Bauart gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 2000~6000W U Distributed Power System RKP-U Rack System File Name:RKP-U RACK SYSTEM-SPEC 206-07-26
2000~6000W U Distributed Power System RKP-U Rack System SPECIFICATI - Power Supply System MODEL RKP-6KU -2 RKP-6KU -24 RKP-6KU -4 RECTIFIER RCP-2000-2 RCP-2000-24 RCP-2000-4 RACK SHELF RKP-UI or RKP-UT OUTPUT OUTPUT VOLTAGE 2V 24V 4V MAX. OUTPUT CURRENT 300A 240A 26A MAX. OUTPUT POWER Note.7 3600W 5760W 604W VOLTAGE RANGE Note.6 90 ~ 264VAC 27 ~ 370VDC INPUT FREQUENCY RANGE 47 ~ 63Hz AC CURRENT (Typ.)PER MODULE 3A/5VAC 7A/230VAC 6A/5VAC A/230VAC 6A/5VAC A/230VAC LEAKAGE CURRENT <3.5mA / 230VAC AUXILIARY POWER 5V @ 0.3A, 2V @ 0.A REMOTE - CTROL By electrical signal or dry contact :short :open REMOTE SENSE Compensate voltage drop on the load wiring up to 0.5V. FUNCTI OUTPUT VOLTAGE PROGRAMMABLE Adjustment of output voltage is allowable to 90 ~ 0% of nominal output voltage. Please refer to the Function Manual. DC OK SIGNAL AC OK SIGNAL OVER TEMP WARNING Logic " High" for over temperature warning, Please refer to the Installation Manual, isolated signal FAN FAIL SIGNAL WORKING TEMP. -40 ~ +70 (Refer to "Derating Curve") WORKING HUMIDITY 20 ~ 90% RH non-condensing ENVIRMENT STORAGE TEMP., HUMIDITY -40 ~ +5, 0 ~ 95% RH TEMP. COEFFICIENT ± 0.03%/ (0 ~ 50 ) VIBRATI 0 ~ 500Hz, 2G 0min./cycle, 60min. each along X, Y, Z axes SAFETY & EMC (Note 5) OTHERS NOTE SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATI RESISTANCE EMC EMISSI EMC IMMUNITY UL60950-, TUV EN60950- approved I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC I/P-O/P, I/P-FG, O/P-FG:00M Ohms / 500VDC / / 70% RH Parameter Standard Conducted Radiated Harmonic Current Voltage Flicker EN55024, EN6204-3, EN6000-6-2 Parameter ESD Radiated EFT / Burst Surge Conducted Magnetic Field Voltage Dips and Interruptions EN550 (CISPR) / EN550 (CISPR) Class A EN550 (CISPR) / EN550 (CISPR) Class A EN6000-3-2 ----- EN6000-3-3 ----- Standard EN6000-4-2 EN6000-4-3 EN6000-4-4 EN6000-4-5 EN6000-4-6 EN6000-4- EN6000-4- Test Level / Note Test Level / Note, KV air ; Level 2, 4KV contact Level 4, 4KV/Line-Earth ;, 2KV/Line-Line Level 4 >95% dip 0.5 periods, 30% dip periods, >95% interruptions 0 periods DIMENSI Rack 43.6*350.*44(L*W*H) PACKING 4.Kg; pcs/4.kg/2.67cuft File Name:RKP-U RACK SYSTEM-SPEC 206-07-26
2000~6000W U Distributed Power System RKP-U Rack System Function Manual. Voltage Drop Compensation. Remote Sense The remote sense compensates voltage drop on the load wiring up to 0.5V. RKP-U System +S -S 23 LOAD Sense lines should be twisted in pairs.2 Local Sense Notice : The +S,-S on CN500 have to be connected to the (signal),(signal),respectively, in order to get the correct output voltage if the remote sensing is not used. RKP-U System +S -S 24 23 2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim) ()Connecting an external DC source between PV(4,0,9) and () on CN500 that is shown in Fig. 3.. (2)Adjustment of output voltage is possible between 90~0%(Typ.) of the nominal voltage which is shown in Fig. 3.2. Reducing output current is required when the output voltage is trimmed up. 4,0,9 PV 0~5V Fig. 2. Add on 0~5V external voltage OUTPUT VOLTAGE(%) Vout 0 00 90 0 70 60 0 0.5.5 3 4.5 5 V OUTPUT CURRENT (%) 00 90 0 70 60 70 0 90 00 0 V EXTERNAL VOLTAGE(DC) OUTPUT VOLTAGE (%) Fig. 2.2 Output voltage trimming 3. Remote - Control The power supply can be turned / together or separately by using the "Remote -" function. RKP-U System Remote - A Remote - B Remote - C 7 Remote - A 7 6 Remote - B 6 RKP-U Remote - C System 3 3 Between Remote - and Switch Open Switch Short Output 4.PMBus Communication Interface RCP-2000 supports PMBus Rev.. with maximum 00KHz bus speed, allowing information reading, status monitoring and output trimming. For details, please refer to the Installation Manual. File Name:RKP-U RACK SYSTEM-SPEC 206-07-26
2000~6000W U Distributed Power System RKP-U Rack System Mechanical Specification (Rack System) Case No. 959A Unit:mm Fig 4 3 RKP-UT C B - + A CN500 JK Fig2 FG FG FG N N N L L L 0.2 0.2 0.2 C B - + A CN500 JK RKP-UI Mounting Bracket IEC320-C20 IEC320-C20 IEC320-C20 440 50 3-M5 L=6mm 350. SVR SVR SVR 3-M5 L=6mm 50 24 46 Air flow direction Module C Module B Module A 44 7. 7 0.2 29.4 DC OK DC OK DC OK 466. 43.6 7.42 Mounting Instruction Hole No. Recommended Screw Size MAX. Penetration Depth L Recommended mounting torque M5 6mm 0Kgf-cm Mounting Surface Mounting Screw L Chassis of RKP-U RACK File Name:RKP-U RACK SYSTEM-SPEC 206-07-26
2000~6000W U Distributed Power System RKP-U Rack System LED Status Indicators & Corresponding Signal at Function Pins Function LED Description AC-OK AC-NG DC-OK DC-NG T-OK T-ALARM When input voltage 7V When input voltage 75V When output voltage 0% ± 5% of Vo rated. When output voltage 0% ± 5% of Vo rated. When the internal temperature (TSW & TSW2 short) is within safe limit When the internal temperature (TSW or TSW2 open) exceeds the limit of temperature alarm *Signal between function pin and "GND-AUX". IN/OUT Connector Pin No. Assignment( CN500) : D-Type Right Angle positions (female type) * Signal PSU Output 4 3 Pin No. Function Description REMOTE Each unit can separately turn the output on and off by electrical signal or dry contact between / A,B,C(pin,7,6) and,7,6 / (pin 3). Short:, Open:. (Note.2) 2,,7 3,9, 4,0,9 5,,20 6,2,2 3 4 5 AC-OK DC-OK PV T-ALARM FAN FAIL +2V-AUX GND-AUX +S 23 -S 24 (signal) (signal) Low : When the input voltage is 7Vrms. High : when the input voltage in 75Vrms. (Note.2) High : When the Vout 0± 5%. Low : When Vout 0± 5%. (Note.2) Connection for output voltage programming. High : When the internal temperature (TSW or TSW2 open) exceeds the limit of temperature alarm. Low : When the internal temperature (TSW or TSW2 short) under the limit temperature. (Note.2) High : When the internal fan fail. Low : When the internal fan is normal. (Note.2) Auxiliary voltage output,, referenced to GND- AUX (pin 5). The maximum load current is 0.3A. This output has the built-in "Oring diodes" and is not controlled by the remote / control. Auxiliary voltage output, 0. ~ 3.2V, referenced to GND- AUX (pin 5). The maximum load current is 0.A. This output has the built-in "Oring diodes" and is not controlled by the remote / control. Auxiliary voltage output GND. The signal return is isolated from the output terminals ( & ). Positive sensing for remote sense. Negative sensing for remote sense. Positive output voltage. For local sense use only, can't be connected directly to the load. Negative output voltage. For local sense use only, can't be connected directly to the load. IN/OUT Connector Pin No. Assignment( JK ) : RJ45 positions Pin No.,2 3 4 5 6 Function DA,DB (signal) CTROL NC SDA 7 SCL GND-AUX Serial Clock used in the PMBus interface. (Note.2) Auxiliary voltage output GND. The signal return is isolated from the output terminals ( & ). Note.: Non-isolated signal, referenced to the (signal). Note.2: Isolated signal, referenced to GND-AUX. Installation Manual Please refer to the manual of RKP-U system. Description Differential digital signal for parallel control. (Note.) Negative output voltage. For parallel control, can't be connected directly to the load. Remote / control pin used in the PMBus interface. (Note.2) Retain for future use. Serial Data used in the PMBus interface. (Note.2) File Name:RKP-U RACK SYSTEM-SPEC 206-07-26