PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1- TRANSFORMER USING PCA

Similar documents
International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

Simulation Model of Partial Discharge in Power Equipment

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Why partial discharge testing makes good sense

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

The importance of partial discharge testing throughout the development and operation of power transformers

Partial Discharge Theory, Modeling and Applications To Electrical Machines

PD Solutions. On-Line PD Measurement Devices

Partial Discharge Patterns in High Voltage Insulation

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Practical aspects of PD localization for long length Power Cables

Partial Discharge Detection For Condition Monitoring Of An 11-kV XLPE Cable-Part II

USING DAMPED AC VOLTAGES

High Field Electrical Conduction and Breakdown in Solid Dielectrics

UHF PARTIAL DISCHARGE DIAGNOSIS OF PLUG-IN CABLE TERMINATIONS

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Investigation of PD Detection on XLPE Cables

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

Partial discharge diagnostics on very long and branched cable circuits

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

1409. Comparison study between acoustic and optical sensors for acoustic wave

Partial Discharge Classification Using Novel Parameters and a Combined PCA and MLP Technique

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

CONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Partial Discharge Characteristics of Micro-gaps

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Further Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Corona noise on the 400 kv overhead power line - measurements and computer modeling

Diagnostic testing of cast resin transformers

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors

Software System for Finding the Incipient Faults in Power Transformers

Analysis of Partial Discharge Patterns for Generator Stator Windings

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

EE 1402 HIGH VOLTAGE ENGINEERING

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

PD Testing Considerations for MV Plant Cables

PARTIAL DISCHARGE MEASUREMENT ANALYSIS ON RING MAIN UNIT

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

The Application of Partial Discharge Measurement and Location on CGIS

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Partial Discharge Monitoring and Diagnosis of Power Generator

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Electric Stresses on Surge Arrester Insulation under Standard and

Simulation of Partial Discharge in High Voltage Power Equipment

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

PARTIAL DISCHARGE MEASUREMENT

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Measurement of Partial Discharge inside Metal Enclosed Power Apparatus using Internal Sensor

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

Generation of Sub-nanosecond Pulses

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Comparison of measurement methods for partial discharge measurement in power cables

Ieee Guide For Partial Discharge Testing Of Shielded Power

Corona Current-Voltage Characteristics in Wire-Duct Electrostatic Precipitators Theory versus Experiment

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Power Factor Insulation Diagnosis: Demystifying Standard Practices

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

Diagnostic measurements on instrument transformers. Part II. A classification and overview of diagnostic measurements DIAGNOSIS EVENTS ABSTRACT

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Effect of Shielded Distribution Cable on Very Fast Transients

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

Influence of Impurity Concentration on Insulation Strength of Insulating Oil under Different Voltage Types

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

WAVELET DE-NOISING AND ANALYSIS OF UHF PARTIAL DISCHARGES IN HIGH VOLTAGE POWER TRANSFORMER

Air-Gap Partial Discharge Development Stage Recognition for Power Transformer Insulation Monitoring Considering Effect of Cavity Size

Partial Discharge Measurements on 110kV Current Transformers. Case Study. Results

HV AC TESTING OF SUPER-LONG CABLES

Field Measurement of Transmission Cable Dissipation Factor

Coherence and time-frequency analysis of impulse voltage and current measurements

Prepared by Mick Maytum

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT

A STUDY ON THE PERFORMANCE OF IMPEDANCE MATCHING CIRCUIT IN PARTIAL DISCHARGE MEASURING SYSTEM

Transcription:

International Journal of Information Technology and Knowledge Management January-June 2011, Volume 4, No. 1, pp. 1-5 PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1- TRANSFORMER USING PCA Ganesh Rao 1 & Shailja Shukla 2 Partial discharge is the commencement of failure of insulation of electrical devices used at high voltage. If such discharge is not detected then fault may increase at the working duration. Basically partial discharge is the cause of failure of insulation in electrical equipment. The insulation of electrical equipment deteriorates due to thermal, mechanical, electrical and environmental stresses. Continuous on-line monitoring of partial discharge (PD) activities involves recording large amounts of data and it is hallenging task to extract useful information from them. This paper proposes a partial discharge analysis and its pattern classification in LV winding of single phase Transformer using straight or electrical technique for analysis and principle component analysis algorithm for recognition of partial discharge pattern. Getting different patterns by changing fault location, we can classify these patterns according to their position in the LV winding. To measure the partial discharge we have different technique like direct or electrical method, acoustic measurement, balance. In this paper electrical method is used in which PD Analyzer DDX-9101 is used in which we get the 2-D pattern in sinusoidal waveform at different voltage level by changing location of fault in LV winding. When we vary voltage level with changing location of fault in LV winding we get variation in peaks level and also peaks location i.e. in +ve and ve half cycle. By analysis of these peaks level and peaks location at different fault location we can analysie these pattern and also recognize or classify these partial discharge pattern with the help of principle component analysis (PCA) algorithm. It has been concluded that the discharge magnitude (PD level) will be very low if fautl is at near supply end, as we go onwards to the supply end discharge magnitude will increase. Keyword: LV Winding of 1 Φ Transformer, PD Analyzer (DDX-9101), 2-D Partial Discharge Patterns, Principle Component Analysis (PCA) Algorithm 1. INTRODUCTION The steep increase in the demand for electric power necessitates the introduction of higher capacity power equipment with increased voltage rating. The reliability of such equipment is very important, as an unplanned outage of any equipment causes a heavy replacement cost, in addition to the loss due to power shut down from the reliability point of view, an insulation structured is considered as a key factor, moreover, the high cost of insulation necessitates insulation optimization. An insulation system is seldom made from a single material. Often it is made up of few insulating material. Obviously the electrical stress within the system is never uniform and a material with low dielectric constants viz. an air gap is more stressed. If such a gap does not able to with stand the stress, then flash over takes place. Since the discharges occur partially in the insulation system, they are known as Partial Discharges (PD) that can occur in the insulation. Partial discharge detection and measurement in EHV equipment during manufacturing period plays very 1 M.E. (Control System), JEC, Jabalpur 2 Electrical Engg. Deptt., JEC, Jabalpur Email: 1 ganesh_raobe@yahoo.co.in, 2 shailja.shukla@indiatimes.com important role in order to predict the severity with which insulation system is functioning. Also it is necessary for a practicing to engineer to understand the cause, behavior of partial discharges and the associated measurement techniques. Partial discharge is the commencement of failure of insulation of all electrical devices those are used at high voltage. If such discharge is not detected it will lead to failure of insulation. It begins with voids, cracks, bubbles etc. for different insulation materials such as solid, liquid and air the level of discharge, the breakdown voltage is different. By various techniques Partial discharge can be detected and measured. Acoustic measurement, straight detection, balance detection are commonly used techniques. In our experiment we detected it through straight detection technique. Under it we used PD detector DDX - 9101 type device that gives the PD voltage, charge, and waveform. The results were recorded and compared in a table as well as in a graph which shows how P.D. varies at different voltages for different materials. 2. WHAT IS PARTIAL DISCHARGE A partial discharge defined as localized discharged in which the distance between two electrodes is only partially bridged

2 GANESH RAO & SHAILJA SHUKLA i.e. the insulation between the two electrodes is partially punctured. Partial discharge may originates at one of the electrode or occur in a cavity in the dielectric. The air or gas cavities are one of the most wide spread types of localized defect. Due to the fact that the dielectric permittivity of air is few times less than the dielectric filed intensity in the gas layer can considerably exceed the average field intensity in the insulator [11]. Therefore in the no. of cases ionization process start even the working voltage. The sum total of this ionization process is called the partial discharge since they cover a small part of total distance between the electrodes. Once begin PD causes progressive deterioration of insulating materials ultimately leading to electric breakdown. PD can be prevented through careful design and material is confirmed using PD detector equipment during the manufacturing stage as well as periodically through the equipments useful life. PD prevention and detection are essential to ensure reliable, long term operation of HV equipment used by electric power utilities[12]. Terminology used: 1. Electric Discharge: The movement of electrical charges through and insulating medium, initiated by electron avalanches. 2. Partial Discharge: An electrical discharge that only partially bridges the dielectric insulating medium between two conductors. Examples are: internal discharges, surface discharges, corona discharges. Internal discharges are discharges in the cavities or voids which lie inside the volume of the dielectric or at the edges of conducting inclusions in a solid or liquid insulating media. Surface discharges are discharges from the conductor into a gas or a liquid medium and form on the surface of the solid insulation not covered by the conductor. Corona discharges are a discharge in a gas or liquid insulator around the conductors that are away or remove from solid insulation. 1. Discharge Inception Applied Voltage: This is the lowest voltage at which discharges of specified magnitude will occur when an increasing a.c. voltage is applied. 2. Discharge Extinction Applied Voltage: This is the lowest voltage at which discharges of specified magnitude will appear when an applied a.c. voltage, which is more than the inception voltage, is reduced. 3. Discharge Magnitude: It is the quantity of charge, as measured at the terminals of sample due to a single discharge. 4. Discharge Detector: It is a device or an instrument used for either detecting or measuring the discharges[12]. When a partial discharge occurs the event may be detected as a very small change in the current drawn by the sample under test. PD currents are difficult to measure because of their small magnitudes and short duration. 3. NEED OF DETECTION OF PD Partial discharge which in course of time reduce the strength of insulation, leading to a total or partial failure or breakdown of the insulation. Measurement of partial discharge on a regular basis can detect failure that would have occurred on account of, 1. Thermal deterioration; 2. Load cycling; 3. Loose winding in the slot; 4. Contaminated winding tracking. Whenever there are voids in the insulation, there is a certain voltage existing across the gap. This causes electrical breakdown in the voids as soon as the gradient is around 2.7 to 3.0 KV per mm. When electrical breakdown occurs, the void keeps on enlarging, leading to ultimate failure of insulation. Partial discharge measurement should be carried out at least twice a year. The frequency of carrying out partial discharge measurement depends on the rated voltage of motor[11]. The measurement of PD current pulses provides important information concerning the discharge process in a test specimen. The time response of the fault and design of insulating material. The shape of circular current is an indication of physical discharge process at the fault location in the test object. 4. EXPERIMENT SETUP To measure the partial discharge pattern by electrical method the experiment set up is shown in fig. 1.In this paper DDX- 9101 PD analyzer are used to take the 2-D partial discharge pattern of 1-Φ LV winding with capacitor coupled circuit, high voltage generator and high voltage switch plate[2]. Fig.1: PD Measuring System Diagram[10]

PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1-Φ TRANSFORMER USING PCA 3 By varying the voltage level from the auto transformer and potentiometer and changing the fault location we take the partial discharge patterns waveshape in sinnusoidal form. These experiments is conducted in high voltage lab of Electrical Engg. Department of Jabalpur Engineering College, Jabalpur. Fig. 2: Tested LV Winding 5. PD ANALYSIS In this paper partial discharge pattern in LV winding of single phase transformer analyzed creating different fault in different location of LV coil. In fig. 3 list of different pattern with changing location of faults are given. In table given below, when coil is in healthy condition partial discharge level is much low (.607 nc) also partial discharge pattern wave shape showing minimum amount of peaks level at constant voltage 20 KV. But in foulty condition (the black sign in coil showing the fault location) at the supplying end the partial discharge level increases also peaks are increase in both positive and negative half cycle.in these wave shape, green color indicates discharge activity that is being measured on the PD meter and red color indicates a section of display that falls within the horizontal gate period, as set up using the gating menu option on the scope mode menu. As we increase the fault level, the discharge magnitude will increase and the partial discharge pattern wave shape will change but with the increasing fault level and magnitude of partial discharge it is not necessary that the peak level, peaks quantity will increase. It will change its location, length and section only. Also the discharge magnitude for the fault near supply end is very low (37.91 nc) as we go onwards to the coil discharge magnitude will increase rapidly[3]. 6. INTRODUCTION TO PCA Principal Component Analysis (PCA) is a very popular data pre-processing algorithm for simplifying a dataset by reducing a complex dataset to lower dimensions for analysis. It still effectively retains the characteristics of the dataset while having simplified structure and able to reveal underlying features in the dataset [7]. Fig. 3: PD Pattern According to Fault Location Fundamentally, PCA is a linear transformation that projects the input data to a new coordinate system. The greatest variance by any projection of the data becomes the first principal component; the second greatest variance becomes the second principal component and so on. The lower order components will be the ones to keep as they retain most of the important aspects of the dataset. The mathematical steps for doing the PCA are presented in the following[9].

4 GANESH RAO & SHAILJA SHUKLA Consider PCA is being performed on an input data array C(M N). It has M input dimensions and N number of samples. 1. The input data C is firstly processed by subtracting off the mean for each dimension to get a centered observation. 2. Find the covariance matrix: C = 1/(N 1 ). X.X T 3. By solving the eigenvalue equation λν = Cν, the eigen value λ(m 1) and eigen vector ν(m M) are found. 4. The eigen value λ is sorted in decreasing order with the eigenvector v following the sorting. 5. The projection of the input data X to the new coordinates is computed: P = ν T.C. 6. The Euclidean distance computed between training data and input data. 7. Euclidean distance algorithm will find different distance between all training set and input data.minimum distance will show the output image or pattern. Each row of the projection P re presents the principal components, with a lower order in the top row and higher order in the bottom row[6]. 7. RESULTS This paper presents an on line method for analysis of fault detection and its classification in transformer winding using partial discharge analyzer DDX 9101 and using principle component analysis algorithm. In this paper we analyzed the electrical or direct method of partial discharge analysis by locating fault in transformer and other electrical equipment. In this particular method, we can detect the fault location and discharge magnitude of the equipment by PD analyzer DDX-9101. In this partial discharge analyzer we get direct partial discharge magnitude, voltage level and wave shape by which we can easily analyze the fault location. We can see the wave shape at healthy condition showing no peaks in any section,on the other hand when we create faults at different locations, we get partial discharge waveshapes with peaks in different sections. Also the discharge magnitude for the fault near supply end is very low (37.91 nc) as we go onwards to the coil discharge magnitude will increase rapidally. The green color of Wave shape indicates discharge activity that is being measured on the PD meter and red color indicates a section of display that falls within the horizontal gate period, as set up using the gating menu option on the scope mode menu. 8. CONCLUSION Partial discharge measurements are very popular for the monitoring of the condition of the installation and they have become essential in the quality assessment of the insulation. By means of partial discharge analysis, we can easily avoid unexpected in-service failures, improve the overall reliability of system.the discharge analysis is an efficient device which allows customers to avoid failures and to reduce their maintenance costs. This analysis is used to identify deterioration mechanisms such as slot discharge, internal voids, wedge and winding looseness. Two final studies, noise suppression and field-testing, are required before the system can be deployed in the field. The data from such tests would then allow a commercial company to take on the manufacture and installation of this system in High voltage equipment. 9. ACKNOWLEDGMENT The author would like to thank HV Lab of Electrical Engg. Department, Jabalpur Engg. College Jabalpur TEQIP,TIFAC CORE for providing the facility to collect valuable field test data. REFRENCES [1] Borsi, H., 2000, A PD Measuring and Evaluation System Based on Digital Signal Processing, IEEE Transactions on Dielectrics and Electrical Insulation, 7, No. 1, pp. 21-29. [2] High-Voltage Test Techniques Partial Discharge Measurements, IEC 60 270, 2001. [3] N.H. Ahmed, N.N. Srinivas, 1998, On-line Partial Discharge Detection in Cables, IEEE Trans. Diel. Elect. Insul., 5, No. 2, pp. 181-188. [4] M. Hanai, F. Endo, S. Okabe, T. Kato, H. Hama, M. Nagao, 2006, "New Development for Detecting Partial Discharge using an UHF Method and its Application to Power Apparatus in Japan, Presented at CIGRE Session, Paris, Franlce, Paper Nr. D1-106. [5] S. M. Hoek, U. Riechert, T. Strehl, S. Tenbohlen, 2007, New Procedures for Partial DischargeLocalization in Gas Insulated Switchgears in Frequency and Time Domain, 15th International Symposium on High Voltage Engineering, Ljubljana, Slovenia (Accepted). [6] Abdul Rahman, M.K., Arora, R., and Srivastava, S.C. (2000), Partial Discharge Classification using Principal Component Transformation, IEE Proceedings of Scientific Measurement Technologies, 147, No. 1, pp7-13.

PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1-Φ TRANSFORMER USING PCA 5 [7] Duda, R. O., Hart, P. E., and Stork, D. G. (2000), "Pattern Classification", John Wiley & Sons, Inc., New York, NY. [8] Kitter, J. (1978), Feature Set Search Algorithm, Pattern Recognition and Signal Processing, Sithoff and Noordhoff, Alphen ann Den Riju, The Netherlands, pp41-60. [9] K.X.Lai, B.T.Phung, T.R. Blackburn, Partail Discharge Analysis using PCA and SOM, Paper ID:499. [10] Mang-hui Wang, Partial Discharge Pattern Recognition of Current Transformer using an ENN", IEEE Transaction on Power Delivery, 20, No. 3, July 2005. [11] F.H. Kreuger, E. Gulski and A. Krivda, Classification of Partial Discharges, IEEE Trans. on Electrical Insulation, 28, 1993, pp. 917-931. [12] R. Bartnikas, "Partial Discharge Measurement IEEE Trans", Elec. Insul.