Year. Caution. Index. 2 Features. 5/6 Range and Application. 7 Other Features. 8 Specifications. 12 Terminal Functions

Similar documents
AV-300i Specifications. Saftronics Inc. VG10 Product Specifications VG10. Dynamic Vector Drive

High Performance AC Drives kW VXM

General Specifications FECA-TE /2010. Phone: Fax: Web:

idrive AC variable speed

CTi Automation - Phone: Fax: Web: -

AV-300i Specifications. Saftronics Inc. PC10 Product Specifications PC10. Mini Vector AC Drive

AF-300 G11 Specifications. GE Industrial Systems. Product Specifications AF-300 G11

Caution. Three-phase 400V series FRN0.4C1S-4A FRN0.75C1S-4A FRN1.5C1S-4A FRN2.2C1S-4A FRN3.7C1S-4A

FUJI Inverter. Standard Specifications

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81)

Series Concepts. Ideal functions to meet various needs. New, compact design. Simple operation. Flexible through optionals

[ 4 ] Using pulse train input (F01 = 12)

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

General Specifications

Series Concepts. Ideal functions to meet various needs. New, compact design. Simple operation. Flexible through optionals

FRN E1-4LM FRN E1-7LM

S11 Adjustable Speed Drive Engineering Specification

QUICK GUIDE PUMP CONTROL. High performance Compact Inverter. Date Version 22/09/

Series Concepts -'0+ ) 1!!!! $ ( $ $ # $ 2 ( $!! $ #!! $! $ ( $! # # $ $ 2 3 $! 45 (. ( ) / # 6 $( $ * &7 89 : $ ')8;" : - 2 -

VF-nC1 Adjustable Speed Drive Engineering Specification

Fan and Pump AC Inverter

Solutions for Drives G11S FRN. The Universal Drive

E3 Adjustable Speed Drive Engineering Specification

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

General Specifications

The new Yaskawa Varispeed G7 Inverter

GS1 Parameter Summary Detailed Parameter Listings...4 9

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

α α Retry count clear Alarm reset Active End of retry S-curve time during accelerati on H04: (Count) setting S curve time during decelerati on

ADJUSTABLE SPEED DRIVES. AS1 Drive

CHAPTER 8 PARAMETER SUMMARY

SX (690 V) System configuration

IMO Jaguar VXG. Quick Start Guide. Refer to VXG Manual for full data. Available to download from IMO Precision Controls Ltd.

TOSVERT TM VF-nC3 Parameter List

SX (400 V) System configuration

SX (400V) System configuration

P-SERIES VFD 1-40HP (200~230VAC), 1-400HP (380~480VAC),3Ø Dual Rated for Constant & Variable Torque Integrated PID Control

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

ADJUSTABLE SPEED DRIVES VF-S11 Sords Electric

Multi-function, Compact Inverters. 3G3MV Series

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

6.9 Jump frequency - Avoiding frequency resonance

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

D SERIES LM16. COMPACT DRIVE V/f and SLV CONTROL. LM16 COMPACT DRIVE V/f and SLV CONTROL

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

OPC-E1-PG3 Specifications

Inverter Drive /Vector Drive Motors & Controls

ADJUSTABLE SPEED DRIVES FS1

SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

Operating Instructions

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

SJ700 series High performance with Many useful Functions and, yet User Friendly. WJ200 series Pursuing the Ideal Compact Inverter NEW

AF91 Adjustable Frequency Drives Series B

General Specifications

Manual Overview...1 2

(Supplement to Instruction Manual)

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

VFS11 Parameter List for up to CPU version 105

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ACH550 HVAC Drive Submittal

Frequency Inverters. SJ700B Series. Powerful Inverter for General Purpose Use. SJ700B Series

QUICK GUIDE SINGLE PUMP CONTROL. Frequency inverter for pump control applications SG_PUMP_CONTROL_HVAC_EN_1.1.0

13. Before making a service call Trip information and remedies

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life.

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

NX series Constant and variable torque Variable Speed Drives for induction motors

Before you operate the inverter, the parameters that you must first program are the basic parameters.

vacon nx all in one application manual ac drives Phone: Fax: Web: -

General Purpose Drives

New FUJI ELECTRIC INVERTERS

HPVFP High Performance Full Function Vector Frequency Inverter

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

9. RS485 Communication (Option)

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

Compact Inverter User's Manual

WJ200 series Pursuing the Ideal Compact Inverter

USER'S MANUAL Fuji Electric FA Components & Systems Co., Ltd. MEH446a

LG Variable Frequency Drive

9. RS485 Communication

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i

ADVANCED AND EVER ADVANCING FR-V200. FR-V200 series

User's Manual. Phone: Fax: Web: -

Version number A=standard P=Cold Plate (Frame A only) T=Brake chopper (Frame A only) Input voltage 11=115VAC 21=230VAC 1φ 23=230VAC 3φ 43=400VAC

Intelligent Drive Systems, Worldwide Services SK 700E F 3070 GB

THYFREC-VT210S 400V System 37 to 315kW (C/T) 400V System 45 to 370kW (V/T) QUICK START GUIDE

SAFETY INSTRUCTIONS WARNING

P Series. Installation, Programming Operation, & Maintenance Manual. Fan & Pump Optimized Variable Frequency Drive.

TECHNICAL SPECIFICATION INVERTER VEGA DRIVE

G+ Mini Transition Guide. Product Transition Guide P3 Series 2 to G+ Mini

VFS9 Parameter List for Version110 or later

INSTRUCTION MANUAL FVR-E11S-7EN

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

EFC 3600 Frequency converter for higher energy efficiency and improved process control

INVERTER FR-D700. Global standard FACTORY AUTOMATION. Pursuing the easy operation. Long life and simple maintenance. Compact and space-saving

Transcription:

Index Caution 2 Features 5/6 Range and Application 7 Other Features 8 Specifications 2 Terminal Functions This publication is only to be used as a guide. Please seek the full instruction manual before installation. If in doubt please call IMO on 020 8452 6444 or visit our website on www.imopc.com (Please refer to inside back cover for further details) 4/5 Basic Electrical Connections 6 The Keypad 8 Main Functions (F) 9 Extension Functions (E) Year Guarantee 20 Frequency Functions (C) 2 Motor Functions (P) 2 Higher Functions (H) 22 Alternative Motor Functions (A) 23 Protective Functions 24 Dimensions 26 Options 3 Wiring Equipment 32/33 User Notes 34 Warranty, Safety Precautions, and Help Lines

Ideal combination of power and multiple-functionality. Dynamic torque-vector control ensures optimum motor control under virtually any operating condition. Dynamic torque-vector control Dynamic torque-vector control system performs highspeed calculation to determine the required motor power for the load status. IMO s key technology is optimal control of voltage and current vectors for maximum output torque. A high starting torque of >200% at 0.5Hz.* *80% for 30kW or larger models. Achieves smooth acceleration/deceleration in the shortest time for the load condition. Using a high-speed CPU quickly responds to an abrupt load change, detects the regenerated power to control the deceleration time. This automatic deceleration function greatly reduces the inverter tripping. Feedback control with encoder feedback enables the inverter to execute vector control with encoder feedback by adding an optional PG feedback card to obtain higher performance. Speed control range : :200 Speed control accuracy : ±0.02% Speed control response : 40Hz (22kW or smaller) Output torque [%] 300 200 00 0 00 200 300 Torque characteristics with Dynamic torque-vector control (Sample: 4.0kW) PG Vector Control Actual torque [%] Torque reference [%] Motor speed [r/min] Motor current [A] 00 0 00 0 500 400 0 0 000 2000 Motor speed [r/min] Step load response (Sample : 4.0kW) Time 320ms Reduced motor wow at low speed Wow characteristics (Sample: 4.0kW) Motor wow at low speed (Hz) reduced to less than / 2 of that achieved by conventional inverters, with the dynamic torque-vector control system, in combination with the VXM s unique digital AVR. 0 Conventional inverter 4 r/min Jaguar VXM 0 5 r/min Time 500ms 2

JAGUAR VXM New on-line tuning system On-line tuning to continuously check for variation of motor characteristics during running for high-precision speed control. This tuning function also available for a second motor, which allows high-precision driving of the second motor by changeover operation between two motors. Motor temperature vs speed variation (Sample: 4.0kW) 70 C 0Motor speed [r/min] 30 C With on-line tuning Without on-line tuning Time [min] 80 Temperature [ C] Environment-friendly features Provided with soft switched control power supply systems which minimise noise interference on peripheral devices such as sensors. Equipped with terminals for connecting DC REACTOR that will suppress harmonics. Complies with EMC Directive. RUN 3

JAGUAR VXM Advanced, convenient functions 6-step speed, 7 pattern operation with timer control, rotating motor pick-up control for conveyance machinery. PID control, cooling fan on/off control, line/inverter changeover operation for fans and pumps. Rotating motor pick-up control: Restarts motor without any shocks, by detecting motor speed where motor is coasting after momentary power failure occurs. Automatic energy-saving operation function: Minimises inverter and motor loss at light load. Rotating motor pick-up control characteristics (Sample: 4.0kW) Power source Motor speed [r/min] Output current [A] Time 00 Energy saving effect Required power [%] Damper control Energy saved Inverter control (V / f control) Inverter control (Automatic energy-saving control) 0 Flow rate [%] 00 Global products, communication Conforms to major world safety standards: UL, cul, TÜV (up to 22kW), CE marked for EMC + LVD compliance. Equipped with RS485 interface as standard. Connection to field bus: Profibus-DP, Interbus-S, DeviceNet, Modbus Plus (Option). Universal DI/DO: Monitors digital I/O signal status and transmits to a host controller, helping to simplify factory automation. 4

RANGE AND APPLICATION Model numbers and range Easy to apply to customer systems. A consistent design concept in all models from 0.4kW to 35kW. Nominal applied motors (kw) 0.4 0.75.5 2.2 4.0 5.5 7.5 5 8.5 22 30 37 45 55 75 90 0 32 60 200 220 280 35 400 Constant Torque Rating (CT) VXM40 VXM75 VXM50 VXM220 VXM400 VXM550 VXM750 VXM00 VXM500 VXM850 VXM2200G VXM30K VXM37K VXM45K VXM55K VXM75K VXM90K VXM0K VXM32K VXM60K VXM200K VXM220K VXM280K VXM35K 400V series Variable Torque Rating (VT) VXM550 VXM750 VXM00 VXM500 VXM850 VXM30KP VXM30K VXM37K VXM45K VXM55K VXM75K VXM90K VXM0K VXM32K VXM60K VXM200K VXM220K VXM280K VXM35K Jaguar VXM can be Fans Air-conditioning systems (for factory, building, office, hospital, clean room, supermarkets and farms) Dryers Boiler fans Fans for controlling furnace temperature Roof fans controlled as a group Refrigeration Compressors Built-in blowers in filmmanufacturing machines Cooling-tower fans Ventilating fans * : Available soon How to read the model number JAGUAR VX M 500 * Family Type Standard rating examples 40 = 0.4kW 50 =.5kW 500 = 5kW CE marked for EMC + LV directives Terminators * Standard rating Terminator No letter = Standard rating applies K = Rating is in actual kw KP = As K but for fans + pumps only G = Cannot be used for higher power than rated Food processing machines Food mixing machines Food slicers Grain milling machine (bread, cake, noodles) Tea making machines Rice cleaning machines 5

RUN RUN RUN RUN RUN JAGUAR VXM used for most general purpose industrial and commercial applications Machine tools Grinding machines Sanding machines Milling machines Lathes Drilling machines Turntables Work positioning machines PC board drilling machines Winding machines Presses Conveyance machinery Cranes (travelling, traversing, hoisting) Automated warehouse Conveyor (belt, chain, screw, roller) Lifts and hoists Car parking facilities Elevator, escalator Automatic door Shutter equipment Speed-change gear Chemical machinery/wood working machines Fluid mixing machine Extruders Vibrators Centrifugal separators Coating machines Take-up rollers Routing machines Sanding machines Planing machines Band/circular saws Pumps Tankless water supply systems Submersible motor pumps Vacuum pumps Fountain pumps Cooling water pumps Circulating hot water pumps Well pumps Agricultural storage pumps Water treatment systems Constant-flow pumps Sludge pumps Packaging machinery Palletisers Paper making/textile machinery Spinning machines Knitting machines Textile printing machines Synthetic fibre manufacturing plant Other machinery Automated feed/medicine mixers Commercial-use washing machines Offset printing presses Book-binding machines Car-washing machines Shredders Dishwashers Test equipment Crushers 6

JAGUAR VXM Intelligent keypad panel Copy function: Easily copies function codes and data to other inverters. Six languages (English, French, German, Italian, Spanish and Japanese) are available as standard. Jogging (inching) operation from the Keypad or external signal. Remote operation using optional extension cable (VXM podcable). Extensive product line Since the product is equipped with a dual rating feature, it can be used for variable torque rating control (VT) (5.5kW or larger), as well as constant torque rating (CT]. The variable torque rating can be used for one-class higher than the constant torque rating. *For 30kW only, the model numbers for the VT rating and CT rating are different. Totally-enclosed casing (IP40) (up to 22kW as standard). Optional IP20 enclosure available for 30kW or larger models. Waterproof models (IP65 for 7.5kW or smaller, IP54 for to 22kW) as a separate series (available soon). Protective functions, maintenance Protection Motors with various characteristics can be used by setting thermal time constant for the electronic thermal overload relay. Input phase loss protective function protects the inverter from damage caused by disconnection of power supply lines. Motor is protected with a PTC thermistor. Input terminals for auxiliary control power supply (.5kW or larger models): Alarm signal output will be held even if main circuit power supply has shut down. Maintainability The items below can be monitored on the Keypad panel, making it easy to analyse the cause of trip and to take preventive measures. Input/output terminals check Life expectancy of main-circuit capacitors Inverter on-load factor Accumulated operation time Inverter operating condition (output current, heat sink temperature, input power, etc) Detailed data on trip cause. Other useful functions Side-by-side mounting (up to 22kW) saves space when inverters are installed in a panel. The uniform height (260mm) of products (up to 7.5kW) makes it easy to design panels. User-definable control terminals: Digital input (9 points), transistor output (4 points) and relay contact output ( point). Active drive feature: Performs prolonged acceleration at reduced torque, monitoring the load status to prevent tripping. Stall prevention function is provided as standard. Active or inactive can be also selected. Output torque [%] Torque characteristics with Dynamic torque-vector control 00% of output torque refers to the rated torque of the motor driven at 50Hz. 200 00 90 50 Continuous operation torque 0.4 to.5kw 2.2 to 22kW Short time operation torque 6 520 50 00 Output frequency [Hz] The above torque characteristics depend on the motor characteristics. 7

STANDARD SPECIFICATIONS JAGUAR VXM Type VXM/VXMK 0.4 0.75.5 2.2 4.0 5.5 7.5 5 8.5 22 30 37 45 55 75 90 0 32 60 200 220 280 35 VXMKP *) 30 Applied Nominal (CT use) kw 0.4 0.75.5 2.2 4.0 5.5 7.5 5 8.5 22 30 37 45 55 75 90 0 32 60 200 220 280 35 motor Maximum (VT use) kw 7.5 5 8.5 22 30 37 45 55 75 90 0 32 60 200 220 280 35 400 Output Rated capacity *2) kva.0.7 2.6 3.9 6.4 9.3 2 7 2 28 32 32 43 53 65 80 07 26 50 8 28 270 298 373 ratings Rated voltage *3) V 3 phase 380, 400, 45V/50Hz 380, 400, 440, 460V/60Hz OM: 440V/50Hz Rated current *4) A.5 2.5 3.7 5.5 9.0 3 8 24 30 39 45 60 75 9 2 50 76 20 253 304 377 45 520 Overload Cont. (VT use) A 6.5 23 30 37 44 60 75 9 2 50 76 20 253 304 377 45 520 capability Short time *) 50% of rated current for min. 50% of rated current for min. (CT use) 200% of rated current for 0.5s 80% of rated current for 0.5s Output frequency Hz 0. 400 Input Phases, Voltage, Frequency 3 phase 380 to 480V 50/60Hz 3 phase 380 to 440V/50Hz 380 to 480V/60Hz *5) ratings Voltage/Frequency variations Voltage: +0 to -5% (Voltage unbalance *6): 2% or less) Frequency: +5 to -5% Momentary voltage dip capability *7) When the input voltage is 30V or more, the inverter can be operated continuously. When the input voltage drops below 30V from rated voltage, the inverter can be operated for 5ms. The smooth recovery method is selectable. Rated current *8) (with DCR) 0.82.5 2.9 4.2 7. 0.0 3.5 9.8 26.8 33.2 39.3 54 54 67 8 00 34 60 96 232 282 352 385 49 A (without DCR).8 3.5 6.2 9.2 4.9 2.5 27.9 39. 50.3 59.9 69.3 86 86 04 24 50 Required power kva 0.6. 2. 3.0 5.0 7.0 9.4 4 9 24 28 38 38 47 57 70 93 36 6 96 244 267 34 supply capacity (with DCR) Control Starting torque *) >200% (with Dynamic torque-vector control selected) >80% (with Dynamic torque-vector control selected) Braking Braking torque 50% 00% 20% *9) 5 to 0% *9) Standard Time s 5 5 No limit Duty cycle % 5 3 5 3 2 3 2 No limit Braking torque (Using options) 50% 00% DC injection braking Starting frequency: 0. to 60.0Hz Braking time: 0.0 to 30.0s Braking level: 0 to 00% of rated current Enclosure (IEC 60529) IP 40 IP 00(IP20: Option) Cooling method Natural cooling Fan cooling Standards -UL/cUL -CE Marking (Low Voltage) -EMC Directive -TÜV (up to 22kW) -EN 6800-2 (Ratings, specifications for low voltage adjustable frequency a.c. power drive systems) -EN 6800-3 (EMC product standard including specific test methods) Mass kg 2.2 2.5 3.8 3.8 3.8 6.5 6.5 0 0 0.5 0.5 3 3 36 4 42 50 73 73 04 04 45 45 CT: Constant torque VT: Variable torque Notes: *) Specifications for VT use are shown below. Output ratings Overload capability Short time Control Starting torque 50% 0% of rated current for min. *2) Inverter output capacity (kva) at 45V. *3) Output voltage is proportional to the power supply voltage and cannot exceed the power supply voltage. *4) Current derating may be required in case of low impedance loads such as high frequency motor. *5) When the input voltage is 380V/50Hz or 380 to 45V/60Hz, the top of the auxiliary transformer must be changed. *6) Refer to the EN 6800-3 (5.2.3). *7) Tested at standard load condition (85% load). *8) This value is calculated. (Refer to IMO). *9) With a nominal applied motor, this value is average torque when the motor decelerates and stops from 60Hz. (It may change according to motor loss.) Conformity to Low Voltage Directive The Jaguar VXM Series conforms to the Low Voltage Directive with EN5078. Conformity to EMC Directive Emission requirement EMC filters in compliance with EN6800-3 are provided for all models as an optional extra Immunity requirement The Jaguar VXM Series inverters meet EN6800-3 as standard. 8

COMMON SPECIFICATIONS Item Output Maximum frequency 50 to 400Hz *) frequency Base frequency 25 to 400Hz *) Explanation Starting frequency 0.2 to 60Hz, Holding time: 0.0 to 0.0s Carrier frequency *2) CT use VT use 0.75 to 5kHz (55kW or smaller) *3) 0.75 to 5kHz (22kW or smaller) 0.75 to 0kHz (75kW or larger) 0.75 to 0kHz (30 to 75kW) 0.75 to 6kHz (90kW or larger) Accuracy (Stability) Analog setting : ±0.2% of maximum frequency (at 25 ±0 C) Digital setting : ±0.0% of maximum frequency (at -0 to +50 C) Setting resolution Analog setting : /3000 of maximum frequency ex.) 0.02Hz at 60Hz, 0.04Hz at 20Hz, (0.5Hz at 400Hz : EN) Digital setting : 0.0Hz at maximum frequency of up to 99.99Hz (0.Hz at Maximum frequency of 00Hz and above) LINK setting : /20000 of maximum frequency ex.) 0.003Hz at 60Hz, 0.006Hz at 20Hz, (0.02Hz at 400Hz : EN) 0.0Hz (Fixed) Control Control method V/f control (Sinusoidal PWM control) Dynamic torque-vector control (Sinusoidal PWM control) Vector control with PG (*) (EN only) Setting Voltage/freq. (V/f) characteristic Torque boost Adjustable at base and maximum frequency, with AVR control : 320 to 480V Selectable by load characteristics: Constant torque load (Auto/manual), variable torque (manual) Operation method KEYPAD operation : or key, key Digital input signal operation : FWD or REV command, Coast-to-stop command, etc. LINK operation : RS485 (Standard) Profibus-DP, Interbus-S, DeviceNet, Modbus Plus, CAN open (Option) Frequency setting KEYPAD operation : or key (Frequency command) External potentiometer (*) : to 5k (/2W) Analog input : 0 to +0VDC (0 to +5VDC), 4 to 20mA DC (Reversible 0 to ±0VDC (0 to ±5VDC)... Reversible operation by polarised signal can be selected. (Inverse) +0 to 0VDC, 20 to 4mA DC... Inverse mode operation can be selected. UP/DOWN control : Output frequency increases when UP signal is ON, and decreases when DOWN signal is ON. Multistep frequency : Up to 6 different frequencies can be selected by digital input signal. Pulse train input (*) : 0 to 00kp/s Digital signal (parallel) (*) : 6-bit binary LINK operation : RS485 (Standard) Profibus-DP, Interbus-S, DeviceNet, Modbus Plus, CAN open (Option) Programmed PATTERN operation: Maximum 7 stages Jogging operation or key, FWD or REV digital input signal Running status signal Transistor output (4 points) : RUN, FAR, FDT, OL, LU, TL, etc. Relay output (2 points) : Same as transistor output Alarm output (for any fault) Analog output ( point) : Output frequency, output current, output torque, etc. Pulse output ( point) : Output frequency, output current, output torque, etc. Acceleration/Deceleration time 0.0 to 3600s : Independently adjustable acceleration and deceleration 4 different times are selectable. Active drive Frequency limiter Bias frequency Mode select : Linear, S-curve (weak), S-curve (strong), Non-linear When the acceleration time reaches 60s, the motor output torque is automatically reduced to rated torque. After 60s the motor operation mode is changed to torque limiting operation. The acceleration time is automatically extended up to 3 times. High and low limiter can be preset. Bias frequency can be preset. Gain for frequency setting Gain for frequency setting can be preset (0.0 to 200.0%) ex.) Analog input 0 to +5VDC with 200% gain results in maximum frequency at 5VDC. Skip frequency control Rotating motor pick up (Flying start) Auto-restart after momentary power failure Skip frequency (3 points) and its common skip hysteresis width (0 to 30Hz) can be preset. A rotating motor (including inverse rotating mode) can be smoothly picked up without stopping the motor (speed search method). Automatic restart is available without stopping motor after a momentary power failure (speed search method). When Smooth recovery mode is selected, the motor speed drop is held minimum. (The inverter searches the motor speed and smoothly returns to setting frequency.) Line/Inverter changeover operation Controls the switching operation between line power and inverter. The inverter has internal sequence function. Slip compensation The inverter output frequency is controlled according to the load torque to keep motor speed constant. When the value is set at 0.00 and Torque-vector is set at active, the compensation value is automatically set. Droop operation Torque limiting Torque control PID control Slip compensation can be preset for the second motor. The motor speed droops in proportional to output torque (-9.9 to 0.0Hz). When the motor torque reaches a preset limiting level, this function automatically adjusts the output frequency to prevent the inverter from tripping due to an overcurrent. Torque limiting and 2 can be individually set, and are selectable with a digital input signal. Output torque (or load factor) can be controlled with an analog input signal. This function can control flow rate pressure, etc. (with an analog feedback signal.) Reference KEYPAD operation ( or key): Setting freq./max. freq. X 00 (%) PATTERN operation : Setting freq./max. freq. X 00 (%) signal Voltage input (Terminal 2 and V2) : 0 to +0V DC DI option input (*) : BCD, setting freq./max. freq. X 00 (%) Current input (Terminal C) : 4 to 20mA DC Binary, full scale/00 (%) Reversible operation with polarity (Terminal 2) : 0 to ±0V DC Multistep frequency setting : Setting freq./max freq. X 00 (%) Reversible operation with polarity (Terminal 2 + V) : 0 to ±0V DC RS485 : Setting freq./max freq. X 00 (%) Inverse mode operation (Terminal 2 and V2) : +0 to 0V DC Inverse mode operation (Terminal C) : 20 to 4mA DC Feedback Terminal 2 (0 to +0V DC or +0 to 0V DC) signal Terminal C (4 to 20mA DC or 20 to 4mA DC) NOTES: (*) Option *) For application at 20Hz or above, please contact IMO. *2) Inverter may automatically reduce carrier frequency, in accordance with ambient temperature or output current for protection purposes. *3) The minimum carrier frequency changes depending on maximum output frequency. 9

JAGUAR VXM Item Explanation Control Automatic deceleration Torque limiter (braking) is set at F4:0 (Same as Torque limiter 2 (braking). In deceleration : The deceleration time is automatically extended up to 3 times the setting time for tripless operation even if braking resistor not used. In constant speed operation : Based on regenerative energy, the frequency is increased and tripless operation is active. Second motor s setting Energy saving operation Fan stop operation Universal DI Universal DO Universal AO Zero speed control (*) Positioning control (*) Synchronised operation (*) This function is used for two motors switching operation. The second motor s V/f characteristics (base and maximum frequency) can be preset. The second motor s circuit parameter can be preset. Torque-vector control can be applied to both motors. This function minimises inverter and motor losses at light load. This function is used for silent operation or extending the fan s lifetime. Transmits to main controller of LINK operation. Outputs command signal from main controller of LINK operation. Outputs analog signal from main controller of LINK operation. The motor speed is controlled with the speed reference of zero (holding torque). The SY option card can be used for positioning control by differential counter method. The function controls the synchronised operation between 2 axes with encoders. Indication Operating mode (Running) LED monitor LCD monitor (English, German, French, Spanish, Italian, Japanese) Output frequency (before slip compensation) (Hz) Output frequency 2 (after slip compensation) (Hz) Setting frequency (Hz) Output current (A) Output voltage (V) Motor synchronous speed (r/min) Line speed (m/min) Load shaft speed (r/min) Torque calculation value (%) Input power (kw) PID reference value ( F0 ) PID reference value (Remote) ( C30 ) PID feedback value Trip history: Cause of trip by code (even when main power supply is off, trip history data of the last 4 trips are retained). Operation monitor and alarm monitor Operation monitor Displays operation guidance Bargraph: Output frequency (%), output current (A), output torque (%) Alarm monitor The alarm data is displayed when the inverter trips. Function setting and monitor Function setting Displays function codes and its data or data code, and changes the data value. Operation condition Output frequency (Hz) Motor synchronous speed (r/min) Output current (A) Load shaft speed (r/min) Output voltage (V) Line speed (m/min) Torque calculation value (%) PID reference value Stopping Selected setting value or output value Setting frequency (Hz) PID feedback value Trip mode Displays the cause of trip by codes as follows. Operation condition Driving torque limiter setting value (%) OC (Overcurrent during acceleration) OC2 (Overcurrent during deceleration) OC3 (Overcurrent running at constant speed) EF (Ground fault) Lin (Input phase loss) FUS (Fuse blown) (FWD/REV, IL, VL/LU, TL) Braking torque limiter setting value (%) Tester function (I/O check) Digital I/O: (ON), (OFF) Analog I/O: (V), (ma), (H), (p/s) Maintenance data OU (Overvoltage during acceleration) Operation time (h) Cooling fan operation time (h) OU2 (Overvoltage during deceleration) DC link circuit voltage (V) Communication error times OU3 (Overvoltage running at constant speed) Temperature of inside air ( C) (KEYPAD, RS485, Option) LU (Undervoltage) Temperature of heat sink ( C) ROM version OH (Overheating at heat sink) Maximum current (A) (Inverter, KEYPAD, Option) OH2 (External thermal relay tripped) OH3 (Overtemperature of inside air) dbh (Overheating of DB circuit) Main circuit capacitor life (%) Control PC board life (h) Load factor calculation OL (Motor overload) Measurement time (s) Average current (A) OL2 (Motor 2 overload) Maximum current (A) Average braking power (%) OLU (Inverter unit overload) Alarm data OS (Overspeed) Output frequency (Hz) Temperature of inside air ( C) PG (PG error) Output current (A) Heat sink temperature ( C) Er (Memory error) Output voltage (V) Communication error times Er2 (KEYPAD panel communication error) Torque calculation value (%) (KEYPAD, RS485, Option) Er3 (CPU error) Setting frequency (Hz) Digital input terminal condition Er4 (Option error) Operation condition (Remote, communication) Er5 (Option error) (FWD/REV, IL, VL/LU, TL) Transistor output terminal condition Er7 (Output phase loss error, impedance imbalance) Operation time (h) Trip history code Er8 (RS485 error) DC link circuit voltage (V) Multiple alarm occurrence Charge lamp When the DC link circuit voltage is higher than 50V, the charge lamp is ON. 0

JAGUAR VXM Item Explanation Protection Overload Protects the inverter by electronic thermal and detection of inverter temperature. Overvoltage Detects DC link circuit overvoltage, and stops the inverter. 400V series: 800VDC. Undervoltage Detects DC link circuit undervoltage, and stops the inverter. 400V series: 400VDC. Input phase loss Overheating Short-circuit Ground fault Motor overload DB resistor overheating Stall prevention Output phase loss Motor protection by PTC thermistor Auto reset Phase loss protection for power line input. Protects the inverter by detection of inverter temperature. Short-circuit protection for inverter output circuit. Ground fault protection for inverter output circuit (3 phase current detection method). Zero-phase current detection method (30kW or larger). Electronic thermal overload relay can be selected for standard motor or inverter rated motor. Thermal time constant (0.5 to 75.0 minutes) can be preset for a special motor. The second motor s electronic thermal overload relay can be preset for 2-motor changeover operation. Prevents DB resistor overheating by internal electronic thermal overload relay (7.5kW or smaller). Prevents DB resistor overheating by external thermal overload relay attached to DB resistor (kw or larger). (The inverter stops discharge operation to protect the DB resistor). Controls the output frequency to prevent (overcurrent) trip when the output current exceeds the limit value during acceleration. Lowers the output frequency to hold almost constant torque when the output current exceeds the limit value during operation at constant speed. Controls the output frequency to prevent (overvoltage) trip when the DC link circuit voltage exceeds the limit value during deceleration. When the inverter executes auto-tuning, detects each phase impedance imbalance and displays an Error code. When the motor temperature exceeds allowable value, the inverter trips automatically. When the inverter is tripped it can be set to automatically reset and start. Condition Installation location Free from corrosive gases, flammable gases, oil mist, dusts and direct sunlight. Indoor use only. (Installation and Altitude 000m or less. Applicable to 3000m with power derating (-0%/000m). operation) Ambient temperature -0 to +50 C. For inverters of 22kW or smaller, remove the ventilation covers when operating it at a temperature of 40 C or above. Ambient humidity 5 to 95%RH (non-condensing). Vibration 3mm from 2 to less than 9Hz, 9.8m/s 2 from 9 to less than 20Hz 2m/s 2 from 20 to less than 55Hz, m/s 2 from 55 to less than 200Hz Storage condition Temperature: -25 to +65 C, Humidity: 5 to 95%RH (non-condensing)

TERMINAL FUNCTIONS JAGUAR VXM Symbol Terminal name Function Remarks Func. code Main L/R, L2/S, Power input Connect a 3 phase power supply circuit L3/T U, V, W Inverter output Connect a 3 phase induction motor P, P(+) For DC REACTOR Connect the DC REACTOR for power-factor correcting or harmonic current reducing DC REACTOR: Option P(+), N(-) For BRAKING UNIT Connect the BRAKING UNIT (option) BRAKING UNIT (Option): kw or larger Used for DC bus connection system P(+), DB For EXTERNAL BRAKING RESISTOR Connect the EXTERNAL BRAKING RESISTOR (option) Only for 7.5kW or smaller G Grounding Ground terminal for inverter chassis (housing) R0, T0 Auxiliary control Connect the same AC power supply as that of the main circuit to back up the control power supply circuit power supply 0.75kW or smaller: Not applicable Analog input 3 Potentiometer power supply +0VDC power supply for frequency setting POT (POT: to 5kΩ) Allowable maximum output current: 0mA 2 Voltage input 0 to +0VDC/0 to 00% (0 to +5VDC/0 to 00%) Input impedance: 22kΩ F0, C30 Reversible operation can be selected by function setting. Allowable maximum input voltage: ±5VDC 0 to ±0VDC/0 to ±00% (0 to ±5VDC/0 to ±00%) If input voltage is 0 to 5VDC, the inverter Inverse mode operation can be selected by function setting or digital input signal estimates it to 0VDC +0 to 0VDC/0 to 00% (Torque control) Used for torque control reference signal H8 (PID control) Used for PID control reference signal or feedback signal F0, H2 (PG feedback) Used for reference signal of PG feedback control (option) C Current input 4 to 20mA DC/0 to 00% Input impedance: 250kΩ Inverse mode operation can be selected by function setting or digital input signal. Allowable maximum input current: 30mA DC 20 to 4mA DC/0 to 00% If input current is 20 to 30mA DC, the inverter estimates it to 20mA DC (PID control) Used for PID control reference signal or feedback signal F0, H2 (PTC-Thermistor input) The PTC-thermistor (for motor protection) can be connected to terminal C- Change over the PIN switch on control board (SW2: PTC) H26, H27 V2 Voltage input 2 0 to +0VDC Can t change over the terminal C F0 Common Common for analog signal Isolated from terminal CMY and CM Digital FWD Forward operation FWD: ON... The motor runs in the forward direction When FWD and REV are simultaneously ON, the F02 input command FWD: OFF... The motor decelerates and stops decelerates and stops REV Reverse operation REV: ON... The motor runs in the reverse direction command REV: OFF... The motor decelerates and stops X Digital input These terminals can be preset as follows ON state maximum input voltage: 2V E0 to E09 X2 Digital input 2 (maximum source current: 5mA) X3 Digital input 3 OFF state maximum terminal voltage: 22 to 27V (allowable maximum leakage current: 0.5mA) X4 Digital input 4 X5 Digital input 5 X6 Digital input 6 X7 Digital input 7 X8 Digital input 8 X9 Digital input 9 (SS) Multistep freq. (SS) : 2 (0,) different frequencies are selectable Frequency 0 is set by F0 (or C30) C05 to C9 (SS2) selection (SS, SS2) : 4 (0 to 3) different frequencies are selectable (All signals of SS to SS8 are OFF) (SS4) (SS, SS2, SS4) : 8 (0 to 7) different frequencies are selectable (SS8) (SS, SS2, SS4, SS8) : 6 (0 to 5) different frequencies are selectable (RT) ACC/DEC time selection (RT : 2 (0, ) different ACC/DEC times are selectable Time 0 is set by F07/F08 F07, F08 (RT2) (RT, RT2) : 4 (0 to 3) different ACC/DEC times are selectable (All signals of RT to RT2 are OFF) E0 to E5 (HLD) 3 wire operation Used for 3 wire operation Assigned to terminal X7 at factory setting stop command (HLD): ON... The inverter self-holds FWD or REV signal (HLD): OFF... The inverter releases self-holding (BX) Coast-to-stop (BX): ON... Motor will coast-to-stop. (No alarm signal will be output) The motor restarts from 0Hz by turning off BX H command with the operation command (FWD or REV) ON Assigned to terminal X8 at factory setting (RST) Alarm reset (RST): ON... Faults are reset. (This signal should be held for more than 0.s) During normal operating, this signal is ignored Assigned to X9 at factory setting (THR) Trip command (External fault) (THR): OFF... OH2 trip occurs and motor will coast-to-stop This alarm signal is held internally (JOG) Jogging operation (JOG): ON... JOG frequency is effective This signal is effective only while the inverter is stopped C20 (Hz2/Hz) Freq. set 2/Freq. set (Hz2/Hz): ON... Freq. set 2 is effective If this signal is changed while the inverter is running C30/F0 the signal is effective only after the inverter stops (M2/M) Motor 2/Motor (M2/M): ON... The motor circuit parameter and V/f characteristics are changed If this signal is changed while the inverter is running A0 to A8/ to the second motor s ones the signal is effective only after the inverter stops P0 to P09 (DCBRK) (TL2/TL) DC brake command Torque limiter 2/ Torque limiter (DCBRK): ON... The DC injection brake is effective. (In the inverter deceleration mode) (TL2/TL): ON... Torque limiter 2 is effective If the operation command (FWD/REV) is input while DC braking F20 to F22 is effective, the operation command (FWD/REV) has priority (SW50) Switching operation (SW50(SW60)): ON... The motor is changed from inverter operation to line operation Main circuit changeover signals are output through (SW60) between line and inverter (SW50(SW60)): OFF... The motor is changed from line operation to inverter operation Y to Y5 terminal (UP) UP command (UP): ON... The output frequency increases When UP and DOWN commands are simultaneously (DOWN) DOWN command (DOWN): ON... The output frequency decreases ON, DOWN signal is effective The output frequency change rate is determined by ACC/DEC time Restarting frequency can be selected from 0Hz or setting value at the time of stop F0, C30 (WE-KP) Write enable for KEYPAD (WE-KP): ON... The data is changed by KEYPAD F00 (Hz/PID) PID control cancel (Hz/PID): ON... The PID control is cancelled, and frequency setting by KEYPAD H20 to H25 ( or ) is effective (IVS) Inverse mode changeover (IVS): ON... Inverse mode is effective in analog signal input If this signal is changed while the inverter is running F0, C30 the signal is effective only after the inverter stops (IL) Interlock signal for 52-2 Connect to auxiliary contact (NC) of 52-2 (Hz/TRQ) TRQ control cancel (Hz/TRQ): ON... The torque control is cancelled, and ordinary operation is effective H8 (LE) Link enable (RS485, Bus) (LE): ON... The link operation is effective. Used to switch between manual RS485: Standard, Bus: option H30 operation and serial link auto mode (U-DI) Universal DI This signal is transmitted to main controller of LINK operation (STM) Pick up start mode (STM): ON... The Pick up start mode is effective H09 (PG/Hz) SY-PG enabled (PG/Hz): ON... Synchronised operation or PG-feedback operation is effective Option (SYC) Synchronised command (SYC): ON... The motor is controlled for synchronised operation between 2 axes with PGs Option (ZERO) Zero speed command (ZERO): ON... The motor speed is controlled with the speed reference of zero This function can be selected at PG feedback control. Option (STOP ) Forced stop command (STOP ): OFF... The motor decelerates and stops (STOP 2) Forced stop command (STOP 2): OFF... The motor decelerates and stops with Deceleration time 4 E5 with Deceleration time 4 (EXITE) Pre-exciting command (EXITE): ON... Motor magnetic flux is established before starting in PG vector mode PLC PLC terminal Connect PLC power supply to avoid malfunction of the inverter that has SINK type digital input, when PLC power supply is off P24 DC voltage supply DC voltage supply (+24V, maximum 00mA) E6, E7/ F40, F4 2

JAGUAR VXM Symbol Terminal name Function Remarks Func. code Analog FMA Analog monitor Output voltage (0 to 0VDC) is proportional to selected function s value as follows. Allowable maximum output current: 2mA F30 to F3 output The proportional coefficient and bias value can be preset. Output frequency (Before slip compensation) (0 to max. frequency) Output frequency 2 (After slip compensation) (0 to max. frequency) Output current (0 to 200%) Output voltage (0 to 200%) Output torque (0 to 200%) Load factor (0 to 200%) Input power (0 to 200%) PID feedback value (0 to 00%) PG feedback value (0 to max. speed) DC link circuit voltage (0 to 000V) () (Common) Universal AO (0 to 00%) Pulse FMP Pulse rate monitor Pulse rate mode: Pulse rate is proportional to selected function s value* (50% duty pulse) Allowable maximum output current: 2mA F33 to F35 Output Average voltage mode: Average voltage is proportional to selected function s value* (2670p/s pulse width control) (CM) (Common) Function to be output is same as those of analog output (FMA) CM Common Common for pulse output Isolated from terminal CMY and Transistor Y Transistor output Output the selected signals from the following items ON state maximum output voltage: 3V E20 to E23 output Y2 Transistor output 2 (Allowable maximum sink current: 50mA) Y3 Transistor output 3 OFF state maximum leakage current: 0.mA Y4 Transistor output 4 (Allowable maximum voltage: 27V) (RUN) Inverter running Outputs ON signal when the output frequency is higher than starting frequency (FAR) Frequency equivalence Outputs ON signal when the difference between output frequency and setting frequency is E30 signal smaller than FAR hysteresis width (FDT) Frequency level detection Outputs ON signal by comparison of output frequency and preset value (level and hysteresis) E3, E32 (LU) Undervoltage detection signal Outputs ON signal when the inverter stops by undervoltage while the operation command is ON. (B/D) Torque polarity Outputs ON signal in braking or stopping mode, and OFF signal in driving mode (TL) Torque limiting Output ON signal when the inverter is in torque-limiting mode (IPF) Auto-restarting Outputs ON signal during auto restart operation (Instantaneous power failure) mode. (Including restart time ) (OL) Overload early warning Outputs ON signal when the electronic thermal value is higher than preset alarm level E33 to E35 Outputs ON signal when the output current value is higher than preset alarm level (KP) KEYPAD operation mode Outputs ON signal when the inverter is in KEYPAD operation mode F02 (STP) Inverter stopping Outputs ON signal when the inverter is in stopping mode or in DC braking mode (RDY) Ready output Outputs ON signal when the inverter is ready for operation (SW88) Line/Inv changeover Outputs 88 s ON signal for Line/Inverter changeover operation (for 88) (SW52-2) Line/Inv changeover Outputs 52-2 s ON signal for Line/Inverter changeover operation (for 52-2) (SW52-) Line/Inv changeover Outputs 52- s ON signal for Line/Inverter changeover operation (for 52-) (SWM2) Motor2/Motor Outputs the motor changeover switch ON signal from motor to motor 2 A0 to A8 (AX) Auxiliary terminal Used for auxiliary circuit of 52- Refer to wiring diagram example (for 52-) (Same function as AX, AX2 terminal Jaguar VX series. (30kW or larger) (TU) Time-up signal Outputs time up signal (00ms ON pulse) at every stage end of PATTERN operation C2 to C28 (TO) Cycle completion signal Outputs one cycle completion signal (00ms ON pulse) at PATTERN operation (STG) Stage No. indication Outputs Pattern operation s stage No. by signals STG, STG2 and STG4 (STG2) Stage No. indication 2 (STG4) Stage No. indication 4 (AL) Alarm indication Outputs trip alarm No. by signals AL, AL2, AL4 and AL8 (AL2) Alarm indication 2 (AL4) Alarm indication 4 (AL8) Alarm indication 8 (FAN) Fan operation signal Outputs the inverter cooling fan operation status signal H06 (TRY) Auto-resetting Outputs ON signal at auto resetting mode. (Including Reset interval ) H04, H05 (U-DO) Universal DO Outputs command signal from main controller of Link operation (OH) Overheat early warning Outputs ON signal when the heat sink temperature is higher than (trip level 0 C) and outputs OFF signal when the temperature is lower than (trip level 5 C) (SY) Synchronisation Synchronisation completion signal for synchronised operation Option completion signal (LIFE) Lifetime alarm Outputs ON signal when the calculated lifetime is longer than preset alarm level (FDT2) 2nd Freq. level 2nd outputs ON signal by comparison of output frequency and preset value (FDT2 level) detection (OL2) 2nd OL level early 2nd outputs ON signal when the output current value is larger than preset alarm level warning (OL2 level) (COFF) Terminal C off signal Outputs ON signal when the C current is smaller than 2mA (N-EX) Speed existence signal Outputs ON signal when motor speed is larger than stop speed* on vector control with PG *stop speed = stop frequency (F25) x 20/pole (r/m) F25 CMY Common (transistor Common for transistor output signal Isolated from terminals CM and output) Relay 30A, 30B Alarm relay output Outputs a contact signal when a protective function is activated Contact rating: F36 output 30C Changeable exciting mode active or non-exciting mode active by function F36 250VAC, 0.3A, cosø=0.3 E24 Y5A, Y5C Relay output Functions can be selected the same as Y to Y4 48VDC, 0.5A, non-inductive E25 Changeable excitation mode active or non-excitation mode active by function E25 Link DX+, DX-, RS485 I/O terminal Connect the RS485 link signal SD 3

BASIC WIRING DIAGRAM JAGUAR VXM Keypad panel operation The following diagram is for reference only. For detailed wiring diagrams, refer to the relevant instruction manual. Power supply ( *) 3-phase 400 to 480V 50/60Hz MCCB or ELCB ( *2) Auxiliary control power supply( *5) Analog input *Option Digital input Earth Potentiometer power supply Voltage input Voltage input 2 or Current input Analog output (analog monitor) Pulse output (frequency monitor) Main circuit to 55 kw Jumper wire (*3) P L/R L2/S L3/T (R0) (T0) [3] [2] [] [V2] [C] [FMA] (P24) (PLC) (FWD) (REV) (CM) (X) (X2) (X3) (X4) (X5) (X6) (X7) (X8) (X9) (CM) (FMP) G Control circuit +DC0V P(+) CNUX ( ) U U2 +DC0~0V +DC24V 0V 0V N(-) 30 Pulse output (DX-) (DX+) (SD) RS485 interface port U V W G 30A 30B 30C < Y5C > < Y5A > < Y4 > < Y3 > < Y2 > < Y > < CMY > DC reactor (DCR) (*6) Earth M Motor* P P(+) N(-) G (*3) *3) 55kW or smaller: Alarm output (for any fault) Relay output Transistor output 7.5 kw or smaller P P(+) DB N(-) DBR (*4) (*6) NOTE: Common terminals [], (CM), and <CMY> for control circuits are isolated from one another. *) Use the inverter whose rated input voltage matches the power supply voltage. *2) Use this peripheral device when necessary. Terminals (P) and (P(+)] are connected with a jumper wire before shipping. When connecting an optional DC reactor (DCR)*6), remove the jumper wire that connects the terminals (P) and (P(+)]. *4) For models from 0.4 to 7.5kW, a built-in braking resistor (DBR) is connected to the inverter before shipping. (DBR is not mounted on models kw or larger.) *5) Terminals (R0) and (T0) are provided for models.5kw or larger. These terminals are not provided for models 0.75kW or smaller. Even if these terminals are not powered, the inverter can be operated. *6) For EMC compliance it is necessary to use screened/armoured cable between inverter U, V, W terminals and the motor. The screen should be terminated to earth at both ends of the cable. The appropriate power supply filter kit should also be fitted to the inverter input circuit. For further details contact IMO. Input voltage CNUX connector 400 to 440V/50Hz, 440 to 480V/60Hz U (Factory setting) 380V/50Hz (398V or smaller), U2 380 to 45V/60Hz (430V or smaller) Terminal arrangement Main circuit terminals VXM40 VXM75 VXM30KP VXM0K Control circuit terminals VXM50 VXM400 VXM32K VXM220K VXM550 VXM750 VXM00 VXM2200G 4

JAGUAR VXM External signal input operation The following diagram is for reference only. For detailed wiring diagrams, refer to the relevant instruction manual. Analog input MCCB or ELCB ( *3) Power supply ( *) 3-phase 400 to 480V 50/60Hz Auxiliary control power supply ( *7) Potentiometer power supply (*2) ( *8) 4 to 20mA Analog frequency meter (FM) 0 to 60Hz (*2) Digital input *Caution see note below Voltage input 2 0 to +0V DC (0 to +5V DC) or Current input Earth Earth ( + ) ( 0V ) ( + ) ( - ) 50Hz Digital frepuency meter (pulse counter) (*2) DC reactor (DCR) (*2) ( *9) Main circuit 3 2 P L/R L2/S L3/T (R0) (T0) [3] [2] [] [V2] [C] [FMA] (P24) (PLC) (FWD) (REV) (CM) (X) (X2) (X3) (X4) (X5) (X6) (X7) (X8) (X9) (CM) (FMP) G Control circuit to 22 kw External braking resistor (DB) (*2) (*6) 2 (THR) P DB G G (*4) +DC0V P(+) +DC0~0V +DC24V 0V 0V N(-) 30 Pulse output (DX-) (DX+) (SD) RS485 interface port P P CNUX ( ) U U2 DB 2 N (P24) Braking unit ( *2) ( *8) U V W G 30A 30B 30C < Y5C > < Y5A > < Y4 > < Y3 > < Y2 > < Y > < CMY > NOTE: Digital inputs can be source or sink depending on position of switch SW on control PCB. Do not connect (P24) to (CM) as shown or damage may occur. (*8) Earth M Motor* G Alarm output (for any fault) Relay output Transistor output 7.5 kw or smaller External braking resistor (DB) (*2) (*6) G P DB x x P(+) DB DBR (*5) (*4) 2 N(-) (THR) (P24) 30 kw or larger External braking resistor (DB) (*2) (*6) 2 (THR) P DB G G P(+) P(+)R P(+) DB 2 N(-) (P24) Braking unit ( *2) ( *8) N(-) NOTE: Common terminals [], (CM), and <CMY> for control circuits are isolated from one another. Input voltage CNUX connector 400 to 440V/50Hz, 440 to 480V/60Hz U (Factory setting) 380V/50Hz (398V or smaller), U2 380 to 45V/60Hz (430V or smaller) *Option *) Use the inverter whose rated input voltage matches the power supply voltage. *2) An optional device. Use it when necessary. *3) Use this peripheral device when necessary. *4) Terminals (P) and (P(+)] are connected with a jumper wire before shipping. When connecting an optional DC reactor (DCR) *9), remove the jumper wire that connects the terminal (P) and (P(+)]. *5) For models from 0.2 to 7.5kW, a built-in braking resistor (DBR) is connected to the inverter before shipping. (DBR is not mounted on models kw or larger.) When connecting an optional external braking resistor (DB), remove the DBR connection cables from (P(+)] and (DB) terminals. The end of the removed cables (indicated with an X) must be insulated. *6) When connecting an optional external braking resistor (DB), be sure to also use an optional braking unit *8). Connect the optional braking unit to the (P(+)] and (N(-)] terminals. Auxiliary terminals () and (2) have polarity. Be sure to connect cables to these terminals correctly. (See the diagram). *7) Terminals (R0) and (T0) are provided for models.5kw or larger. These terminals are not provided for models 0.75kW or smaller. Even if these terminals are not powered, the invertor can be operated. *8) For EMC compliance it is necessary to use screened/armoured cable between inverter U, V, W terminals and the motor. The screen should be terminated to earth at both ends of the cable. The appropriate power supply filter kit should also be fitted to the inverter input circuit. For further details contact IMO. 5

KEYPAD PANEL FUNCTIONS AND OPERATIONS Keypad Panel LED monitor In operation mode: Displays the setting frequency, output current, voltage, motor speed, or line speed. In trip mode: Displays code indicating the cause of trip. LCD monitor In operation mode : Displays various items of information such as operation condition and function data. Operation guidance, which can be scrolled, is displayed at the bottom. In program mode : Displays functions and data. Up/Down keys In operation mode : Increases or decreases the frequency or speed. In program mode : Increases or decreases function code number and data set value. Unit indication Displays the unit for the information shown on the LED monitor. Program key Switches the display to a menu screen or to the initial screen for operation mode or alarm mode. RUN FWD/REV keys In operation mode : Starts the inverter with forward or reverse operation command. Pressing the FWD or REV key lights the RUN lamp. Invalid when the function code F02 (Operation method) is set at (External signal operation). Shift key (Column shift) In program mode : Moves the cursor horizontally at data change. Pressing this key with the UP or DOWN key, the screen changes to the next function block. Stop key In operation mode : Stops the inverter. Invalid when the function code F02 (Operation method) is set at (External signal operation). Reset key In program mode : Cancels the current input data and shifts the screen. In trip mode : Releases the trip-stop state. Function/Data Select key In operation mode : Changes the displayed values of LED monitor. In program mode : Selects the function code or store the data. 6

JAGUAR VXM Keypad Panel Operation Perform the wiring shown in the Basic wiring diagram on page 4. Turn on inverter power, and use the or key to set an output frequency. Press the key, then press the or key. The inverter starts running using the factory setting function data. Press the key to stop the inverter. 7

FUNCTION SETTINGS JAGUAR VXM The functions in the white boxes can be set while the inverter is running. Other functions must be set while the inverter is stopped. Fundamental Functions Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- Basic Functions Data protection F00 DATA PRTC 0 : Data change enable : Data protection Frequency command F0 FREQ CMD 0 : KEYPAD operation ( or key) : Voltage input (terminals 2 and V2) (0 to +0VDC, 0 to +5VDC) 2 : Current input (terminal C) (4 to 20mA DC) 3 : Voltage and current input (terminals 2 and C) 4 : Reversible operation with polarity (terminal 2) (0 to ±0VDC) 5 : Reversible operation with polarity (terminals 2 and V) (0 to ±0VDC) 6 : Inverse mode operation (terminals 2 and V2) (+0 to 0VDC) 7 : Inverse mode operation (terminal C) (20 to 4mA DC) 8 : UP/DOWN control (initial freq. = 0Hz) 9 : UP/DOWN control 2 (initial freq. = last value) 0 : PATTERN operation : DI option or Pulse train input Operation method F02 OPR METHOD 0 : KEYPAD operation ( or or key) : FWD or REV command signal operation Maximum frequency F03 MAX Hz- 50 to 400Hz Hz 50 Base frequency F04 BASE Hz- 25 to 400Hz Hz 50 Rated voltage (at Base frequency ) F05 RATED V- 0 (Free), 320 to 480V V 400 Maximum voltage F06 MAX V- (at Maximum frequency ) 320 to 480V V 400 Acceleration time F07 ACC TIME 0.0 to 3600s 0.0s 6.00 20.00 Deceleration time F08 DEC TIME 0.0 to 3600s 0.0s 6.00 20.00 Torque boost F09 TRQ BOOST 0.0 : Automatic (for constant torque load) 0.0 0. to.9 : Manual (for variable torque load) 0. 2.0 to 20.0 : Manual (for constant torque load) (EV : 0.) Electronic thermal (Select) F0 ELCTRN OL 0 : Inactive overload relay : Active (for 4-pole standard motor) for motor 2 : Active (for 4-pole inverter motor) (Level) F OL LEVEL Approx. 20 to 35% of rated current 0.0A *) (Thermal time constant) F2 TIME CNST 0.5 to 75.0 min 0. min. 5.0 0.0 Electronic thermal F3 DBR OL (7.5kW or smaller) overload relay (for braking resistor) 0 : Inactive : Active (for built-in braking resistor) 2 : Active (for external braking resistor) (kw or larger) 0 : Inactive Restart mode after F4 RESTART 0 : Inactive (Trip and alarm when power failure occurs.) momentary power failure : Inactive (Trip and alarm when power recovers.) 2 3 : Inactive (Deceleration stop and alarm.) : Active (Smooth recovery by continuous operation mode) 4 : Active (Momentarily stops and restarts at output frequency of before power failure) 5 : Active (Momentarily stops and restarts at starting frequency) Frequency limit (High) F5 H LIMITER 0 to 400Hz Hz 70 (Low) F6 L LIMITER 0 to 400Hz Hz 0 Gain (for frequency F7 FREQ GAIN 0.0 to 200.0% setting signal) 0.% 00.0 Bias frequency F8 FREQ BIAS -400.0 to 400.0Hz 0.Hz 0.0 DC brake (Starting freq.) F20 DC BRK Hz 0.0 to 60.0Hz 0.Hz 0.0 (Braking level) F2 DC BRK LVL 0 to 00% % 0 (Braking time) F22 DC BRK t 0.0 (DC brake inactive). 0. to 30.0s 0.s 0.0 Starting Frequency (Freq.) F23 START Hz 0. to 60.0Hz 0.Hz 0.5 (Holding time) F24 HOLDING t 0.0 to 0.0s 0.s 0.0 Stop frequency F25 STOP Hz 0. to 6.0Hz 0.Hz 0.2 Motor sound (Carrier freq.) F26 MTR SOUND CT use VT use* 0.75 to 5kHz (Up to 55kW) 0.75 to 5kHz (Up to 22kW) 0.75 to 0kHz (75kW and above) 0.75 to 0kHz (30 to 75kW) khz 5 (Up to 55kW)* 0.75 to 6kHz (90kW and above) 0 (75kW and above)* *In case of VT use, carrier frequency should be adjusted depending on capacity. (Sound tone) F27 SOUND TONE 0 : level 0 2 : level : level 2 3 : level 3 FMA (Voltage adjust) F30 FMA V-ADJ 0 to 200% % 00 (Function) F3 FMA FUNC 0 : Output frequency (Before slip compensation) : Output frequency 2 (After slip compensation) 2 : Output current 3 : Output voltage 4 : Output torque 5 : Load factor 6 : Input power 7 : PID feedback value 8 : PG feedback value 9 : DC link circuit voltage 0 : Universal AO FMP (Pulse rate) F33 FMP PULSES 300 to 6000 p/s (at full scale) p/s 440 (Voltage adjust) F34 FMP V-ADJ 0% : Pulse rate output: 50% duty) to 200% : Voltage adjust: 2670 p/s, duty adjust) % 0 (Function) F35 FMA FUNC 0 : Output frequency (Before slip compensation) : Output frequency 2 (After slip compensation) 2 : Output current 3 : Output voltage 4 : Output torque 5 : Load factor 6 : Input power 7 : PID feedback value 8 : PG feedback value 9 : DC link circuit voltage 0 : Universal AO 30RY operation mode F36 30RY MODE 0 : The relay (30) excites on trip mode. : The relay (30) excites on normal mode. Torque limiter (Driving) F40 DRV TRQ 20 to 200, 999% (999: No limit) *2) % 80 50 (Braking) F4 BRK TRQ 0 (Automatic deceleration control), 20 to 200, 999% (999: No limit) *2) % 50 00 Torque vector control F42 TRQVECTOR 0 : Inactive : Active 8

JAGUAR VXM 9 The functions in the yellow boxes can be set while the inverter is running. Other functions must be set while the inverter is stopped. Extension Terminal Functions Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- X-X9 X terminal function E0 X FUNC Selects from the following items. Terminal X2 terminal function E02 X2 FUNC X3 terminal function E03 X3 FUNC 2 X4 terminal function E04 X4 FUNC 3 X5 terminal function E05 X5 FUNC 4 X6 terminal function E06 X6 FUNC 5 X7 terminal function E07 X7 FUNC 6 X8 terminal function E08 X8 FUNC 7 X9 terminal function E09 X9 FUNC 8 0 : (SS) : Multistep freq. selection ( to 4 bit) (SS2) 2 :} (SS4) 3 : (SS8) 4 5 : : } ACC/DEC time selection ( to 2 bit) (RT) (RT2) 6 : 3-wire operation stop command (HLD) 7 : Coast-to-stop command (BX) 8 : Alarm reset (RST) 9 : Trip command (External fault) (THR) 0 : Jogging operation (JOG) : Freq. set. 2/Freq. set. (Hz2/Hz) 2 : Motor 2/Motor (M2/M) 3 : DC brake command (DCBRK) 4 : Torque limiter 2/Torque limiter (TL2/TL) 5 : Switching operation between line and inverter (50Hz) (SW50) 6 : Switching operation between line and inverter (60Hz) (SW60) 7 : UP command (UP) 8 : DOWN command (DOWN) 9 : Write enable for KEYPAD (WE-KP) 20 : PID control cancel (Hz/PID) 2 : Inverse mode changeover (terminals 2 and C) (IVS) 22 : Interlock signal for 52-2 (IL) 23 : TRQ control cancel (Hz/TRQ) 24 : Link enable (Bus, RS485) (LE) 25 : Universal DI (U-DI) 26 : Pick up start mode (STM) 27 : SY-PG enable (PG/Hz) 28 : Synchronisation command (SYC) 29 : Zero speed command (ZERO) 30 : Forced stop command (STOP ) 3 : Forced stop command with Deceleration time 4 (STOP 2) 32 : Pre-exciting command (EXITE) ACC, 2,3,4 Acceleration time 2 E0 ACC TIME 2 0.0 to 3600s 0.0s 0.0 00.00 DEC 2,3,4 Deceleration time 2 E DEC TIME 2 0.0s 0.0 00.00 Acceleration time 3 E2 ACC TIME 3 0.0s 5.0 00.00 Deceleration time 3 E3 DEC TIME 3 0.0s 5.0 00.00 Acceleration time 4 E4 ACC TIME 4 0.0s 3.0 00.00 Deceleration time 4 E5 DEC TIME 4 0.0s 3.0 00.00 Torque limiter 2 (Driving) E6 DRV TRQ 2 20 to 200%, 999% (999: No limit) *2) % 80 50 (Braking) E7 BRK TRQ 2 0 (Automatic deceleration control), 20 to 200%, 999% (999: No limit) *2) % 50 00 Y-Y5C Y terminal function E20 Y FUNC Selects from the following items Terminal Y2 terminal function E2 Y2 FUNC Y3 terminal function E22 Y3 FUNC 2 Y4 terminal function E23 Y4 FUNC 7 Y5A, Y5C terminal function E24 Y5 FUNC 0 0 : Inverter running (RUN) : Frequency equivalence signal (FAR) 2 : Frequency level detection (FDT) 3 : Undervoltage detection signal (LU) 4 : Torque polarity (B/D) 5 : Torque limiting (TL) 6 : Auto-restarting (IPF) 7 : Overload early warning (OL) 8 : KEYPAD operation mode (KP) 9 : Inverter stopping (STP) 0 : Ready output (RDY) : Line/Inv changeover (for 88) (SW88) For Line/Inverter changeover 2 : Line/Inv changeover (for 52-2) (SW52-2)} operation 3 : Line/Inv changeover (for 52-) (SW52-) 4 : Motor 2/Motor (SWM2) 5 : Auxiliary terminal (for 52-) (AX) 6 : Time-up signal (TU) 7 : Cycle competition signal (TO) 8 : Stage No. indication (STG) For PATTERN operation 9 : Stage No. indication 2 (STG2)} 20 : Stage No. indication 4 (STG4) 2 : Alarm indication (AL) 22 : Alarm indication 2 (AL2) For Alarm signal output 23 : Alarm indication 4 (AL4) } 24 : Alarm indication 8 (AL8) 25 : Fan operation signal (FAN) 26 : Auto-resetting (TRY) 27 : Universal DO (U-DO) 28 : Overheat early warning (OH) 29 : Synchronisation completion signal (SY) 30 : Lifetime alarm (LIFE) 3 : 2nd Freq. level detection (FDT2) 32 : 2nd OL level early warning (OL2) 33 : Terminal C off signal (COFF) 34 : Speed existence signal (N-EX) Y5RY operation mode E25 Y5RY MODE 0 : Inactive (Y5 Ry excites at ON signal mode.) : Active (Y5 Ry excites at OFF signal mode.) FAR function signal (Hysteresis) E30 FAR HYSTR 0.0 to 0.0Hz 0.Hz 2.5 FDT function signal (Level) E3 FDT LEVEL 0 to 400Hz Hz 50 (Hysteresis) E32 FDT HYSTR 0.0 to 30.0Hz 0.Hz.0 OL function signal (Mode select) E33 OL WARNING 0 : Thermal calculation : Output current (Level) E34 OL LEVEL Approx. 5 to 200% of rated current 0.0A * (Timer) E35 OL TIMER 0.0 to 60.0s 0.s 0.0 FDT2 function (Level) E36 FDT2 LEVEL 0 to 400Hz Hz 50 OL2 function (Level) E37 OL2 LEVEL Approx. 5 to 200% of rated current 0.0A *

FUNCTION SETTINGS JAGUAR VXM The functions in the white boxes can be set while the inverter is running. Other functions must be set while the inverter is stopped. Extension Terminal Functions (cont d) Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- LED & LCD Display coefficient A E40 COEF A -999.00 to 999.00 0.0 0.0 Monitor Display coefficient B E4 COEF B -999.00 to 999.00 0.0 0.00 LED Display filter E42 DISPLAY FL 0.0 to 5.0s 0.s 0.5 LED Monitor (Function) E43 LED MNTR 0 : Output frequency (Before slip compensation) (Hz) : Output frequency 2 (After slip compensation) (Hz) 2 : Setting frequency (Hz) 3 : Output current (A) 4 : Output voltage (V) 5 : Motor synchronous speed)r/min) 6 : Line speed (m/min) 7 : Load shaft speed (r/min) 8 : Torque calculation value (%) 9 : Input power 0 : PID reference value : PID reference value (remote) 2 : PID feedback value (Display at STOP mode) E44 LED MNTR2 0 : Setting value : Output value LCD Monitor (Function) E45 LCD MNTR 0 : Displays operation guidance : Bar graph (Output freq. Output current and Output torque) Language E46 LANGUAGE 0 : Japanese : English 2 3 : German : French 4 : Spanish 5 : Italian LCD Monitor (Contrast) E47 CONTRAST 0 (Soft) to 0 (Hard) 5 The functions in the white boxes can be set while the inverter is running. Other functions must be set while the inverter is stopped. Control Functions of Frequency Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- Jump Hz Jump (Jump freq. ) C0 JUMP Hz 0 to 400Hz Hz 0 Control frequency (Jump freq. 2) C02 JUMP Hz 2 Hz 0 (Jump freq. 3) C03 JUMP Hz 3 Hz 0 (Hysteresis) C04 JUMP HYSTR 0 to 30Hz Hz 3 Multi-Hz Multistep (Freq. ) C05 MULTI Hz- 0.00 to 400.00Hz 0.0Hz 0.00 Control frequency setting (Freq. 2) C06 MULTI Hz-2 0.0Hz 0.00 (Freq. 3) C07 MULTI Hz-3 0.0Hz 0.00 (Freq. 4) C08 MULTI Hz-4 0.0Hz 0.00 (Freq. 5) C09 MULTI Hz-5 0.0Hz 0.00 (Freq. 6) C0 MULTI Hz-6 0.0Hz 0.00 (Freq. 7) C MULTI Hz-7 0.0Hz 0.00 (Freq. 8) C2 MULTI Hz-8 0.0Hz 0.00 (Freq. 9) C3 MULTI Hz-9 0.0Hz 0.00 (Freq. 0) C4 MULTI Hz0 0.0Hz 0.00 (Freq. ) C5 MULTI Hz 0.0Hz 0.00 (Freq. 2) C6 MULTI Hz2 0.0Hz 0.00 (Freq. 3) C7 MULTI Hz3 0.0Hz 0.00 (Freq. 4) C8 MULTI Hz4 0.0Hz 0.00 (Freq. 5) C9 MULTI Hz5 0.0Hz 0.00 JOG frequency C20 JOG Hz 0.00 to 400.00Hz 0.0Hz 5.00 PATTERN PATTERN (Mode select) C2 PATTERN 0 : Active (Mono-cycle operation, and then stops.) Operation operation : Active (Continuous cyclic operation while operation command is effective.) 2 : Active (Mono-cycle operation then continues at final frequency.) (Stage ) C22 STAGE Operation time: 0.00 to 6000s 0.0s 0.00 F (Stage 2) C23 STAGE 2 F to F4 and R to R4 0.0s 0.00 F (Stage 3) C24 STAGE 3 Code FWD/REV ACC/DEC 0.0s 0.00 F (Stage 4) C25 STAGE 4 F: FWD ACC/DEC 0.0s 0.00 F (Stage 5) C26 STAGE 5 F2: FWD ACC2/DEC2 0.0s 0.00 F (Stage 6) C27 STAGE 6 F3: FWD ACC3/DEC3 0.0s 0.00 F (Stage 7) C28 STAGE 7 F4: FWD ACC4/DEC4 0.0s 0.00 F *Setting for R: REV ACC/DEC operation time, R2: REV ACC2/DEC2 FWD/REV rotation and R3: REV ACC3/DEC3 ACC/DEC time select. R4: REV ACC4/DEC4 Frequency command 2 C30 FREQ CMD 2 0 : KEYPAD operation ( or key) : Voltage input (terminal 2) (0 to +0VDC, 0 to +5VDC) 2 : Inactive 3 : Inactive 4 : Reversible operation with polarity (terminal 2) (0 to ±0VDC) 5 6 : Reversible operation with polarity (terminal 2 and V) (0 to ±0VDC) : Inverse mode operation (terminal 2) (+0 to 0VDC) 2 7 : Inactive 8 : UP/DOWN control (initial freq. = 0Hz) 9 : UP/DOWN control 2 (initial freq. = last value) 0 : PATTERN operation : DI option or Pulse train input Bias (Terminal 2) C3 BIAS 2-00 to +00.0% 0.% 0.0 Gain (Terminal 2) C32 GAIN 2 0.0 to +200.0% 0.% 00.0 Analog setting signal filter C33 REF FILTER 0.00 to 5.00s 0.0s 0.05 20

EXTENSION TERMINAL FUNCTIONS 2 Motor Parameters Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- Motor Number of motor poles P0 M POLES 2 to 4 2 4 Motor (Capacity) P02 M-CAP 22kW or smaller : 0.0 to 45.00kW 30kW or larger : 0.0 to 500.00kW 0.0kW *) (Rated current) P03 M-lr 0.00 to 2000A 0.0A *) (Tuning) P04 M TUN 0 : Inactive : Active (Tuning of %R and %X (static test)) 2 : Active (Tuning of %R, %X and lo (dynamic test)) (On-line Tuning) P05 M TUN2 0 : Inactive : Active (Real time tuning of %R2) (No-load current) P06 M-lo 0.00 to 2000A 0.0A *) (%R setting) P07 M-%R 0.00 to 50.00% 0.0% *) (%X setting) P08 M-%X 0.00 to 50.00% 0.0% *) (Slip compensation control ) P09 SLIP COMP 0.00 to +5.00 0.0Hz 0.00 High Performance Functions The functions in the white boxes can be set while the inverter is running. Other functions must be set while the inverter is stopped. Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- High Data initialising H03 DATA INIT 0 : Manual set value Performance (Data reset) : Return to factory set value Functions Auto-reset (Times) H04 AUTO-RESET 0 (Inactive), to 0 times 0 (Reset interval) H05 RESET INT 2 to 20s s 5 Fan stop operation H06 FAN STOP 0 : Inactive : Active (Fan stops at low temperature mode) ACC/DEC (Mode select) H07 ACC PTN 0 : Linear pattern 2 : S-curve (weak) : S-curve (strong) 3 : Non-linear (For variable torque load) Rev. phase sequence lock H08 REV LOCK 0 : Inactive : Active Start mode H09 START MODE 0 : Inactive (Rotating motor pick-up) : Active (Only when Auto-restart after momentary power failure mode) 2 : Active (All start modes) Energy-saving operation H0 ENERGY SAV 0 : Inactive : Active (Only when torque boost F09 is set at manual setting mode.) 0 (EV : ) DEC mode H DEC MODE 0 : Normal (according to H07 mode) : Coast-to-stop Instantaneous overcurrent H2 INST CL 0 : Inactive limiting : Active Auto-restart (Restart time) H3 RESTART t 0. to 0.0s 0.s 0. 0.5 (Freq. fall rate) H4 FALL RATE 0.00 to 00.00Hz/s 0.0Hz/s 0.00 (Holding DC voltage) H5 HOLD V 400 to 600V V 470 (OPR command selfhold time) H6 SELFHOLD t 0.0 to 30.0s, 999s (999s : The operation command is held while DC link circuit voltage is larger than 50V.) 0.s 999 Torque control H8 TRQ CTRL 0 : Inactive (Frequency control) : Active (Torque control by terminal 2 (Driving)) (0 to +0V/0 to 200%) 2 : Active (Torque control by terminal 2 (Driving and Braking) (0 to ±0V/0 to ±200%) Active drive H9 AUT RED 0 : Inactive : Active PID PID control (Mode select) H20 PID MODE 0 : Inactive Control : Active (PID output 0 to 00%/frequency 0 to max.) 2 : Active (Inverse operation mode: PID output 0 to 00%/frequency max. to 0) (Feedback signal) H2 FB SIGNAL 0 : Terminal 2 (0 to +0V) 2 : Terminal C (4 to 20mA) : Terminal 2 (+0 to 0V) 3 : Terminal C (20 to 4mA) (P-gain) H22 P-GAIN 0.0 to 0.00 0.0 0.0 (I-gain) H23 I-GAIN 0.0: Inactive 0. to 3600.0s 0.s 0.0 (D-gain) H24 D-GAIN 0.00: Inactive 0.0 to 0.0s 0.0s 0.00 (Feedback filter) H25 FB FILTER 0.0 to 60.0s 0.s 0.5 Y-Y5C Terminal PTC thermistor (Mode select) H26 PTC MODE 0 : Inactive : Active (Level) H27 PTC LEVEL 0.00 to 5.00V 0.0V.60 Droop operation H28 DROOP -9.9 to 0.0Hz 0.Hz 0.0 Serial Serial link (Function select) H30 LINK FUNC (Code) (Monitor) (Frequency command) (Operation command) Link 0 : X x : Valid : X X : Invalid 2 : X X 3 : X X X RS 485 (Address) H3 485 ADDRESS to 3 (Mode select on no H32 MODE ON ER 0 : Trip and alarm (Er8) response error) : Operation for H33 timer and alarm (Er8) 2 : Operation for H33 timer and retry to communicate. *If the retry fails, then the inverter trips ( Er8 ) 3 : Continuous operation (Timer) H33 TIMER 0 to 60.0s 0.s 2.0 (Baud rate) H34 BAUD RATE 0 : 9200 bit/s : 9600 2 : 4800 3 : 2400 4 : 200 (Data length) H35 LENGTH 0 : 8 bit : 7 bit (Parity check) H36 PARITY 0 : No checking : Even parity 2 : Odd parity (Stop bits) H37 STOP BITS 0 : 2 bit : bit (No response error) H38 NO RES t 0 (No detection), to 60s detection time) s 0 (Response interval) H39 INTERVAL 0.00 to.00s 0.0s 0.0

FUNCTION SETTINGS JAGUAR VXM The functions in the white boxes can be set while the inverter is running. Other functions must be set while the inverter is stopped. Alternative Motor Parameters Function Min. Factory setting Setting range Code Name LCD monitor unit -22kW 30kW- Motor 2 Maximum frequency 2 A0 MAX Hz-2 50 to 400Hz Hz 50 Base frequency 2 A02 BASE Hz-2 25 to 400Hz Hz 50 Rated voltage (at Base frequency 2) A03 RATED V-2 0 (Free), 320 to 480V V 400 Maximum voltage 2 A04 MAX V-2 320 to 480V (at Maximum frequency 2) V 400 Torque boost 2 A05 TRQ BOOST2 0.0 : Automatic (for constant torque load).0 0. to.9 : Manual (for variable torque load) (EV : 0) 2.0 to 20.0 : Manual (for constant torque load) Electronic (Select) A06 ELCTRN OL2 0 : Inactive thermal : Active (for 4-pole standard motor) overload relay 2 : Active (for 4-pole inverter motor) for motor 2 (Level) A07 OL LEVEL2 Approx. 20 to 35% of rated current 0.0A *) (Thermal time constant) A08 TIME CNST2 0.5 to 75.0 min 0. min 5.0 0.0 Torque vector control 2 A09 TRQVECTOR2 0 : Inactive : Active Number of motor 2 poles A0 M2 POLES 2 to 4 2 4 Motor 2 (Capacity) A M2-CAP 22kW or smaller : 0.0 to 45.00kW 30kW or larger : 0.0 to 500.00kW 0.0kW *) (Rated current) A2 M2-lr 0.00 to 2000A 0.0A *) (Tuning) A3 M2 TUN 0 : Inactive : Active (Tuning of %R and %X (static test)) 2 : Active (Tuning of %R, %X and lo (dynamic test)) (On-line Tuning) A4 M2-TUN2 0 : Inactive : Active (Real time tuning of %R and %X) (No-load current) A5 M2-lo 0.00 to 2000A 0.0A *) (%R setting) A6 M2-%R 0.00 to 50.00% 0.0% *) (%X setting) A7 M2-%X 0.00 to 50.00% 0.0% *) Slip compensation control 2 A8 SLIP COMP2 0.00 to +5.00Hz 0.0Hz 0.00 Notes: *) Typical value of standard IMO 4P motor. *2) Percent shall be set according to FUNCTION CODE: P02 or A09, motor capacity. Torque referenced here may not be obtainable when DATA CODE: 0 is selected for FUNCTION CODE: P02 or A09. 22

PROTECTIVE FUNCTIONS Function Description LED monitor Overcurrent Stops running to protect inverter from an overcurrent resulting from overload. During protection Stops running to protect inverter from an overcurrent due to a short-circuit in the acceleration (Short-circuit) output circuit. During (Earth fault) deceleration Stops running to protect inverter from an overcurrent due to an earth fault in the While running at output circuit. constant speed Stops running to protect inverter from an overcurrent resulting from earth fault in 30kW or larger model the output circuit by detecting zero-phase current. only Earth Overvoltage The inverter stops when it detects an overvoltage in the DC link circuit. 400V series: 800VDC or During protection more acceleration Protection is not assured During if excess AC line voltage is deceleration applied inadvertently. While running at constant speed Incoming surge Protects the inverter against surge voltage between the main circuit power line and The inverter may be tripped by some other protection earth. protective function. Protects the inverter against surge voltage in the main circuit power line. Undervoltage Stops the inverter when the DC link circuit voltage drops below undervoltage level. 400V series : 400VDC or less protection 200V series : 200VDC or less Input phase loss The inverter is protected from being damaged when open-phase fault occurs. protection Overheat Stops the inverter when it detects excess heat sink temperature in case of protection cooling fan failure or overload. Stops the inverter when it detects an abnormal rise in temperature in the inverter unit caused by insufficient ventilation in cubicles or an abnormal ambient temperature. Stops the inverter when it detects an abnormal rise in temperature inside the inverter. When the built-in braking resistor overheats, the inverter stops discharging and 7.5kW or smaller model only running. Function data appropriate for the resistor type (built-in/external) must be set. Electronic thermal This function stops the inverter by detecting an inverter overload. overload relay This function stops the inverter by detecting an overload in a standard motor or Motor overload (Motor protection) inverter motor. Motor 2 overload Fuse blown When a blown fuse is detected, the inverter stops running. 30kW or larger model only Stall prevention When an output current exceeds the limit during acceleration, this function lowers The stall prevention function can be disabled. (Momentary output frequency to prevent an OC trip. overcurrent limitation) Active drive During running in which acceleration is 60s or longer, this function increases the The acceleration time can be prolonged up to acceleration time to prevent the occurrence of an OLU trip. three times the preset time. External alarm input The inverter stops on receiving external alarm signals. Use THR terminal function (digital input). Overspeed Stops the inverter when the output frequency exceeds the rated maximum protection frequency by 20%. PG error Alarm output if encoder (PG) signals are disconnected. Alarm output The inverter outputs a relay contact change over signal. Output terminals: 30A, 30B and 30C (for any fault) Use the RST terminal function for signal input. Alarm reset An alarm-stop state of the inverter can be cleared with the RESET key or by a Even if main power input is turned off, alarm command digital input signal (RST). history and trip-cause data are retained. Alarm history memory Storage of data on cause of trip Memory error Stores up to four previous alarm conditions. The inverter will store and display details of the latest alarm history data. The inverter checks memory data after power-on and when the data is written. If a memory error is detected, the inverter trips. KEYPAD panel If an error is detected in communication between the inverter and KEYPAD when When operated by external signals, the inverter communication the Keypad panel is being used, the inverter trips. continues running. The alarm output (for any error fault) is not output. Only Er2 is displayed. CPU error If the inverter detects a CPU error caused by noise or some other factor, the inverter trips. Option If a checksum error or disconnection is detected during communication, the communication error inverter issues an alarm. Option error Output phase loss error If a linkage error or other option error is detected, the inverter issues an alarm. If an unbalance of output circuits is detected during auto-tuning, this function issues an alarm (and trips the inverter). RS485 If an RS485 communication error is detected, the inverter issues an alarm. communication error NOTES: ) Retaining alarm signal when auxiliary control power supply is not used: If the inverter power supply is cut off while an internal alarm signal is being output, the alarm signal cannot be retained. 2) To issue the RESET command, press the key on the KEYPAD panel or connect terminals RST and P24 and disconnect them afterwards. 3) Fault history data is stored for the past four trips. 23

EXTERNAL DIMENSIONS JAGUAR VXM Fig. VXM40 VXM75 Fig. 2 VXM50 VXM400 Type D D4 D5 VXM40 30 36.5 80 VXM75 45 5.5 95 Fig. 3 VXM550 VXM750 Fig. 4 VXM00 VXM2200G 24

JAGUAR VXM Fig. 5 Fig. 6 Internal mounting type (30kW or larger) External cooling type (30kW or larger) KEYPAD panel (Common for all models) W W 2 or 3 - øc H2 H5 H H4 H D D ø5 or ø8 Lifting hole D2 D D D2 ø5 or ø8 Lifting hole C Panel drilling W 4 or 6-Bolt Panel cutting W2 W 4 or 6-Bolt H H3 H6 H Power Nominal Dimensions (mm) Mtg. supply applied Type Bolt voltage motor (kw) W W W2 H H H2 H3 H4 H5 H6 D D D2 C 400V 30 VXM30K/VXM30KP 340 240 326 255 645 530 500 52 37 VXM37K 2 25 9 270 45 0 M8 45 VXM45K 375 275 36 770 655 625 637 55 VXM55K 75 VXM75K 835 720 690 702 90 VXM90K 0 VXM0K 32 VXM32K 60 VXM60K 200 VXM200K 220 VXM220K 530 430 50 680 580 660 827.5 70 675 685 35 75 5.5 32.5 2.5 5 M2 087.5 970 935 945 360 220 4 280 VXM280K 35 VXM35K Available soon 25

OPTIONS JAGUAR VXM Reactor, Filter and Other Accessories Name Function Mounting position Surge arrester Suppresses induced transient surges from power source, thus protecting all (Contact IMO) equipment connected to the power supply. Ferrite ring for reducing Reduces radio frequency noise. If the wiring between motor and inverter is radio noise shorter than 20m, use the ferrite ring in the power supply side. If longer than (OC-OC5) 20m, use it in the output side, if required. Dynamic brake resistor Converts excess regenerated energy into heat. A light duty resistor is supplied as (DBR R W) standard for drives less than kw. For higher powers/duty, extra resistors or additional equipment is necessary. RFI Filter This is a special filter which complies with the European EMC (Emission) Directive. (RFM FP/K) This filter should be used with a screened motor cable. Note: Other prerequisites must be fulfiled to ensure compliance with EMC Directives. Refer to IMO for details. Optional Sin O/P filter Connected to the output circuit of inverters under low-noise operation with (Contact IMO) carrier frequency from 8 to 5kHz, (6kHz higher for 30kW or larger inverters), this filter has the following functions:. Suppresses fluctuation of motor terminal voltage. Protects the motor insulation from being damaged by PWM voltage overshoot. (400V series) 2. Suppresses leakage current from output side wiring. Reduces leakage current caused when several motors are operated in parallel or connected with long wiring. *Total wiring length should be less than 400m. 3. Suppresses radial noise or inductive coupling from output side wiring. Effective noise suppression device for long wiring applications such as plant. Note: When connecting this filter, set the carrier frequency F26 at 8kHz or more. DC Reactor (DCR) (Use the DCR to normalise the power supply in the following cases.] (VXMLC) (optional for. The power transformer capacity is 500kVA or over and exceeds the inverter smaller power ratings) rated capacity by 0 times. 2. The inverter and a thyristor converter are connected with the same transformer. * Check if the thyristor converter uses a commutation reactor. If not, AC reactor must be connected to the power supply side. 3. Overvoltage trip occurs due to open/close of the phase-advancing capacitor for the power supply lines. 4. The voltage unbalance exceeds 2%. Voltage unbalance (%) = Max. voltage [V] - Min. Voltage [V] x 67 (%) Three-phase average voltage [V] AC Reactor (ACR) (LO -3) Frequency meter (X72M0V) Frequency setting device (JAGPOTK) Output relay and DIN rail base (VXEJ) (For improving input power-factor, reducing harmonics) Used to reduce input harmonic current (correcting power-factor) For the resultant effects, contact IMO. Optional. May be fitted to compensate for long motor cables, or shock loads Analog frequency meter 72mm square, 0-0VDC, M/C, 000 /V Frequency setting potentiometer (mounted externally) Low power DC coil, 8A capacity, for extending VXM digital outputs Y-Y4. * * Screened motor cable not shown for simplicity 26

JAGUAR VXM EMC Filter, DC Reactor EMC filters (typical) Fig. A Fig. B Inverter type Filter Rated (and use) required current (A) Fig. Dimensions (mm) W W H H H2 H3 D VXM40-75 RFM75FP 5 6 90 30 293 265 0 42 VXM50-400 RFM400FP 2 55 05 30 293 265 0 45 VXM550-750 RFM750FP 35 A 225 67 33 3 260 0 47.5 VXM00-500 RFM500FP 50 250 85 480 449 400 20 70 VXM850-2200G RFM2200FP 72 250 85 480 449 400 20 70 VXM30K (CT) -30KP RFM30K 00 200 66 435 408 30 VXM30K (VT) -90K (CT) RFM90K 80 B 200 66 495 468 60 VXM90K (VT) -32K (CT) RFM32K 280 250 70 587 560 205 Fig. C VXM32K (VT) -220K (CT) RFM220K 400 C 250 70 587 560 205 VXM220K (VT) -35K RFM35K 880 * 364 300 688 648 80 * See Jaguar VXM instruction manual or contact IMO for details DC reactors (typical) Fig. A Fig. B Fig. C Power Nominal Typical dimensions, mm Typical supply applied Inverter type Reactor Fig. mass voltage motor (kw) type A B C D E F G H Terminal screw (kg) Three 0.4 VXM40 * A 66 56 72 90 60 35 5.2 x 8 94 M4.0 phase 400V 0.75 VXM75 * A 66 56 72 90 60 40 5.2 x 8 94 M4.4.5 VXM50 * A 66 56 72 90 60 45 5.2 x 8 94 M4.6 2.2 VXM220 * A 86 7 80 00 65 45 6 x 9 0 M4 2.0 4.0 VXM400 * A 86 7 80 00 70 50 6 x 9 0 M4 2.6 5.5 VXM550 * A 86 7 80 00 70 50 6 x 9 0 M4 2.6 7.5 VXM750 * A 95 80 00 75 60 7 x 30 M5 4.2 VXM00 VXLC A 95 80 00 75 60 7 x 30 M5 4.3 5 VXM500 VXLC5 A 46 24 96 20 75 60 7 x 7 M5 5.9 8.5 VXM850 VXLC8 A 46 24 96 20 85 65 7 x 7 M6 7.2 22 VXM2200G VXLC22 A 46 24 96 20 85 65 7 x 7 M6 7.2 30 VXM30K VXLC30 B 52 90 5 57 00 78 8 30 M8 3 37 VXM37K VXLC37 B 7 0 0 50 00 75 8 50 M8 5 45 VXM45K VXLC45 B 7 0 25 65 0 82 8 50 M8 8 55 VXM55K VXLC55 B 7 0 30 70 0 85 8 50 M8 20 75 VXM75K VXLC75 C 90 60 5 5 00 75 0 240 M0 20 90 VXM90K VXLC90 C 90 60 25 6 20 80 0 250 ø2 23 0 VXM0K VXLC0 C 90 60 25 6 20 80 0 250 ø2 25 32 VXM32K VXLC32 C 200 70 35 7 20 85 0 260 ø2 28 60 VXM60K VXLC60 C 20 80 35 7 20 85 2 290 ø2 32 200 VXM200K VXLC200 C 20 80 35 7 40 90 2 295 ø2 35 220 VXM220K VXLC220 C 220 90 35 7 40 90 2 300 ø5 40 280 VXM280K VXLC280 C 220 90 45 8 50 95 2 320 ø5 45 35 VXM35K VXLC35 Available soon NOTE: () A DC reactor must be used for 75kW and above. (2) The above drawings, masses and dimensions are intended as a guide only. Product details may be subject to change without prior notice. If in doubt contact IMO Ltd. *Please contact IMO for details. 27

OPTIONS JAGUAR VXM Braking Unit, Braking Resistor Continuous braking (00% Repetitive braking Continuous braking Repetitive braking Inverter Option CT VT torque conversion value) (00s or less cycle) (MAX. braking torque) (00s or less cycle) Power supply Constant Torque Rating (CT) Variable Torque Rating (VT) Braking Braking Max. Braking Discharging Duty Average Max. Braking Discharging Duty Average voltage Unit resistor braking time capability cycle loss braking time capability cycle loss Motor Inverter Motor Inverter (kw) type (kw) type Type Qty (min) kw torque (s) (kws) (%) (kw) torque (s) (kws) (%) (kw) (%) (%) Three- 0.4 VXM40 200 0.2 45 9 22 0.044 phase 0.75 VXM75 200 0.2 45 7 8 0.068 400V.5 VXM50 60 0.4 45 34 0 0.075 2.2 VXM220 60 0.4 30 33 7 0.077 4.0 VXM400 30 0.4 20 37 5 0.093 5 37 3.5 0.093 5.5 VXM550 7.5 VXM550 80 0.8 50% 20 55 5 0.38 5 55 3.5 0.38 7.5 VXM750 VXM750 60 0.9 0 38 5 0.88 7 38 3.5 0.88 VXM00 5 VXM00 40.4 0 55 5 0.275 00% 7 55 3.5 0.275 5 VXM500 8.5 VXM500 VXDBU 35.4 0 75 5 0.375 8 75 4 0.375 8.5 VXM850 22 VXM850-22 27.8 0 93 5 0.463 8 93 4 0.463 22 VXM2200G 22.8 8 88 5 0.55 6 88 3 0.55 30 VXM30KP VXDBU 5 3.6 0 50 0.5 30 VXM30K 37 VXM30K 30-37 5 3.6 0 50 0.5 0 50 0.5 37 VXM37K 45 VXM37K 2 4.8 0 85 0.85 0 85 0.85 VXDBU 45 VXM45K 55 VXM45K 0 6 0 225 0 2.25 0 225 0 2.25 45-55 55 VXM55K 75 VXM55K 7.5 7.2 0 275 0 2.75 0 275 0 2.75 75 VXM75K 90 VXM75K VXDBU 6 9.6 00% 0 375 0 3.75 0 375 0 3.75 90 VXM90K 0 VXM90K 75-90 5 2 0 450 0 4.5 75% 0 450 0 4.5 0 VXM0K 32 VXM0K VXDBU 3.75 4.4 0 550 0 5.5 0 550 0 5.5 32 VXM32K 60 VXM32K 0-32 3.33 8 0 660 0 6.6 0 660 0 6.6 60 VXM60K 200 VXM60K VXDBU 3.0 9.2 0 800 0 8.0 0 800 0 8.0 200 VXM200K 220 VXM200K 2.5 24 0 000 0 0.0 0 000 0 0.0 60-220 220 VXM220K 280 VXM220K.88 28.8 0 00 0.0 0 00 0.0 280 VXM280K 35 VXM280K Available soon 35 VXM35K 400 VXM35K NOTE: The braking time and duty cycle (%) are calculated as the constant-torque braking used for deceleration. 00% Braking power T Duty cycle (%) = T0 x 00[%] Braking time T Braking interval T0 Braking time T (Procedure for selecting options) All three conditions listed below must be satisfied.. The maximum braking torque does not exceed the value shown in the table. 2. The energy discharged in the resistor for each braking (the area of the triangle shown in the above figure) does not exceed the discharging capability (kws) in the table. 3. The average loss (energy discharged in the resistor divided by a braking interval) does not exceed the average loss (kw) shown in the table. 28

JAGUAR VXM Name (type) Braking unit Fig.A 65.5 0 40 30 5 5 Fig.B Dimensions Mounting hole Fig.C 52.5 9 4.5 N.P 60 70 H2 H H H2 H H 30 4.5 5 W W 6 5 7.5 D.2 W W 6 5 7.5 D D Dimensions (mm) Mass Voltage Type Fig. (kg) W W H H H2 D D VXDBU -22 A See Fig. A. VXDBU 30-37 B 50 00 4 400V VXDBU 45-55 280 265 250 230 30.2 5.5 Series VXDBU 75-90 60 C VXDBU 0-32 370 355 340 9 250 50 2.4 VXDBU 60-220 450 435 420 3 Braking resistors (typical combinations for heavier duty applications) Example PE380H 60 380W Covers: VXM50 VXM400 60 380W Covers: VXM550 VXM750 80 760W Covers: VXM00 VXM2200G 40 520W Example 2 PE50H 20 50W Covers: VXM40 VXM75 20 50W Ferrite ring Dimensions C H L L2 L3 U V W Ferrite ring Motor M X W Y D Filter Inverter Optional ferrite ring wiring position for further HF noise reduction (if required) Part No. Centre Width Height Depth Mounting Mounting Mounting Hole C W H D Dim X Dim Y Holes Dia Ferrite2 (OC) 2 85 46 22 70 5 Ferrite28.5 (OC2) 28.5 05 62 25 90 5 Ferrite50 (OC3) 50 50 0 50 25 30 5 Ferrite58 (OC4) 58 200 70 65 80 45 6 29

JAGUAR VXM Option Cards and Other Options Name (type) Function Specifications Relay output card Includes four relay output circuits. (VXMROC) Converts transistor output signals from inverter control output terminals Y to Y4 to relay (SPDT) output signals. Digital I/O interface card For setting frequency using a binary code. (VXMDI0) For monitoring frequency, output current and output voltage using a binary code. For input and output of other individual signals. Analog I/O interface card For setting a torque limit value using an input analog signal. (VXMAI0) For input of auxiliary signal to set frequency. For analog monitoring of inverter output frequency, output current and torque. T-link interface card For setting a frequency. Used together with MICREX-F series PLC. (OPC-GS-TL) For setting and reading function data for function codes. For setting operation commands (FWD, REV, RST, etc.). For monitoring the operation status. For reading trip information. PG feedback card For performing PG vector control using feedback signals Applicable Pulse Encoder specification: (VXMEFC) obtained from an encoder. 00 to 3000P/R A, B, Z phase 2V or 5V Synchronised operation card Wait and synchronise mode, simultaneous start and (VXMSYN) synchronising mode. Proportional speed operation. Speed control by pulse train input can be made. Extension cable for keypad Connects the keypad panel to an inverter unit. Type Nominal length Maximum length (VXPODCABLE) Three cable types are available: straight 2m, curled m and curled 2m. VXPODCABLE 2m 2m The curled m cable can be extended up to 5m, and the curled 2m cable up to 0m. CONTACT IMO m 5m Note: Cables once extended to the maximum length do not return to their original length. CONTACT IMO 2m 0m Copy unit For batch data transfer (read, store, write) between an Application (VXMCOPY) inverter unit and the copy unit. Copying For comparison of data stored in an inverter and data stored Vertification in the copy unit. Editing For comparison of two sets of data stored in the copy unit. Write protect For editing a part of the data stored in an inverter. Write protection is available in copy mode and edit mode. The copy unit can write data to inverter memory even though the inverter is not connected to power source. IP20 enclosure adaptor Used to put 30kW or larger models to increase enclosure Type Applicable inverter type rating from IP00 to IP20. VXM30K P20G-30 VXM30KP P20G-55 VXM37K to VXM55K P20G-75-4 VXM75K P20G-75-2 Not Available P20G-0 VXM90K to VXM0K P20G-60 VXM32K to VXM60K P20G-220 VXM200K to VXM220K Mounting adaptor for external cooling Used to put the cooling fan section of the inverter outside the panel. Only applicable to 22kW and below inverters. (30kW and above inverters can be modified to external cooling type by replacing the mounting bracket, as standard.) Type PBG-0.75 PBG-3.7 Applicable inverter type VXM40 to VXM75 VXM50 to VXM400 PBG-7.5 VXM550 to VXM750 PBG-22 VXM00to VXM2200G Panel-mount adaptor (MAG9- ) Used to mount a Jaguar VXM inverter in panel holes that were used to mount a Fuji G7S inverter. Type MAG9-3.7 Applicable inverter type VXM40 to VXM400 MAG9-7.5 VXM550 to VXM750 MAG9-22 VXM00 to VXM2200G 30

JAGUAR VXM Wiring Equipment MCCB or ELCB Magnetic contactor (MC) Recommended wire size (mm Inverter type 2 ) Power Nominal Rated current (A) MC for input circuit supply applied MC2 for Input circuit Output circuit DCR DB voltage motor Constant Torque Variable Torque With DCR Without With DCR Without output (L/R, L2/S, L3/T) (U.V.W.) circuit circuit (kw) Rating (CT) Rating (VT) reactor reactor circuit With DCR Without (P,P(+)) (P(+),DB,N(-)) CT VT reactor Three 0.4 VXM40 phase 6 0.75 VXM75 6 400V.5.5 VXM50 0 K22A0 K22A0 K22A0.5.5.5 2.2 VXM220 0 6 4.0 VXM400 2.5.5 5.5 VXM550 6 20 4 K223A0 K223A0 K223A0 2.5 2.5 2.5 7.5 VXM750 VXM550 20 32 6 2.5 VXM00 VXM750 32 40 K230A0 K230A0 K230A0 0 4 4 4 5 VXM500 VXM00 50 K237A0 K237A0 K237A0 4 6 40 6 8.5 VXM850 VXM500 60 6 6 6 K245A00 K245A00 K245A00 0 22 VXM2200G VXM850 50 75 0 0 0 25 30 VXM30K VXM30KP 75 00 K260A00 K260A00 K260A00 6 2.5 6 6 6 37 VXM37K VXM30K 25 K85A22 K85A22 K85A22 35 25 00 45 VXM45K VXM37K 50 K0A22 K0A22 K0A22 25 50 25 35 25 4 55 VXM55K VXM45K 25 75 K350A K350A K350A 35 70 35 50 35 75 VXM75K VXM55K 75 50 50 70 50 K350A K350A 6 90 VXM90K VXM75K 200 70 70 95 70 0 VXM0K VXM90K 225 K375A 95 95 20 95 K375A 0 32 VXM32K VXM0K 300 20 20 50 20 K335A 60 VXM60K VXM32K 350 K335A 85 50 240 85 6 200 VXM200K VXM60K 400 K3450A22 240 300 K3450A22 300 300 220 VXM220K VXM200K 500 300 400 25 K3700A22 280 VXM280K VXM220K 600 K3700A22 500 400 500 35 VXM35K VXM280K 400 VXM35K Available soon NOTES: For molded-case circuit breakers (MCCB) and earth-leakage circuit breakers (ELCB), the required frame type and series depend on the transformer capacity and other factors. When selecting breakers, refer to IMO, if uncertain. Select the current sensitivity of ELCB, with reference to motor cable length and type, and carrier frequency. The recommended cable sizes are based on the condition that the temperature inside the panel does not exceeds 50 C. The above are 600V PVC insulated (75 C). Data in the above table may differ for different conditions (ambient temperature, power supply voltage and other factors). CAUTION: If in doubt, consult local/national wiring regulations such as the relevant IEE Wiring Regulations - latest edition. 3