFORMANCE PMU Model Response Time (ms Delay Time (ms Max. Over /Undershoot (% of step C37.118.1 limit 116.67 4.17 1. Model 15.2.58. M-class Model 27.85.42 6. C37.118.1 limit 116.67 4.17 1. Model 32.95 2.55 4.7 M-class Model 66.56.42 8.5 IV. POWER SYSTEM APPLICATION The IEEE 39-bus test system (New England power system [12] was used to demonstrate the dynamic performances of the model. It was assumed that PMUs are installed at the generator terminals. The test system was simulated in the RTDS, which is equipped with a GTNETx2 hardware board to emulate both and reference M-class PMU modules. A SEL-247 GPS clock [13] was used to provide inter-range instrumentation group time code format B (IRIG-B time signal to the RTDS simulator via a GTSYNC card. PMUs in the RTDS were configured to report synchrophasors through a laboratory scale synchrophasor network at 6 frame/s rate. The synchrophasor data were collected by the openpdc v2. [14] phasor data concentrator (PDC. In order to examine the dynamic performances, two cases were considered. In the first case, a three-phase to ground fault applied on Line 16-17 (at 25% of the length from bus 16 when universal coordinated time ( is 14:36:28.15. The fault was cleared by removing the line after 6 cycles. The variations of the voltage magnitudes and the phase angles obtained from both and M-class models are shown in Fig. 8. Note that a few generator terminals were selected for the demonstration. It was observed that the power system is stable following the fault clearance and both PMU models showed similar performances where the trajectories obtained from two PMU models are coincided. The M-class model displayed slight overshoot before and after the fault due to the step change in voltage magnitudes. In the second example, a three-phase to ground fault was applied on same Line 16-17 (at 75% of the length from bus

Voltage magnitude (pu Voltage phase angle (deg Voltage magnitude (pu Voltage phase angle (deg 8. 1.1 6..9.8.7.6.5 Gen.-32 : Gen.-33 : Gen.-35 : Gen.-38 : Gen.-39 : Gen.-32 : M-Class Gen.-33 : M-Class Gen.-35 : M-Class Gen.-38 : M-Class Gen.-39 : M-Class 4. 2.. -2. -4. -6. -8. (a Voltage magnitude Fig. 8. Voltage phasors at generator terminal : Stable case (b Voltage phase angle 1.1.9.8.7.6.5 2. 16. 12. 8. 4.. -4. -8. -12. -16. -2. -24. Gen.-32 : Gen.-33 : Gen.-35 : Gen.-38 : Gen.-39 : Gen.-32 : M-Class Gen.-33 : M-Class Gen.-35 : M-Class Gen.-38 : M-Class Gen.-39 : M-Class (a Voltage magnitude Fig. 9. Voltage phasors at generator terminal : Unstable case 16 when is 14:55:43.233 and cleared by removing the line after 6 cycles. Fig. 9 shows the variations of the voltage magnitudes and the phase angles obtained from both and M-class models. This is a multi-swing instability and both PMU models showed similar performances. Therefore, the model implemented in the RTDS simulator precisely captures the dynamic behavior of the simulated power system and realizes the same accuracy level of the reference M-class algorithm [1], with less computational resources. V. CONCLUSIONS The algorithm demands a less amount of memory and computational resources compared to the reference M- class algorithm [1] and therefore, it offers a significant advantage in a real-time computing environment. A PMU model based on the was implemented in a real-time simulator. The standard tests showed that based PMU is well within the error limits specified in the current synchrophasor standards [1], [2] for M-class PMUs (which are more stringent than P-class with minimal additional filtering. Comparisons with the reference M-class PMU model [1] showed that based PMU has improved performance compared to the reference M-class model, except in the measurement bandwidth test. Finally, the developed PMU model in the real-time environment is applied to analyze the dynamic behavior of the IEEE 39-bus test system and displayed promising performances. Availability of realistic PMU models in electromagnetic transient simulators, especially in real-time simulators, allows verification of critical synchrophasor applications before they are deployed in actual power systems. (b Voltage phase angle VI. REFERENCES [1] IEEE standard for synchrophasor measurements for power systems, IEEE Standard C37.118.1-211, Dec. 211. [2] IEEE standard for synchrophasor measurements for power systems (Amendment 1: Modification of selected performance requirements, IEEE Standard C37.118.1a-214, Apr. 214. [3] D. R. Gurusinghe, A. D. Rajapakse, and K. Narendra, Testing and enhancement of the dynamic performance of a phasor measurement unit, IEEE Trans. on Power Delivery, vol. 29, no. 4, pp. 1551-156, Aug. 214. [4] J. Z. Yang and C. W. Liu, A precise calculation of power system frequency and phasor, IEEE Trans. on Power Delivery, vol. 15, no. 2, pp. 494-499, Apr 2. [5] J. Z. Yang and C. W. Liu, A precise calculation of power system frequency, IEEE Trans. on Power Delivery, vol. 16, no. 3, pp. 361-366, July 21. [6] Y. Xia, Y. He, K. Wang, W. Pei, Z. Blazic, and D. P. Mandic, A complex least squares enhanced smart DFT technique for power system frequency estimation, IEEE Trans. on Power Delivery, (early access. [7] IEEE standard for synchrophasors for power systems, IEEE Standard C37.118-25, Mar 26. [8] IEEE standard for synchrophasor data transfer for power systems, IEEE Standard C37.118.2-211, Dec. 211. [9] D. R. Gurusinghe, D. Ouellette, and R. Kuffel, An automated test setup for performance evaluation of a phasor measurement unit, in Proc. of Protection, Automation & Control World Conference (PAC World 216, Ljubljana, Slovenia, June 216, pp. 1-18. [1] IEEE synchrophasor measurement test suite specification, IEEE Std. Association, Dec. 214. [11] J. Ren, M. Kezunovic and G. Stenbakken, Dynamic characterization of PMUs using step signals, in Proc. 29 IEEE Power & Energy Society General Meeting, Calgary, AB, Canada, pp. 1-6. [12] M. A. Pai, Energy function analysis for power system stability. Kluwer academic publishers, Boston/Dordrecht/London, 1989. [13] SEL-247 Satellite-Synchronized Clock Instruction Manual, SEL Inc., Pullman, WA, pp. 1-4, 213. [14] OpenPDC, Grid Protection Alliance [Online]. Available: http:// openpdc.codeplex.com.