General Technical Specifications of Frequency Converters for Tokyo-Chubu Interconnection Project

Similar documents
PTTS series. Power Transformer Test System. Scope of Work:

Functional Specification Revision History

ATTACHMENT - AESO FUNCTIONAL SPECIFICATION

Experience with Connecting Offshore Wind Farms to the Grid

East-South HVDC Interconnector II, India : in commercial operation since 2003

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Fundamental Concepts of Dynamic Reactive Compensation. Outline

HVDC High Voltage Direct Current

Single Line Diagram of Substations

CERN - ST Division THE NEW 150 MVAR, 18 KV STATIC VAR COMPENSATOR FOR SPS: BACKGROUND, DESIGN AND COMMISSIONING

PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS

Transformers TRANS FORM ERS

DYNAMIC PERFORMANCE OF THE EAGLE PASS BACK-TO-BACK HVDC LIGHT TIE. Å Petersson and A Edris ABB Power Systems AB, Sweden and EPRI,USA

Unit 2. Single Line Diagram of Substations

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Grid Impact of Neutral Blocking for GIC Protection:

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Quanta Technology Advancing the Grid. Flexible AC Transmission System (FACTS) BGE Technology - Application Cases January 4, 2008 Q U A N T A SERVI CES

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

GENERAL TECHNICAL SPECIFICATION

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

VI 3 - i TABLE OF CONTENTS

Technical and Economic Analysis of Connecting Nuclear Generation to the National Electricity Transmission System via HVDC Technology.

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Siemens AG Österreich Transformers Weiz. Reference for Autotransformer. Autotransformer. Customer National Grid, UK

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Guaranteed Dmax (MW) at Year 1-10 (See note 2 below)

Company Replaces previous document Document ID Issue E.ON Energidistribution AB Ny engelsk utgåva D

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

SYSTEM STUDIES for HVDC

STATE OF NEW JERSEY BOARD OF PUBLIC UTILITIES

Recent trends in High Voltage Direct Current (HVDC)Transmission Systems Abstract

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Do Capacitor Switching Transients Still Cause Problems?

RAP Ripple Control Coupling for parallel injection of RC signals in Medium and High Voltage Networks

Agenda for the 18 th Northern Region constituents meeting regarding Connectivity/LTA Applications in NR

Impulse Voltage Test System

Principles for Controlling Harmonics

INTEGRATED TRANSMISSION PLAN Glossary

Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering

A Review Paper on Technical Data of Present HVDC Links in India

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

EXECUTIVE PEER EXCHANGE WORKSHOP

EI HIGH VOLTAGE INSULATION TESTING POLICY

CIGRE WG A3.06 Reliability of High Voltage Equipment Intermediate Results CIGRE WG A3.06. Reliability of High Voltage Equipment

IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Ritz Instrument Transformers GmbH. Welcome

Reliability Analysis Update

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

In Class Examples (ICE)

Distribution transformers Part 2 Ground mounted transformers not closecoupled

VARIABLE FREQUENCY RESONANT TEST SYSTEM

Simulation Study of a Monopole HVDC Transmission System Feeding a Very Weak AC Network with Firefly Algorithm Based Optimal PI Controller

MEDIUM & HIGH VOLTAGE

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

50-SDMS-01 SPECIFICATIONS FOR

Voltage Instrument Transformer Medium Voltage Block Type 7,2 kv - 24 kv

Shunt Reactors for Medium and High-Voltage Networks

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

Magnetization System of Magnetically Controlled Shunt Reactors

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

ECP HV INSULATION TESTING

SECTION - II BID DATA SHEET

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

Functional Specification Revision History

ESB National Grid Transmission Planning Criteria

Autotransformer Condition Monitoring Systems

Central East Voltage and Stability Analysis for Marcy FACTS Project Phase I

MINISTRY OF ELECTRICITY

Energy Delivery. Holland Bottom 500/161/115kV Substation. Delivering energy safely, reliably, efficiently and affordably.

Southern Company Interconnection Requirements for Inverter-Based Generation

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Wide Area Voltage Dispatch. - Case studies of ISO New England using NETSS AC XOPF program

ECP HV INSULATION TESTING

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Onsite Mobile AC High Voltage Test System

The rapid evolution of voltage Source Converters as applied to High Voltage DC power transmission Carl Barker

Utility Interconnection and System Protection

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

Insulation Co-ordination For HVDC Station

EL-INSTA ENERGO ltd. Zizkova Hrusovany u Brna Czech republic tel

Power Quality enhancement of a distribution line with DSTATCOM

X-band Magnetron. Cooling (note 5) Water Output coupling (note 6) UG51/U Magnet (note 7) Integral, Permanent

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

TECHNICAL SPECIFICATION

Transmission Facilities Rating Methodology for Florida

Digital Fault Recorder Deployment at HVDC Converter Stations

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

Transcription:

General Technical Specifications of Converters for Tokyo-Chubu Interconnection Project Note: It is possible that the contents of these specifications may be changed according to our detailed studies. Present basic specifications of frequency converters ( Higashi-Shimizu 600MW, Shin- Sakuma (tentative name) 300MW ) are as follows. This project is planned to be commissioned in the fiscal year 2027. Procurement by Chubu Electric Power Co., Inc. Converter Type: Voltage-Sourced Converter Rated Power: 600MW (300MW x 2Units) : 50Hz (Tokyo Side)/60Hz (Chubu Side) Procurement by Electric Power Development Co., Ltd. Converter Type: Voltage-Sourced Converter Rated Power: 300MW (300MW x 1Unit) : 50Hz (Tokyo Side)/60Hz (Chubu Side) Chubu Electric Power Co., Inc. (CEPCO) Electric Power Development Co., Ltd. (J-POWER)

1. Outline of Converters for Tokyo-Chubu Interconnection Project [900MW Increase This project is planned to be commissioned in the fiscal year 2027 and three (3) frequency converters (300MW x 3units) are scheduled to be installed.

2-1. Outline of Converter (Higashi-Shimizu S/S) Converter (Higashi-Shimizu S/S, CEPCO) List of Equipment converter AC equipment Circuit Configuration Equipment Quantity - Voltage-sourced converter 300MW x 2Units - Converter transformer 4Units (50Hz: 2Units, 60Hz: 2Units) - Buffer reactor (Valve reactor) Installed when necessary, based on the bidder's proposal - AC filter Installed when necessary, based on the bidder's proposal - Shunt capacitor, Shunt reactor Installed when necessary, based on the bidder's proposal - 275kV GIS (50Hz, outdoor) 2bays for line, 2bays for converter transformer,1bay for bus section - 275kV GIS (60Hz, outdoor) 2bays for converter transformer (out of scope from this open bidding) - AC switchgear Installed when necessary, based on the bidder's proposal except for the above GIS - Station power supply system - Generator system for emergency

2-2. Outline of Converter (Shin-Sakuma FC) Converter (Shin-Sakuma FC, J-POWER) List of Equipment converter system AC equipment Equipment - Voltage-sourced converter - Converter transformer - Buffer reactor (Valve reactor) -AC filter - 275kV GIS (50Hz, outdoor) - 66kV GIS (50Hz, outdoor) - Step-down transformer (50Hz) - Shunt capacitor (50Hz) - 275kV GIS (60Hz, outdoor) - AC switchgear Circuit Configuration Quantity 300MW x 1Unit 2Units (50Hz: 1Unit, 60Hz: 1Unit) Installed when necessary, based on the bidder's proposal Installed when necessary, based on the bidder's proposal 2bays for line, 1bay for bus section, 1bay for converter transformer, 1 bay for stepdown transformer (5bays in total) 1bay for stepdown transformer, 2bays for shunt capacitor (3bays in total) 1Unit for shunt capacitors 2Units 2bays for line, 1bay for converter transformer (3bays in total) Installed when necessary, based on the bidder's proposal except for the above GIS

3-1. Outline of Converter (Higashi-Shimizu S/S) Tentative Layout (Higashi-Shimizu S/S, CEPCO) #3FC frequency converter *2 (converter transformer, voltage-sourced converter, buffer reactor (valve rector) *1, switchgear *1, AC filter *1, shunt capacitor *1, shunt reactor *1 ) #1FC frequency converter *2 (converter transformer, voltage-sourced converter, buffer reactor (valve rector) *1, switchgear *1, AC filter *1, shunt capacitor *1, shunt reactor *1 ) 275kV GIS (50Hz), bushings and gantry towers Station power supply system and a part of DC equipment of #1FC It might be possible that additional area can be available for the FC after our scheduled study. *1 The equipment can be installed when necessary, based on the bidder's proposal. *2 The grading area of will be changed depending on the size of the adopted system for #3FC.

3-2. Outline of Converter (Shin-Sakuma FC) Layout Plan 1 *1 Layout Plan 2 *1 converter system (converter transformer, voltage-sourced converter, buffer reactor (valve reactor) *2, AC filter * ) 275kV GIS (50Hz), bushings and gantry towers 275kV GIS (60Hz), bushings and gantry towers Step-down transformer, 66kV GIS and shunt capacitors (50Hz) Main building Internal road *1 The plans are tentative and may be changed depending on our scheduled study and/or land acquisition. *2 The equipment can be installed when necessary, based on the bidder's proposal.

4-1. Scope of Work (Higashi-Shimizu S/S, CEPCO) Item Specifications Rated power 300MW100Mvar (50Hz, 60Hz) converters with voltage-sourced converters #1FC #3FC Voltage-sourced converter converter transformer Type Rated primary voltage 50Hz (Tokyo side) / 60Hz (Chubu side) Indoor, air insulated, water-cooled system The circuit configuration can be proposed by the bidder. Should be determined based on the rated power of VSC 275kV (50Hz, 60Hz) Buffer reactor (valve reactor), AC filter, shunt capacitor, shunt reactor and so on can be installed when necessary, based on the bidder's proposal. Voltage-sourced converter converter transformer Rated power Type Rated primary voltage 300MW100Mvar (50Hz, 60Hz) 50Hz (Tokyo side) / 60Hz (Chubu side) Indoor, air insulated, water-cooled system The circuit configuration can be proposed by the bidder. Should be determined based on the rated power of VSC 275kV (50Hz, 60Hz) Buffer reactor (valve reactor), AC filter, shunt capacitor, shunt reactor and so on can be installed when necessary, based on the bidder's proposal. AC system 275kV GIS (50Hz) Insulation type SF 6 gas insulated, outdoor installation Station power supply system, Generator system for emergency For frequency converters

4-2. Scope of Work (Shin-Sakuma FC, J-POWER) Item Specifications Voltage-sourced converter Converter transformer Rated power Type Rated primary voltage 300MW100Mvar (50Hz) 300MW0Mvar (60Hz) 50Hz (Tokyo side) / 60Hz (Chubu side) Indoor, air insulated, water-cooled system The circuit configuration can be proposed by the bidder. Should be determined based on the rated power of VSC 275kV (50Hz, 60Hz) Buffer reactor (valve reactor), AC filter and so on can be installed when necessary, based on the bidder'sproposal. 275kV GIS (50Hz) Insulation type SF 6 gas insulated, outdoor installation 66kV GIS (50Hz) Insulation type SF 6 gas insulated, outdoor installation Step down transformer (50Hz) Rated primary voltage 180MVA 275kV 80Mvar x 2 Units Shunt capacitor (50Hz) Rated voltage 66kV Others Low order harmonics damping circuit may be necessary. 275kV GIS (60Hz) Insulation type SF 6 gas insulated, outdoor installation