PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS

Similar documents
PD Solutions. On-Line PD Measurement Devices

Software for Partial Discharge and Localization

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

CHAPTER 3 ACOUSTIC EMISSION TECHNIQUE FOR DETECTION AND LOCATION OF PD

1409. Comparison study between acoustic and optical sensors for acoustic wave

Evaluation of Partial Discharge in Power Transformers by Acoustic Emission Method and Propagation Modeling of Acoustic Signal

TECHIMP Power Transformer Monitoring

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

IEEE Transactions on Power Delivery. 15(2) P.467-P

WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

PARTIAL DISCHARGE MEASUREMENT

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

The Application of Partial Discharge Measurement and Location on CGIS

Partial Discharge Monitoring and Diagnosis of Power Generator

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

Strathprints Institutional Repository

APPLICATIONS OF ACOUSTIC LOCALIZATION TO ONLINE POWER TRANSFORMERS

CVVOZE Power Laboratories (CVVOZEPowerLab)

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

KEYWORDS On-line diagnostics, cable termination, partial discharge (PD), ultra-high frequency (UHF), sensitivity check.

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Coherence and time-frequency analysis of impulse voltage and current measurements

Practical aspects of PD localization for long length Power Cables

Digital Signal Processing for the Detection and Location of Acoustic and Electric Signals from Partial Discharges

Why partial discharge testing makes good sense

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Partial Discharge Monitoring of Power Transformers by UHF Sensors

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

Automated PRPD Pattern Analysis using Image Recognition

Parameters influencing Partial Discharge Measurements and their Impact on Diagnosis, Monitoring and Acceptance Tests of Power Transformers

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

UHF PARTIAL DISCHARGE DIAGNOSIS OF PLUG-IN CABLE TERMINATIONS

Abstract. 1 Introduction

MONTRANO. Continuous monitoring system for power transformers

Measurement of Partial Discharge inside Metal Enclosed Power Apparatus using Internal Sensor

High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications

Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals

6 - Stage Marx Generator

Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors

Partial Discharge, Survey or Monitor?

PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Simulation Model of Partial Discharge in Power Equipment

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Partial discharge diagnostics on very long and branched cable circuits

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Comparison of measurement methods for partial discharge measurement in power cables

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Effect of coupling conditions on ultrasonic echo parameters

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

A STUDY ON THE PERFORMANCE OF IMPEDANCE MATCHING CIRCUIT IN PARTIAL DISCHARGE MEASURING SYSTEM

UHF PD-DIAGNOSIS AT HIGH VOLTAGE CABLE TERMINATIONS INTERNATIONAL CASE STUDIES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

International Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015)

BY JASON SOUCHAK, Megger

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS

Application of Wavelet Transform Technique for Extraction of Partial Discharge Signal in a Transformer

The importance of partial discharge testing throughout the development and operation of power transformers

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

New Techniques for the Monitoring of Transformer Condition

NJ. ISBN (2017) , /URSIGASS

Partial Discharge Patterns in High Voltage Insulation

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

Further Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Chapter 5. Signal Analysis. 5.1 Denoising fiber optic sensor signal

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

3.003 Lab 3 Part A. Measurement of Speed of Light

WAVELET TRANSFORM ANALYSIS OF PARTIAL DISCHARGE SIGNALS. B.T. Phung, Z. Liu, T.R. Blackburn and R.E. James

EQUIPMENT AND MOBILE LABORATORIES FOR NDT AND DIAGNOSTICS OF UNDERGROUND COMMUNICATION LINES.

Transient calibration of electric field sensors

Signal and Noise Measurement Techniques Using Magnetic Field Probes

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

Experimental Observation of RF Radiation Generated by an Explosively Driven Voltage Generator

Detection of Obscured Targets: Signal Processing

GFT1504 4/8/10 channel Delay Generator

3 - Using the Telecoms-Trainer 101 to model equations

Sources of transient electromagnetic disturbance in medium voltage switchgear

MPD 600. High-End Measurement and Analysis System for Partial Discharges (PD)

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

Product Datasheet P MHz RF Powerharvester Receiver

HYUNDAI HEAVY INDUSTRIES CO. LTD

Application of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment

UWB Type High Power Electromagnetic Radiating System for Use as an Intentional EMI Source

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

Transcription:

PARTIAL DISCHARGE DETECTION AND LOCATION IN TRANSFORMERS BY PERFORMING PARTIAL DISCHARGE TESTS IN OIL USING UHF SENSORS by K.K.JEMBU KAILAS and W. ADITHYA KUMAR L&T CONSTRUCTION L&T CONSTRUCTION KKJK@LNTECC.COM AADI@LNTECC.COM

Objective Partial Discharge detection & location in Power transformers and to evaluate the most important property of UHF sensor i.e. SENSITIVITY through preliminary testing. To de-noise the captured signals and to extract the original PD signal after de-noising. To evaluate the approximate location of PD source

Partial Discharge (PD) PD - Intermittent nanosecond range pulses Causes of PD. Weak insulation - When electric field across the insulation > dielectric strength of the insulation = PD. Arcing due to poor contacts 3. Corona 4. Surface discharges Effects of PD. Insulation degradation over a period of time. Equipment failure, Effect on men & materials, Disruption of economic activities, Customer dissatisfaction, Penalty clauses 3

PD Detection using UHF Principle and aspects Electrons accelerated under high electric field and immediately brought to rest (nano sec range pulses) produce Ultra High Frequency (UHF) EM waves. UHF waves = 300 MHz -3000 MHz Non conventional method energy from EM waves can be captured using sensors and their outputs can be shown in V or mv PD pulses can be detected if wave length of UHF signals < tank dimensions Narrow pulse, more spectral energy & vice versa 4

UHF sensors & UHF PD Detector Module Internal & External sensor respectively, internal sensor placed inside the drain valve, while external sensor placed in specially designed dielectric windows on the transformer, both require modifications on transformer tank. 5

Conventional Method (IEC 6070) UHF Method Offline measurements Online measurements Measurements at factory Measurements at factory and site Considers the transformer as a single unit. Hence fault location is not possible Able to locate multiple faults as the system considers each fault location as a localized unit Basic method to analyze the Can be coupled with conventional method overall strength of insulation for diagnosis, while testing transformers in in the factory the factory. Highly sensitive to noise Less sensitive to noise, as this operates in UHF range. Even corona and other noises happen only below this range. Hence sensitivity is high 7

Types of Sensors Patch antenna Internal sensor External sensor 8

Preliminary testing of Sensors Before inserting the sensor directly in to the drain valve of Transformer it is necessary to evaluate the performance of antenna. More over the charge levels in a transformer will be in the order of some thousand pc. So the sensitivity of the sensor is evaluated by keeping the antenna at a relative distance from PD source. 9

Sensitivity verification of UHF Conical Monopole Antenna Experimental Set-up LDIC PD measuring system 0

Applied voltage (KV) v/s charge (pc) The charge (pc) was linearly varying with applied voltage i.e. it has a linear relationship. The center frequency of received signals at PD inception voltage was 963MHz. The minimum energy of the PD signal is 60μJ with sensitivity 90pC.

Experimental Set-up

Preliminary testing in Oil Internal UHF sensor Signal captured at 0.KV Signals captured by all the 4 sensors at KV 3

De-noised signal 4

Results Type of sensor Distance Max Peak to test (m) voltage peak (mv) voltage (mv) Frequency Energy Time Phase Power (MHz) (pj) period (degre (dbm) (ns) es) Time difference t s.4 47 376 960 49.03 3.8 55.8 46.53 s.4 400 970 38.6 3.5 83.75 4.7 s3.4 45 650 979 40.9 77. 5.47 s4.4 45 50 960 37 8.7 46.3 47 s.4 75 86 000 6 5.7 5.8 6.94 s. 95 6 979 306 4.8 50.7 59.9 s3.4 43 79 965 0 0.6 04.4 60.8 s4 0.75 6 3 980 45 8.9 5.48 64.98 Triggering Triggering voltage Channel (mv) t3 t4 4.3 43. 45. 50 C 43.9 49.5 4. 50 C in Air in Oil 5

Observations from Oil test The Internal sensor (conical monopole antenna) has detected the corona discharge at an inception of voltage of 0.KV where as all the other external antennas (Patch antennas) did not capture it. As the distance between internal sensor and the electrodes was 8cm where as the distance between external sensors and the electrodes is m, the UHF internal sensor detected the signal. After repeating the experiment keeping all the sensors at same positions and with voltage being increased, external sensors detected corona at KV, where as the UHF internal sensor detected at 0.6KV. The results show that the UHF internal sensor is more sensitive than the external sensors when placed very close to the PD source without actually knowing the level of PD. As the test was carried out under controlled conditions and without any ground noise de-noising the signal was done in oscilloscope. 6

Experiment on real time Transformer Internal Sensor Mounted in to one of the valves 7

UHF FFToutput 0.35 De-Noising Wavelet De-noising Principle Amplitude(volts) 0.3 FFT of original signal Maximum Amplitude = 0.669 volts at a frequency of 979 MHz 0.5 0. 0.5 0. 0.05 Original signaluhfcaptured by sensor output 0.5 0.06 0-0.05-0. -0.5-0. -.5 0.0 0-0.0-0.5 0 0.5 Time(seconds) -0.06.5 -.5-7 x 0 4 6 8 FFT offrequency(hz) Denoised signal 0 9 x 0 Maximum Amplitude is 0.53 at 000 MHz 0.08 0.06 0.04 0.0-0.04-0. Amplitude(volts) 0.05 0 0 0. 0.04 Amplitude(volts) Amplitude(volts) 0. De-noised signal using wavelets in MATLAB Denoised signal - -0.5 0 Time(seconds) 0.5 0 0.5-7 x 0 4 6 Frequency(Hz) 8 0 9 x 0 8

PD location using UHF Time of Arrival Approach There will be definite time difference between arrival of signal from a particular PD source at each sensor. The time difference governed by minimum time delay path traveled by the EM wave front to reach each sensor. Distance traveled (D) = EM Wave speed (v) x time (t) or more distinct but repeatable time period = multiple PD sources 9

Flow Chart of TDOA Enter the sensor coordinates in D/3D Calculate the sensor position values Call TDOA Read the time domain signal from each sensor Cross correlation TDOA values Solve the non-linear equations Newton Raphson Iterative method Non-Iterative method Source location 0

Evaluation of -Dimensional PD source Location using MATLAB Sl.no Applied Sensor Sensor Sensor 3 Time Computed Source Computed Error Error voltage Position Position Position Difference Of Velocity of position position in in (KV) (x,y) cm (x,y) cm (x3,y3) cm Arrival (TDOA) electromagneti (x,y) cm (xc,yc) cm X (%) Y (%) 50,00 50.069, 0.4-0.07 0.4-0.07 0.4-0.07 0.4-0.07 0.4-0.07 0.4-0.07 4.4 (50,00) (50,75) (50,0) T T3 c waves (ns) (ns) Cm/sec...3*0^0 99.93 4.6 (50,00) (50,75) (50,0)...3*0^0 50,00 50.069, 99.93 3 4.7 (50,00) (50,75) (50,0)...3*0^0 50,00 50.069, 99.93 4 4.8 (50,00) (50,75) (50,0)...3*0^0 50,00 50.069, 99.93 5 7 (50,00) (50,75) (50,0)...3*0^0 50,00 50.069, 99.93 6 3.3 (50,00) (50,75) (50,0)...3*0^0 50,00 50.069, 99.93 Comparison of actual source and evaluated source with sensor as reference

Evaluation of -Dimensional PD source Location using MATLAB Sl.no Applied Sensor Sensor Sensor 3 Time Difference Computed Source Computed Error in Error voltage Position Position Position Of Arrival Velocity of position position X (%) in (KV) (x,y) cm (x,y) cm (x3,y3) cm (TDOA) electromagnetic (x,y) cm (xc,yc) cm T3 T3 waves (ns) (ns) Cm/sec Y (%) 0.4 (50,00) (50,75) (50,50) 3.4.7.3*0^0 50,00 5.85,03.4 5.7 3.4 4 (50,00) (50,75) (50,50).5 5 *0^0 50,00 53.55,0.6 6.9.6 3 4. (50,00) (50,75) (50,50) 3.4.7.3*0^0 50,00 54.35,0.7 8.7.7 4 4. (50,00) (50,75) (50,50) 3.4.7.3*0^0 50,00 54.4,0.4 8.4.4 8.4.4 8.4.4 8.4.4 5 4. (50,00) (50,75) (50,50) 3.4.7.3*0^0 50,00 54.4,0.4 6.4 (50,00) (50,75) (50,50) 3.4.7.3*0^0 50,00 54.4,0.4 7 8 (50,00) (50,75) (50,50) 3.4.7.3*0^0 50,00 54.4,0.4 Comparison of actual source and evaluated source with sensor 3 as reference

Results When the FFT of original signal was performed, the dominant frequency was 979MHz and the dominant frequency in denoised signal was found to be 000MHz. This shows that the noise which the sensor captured even between 900MHz-000MHz is eliminated The amplitude of denoised signal is less than that of the original signal amplitude. This gives clear information that noise levels are generally higher than PD signal amplitude. Wavelet de-noising using Daubechey s filter is the best method among different techniques -D source has been located in a steel tank with an error of 8% using iteration method (Newton-Raphson method). The accuracy of Dimensional source location has been improved to 96% when NewtonRaphson method is implemented on denoised signals 3

Conclusion UHF method has numerous applications and one of them is transformer. The sensor designed for inserting it in to the drain valve of transformer has very good sensitivity of 90pC under controlled conditions. So the UHF sensors can be installed at sites, factories without de-energizing the transformers and the approximate location of PD source can be traced such that the insulation strength of that particular area is increased and also the life of transformer is increased. -D PD source has been located in steel tank using iteration method (Newton-Raphson method) with a error of 8%, where as 3Dimensional source localization is done with non-iterative method like TDOA, PRPA. 3Dimensional PD source is also localized but with a certain error 4

FUTURE SCOPE This research is vast and can be extended to on-line monitoring of the transformer with a suitable hardware. The best way to implement this technique on-line is by using DAQ unit along with LABVIEW. This gives important information about condition monitoring and diagnostics of power transformers for a full day, week, month depending upon the size of data to be analyzed. So the best way to implement this technique on-line is to reduce the amount of data recorded in the hardware every second by erasing unnecessary data 5

6