Analysis of transfer touch voltages in low-voltage electrical installations

Similar documents
NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

Chapter 6. WIRING SYSTEMS Safe Electrical Design

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

Options to Improve the MEN System into the 21 st Century

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

ENSURING PUBLIC SAFETY THROUGH PROPER EARTHING IN LOW VOLTAGE NETWORKS

Module Title: Electrical Installation II Laboratory Sheet:

Les Hampson Cert Ed FSCTE, Chairman CAI Technical Committee

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

ET 61 - Electrician Theory Examination Marking Schedule

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

power Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.

7P Series - Surge Protection Device (SPD) Features 7P P P

ModieLoad. Static capacitive load unit 9.8A 240vac single phase. CAUTION: Ensure only Phase to Neutral connection CAT IV 300V

UNIT Earthing and Earth Fault Current Protection (SCQF level 6)

MinorWorks/Single Circuit Electrical Certificate

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Licensed Electricians Practical Assessment (LEP)

6. Internal lightning protection

EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)

Licensed Electricians Practical Assessment (LEP)

So, let us investigate those parts of the Wiring Regulations that need to be considered in the early stages of the design procedure.

Grounding and Lightning arrestors

, Power Industries and Communications Industry Training Board

ET 40 - Electrician Theory Examination Marking Schedule

Automatic disconnection of lighting circuits from dimming equipment

3B SCIENTIFIC PHYSICS

G SAFETY WARNINGS. LT300 High current loop tester. User guide

Choice of earth leakage protection devices

TN, TT & IT Earthing Arrangements

/B

2 Grounding of power supply system neutral

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Bringing power to life. THE RCD HANDBOOK. BEAMA GUIDE TO THE SELECTION AND APPLICATION OF RESIDUAL CURRENT DEVICES (RCDs)

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Residual Current Operated Circuit-Breakers (RCCBs)

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET

Technical Certificate in Electrical Installation Version Sample September Question Paper Pack

QUICK SETUP GUIDE SECULIFE IP

Industrial and Commercial Power Systems Topic 7 EARTHING

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

Company Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis

Ohm s Law and Electrical Circuits

Chapter F Protection against electric shocks

MARTINDALE INSTRUCTIONS. E-ZeTest EZ2500 LOOP TESTER ELECTRIC. Trusted by professionals. Other products from Martindale:

User's Guide. AC Circuit Load Tester. Model CT70

Distribution systems and protection against indirect contact and earth fault

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

3B SCIENTIFIC PHYSICS

U ACTIVE SAT DISTRIBUTION FIELD

technical information

Company Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations

17th Edition IEE Wiring Regulations: Design and Verification of Electrical Installations

Amendment No. 3: lighting and luminaires

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Protection of Electrical Networks. Christophe Prévé

Residual current circuit breakers (RCCBs)

Electrical Protection System Design and Operation

CURRENT FUTURE REGULATIONS PROPOSALS

Chapter F Protection against electric shocks

SR Series Crossovers. Owner s Manual SR 823 SR 834. A Harman International Company

ET 51 - Electrician Theory Examination Marking Schedule

The future of installation testing is here. The 1650 Series Multifunction Testers

TS RES - OUTSTANDING ISSUES

Back to Operator Manual Index MX50 OPERATORS MANUAL. DRAWMER MX50 Dual De-Esser SAFETY CONSIDERATIONS

Section 3. Test Procedures

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

Challenger 400. Instruction manual

EAS Electrical Appliance Serviceperson Answer Schedule

Using Virtual Reality Modelling to Enhance Electrical Safety and Design in the Built Environment.

EPG. by Chris C. Kleronomos

Earthing Guidance Notes

PROTECTION AGAINST FAULT CURRENT

ECE 528 Understanding Power Quality

INSTALLATION WARNING: BEFORE COMMENCING INSTALLATION ISOLATE YOUR MAINS ELECTRIC SUPPLY

17th Edition IEE Wiring Regulations: Explained and Illustrated

Multi-Function Installation Tester MEGGER CM500. User Guide MEGGER

TT W Wireless receiver Inline Switch

17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.

RIGOL. User s Guide. RP1000D Series High Voltage Differential Probe. Feb RIGOL Technologies, Inc

DM-45 Digital Multimeter

ELECTRICIAN S THEORY EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET

1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact

YAL. 12 Electricity. Assignments in Science Class X (Term I) IMPORTANT NOTES

Wallace Hall Academy Physics Department. Electricity. Pupil Notes Name:

Low Voltage Products. Third Harmonic Filter THF and THF star System components for assembly and retrofitting. Catalogue THFS2GB 03_05 1SCC330004C0201

FINAL - EST Electrical Service Technician Answer Schedule

DVM645BI BENCH MULTIMETER TAFELMULTIMETER MULTIMETRE DE TABLE BANCO MULTÍMETRO TISCHMULTIMETER. User Manual. Gebruikershandleiding

Current Probes. User Manual

Instruction Manual for Digital Grounding Resistance Meter

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

HV Substation Earthing Design for Mines

Transcription:

Building Serv. Eng. Res. Technol. 31,1 (2010) pp. 27 38 Analysis of transfer touch voltages in low-voltage electrical installations M Barrett a BSc, K O Connell a BSc MSc CEng and ACM Sung b BSc MSc PhD CEng a lecturer in the department of Electrical services Engineering, DIT, Dublin, Ireland b Head of the Department of Electrical services Engineering, DIT, NG Bailey Ltd. Protection against electric shock in our homes and work places is one of the most important priorities for electrical services engineers who are now designing electrical installations to conform to the requirements of the 17th edition IEE Wiring Regulations (BS7671: 2008). Now Chapter 41 of BS7671: 2008 requires that additional protection by means of a 30 ma 40 ms residual current protection device be provided for final circuits supplying general purpose socket outlets that are intended for use by Ordinary persons. However, there are few publications and little information available on the theory describing how touch voltage of a dangerous magnitude could be transferred from a faulty circuit onto the exposedconductive-parts of Class 1 equipment of another healthy circuit. This paper summarises the theory of transfer touch voltage calculations and expands on it to show how to carry out a sensitivity analysis in relation to the design parameters that are being used by designers and installers. Based on the results of a real case study, it appears that there is sufficient evidence to show that it may not be sufficiently safe to use the nominal external earth fault loop impedance quoted by the electricity utility companies for adopting a low touch voltage design. Practical application: The touch voltage sensitivity equation derived in this paper is a powerful tool for designers and installers of electrical installations to investigate and identify the sensitivity of resulting touch voltages of any electrical circuits. Nomenclature U t = touch voltage U oc = open circuit voltage of the mains supply = circuit protective-conductor resistance R 1 = phase conductor resistance Z e = earth fault loop impedance external to the faulty circuit U source = the potential drop of Z e MET = the main earthing terminal (or main earth bar) of the electrical installation Address for correspondence: M Barrett, Department of Electrical Services Engineering, Dublin Institute of Technology, Kevin St., Dublin 8, Ireland. E-mail: martin.barrett@dit.ie Figures 1, 2 and 4 8 appear in color online: http://bse.sagepub.com U o = the nominal declared voltage of the mains supply 1 Introduction Statistically it has been shown that electric shock is one of the main causes of fatality in the workplace 1 and homes. 2 To ensure a negligibly small risk of electric shock in the built environment, designers and installers adopt good wiring practices and abide by the relevant national wiring rules, e.g. NEC 2008, 3 BS7671: 2008 4 or IEC 60364, 5 to enable them to produce a safe electrical installation. It has been agreed universally that for ß The Chartered Institution of Building Services Engineers 2010 10.1177/0143624409351796

28 Analysis of transfer touch voltages general applications, an earthed and potentially equalised (i.e. main-bonded) system will afford protection against electrical shock hazards. The circuit-protective-conductor (cpc) of a final circuit provides a dedicated low resistance and high efficiency earth fault current return path to the supply source. An effective low impedance earth-fault current return path ensures an almost guaranteed operation of the overcurrent and/or shock protection device thus disconnecting the electric shock energy source under earth-fault conditions, limiting the duration of the touch voltage. In addition the main bonding will limit the magnitude of the touch voltage 6 one can receive across two simultaneously accessible bonded conductive parts. Therefore, the use of proper earthing (i.e. grounding) and bonding techniques remains the best way to protect people and equipment against electric shock hazards. However, when an installation has a large number of interconnected circuits and exposed-conductive-parts, a fault in another circuit can result in a touch voltage of a dangerous magnitude and duration being transferred onto a circuit feeding healthy equipment with exposedconductive-parts. 2 Theory of touch voltage For the purpose of this paper, we shall define touch voltage as a difference in voltage potential being experienced by a person who makes contact simultaneously with more than one conductive part, which is not normally energised. By this definition, we have excluded the direct contact electric shock hazard which is defined as the hazard of electric shock arising from making an unimpeded contact with normally live parts and we explicitly restrict our discussions to touch voltage arising from contact with exposed-conductive-parts and extraneous/exposed-conductive-parts. The touch voltage U t of the faulty equipment circuit shown in Figure 1 can be calculated using a simple voltage divider circuit: 7 U t ¼ U oc ð1þ Z e þ R 1 þ From the above formula (1) for touch voltage, it is evident that in practice the magnitude of touch voltage U t is dependent upon four values U oc, Z e, R 1 and. (1) The U oc value will be higher than the declared nominal supply voltage U o. Dist. board R 1 U source Z e Faulty equipment U oct 240V U t MET Figure 1 Touch voltage concept of a single faulty equipment circuit

M Barrett et al. 29 (2) The external earth fault loop impedance Z e will depend on the system earthing type, (3) R 1 will depend on the final chosen size of the phase conductor (which mainly depends on the size of the overcurrent protective device overload protection in particular), and (4) will depend of the final installed size of the cpc (which depends on the standard twin-with-cpc cable if not single-core conductor cables). It can be seen from Figure 1 that governs U t and the size of the cpc of a circuit can be designed or selected to provide a touch voltage that is restricted by the designer or installer intentionally. By assigning a boundary value to each of U t, U oc, Z e,r 1 and, the size of cpc can be designed using the following expression: U t ¼ U oc Z e þ R 1 þ ð2þ U t ¼ U oc Z e þ R 1 þ In the UK and Republic of Ireland, for locations where low body resistance is not expected (i.e. normal dry locations) the following boundary values are used by designers and installers: Safe touch voltage value: U t 50 V Utility supply voltage: U oc ¼ 240 V (16th edition IEE Wiring Regulations) or U o ¼ 230 V (17th edition IEE Wiring Regulations) where U o is the declared nominal voltage of the mains supply. For simplicity, this paper assigns U oc ¼ 240 V and a safe touch U t ¼ 48 V, a limiting value of is found to be: ¼ 1 ð 4 Z e þ R 1 Þ ð3þ From IEC 60479 part 1 8 (Effects of current on human beings and livestock), when the touch voltage is 50 V a.c. or less under normal dry conditions, the body impedance of a person is high enough to prevent a touch current of high enough magnitude to cause any injury. Based on this assumption, Table 41C of the 16th edition of IEE Wiring Regulations 9 permits the extending of the disconnection time from 0.4 to 5 s maximum. The use of a safe touch voltage is limited by the types and rating of a protection device and the associated maximum impedance of the cpc. It will be a simple design procedure for the designer or installer to apply Equation (3) and the appropriate value of Tables 41C and 41D to the required circuit to adopt a safe touch voltage design with an extended 5 s disconnection time. In the UK and Republic of Ireland, R 1 and are normally dictated by economics and standard practice. The standard combinations of conductor size in twin-with-cpc cables are: 16 mm 2 /6 mm 2, 10mm 2 /4 mm 2, 6mm 2 / 2.5 mm 2, 4mm 2 /1.5 mm 2, 2.5 mm 2 /1.5 mm 2 and 1.5 mm 2 /1.0 mm 2. These are general purpose wiring cables used for final circuits in domestic type properties. These would be under the control of the designer and installer. However, during the design stage, the earth-fault-loop impedance that is external to the electrical installation (Z e ) is normally an estimated figure. The exact value cannot be ascertained until the supply is actually installed and energised by the utility company. In most cases at the enquiry stage of a project the utility company will only provide the designer and installer with a worst case nominal Z e of 0.35 X for a TNC- S supply or 0.8 X for TN-S supply. However, the actual installed Z e could be completely different and it is outside the control of the designer and installer. Using the typical nominal value quoted by the utility supplier and assigning a boundary

30 Analysis of transfer touch voltages value of U t ¼ 50 V, Equation (2) will give the result of: U t ¼ 50 ¼ U oc ð0:35 þ R 1 þ Þ It can be seen that the final circuit was originally based on a Z e ¼ 0.35 X to provide a touch voltage of 50 V under an earth fault condition, but the actual resulting touch voltage will be higher than 50 V should the actual Z e be lower than 0.35 X. Hence, the consequence of not knowing the exact value of Z e means that the actual touch voltage resulting from a faulty circuit could not be accurately calculated using a nominal Z e indicatively quoted by the electricity supplier. The indicative Z e is only useful in providing the designer or installer a frame of reference to check if the overall fault-loop impedance (Z s ) of the circuit is designed correctly to ensure operation of the overcurrent or shock protection device promptly. Unfortunately it will err on the unsafe side for the touch voltage value. To illustrate the deficiency of an indicative worst case maximum Z e, the results of touch voltage variations with a decrease in the actual value of Z e and increasing circuit lengths were produced using an Excel spreadsheet for a typical TNC-S supply with Z e 0.35 X. The outcomes are plotted in Figure 2 for final circuits wired in 1.5 mm 2 / 1.0 mm 2 twin-with-cpc cables. It can be seen from Figure 2 that the touch voltage U t will rise from a safe-to-touch value (45 V) to an unsafe value (450 V) with decreasing Z e and increasing circuit length. It should be noted that U t, will be at its maximum or worst case when Z e is at its minimum value. (The minimum value expected for each situation was calculated using the prospective short circuit current (I pf ) value of the incoming supply.) irrespective of Touch voltage 160 140 120 100 80 60 40 20 0 Touch voltage sensitivity to Z e for a general TNC-S system, pscc 16kA at 230V using a 1.5mm twin and earth cable cpc 1mm 0.043555 0.0525 0.07 12.44% 15% 20% 0.105 0.14 0.175 0.21 0.245 Touch voltage at 5M from dist. board Touch voltage at 10M from dist. board Touch voltage at 15M from dist. board Touch voltage at 20M from dist. board Touch voltage at 25M from dist. board Touch voltage at 30M from dist. board Touch voltage at 35M from dist. board Touch voltage at 40M from dist. board 0.28 0.315 0.35 30% 40% 50% 60% 70% 80% 90% 100% External impedance Z e (Ω) Figure 2 Touch voltage plot of 1.5 mm 2 /1.0 mm 2 twin-with-cpc cable circuits

M Barrett et al. 31 the actual circuit length. Most of the results plotted indicate a value of U t well above 50 V. The new BS7671:2008 4 was introduced in January 2008, replacing the 16th edition IEE Wiring Regulations and Table 41C removed. However, additional protection by means of a 30 ma 40 ms residual current protection device (RCD) will have to be provided for final circuits supplying general purpose socket outlets that are intended for use by ordinary persons. It should be noted that the use of RCDs can help to reduce the risk of a high touch voltage and touch current of the associated circuit in the event of an earth fault, but it is unable to provide protection against any touch voltage transferred from a fault arising from another circuit not protected by an RCD within the same installation. 3 Touch voltage transferred from a faulty circuit to a healthy circuit The above analysis was applied to a single circuit. However, within the same building where a number of circuits with mixed disconnection times exist, as illustrated in Figure 3, 10 it has been shown that the resulting touch voltage from an earth fault of another defective circuit will be transferred to the exposed-conductive-part of a healthy circuit. Clearly, unless every circuit within the same installation is protected by an individual RCD or the whole distribution panel by one main RCD, touch voltage of an unsafe value could appear on exposed-conductiveparts for a short duration until it has been cleared by the associated overcurrent protection device. Distribution board L Circuit B Circuit A Fixed load B Exposed-conductive-part Load A (indoors) 230 V U f N E Main earthing terminal I f Protective conductor in cord R c Main equipotential bonding conductor Further equipotential bonding conductor (if necessary) Extraneous-conductive-part Earth Figure 3 Transferred touch voltage appearing on healthy equipment (source: IEE Guidance Note 5)

32 Analysis of transfer touch voltages Healthy equipment location A Faulty equipment location B I fault Healthy equipment location C V touch2 V touch2 R cpc3 R cpc4 V touch1 R cpc2 MET. Rcpc1.1 I fault R cpc1.2 R cpc1.3 Extraneous-conductive-parts Figure 4 Touch voltage is transferred from location B to locations A and C in the same building Figure 4 is a generic diagram illustrating the concept of how touch voltages V touch1 and V touch2 can appear on healthy equipment. The diagram illustrates three separate electrical circuits of an electrical distribution system, which at some point defaulted to utilising a common earthing riser as part of its earth return path. As equipment B develops an earth fault, an earth fault current I fault flows in the cpc resistances, and by Ohm s law, results in transfer touch voltages V touch1 and V touch2 appearing on the exposed-conductiveparts of equipment in locations A and C. 4 Touch volatge practical case study a domestic property This section outlines a method of simulating an electrical fault in the built environment. 50 Hz a.c. currents up to 20A were circulated through the cpc of several electrical circuits in a domestic property to simulate earth fault conditions. The resulting transfer touch voltages in the dwellings were measured and recorded. The electrical installation tested is a domestic property in Dublin built around 1980. The supply is single-phase 230 V 50 Hz a.c. TNC-S. A new consumer unit has recently been installed to meet ET101 11 (equivalent to BS7671: 2008). The meter board has recently been re-housed outside the dwelling for ease of access. At the meter board the measured Z e was 0.37 X at a U o of 233 V and frequency of 50.1 Hz. The practical measurements were carried out as illustrated in Figure 5. A variac acted as the source of supply. One of the output terminals of the 225 VA Variac, which can be varied from 0 to 14 V was connected to the associated cpc at the chosen fault locations and the other terminal was connected to the main earth terminal at the main distribution board.

M Barrett et al. 33 Distribution board Earth Neutral Phase E N P Variac Ammeter Voltmeter Figure 5 Circuit diagram of the test setup The characteristics of the simulated fault were recorded using a voltmeter and ammeter. The temperature of the associated cpc was recorded using a digital thermometer before and during each simulated fault. Figure 6 illustrates the circuits present in the test dwelling. During the simulation of the fault, transferred touch voltages that appeared in various locations were recorded. The test was setup to study in particular what magnitude of transfer touch voltage can exist in a location (i.e. bathrooms) where low body resistance would be commonly encountered. There are a number of countries where supplementary bonding in bathrooms may not be required but the main equipotential bonding should be correctly installed. It is for this reason that the new 17th edition of IEE Wiring Regulations requires that all electrical circuits supplying appliances or equipment in the bathroom be protected by RCDs so that any touch voltage originating from within the bathroom will be automatically disconnected within 40 ms. This particular test has deliberately disconnected the supplementary bonding in the bathroom to study the magnitude of transfer touch voltage in the particular location. For such a case, the results are shown in Figure 7 with an earth fault in the light fitting in the attic. Simulation results At the faulty light prior to simulation, the impedance of the cpc was recorded at 0.18 X. Under test conditions, the voltage and current were recorded at 6.4 V and 15 A, respectively. Using the recorded values (6.4 V/15 A ¼ 0.4266 X) and subtracting the impedance of the variac/ammeter combination and the earth wire from the variac to the MET, the impedance of the cpc can be calculated to be 0.196 X. The increase of resistance is due to copper having a positive temperature coefficient. Under test conditions, the touch voltage recorded between the light and earth in the attic was 2.95 V, while in the bathroom the touch voltage was 2.95 V between the heater and the cold-water copper pipe and shower. Hence, under true fault conditions, if a fault occurred at the light in the attic and a touch voltage developed, a voltage of the same magnitude would develop on the heater

34 Analysis of transfer touch voltages Fault 4 bathroom Fault 2 downstairs sockets no. 8 Fault 1 Downstairs sockets no. 7 Downstairs sockets no. 5 Upstairs sockets no. 5 Immersion heater Fault 5 attic Bar heater Fault 3 oven Oven Hob Upstairs Lights Downstairs Lights 20A MCB B type 30mA RCD Distribution board 63A switch Fuse 33A MCB B type 10A MCB B type Main earth bar Figure 6 Single-line diagram of the test dwelling Main incoming supply Main gas Earth electrode in the bathroom where there was no supplementary bonding present. Using the recorded values an approximated value for the touch voltage can be calculated. Fault loop impedance at distribution board ¼ 0.42 X Resistance of R 1 is approximately 0.12 X Resistance of is approximately 0.1966 X (both R 1 and will vary depending on the temperature of the copper under fault conditions). Using Equation (1): 0:1966 U t ¼ 64 V ¼ 240 0:42 þ 0:12 þ 0:1966 It was found that a touch voltage is transferred into the bathroom where the exposed-conductive-part of a heater, although

M Barrett et al. 35 Fault at light in attic-no supplementary bonding in bathroom Attic Consumer unit Socket Fault location Light Bathroom Heater Showers earth U t =64 V U t =64 V MET Cold water cu. pipe Extraneous conductive part Figure 7 Presence of dangerous touch voltage in bathrooms with no supplementary bonding Fault at light in attic supplementary bonding in bathroom restored Consumer unit Attic Socket Fault location Light Bathroom Heater Showers earth U t =3.6 V MET U t =24 V U t =1.56 V Cold water cu. pipe Extraneous conductive part Figure 8 Elimination of presence of transfer touch voltage in bathrooms by mandatory supplementary bonding it was not switched on, has attained a value of 64 V, which is considered a dangerous voltage for people with low body resistance. In addition to using Earthed Equipotential Bonding by Automatic Disconnection of Supply (EEBADS) as the primary method of protection against electric shock faults, IEE Guidance note 5 10 suggests that additional supplementary equipotential bonding conductors can be installed at strategic locations so that any touch voltage U t originating from outside the particular location is lowered to a safe-touch-value. This was implemented as a control comparison and the results are shown in Figure 8. Simulation results, supplementary bonding restored With a fault simulated on the light in the attic, touch voltages were recorded at the fault location and in the bathroom. The voltage and current were recorded at 4.35 V and 15 A, respectively. The reduction in the voltage required to drive 15 A through the circuit dropping to 4.35 V due to the parallel paths back to the MET as shown in Figure 8. 10 A of the 15 A was recorded flowing towards the bathroom and the remaining

36 Analysis of transfer touch voltages 5.0 A was recorded flowing from the fault towards the distribution board. In the bathroom the 10 A split in two directions, 7 A flowed through the electric showers earth circuit and 3 A flowed through the copper pipes. The touch voltages recorded under simulation were as follows, 0.96 V at the faulty light in the attic, 0.144 V between the heater and electric shower in the bathroom and 0.066 V between the heater and cold-water copper pipes. From the recorded values it was possible to calculate the resistance, 4.35/15 A ¼ 0.29 X ¼ resistance of circuit under fault conditions. 0.29 0.23 X (impedance of earth wire and variac) ¼ 0.06 X ¼. Also, the resistances of the supplementary bonding in the bathroom could be calculated, 0.144 V/ 7A¼ 0.02 X and 0.066 V/3 A ¼ 0.02 X. Using the recorded values an approximated value for the various touch voltages can be calculated. Using Equation (1): Touch voltage at faulty light ¼ U t ¼ 24 V ¼ 240 ð0:06=0:42 þ 0:12 þ 0:06Þ To determine the touch voltages developed in the bathroom, the prospective fault current (I pf ) at the fault location was calculated: I pf ¼ 233 V 0:6 ¼ 388 A Two-thirds (259 A) of the total fault current flows towards the bathroom under fault conditions. The current that would flow to earth via the cold water copper pipes is given by (3/10) 259 A ¼ 78 A. Hence the touch voltage between the heater and cold water copper pipe would be approximately 78 0.02 X ¼ 1.56 V. Therefore the touch voltage between heater and the shower would be approximately be 259 A (7/10) 0.02 X ¼ 3.6 V. The findings demonstrate that with supplementary bonding, the transfer touch voltage was reduced to less than 4 V within the bathroom. Therefore it appears that there is sufficient evidence to show that with supplementary bonding in place, even in the event of a defective RCD a or a sluggish overcurrent protection device such that the faulty circuit might remain in an energised state for quite some time, a person in the bathroom would only be exposed to a touch voltage of 4 V or less. Alternatively, a designer or installer can opt for making sure that all the circuits within the same dwelling will have a very low safe touch voltage value in the event of a fault. For example, to have a transfer touch voltage not exceeding 12 V 4 maximum to provide protection against electric shock for a person with very low body resistance in the special location. This requires the designer and installer to have a good understanding of the sensitivity of the resulting touch voltage in relation to percentage changes of U oc, Z e, R 1 and between design and as-installed phases. 5 Touch voltage sensitivity analysis In this section, the technique of partial differentiation for small percentage changes was used to determine the sensitivity of touch voltage in relation to the four design parameters: Equation (4) is obtained by applying partial differentiation to Equation (1): U t ¼ @f U oc þ @f Z e @U oc @Z e þ @f @R 1 R 1 þ @f @ ð4þ a From the ERA Technology Report In-service reliability of RCDs published in Italy in May 2006 electromechanical RCDs have an average failure rate of 7.1%. If RCDs are tested regularly this figure falls to 2.8%. RCD reliability is improved if the test button is operated regularly. However, the report has indicated that RCDs with an inadequate IP rating subjected to dust and moisture could have a 20% failure rate.

M Barrett et al. 37 where f ¼ U t ¼ U oc ð =Z e þ R 1 þ Þ and U t is the small change in touch voltage, giving the result of (For simplicity, we have let Z e, R 1 and be summed directly. The actual U t can vary significantly when complex quantities are used.): U t ¼ U oc Z e þr 1 þ þ U oc ðz e þr 1 þ Þ 2 Z e þ U oc ðz e þr 1 þ Þ 2 R 1 U oc þ ðz e þr 1 þ Þ 2 þ U oc ðz e þr 1 þ Þ U t ¼ U oc þ U oc w Z s ð5þ Z s where Z s ¼ Z e þ R 1 þ, w ¼ðU oc =Z 2 s Þ, and Z s ¼ Z e þ R 1 þ U 0 t ¼ U t þ U t ð6þ 0 where U t is the final touch voltage after changes of U oc, Z e, R 1 and been accounted for. Equations (5) and (6) allow the designer and installer to investigate the resulting magnitude of the change in touch voltage U t for any combination of percentage changes of the four design parameters U oc, Z e, R 1 and. As an example: for a final circuit with a U o ¼ 230 V, U oc ¼ 240 V TNC-S system, R 1 ¼ 0.1 X and ¼ 0.15 X, during the design stage Z e ¼ 0.35 X and I pf ¼ 16 ka were obtained from the electricity supplier by enquiry. b Using Equation (1), the estimated touch voltage U t can be evaluated equal to 60 V. However, the actual touch voltage will change due to the percentage variation of the four parameters for reasons beyond the control of the designer as below: U oc changes by þ6% c due to the variation of the utility supply, U oc ¼ 240 ðþ6%þ ¼þ14:4 V Z e changes by 35% due to the location of the utility supply transformer, Z e ¼ 0:35 ð 35%Þ ¼ 0:1225 R 1 changes by 15% due to shorter cable runs in the construction stage, R 1 ¼ 0:1 ð 15%Þ ¼ 0:015 and changes by 15% due to shorter cable runs in the construction stage, ¼ 0:15 ð 15%Þ ¼ 0:0225 Using Equation (5), the change of touch voltage will be: U t ¼ð3:6 þð 9ÞÞ ð 16ÞV ¼ 10:6V Hence, U 0 t ¼ð60 þ 10:6ÞV ¼ 70:6V, approximately. The actual U t is 73.72 V if the exact value of R 1 ¼ 0.085 X, ¼ 0.1275 X, Z e ¼ 0.2275 X and U oc ¼ 254.4 V were applied to Equation (1). The discrepancy of (73.72 70.6) V ¼ 3.12 V is mainly due to the large percentage change of Z e but the overall result is still within an acceptable margin. It can be seen from the above, the touch voltage sensitivity equation (5) derived in this paper is thus a powerful tool for designers and installers of electrical installations to investigate and identify the sensitivity of resulting touch voltages of any electrical circuits. b BS7671: 2008, Regulation 434.1 suggests determination of prospective short circuit current (I pf ) at the relevant point of the installation may be done by calculation, measurement or enquiry. c The UK ESQC Regulations state that the declared nominal voltage on LV networks is 230 V 10%, the open circuit voltage at the DNO supply transformer is normally set at 240 V, hence 240 V þ 6% is used in the analysis.

38 Analysis of transfer touch voltages 6 Conclusion The underpinning basic theory of the safe touch voltage design equation has been explained and illustrated with an example. A generic circuit diagram is presented illustrating how a touch voltage of a dangerous magnitude could be transferred from a faulty circuit onto healthy equipment located elsewhere within an electrical installation. A touch voltage case study has been used to demonstrate that a dangerous touch voltage could be present in locations where extreme low body resistance may exist. It has been demonstrated that by the use of local supplementary bonding, the danger of any touch voltage transferred from a fault arising from outside the bathroom can almost be completely eliminated even in the event of a fault of long duration. A set of touch voltage sensitivity calculation equations has been developed and using an example, the authors have demonstrated that the equations can be used by installation designers and installers to investigate and identify the range of resulting touch voltage values that might be the consequence of variation of the four main design parameters U oc, Z e, R 1 and. References 1 HSE. Statistics of fatal injuries, 2006 2007. Caerphilly, UK, HSE Information Services. 2007. 2 Pointer S, Harrison J. Electrical injury and death. Flinders University, South Australia [Online]. 2007 [Cited April 2008]. Available at: http://www.nisu.flinders.edu.au/pubs/reports/ 2007/injcat99.php accessed April 2008. 3 NFPA. NEC 2008 National Electrical Code. USA, NFPA, 2008. 4 BSI/IET. BS7671: 2008 Requirements for Electrical Installations IEE Wiring Regulations, 17th edn. London, UK, BSI/IET, 2008. 5 IEC. IEC60364: 2002 06 Electrical installations of buildings, 2nd edn. Geneva, Switzerland, IEC. 2001. 6 Cook P. Commentary on IEE wiring regulations (BS7671: 2001), 16th edn. Stevenage, UK, The IEE, 2002. 7 Jenkins BD. Electrical installation calculations. UK, Blackwell Scientific Publications Ltd, 1993. 8 IEC. IEC 60479 part 1: effects of current on human beings and live stock. Geneva, Switzerland, IEC, 2007. 9 BSI/IET. BS7671: 2001 Requirements for electrical installations, including amendments No 1 and No 2, 16th edn. London, UK, BSI/IET, 2004. 10 IET. IEE Guidance Note 5, Protection against electric shock. London, UK, IET, 2005. 11 ETCI. ET101: 2006 National rules for electrical installations, 3rd edn. Ireland, Electro-technical Council, 2006.