Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

Similar documents
Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals

Investigation of PD Detection on XLPE Cables

Mathematical Model and Numerical Analysis of AE Wave Generated by Partial Discharges

PD Solutions. On-Line PD Measurement Devices

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges

CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD

Software for Partial Discharge and Localization

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Partial Discharge Patterns in High Voltage Insulation

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

1409. Comparison study between acoustic and optical sensors for acoustic wave

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

IEEE Transactions on Power Delivery. 15(2) P.467-P

High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

Why partial discharge testing makes good sense

Coherence and time-frequency analysis of impulse voltage and current measurements

Resonance Tube. 1 Purpose. 2 Theory. 2.1 Air As A Spring. 2.2 Traveling Sound Waves in Air

OPTICAL EMISSION CHARACTERISTICS OF HELIUM BREAKDOWN AT PARTIAL VACUUM FOR POINT TO PLANE GEOMETRY

USING DAMPED AC VOLTAGES

EWGAE 2010 Vienna, 8th to 10th September

On-Site Partial Discharge Monitoring using the differential LEMKE PROBE LDP-5 and its accessories

Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing

Practical aspects of PD localization for long length Power Cables

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Resonance Tube. 1 Purpose. 2 Theory. 2.1 Air As A Spring. 2.2 Traveling Sound Waves in Air

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

Resonance Tube Lab 9

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Lab 1: Pulse Propagation and Dispersion

NONDESTRUCTIVE EVALUATION OF CLOSED CRACKS USING AN ULTRASONIC TRANSIT TIMING METHOD J. Takatsubo 1, H. Tsuda 1, B. Wang 1

International Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015)

Analysis of Crack Detection in Metallic and Non-metallic Surfaces Using FDTD Method

System Inputs, Physical Modeling, and Time & Frequency Domains

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform


Strathprints Institutional Repository

IMAGING OF DEFECTS IN CONCRETE COMPONENTS WITH NON-CONTACT ULTRASONIC TESTING W. Hillger, DLR and Ing. Büro Dr. Hillger, Braunschweig, Germany

CVVOZE Power Laboratories (CVVOZEPowerLab)

PARTIAL DISCHARGE MEASUREMENT

ACOUSTIC AND ELECTROMAGNETIC EMISSION FROM CRACK CREATED IN ROCK SAMPLE UNDER DEFORMATION

Acoustic emission signal attenuation in the waveguides used in underwater AE testing.

Abstract. 1 Introduction

THE EXTRACTION METHOD FOR DISPERSION CURVES FROM SPECTROGRAMS USING HOUGH TRANSFORM

A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

SODAR- sonic detecting and ranging

P a g e 1 ST985. TDR Cable Analyzer Instruction Manual. Analog Arts Inc.

ELECTROMAGNETIC EMISSIONS OF AC HIGH-VOLTAGE CORONA

EC 554 Data Communications

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Ultrasonic Testing using a unipolar pulse

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

Ultrasonic Level Detection Technology. ultra-wave

Data and Computer Communications Chapter 3 Data Transmission

Partial discharge diagnostics on very long and branched cable circuits

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

A New Elastic-wave-based NDT System for Imaging Defects inside Concrete Structures

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

T40B. Torque Flange. Special features. Data sheet. Overall concept

Application Research on Hydraulic Coke Cutting Monitoring System Based on Optical Fiber Sensing Technology

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

THE PROBLEM of electromagnetic interference between

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

Ultrasound Physics. History: Ultrasound 2/13/2019. Ultrasound

REFLECTION AND TRANSMISSION OF LAMB WAVES AT DISCONTINUITY IN PLATE Z. Liu NDT Systems & Services AG, Stutensee, Germany

Fiberoptic and Waveguide Sensors

INTERNAL CONCRETE INSPECTION AND EVALUATION METHODS FOR STEEL PLATE-BONDED SLABS BY USING ELASTIC WAVES VIA ANCHOR BOLTS

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

Sources of transient electromagnetic disturbance in medium voltage switchgear

PC1141 Physics I. Speed of Sound. Traveling waves of speed v, frequency f and wavelength λ are described by

Dr. Ali Muqaibel. Associate Professor. Electrical Engineering Department King Fahd University of Petroleum & Minerals Dhahran, Saudi Arabia

A GENERIC TECHNIQUE FOR ACOUSTIC EMISSION SOURCE LOCATION

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

A VIEW OF ELECTROMAGNETIC LIFE ABOVE 100 MHz

REVERBERATION CHAMBER FOR EMI TESTING

4.6.1 Waves in air, fluids and solids Transverse and longitudinal waves Properties of waves

EFFECTS OF LATERAL PLATE DIMENSIONS ON ACOUSTIC EMISSION SIGNALS FROM DIPOLE SOURCES. M. A. HAMSTAD*, A. O'GALLAGHER and J. GARY

SPEED is one of the quantities to be measured in many

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

Techniques to reduce electromagnetic noise produced by wired electronic devices

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Waves and Sound Practice Test 43 points total Free- response part: [27 points]

Quantitative Crack Depth Study in Homogeneous Plates Using Simulated Lamb Waves.

EMC standards. Presented by: Karim Loukil & Kaïs Siala

Speed of Light in Air

Measurement of Partial Discharge inside Metal Enclosed Power Apparatus using Internal Sensor

A Novel Method for Exact Determination to Localize Radial Deformation along the Transformer Winding Height

Transcription:

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal Abdolrahman Peimankar, Arman Kazemi, and Seyed Mohammad Taghi Bathaee Khaje Nasir University of Technology, Tehran, Iran Email: a.peimankar@gmail.com, arman_kazemi2@yahoo.com, bathaee@eetd.kntu.ac.ir problems such as electromagnetic waves, acoustic waves, local heating and chemical reactions. The acoustic method is one of the nondestructive diagnostic methods used to measure, detect and localize PD in insulation systems of power facilities. Another advantage of this method is immunity to electromagnetic interference [1]. For diagnosing whether an acoustic wave is produced by a PD source or not it is sufficient to review some characteristics of this acoustic signal such as rise time of first oscillation or length of wave. In electrical PD method in order to consider the severity of PD signal a specific threshold about 300 pc to 500 pc is used, but in acoustic method because of attenuation of acoustic signals that are traveled from PD source to sensor and therefore decreasing amount of amplitude while interfere with material inside the transformer tank, sensors should detect the weakened signals. Each type of acoustic waveform is representative the specific path that signals traveled. The features of two electrical and acoustic methods depend on the type of coupling path and the location of PD source between the detector and event which can be done by electric and acoustic signal, also in order to face noise signal both methods have different ways. Acoustic signals that are produced by PD source have a specific range that can measure by acoustic sensors but this property decreases the amount of noise. Abstract Transformers are one of the most important and costly components of any power system. Proper monitoring of the health of a transformer is thus inevitable. Online monitoring of partial discharges PD is one of the ways by which the risk of catastrophic failure of a power apparatus can be reduced. Common insulation in power transformers are and oil. Unconventional PD measurement was developed for several decades ago as a form of PD detection system. In these PD measurement systems that are named unconventional method PD is analyzed by indirect features of this phenomenon, which includes electrical, acoustic, UHF, optical, and chemical methods. The main advantage of unconventional method is the ability of this method in order to decrease the amount of signal to noise ratio for on-site or on-line measurement. A study of the correlation between acoustic emission signals generated by PD and electrical PD charges is inevitable. By developing the speed of measuring devices like digital signal processor DSP the possibility of evaluation and calculation of acoustic signals in very short time have been increased. The aim of this paper is evaluation of acoustic signals for two different kind of new and aged with two types of sensors 75 khz and 150 khz peak frequency and simulation of Acoustic Emission AE signals propagation which are produced due to PD inside a sample transformer tank by using Finite Element Method FEM. Index Terms partial discharge, transformer, acoustic emission sensor, finite element analysis tools I. INTRODUCTION II. Power transformers are one of the major capital items, and the cost due to a failure, is high in both direct costs and downtime. The early detection of problems is essential in order to reduce losses due to failure. For this reason transformers are monitored frequently by using a variety of methods. An important way for monitoring conditions of high voltage equipment is Partial Discharge PD evaluation for these devices. Electrical, mechanical and thermal stresses can be caused for occurring breakdown on aged insulation and high voltage devices and it can be led to failure on the device. Occurring PD has some effects that can be used in order to indicate the AE signals have frequencies between 50 khz and 350 khz, the main frequency for 150 pc PD is about 100 khz and this frequency will decrease when the discharge become larger [2]. The characteristics of AE signals such as amplitude and time domain depend on some factors that the most important of them are the size of transformer tank and the location of the sensors. In the Fig. 1, one signal in two different domains is shown, the upper one is in the time domain while below is in the frequency domain; the x axis is in Hertz Hz. In this figure, the main sensitivity of sensor is from 20 khz to 180 khz and the second oscillation at 700 μs illustrates the reflection of the AE signal. Manuscript received June 20, 2013; revised September 13, 2013. doi: 10.12720/ijoee.1.4.182-187 ACOUSTIC SIGNALS 182

Fig. 2 shows another phenomenon, if the waveform is considered carefully, it is understood that this signal consists of two-step, at first the longitudinal wave that has lower amplitude is sensed by sensor then the transversal wave arrive to the sensor [3] and [4]. the range of -45 C to +80 C. For ease of use, the integral sensors utilize a standard coaxial cable with BNC connector to power the pre-amp and carry the output signal. HV needle 15 mm sensor plate sensor decoupler oscilloscope Figure 3. Dimension of sample container. IV. Figure 1. In this Section some experiment results and the comparison between them is presented. The aim of these experiments is evaluation of different situation in occurring PD such as with, without and with aged at different distances and analysis of results that are obtained from these experiments Fig. 4 and Fig. 5. A laboratory recorded direct PD signal top and its power spectrum bottom. Figure 4. Comparison between maximum db and different situations at 40 cm and 100 pc average PD via 150 khz peak frequency sensor. Figure 2. The burst envelope of a sample signal. III. EXPERIMENTAL RESULTS TEST SET UP A. Test Container The size of this sample container is 80 cm 40 cm 30 cm which is made of steel Fig. 3. B. Instrumentation and Test Set Up for Acoustic Tests A μsamos Digital AE System DSP Physical Acoustic measuring system was used to diagnosis and evaluation of PD occurring inside the oil. The integral sensors are completely enclosed in a stainless steel case and coated to minimize RFI/EMI interference. The 40dB pre-amplifier is situated inside the sensors. In addition, the critical input stage of the pre-amplifier is provided in such a way to have excellent temperature stability over Figure 5. Comparison between maximum db and different situations at 40 cm and 100 pc average PD via 75 khz peak frequency sensor. 183

A. AE Inception PD AE inception PD is one the most important factors which means the amounts of minimum pc needed to get acoustic signal, in this case this phenomenon is analyzed for 150 khz sensor at different situations. Fig. 6 indicates the results for this experiment. are broken, it gets softer than new and because of this reason the acoustic wave can go through the with higher amplitude. a Figure 6. AE inception PD at different situations and some distance to the measuring point 40 cm. As it can be resulted from the bar charts, minimum necessary apparent charge is much higher in situation without. There is an obvious reason for this difference. When PD occurred within, acoustic signals are much higher in lower apparent charge than without. B. Comparison between AE Signal and PD Apparent Charge In this Section two different types of aged and new in vertical and horizontal situations are compared. TABLE I. Figure 7. Comparison between average db of AE signal for aged and new and PD apparent charges at 40 cm via a 75 khz and b 150 khz peak frequency sensor. COMPARISON OF RESULTS OBTAINED FROM 75 KHZ Average pc 0-50 50-100 100-150 150-200 200-250 TABLE II. b V. Average db Aged New 53 53 60 58 68 65 70 68 74 70 The following two-dimensional model investigates the occurrence of a partial discharge within various geometries containing dielectric liquid. A. Model 1 Sound propagates through a medium by means of wave motion [5]. In order to model the system, the wave equation was selected. The wave equation is a type of classical partial differential equation. Next, the geometry of the model had to be constructed. Fig. 8 shows the first model that was constructed. COMPARISON OF RESULTS OBTAINED FROM 150 KHZ Average pc Average db Aged New 55 52 60 58 65 62 69 64 75 68 0.8 m As is illustrated, the amount of magnitude which is sensed by sensors is higher for aged than new which can be seen in Table І and Table ІІ. Personal viewing of this fact is because of this reason that through broken structure of acoustic wave can transmit with higher amplitude Fig. 7. When a is getting aged the molecular structures of the PD Source Sensor 0.4 m 0-50 50-100 100-150 150-200 200-250 TWO-DIMENSIONAL SIMULATION MODELS Transformer Oil Tank Wall Figure 8. 2D geometry of model 1. 184

Note that the dimensions are arbitrary. The PD source was placed at co-ordinates: x, y = 0.4, 0.2. The first simulation was done as Fig. 8. The tank was set to be reflective, i.e. not permit any energy to pass through the tank walls. Consequently, the tank walls were set with the Neumann boundary condition with g = q = 0. Next, the PD source was set to emit a pulse of constant magnitude. It was therefore set with Dirichlet boundary conditions, with r =100, which specifies that the function would have a value of 100 on the boundary of the source of the partial discharge. The speed of sound in transformer oil was set at 1400 m/s assuming factory conditions. The mass coefficient for the domain, da, was set to be 1.The source term was set to zero. The model was then meshed. When acoustic waves are being modeled, it is important to ensure that there are enough mesh points in order to resolve the waveform accurately. This also ensures that effects such as interference are modeled correctly. In order to achieve this, it is recommended that there be 8 mesh points per wavelength. The system was then simulated for 20 milliseconds, in steps of 10 microseconds. a t= 70 µs b t= 130 µs Figure 9. Initial propagation of the acoustic wave. Fig. 9 represents the initial propagation of the acoustic wave from the PD source. The intensity of the PD was set to 100 under the boundary conditions tab. The intensity of the PD was specified to be constant for all time. c t= 270 µs Figure 10. Propagation of acoustic wave at various times, a 70 µs, b 130 µs, c 270 µs. Note that at times 130 µs and 270 µs reflections at the transformer tank wall can be observed Fig. 10. B. Model 2 In this model three sensors are placed on the tank wall and the PD location is assumed at the specified coordinates x=0.3, y = 0.2. The main goal of this 185

simulation is comparing the result of experimental tests with simulation. By comparing the result from simulation and experiment, it can be possible to determine the accuracy of acoustic arrival time with the electrical reference method and, also, be sure that localizing is accurate. Fig. 11 reveals the acoustic waves that are detected by AE sensors and the time difference between electrical trigger. where, is the measured arrival times, is the are the measured arrival sound velocity and Cartesian sensor coordinates. We can derive from the above equations: 4 5 6 Electrical trigger The coordinates calculated by the Eq. 4 ~ 6 are x = 23 cm, y = 21 cm. According to this coordinates, the model that is used in simulation is shown in Fig. 12. 0.8 m PD Source Sensor2 0,0.2 0.8,0.2 0.23,0.21 0.4 m a Acoustic waveform of sensor 1 Sensor 3 0.5,0 Tank Wall Transformer Oil Sensor 1 80 µs Figure 12. 2D geometry of model 2. The system was simulated and the result of sensing the pressure of acoustic wave that was produced by PD source is presented in Fig. 13. b Acoustic waveform of sensor 2 150 µs c Acoustic waveform of sensor 3 Figure 13. The result of simulation for model 2scattered pressure field vs. time. Fig. 14 shows the pressure during 0.01 second, as it can be seen in this figure the primary time that sensors start to detect the pressure is specified. 270 µs d Figure 11. a Electrical trigger and acoustic waveform of b sensor 1, c sensor 2, d sensor 3. The calculation for localizing PD can be mentioned by Eq. 1 ~ 3 [6]. 1 2 3 Figure 14. Time of sensing pressure by sensors model 2. 186

LIST OF SYMBOLS AND ABBREVIATIONS By comparison between experimental and simulation results it can be confirmed that the value of error is acceptable. Experimental results are given, and. On the other hand, simulation results are given, and. These results show that the error value of this method is less than 10%. VI. Symbol CONCLUSION Experimental tests has been shown that the amount of maximum db detected by sensors is much larger in creepage discharge than other situations, because of displacements of needle that amplifies the acoustic signal and, also, for aged vertical and horizontal the amplitude of all signals detected by sensors were higher than the other case with the new. Another subject that was evaluated is comparing the number of acoustic emission hits for different situations which were discussed above as specific PD apparent charge. All of the results can be seen more clearly as a signal waveforms in time and frequency domain. One more important results that were evaluated is AE inception PD, the result of this experiment confirms this phenomenon that in without situation until 700 pc apparent charge no AE signal could be detected but for other situations the amount of AE inception PD decreases by a fix rate approximately for new, aged, new and aged creepage discharge respectively. Furthermore, the comparison between the amplitude of two sensors confirms that low PD apparent charges have higher AE frequency up to 150 khz than high PD apparent charges. The results obtained from this study confirm the combination of acoustic emission and electrical PD measuring method offers an excellent and real time solution for the detection as well as the localization of partial discharges. REFERENCES [1] [2] [3] [4] [5] [6] B. Vahidi, M. J. Alborzi, H. Aghaeinia, and M. Abedi, Acoustic diagnoses of AC corona on the surfaces of insulators, presented at IEEE Bologna PowerTech Conference, Bologna, Italy, June 2326, 2003. Draft guide for the detection and location of acoustic emissions from partial discharge in oil-immerses power transformers and reactors, IEEE PC57.127/D1.1 Standards Draft, 3. August 2003. T. Bengtsson, M. Leijon, and L. Ming, Acoustic frequencies emitted by partial dischrages in oil, in Proc. 7th International Symposium on High Voltage Engineering, 1993, pp. 113-116. T. Bengtsson and H. Kols, Transformer PD diagnosis using acoustic emission technique, in Proc. 10th International Symposium on High Voltage Engineering, 1997, pp. 25-29. L. E. Lundgaard, Partial discharge. XIV. Acoustic partial discharge detection-practical application, IEEE Electrical Insulation Magazine, vol. 8, no. 5, pp. 34-43, Sep-Oct. 1992. Y. Lu, X. Tan, and X. Hu, PD detection and localization by acoustic measurements in an oil-filled transformer, IEE Proc.-Sci. Meas. Technology, vol. 147, no. 2, pp. 81-85, March 2000. 187 Meaning Symbol Meaning AE acoustic emission µs microsecond cm centimeter pc picocoulomb EMI electromagnetic interference PD partial discharge HV high voltage RFI Radio frequency interference khz kilohertz UHF ultra high frequency FEM Finite element method Abdolrahman Peimankar was born in Sanandaj, Iran in 1985. He received B.Sc. degree in Electrical Engineering from Khaje Nasir Toosi University of Technology, Tehran, Iran in 2009 and M.Sc. degree in Electrical Engineering with specialization in High Voltage Engineering from the Leibniz University of Hannover, Hannover, Germany in 2012. His research interests include high voltage engineering, condition monitoring of power apparatus and industrial applications of high voltage engineering, Electrical Distribution Networks, Renewable Energy, Distributed Generation DG systems. Seyyed Mohammad Taghi Bathaee was born in Qom, Iran in 1950. He received B.Sc. degree in Computer Science and Electrical Engineering from Tehran University and Khaje Nasir Toosi University of Technology in 1977 respectively and M.Sc. degree in Electrical Engineering from the George Washington University, Washington D.C, USA in 1979 and the Ph.D. degree from the Amir Kabir University of technology, Iran in1995. He is an Associate Professor in the Department of Electrical Engineering at Khaje Nasir Toosi University of Technology. He was the president of the Khaje Nasir Toosi University of Technology from 1982 to 1986 and 2007 to 2010. His research interests include power system steady state, dynamics and transient analysis, smart grid and application of optimization in electric appliances and high voltage engineering. He has published over hundred papers in national and international journals and conferences. Arman Kazemi was born in Ahar, Iran in 1983. He received B.Sc. degree in Electrical Engineering from Islamic Azad University, South Branch, Tehran, Iran in 2009 and M.Sc. degree in Electrical Engineering with specialization in High Voltage Engineering from the Leibniz University of Hannover, Hannover, Germany in 2012. His research interests include high voltage engineering such as condition monitoring and Transformer parameter determination for the purpose of failure diagnosis, HVDC, Renewable Energy and Distributed Generation DG systems.