Frequency Linked Price using Unscheduled Interchange (UI) Signals of Two Area Power System

Similar documents
A NOVEL PRICE BASED LOAD FREQUENCY CONTROL APPROACH TO DAMP OUT SYSTEM OSCILLATIONS UNDER DEREGULATED POWER ENVIRONMENT

Shuffled Complex Evolution

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-2015 ISSN

AGC in Five Area Interconnected Power System of Thermal Generating Unit Through Fuzzy Controller

Decentralized Model Predictive Load Frequency Control of deregulated power systems in tough situations

AUTOMATIC VOLTAGE REGULATOR AND AUTOMATIC LOAD FREQUENCY CONTROL IN TWO-AREA POWER SYSTEM

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

Lecture 15 EMS Application II Automatic Generation Contol. Davood Babazadeh

GENETIC ALGORITHM BASED CONGESTION MANAGEMENT BY USING OPTIMUM POWER FLOW TECHNIQUE TO INCORPORATE FACTS DEVICES IN DEREGULATED ENVIRONMENT

Artificial Intelligent and meta-heuristic Control Based DFIG model Considered Load Frequency Control for Multi-Area Power System

Load Frequency Control in an Interconnected Hydro Hydro Power System with Superconducting Magnetic Energy Storage Units

QFT based Robust Load Frequency Controller Design for Multi-Area Power System

Load Frequency Control for Two Area Deregulated Power System Using ANN Control

Automatic Generation Control of Two Area using Fuzzy Logic Controller

AUTOMATIC GENERATION CONTROL OF REHEAT THERMAL GENERATING UNIT THROUGH CONVENTIONAL AND INTELLIGENT TECHNIQUE

Control of Load Frequency of Power System by PID Controller using PSO

SOCI 360. SociAL Movements. Community Change. sociology.morrisville.edu. Professor Kurt Reymers, Ph.D. And

CHAPTER 5 PERFORMANCE EVALUATION OF SYMMETRIC H- BRIDGE MLI FED THREE PHASE INDUCTION MOTOR

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

CHAPTER 5 PSO AND ACO BASED PID CONTROLLER

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

International Journal of Computer Engineering and Applications, Volume XII, Special Issue, March 18, ISSN

Load-Frequency Control Service in a Deregulated Environment

[Jahangir* et al., 5.(6): June, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

LFC in hydro thermal System Using Conventional and Fuzzy Logic Controller

Automatic Generation control of interconnected hydrothermal power plant Using classical and soft computing Technique

Automatic Generation Control of Three Area Power Systems Using Ann Controllers

A NEW LOAD FREQUENCY CONTROL METHOD OF MULTI-AREA POWER SYSTEM VIA THE VIEWPOINTS OF PORT-HAMILTONIAN SYSTEM AND CASCADE SYSTEM

AUTOMATIC GENERATION CONTROL OF INTERCONNECTED POWER SYSTEM WITH THE DIVERSE SOURCES USING SUPERCONDUCTING MAGNETIC ENERGY STORAGE (SMES)

Optimum Coordination of Overcurrent Relays: GA Approach

IMPLEMENTATION OF NEURAL NETWORK IN ENERGY SAVING OF INDUCTION MOTOR DRIVES WITH INDIRECT VECTOR CONTROL

GENETIC ALGORITHM BASED OPTIMAL LOAD FREQUENCY CONTROL IN TWO-AREA INTERCONECTED POWER SYSTEMS

Power Transfer Distribution Factor Estimate Using DC Load Flow Method

FOUR TOTAL TRANSFER CAPABILITY. 4.1 Total transfer capability CHAPTER

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

Analysis and Enhancement of Voltage Stability using Shunt Controlled FACTs Controller

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE

Smart Grid Reconfiguration Using Genetic Algorithm and NSGA-II

1. Governor with dynamics: Gg(s)= 1 2. Turbine with dynamics: Gt(s) = 1 3. Load and machine with dynamics: Gp(s) = 1

Performance Analysis of PSO Optimized Fuzzy PI/PID Controller for a Interconnected Power System

Load frequency control of interconnected system

Load Frequency Control of Multi-Area Power Systems Using PI, PID, and Fuzzy Logic Controlling Techniques

Evolutionary Programming Optimization Technique for Solving Reactive Power Planning in Power System

Load Frequency Controller Design for Interconnected Electric Power System

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Stability Issues of Smart Grid Transmission Line Switching

Lecture 10: Memetic Algorithms - I. An Introduction to Meta-Heuristics, Produced by Qiangfu Zhao (Since 2012), All rights reserved

TWO AREA CONTROL OF AGC USING PI & PID CONTROL BY FUZZY LOGIC

Load Frequency Control of Three Area System using FOPID Controller

The Role of Effective Parameters in Automatic Load-Shedding Regarding Deficit of Active Power in a Power System

I. INTRODUCTION. Keywords:- FACTS, TCSC, TCPAR,UPFC,ORPD

LOAD FREQUENCY CONTROL FOR A TWO-AREA INTERCONNECTED POWER SYSTEM BY USING SLIDING MODE CONTROLLER

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

Review of AGC Implementation Issues Before and After Deregulation

OPTIMAL CONTROL STRATEGY FOR ENERGY STORAGE SYSTEM PARTICIPATING IN AUTOMATIC GENERATION CONTROL

Available online at ScienceDirect. Procedia Computer Science 92 (2016 ) 36 41

Tuning of PID Controller in Multi Area Interconnected Power System Using Particle Swarm Optimization

COMPUTATION OF STABILIZING PI/PID CONTROLLER FOR LOAD FREQUENCY CONTROL

Matlab Design and Simulation of AGC and AVR for Multi Area Power System and Demand Side Management

Enhancement of Voltage Stability by SVC and TCSC Using Genetic Algorithm

UNIT-II REAL POWER FREQUENCY CONTROL. 1. What is the major control loops used in large generators?

Achieving Desirable Gameplay Objectives by Niched Evolution of Game Parameters

Table of Contents Error! Bookmark not defined.

Simulation of Synchronous Machine in Stability Study for Power System: Garri Station as a Case Study

Analysis of Stability and Sensitivity of LFC-DR Model for Single Area Power System

A Genetic Algorithm for Optimum Design of PID Controller in Multi Area Load Frequency Control for Egyptian Electrical Grid

Frequency Response Standard Background Document November, 2012

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

Coordination of overcurrent relay using Hybrid GA- NLP method

DISTRIBUTION NETWORK RECONFIGURATION FOR LOSS MINIMISATION USING DIFFERENTIAL EVOLUTION ALGORITHM

Performance Improvement Of AGC By ANFIS

Position Control of Servo Systems using PID Controller Tuning with Soft Computing Optimization Techniques

IMPROVING POWER SYSTEM STABILITY USING REAL-CODED GENETIC ALGORITHM BASED PI CONTROLLER FOR STATCOM

Stock Price Prediction Using Multilayer Perceptron Neural Network by Monitoring Frog Leaping Algorithm

ADVANCES in NATURAL and APPLIED SCIENCES

OPTIMAL PLACEMENT OF UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEMS USING PARTICLE SWARM OPTIMIZATION METHOD

Optimal PID Tuning for AGC system using Adaptive Tabu Search

Local Search: Hill Climbing. When A* doesn t work AIMA 4.1. Review: Hill climbing on a surface of states. Review: Local search and optimization

Current Control Strategy for Parallel Operation of Inverters Based On Micro grids M.Bavithra 1, Belwin J. Brearley 2

LOAD FREQUENCY CONTROL FOR TWO AREA POWER SYSTEM USING DIFFERENT CONTROLLERS

Design of GA Tuned Two-degree Freedom of PID Controller for an Interconnected Three Area Automatic Generation Control System

Publication P IEEE. Reprinted with permission.

A New Approach Applied to Adaptive Centralized Load Shedding Scheme

Effect of Parameter Tuning on Performance of Cuckoo Search Algorithm for Optimal Reactive Power Dispatch

Wire Layer Geometry Optimization using Stochastic Wire Sampling

Population Adaptation for Genetic Algorithm-based Cognitive Radios

Demonstration of PFR Improvement September ERCOT Operations Planning

Effects of Super Conducting Magnetic Energy Storage Device and Redox Flow Battery in a Genetic Algorithm Based Load Frequency Controller

Evolutionary Programming Based Optimal Placement of UPFC Device in Deregulated Electricity Market

CHAPTER 1 INTRODUCTION

Automatic load frequency control of multi-area power system using ANN controller and Genetic algorithm

ISSN Vol.03,Issue.07, August-2015, Pages:

Meta-Heuristic Approach for Supporting Design-for- Disassembly towards Efficient Material Utilization

VIENNA RECTIFIER FED BLDC MOTOR

Modeling and Simulation of Load Frequency Control for Three Area Power System Using Proportional Integral Derivative (PID) Controller

A Novel Control Approach for Microgrids Islanded Operation - Load Step Pre-announcement and Bang-Bang Control

Chapter 5 OPTIMIZATION OF BOW TIE ANTENNA USING GENETIC ALGORITHM

International Journal of Advance Engineering and Research Development

Design of PID Controller for Higher Order Discrete Systems Based on Order Reduction Employing ABC Algorithm

Transcription:

Frequency Linked Price using Unscheduled Interchange (UI) Signals of Two Area Power System Aravind.R Jennathu Beevi.S Jayashree.R PG Student [Power System], Assistant Professor, Professor, Dept. of EEE, Dept. of EEE, Dept. of EEE, B.S.Abdur Rahman University, B.S.Abdur Rahman University, B.S.Abdur Rahman University, Vandalur, Chennai, Vandalur, Chennai Vandalur, Chennai ABSTRACT: Unscheduled Interchange (UI) price is one of the components of ABT, acts as a Secondary Control mechanism for regulating the grid frequency. This UI price signals fluctuate according to change in grid frequency which can be accessible by participants (generator or load) connected to the grid. This paper, discusses the UI linked frequency price of two area power system for Evolutionary Algorithms. CERC, 2013 UI rate curve has been used for this analysis. KEYWORDS: Availability Based Tariff, Unscheduled Interchange, Deregulated Electricity Market, Generation Control Error, Incremental Marginal Cost, Shuffled Frog Leaping Algorithm. I.INTRODUCTION The successful operation of power system requires the balance between supply and demand on a minute to minute basis. In well developed countries the ancillary service called Automatic generation control (AGC) which measures the deviation in frequency and tie-line power flow instantly due to change in scheduled interchange. Automatic Generation Control is one of the most important ancillary services in deregulated market. This task also becomes more challenging in present deregulated electricity market. Primary control (FGMO) is necessary to maintain frequency within the desirable limits. As the interconnections grow larger in size and the interchanges between areas also increases, so the primary control by governors has to be supplemented by secondary control (AGC) [2]. Both Primary and secondary controls are necessary to keep frequency and schedules within acceptable ranges for reliability. Even a large deviation can be brought in to zero within few minutes using AGC in United States. But in India Automatic Generation Control is incompatible because of generation shortage. The power generation capacity of India has steadily increased over past few years, but demand growth has gone far ahead of supply growth. This tends to an energy shortage.in year 2003 the electricity has gone through a major transformation from vertical integrated utility (VIU) to open market system which encourage the trading activities and competition in the Indian electricity sector. Before 2002, grid operators in India faced a major problem in the form of grid indiscipline, because of random fluctuation in grid frequency 48 Hz to 52 Hz on daily basis resulting in frequent blackouts. The UI mechanism was introduced in 2002 before the market in electricity was developed. The objective of the regulations was to maintain grid discipline as envisaged under the Grid Code through the commercial mechanism of Unscheduled Interchange Charges by controlling the users of the grid in scheduling, dispatch and drawl of electricity [10]. The term Availability Based Tariff stands for a rotational tariff structure for power supply from generating stations on a contracted basis. The special features of this tariff are to handle the peculiar problem of grid operation in India, which is the frequency, linked pricing of UI. 100 Aravind.R, Jennathu Beevi.S, Jayashree.R

2. ABT UI MECHANISM The ABT introduced a three part tariff structure by unbundling the fixed and variable energy charges. The first component is a fixed one and it is purely depends on the availability of generating stations. This is called as Capacity Charge. The second part of this ABT is the variable component which is based on the fuel consumption given by the schedule of the day and is known as Energy charge. In addition to these two charges, a third charge contemplated in the ABT scheme is for the unscheduled interchange of power (UI charges). The UI charges are payable depending upon what is deviated from the schedule and also subject to the grid conditions at that point of time [10]. This ABT element was introduced to bring the effective discipline in power system. Under this scheme UI charges will be payable, if i)a generator generates more than the schedule, thereby increasing the frequency; ii) a generator generates less than the schedule, thereby decreasing the frequency; iii) a beneficiary overdraws power, thereby decreasing the frequency; iv) a beneficiary under draws power, thereby increasing the frequency [10]. It is clear that the UI charges are a commercial mechanism to maintain grid discipline. The UI charges penalize whosoever caused grid indiscipline, whether generator or distributor, is subject to payment of UI charges that who are not following the schedule. UI rate is high during low frequency which discourages the over drawl of power to the beneficiaries and UI charge is low, if the above statement is Vice versa. As long as the actual generation or withdrawal is strict to the given schedule, the third component of ABT is zero [2]. If the frequency is above 50 Hz (nominal frequency of Indian System), UI rate will be less and if it is below 50 Hz, it will be more, which discourages beneficiary the over drawl of power. 3. PRICE BASED AUTOMATIC GENERATION CONTROL (PBAGC) Fig 1: FGMO and ABT Based Frequency Control Loop It explains the PBAGC ensuring that the generation units respond to the UI price signal automatically. Fig 1. Shows both primary and ABT based secondary control mechanism. The primary control remains same that of the conventional method but the automatic secondary control uses UI price signals. Primary control responds to a change in frequency instantly by Free Governor Mode of Operation (FGMO), and the secondary control loop operates automatically following the UI price signals which is available in real time. In case there is a need of more generation that cannot be supplied through primary control. This can be satisfied by ABT based secondary control mechanism. 101 Aravind.R, Jennathu Beevi.S, Jayashree.R

Fig 2. shows the ABT Based Frequency Control Loop. Each generator monitors UI price ρ, its marginal cost ɤ and compares, and then the error signal (ρ- ɤ) is generated. This error signal is fed in to an Integral controller which brings the frequency to its nominal value. Fig 2: ABT Based Frequency Control Loop 4. SYSTEM MODELING I. FREQUENCY-UI PRICE BLOCK UI curve was introduced in the year 2000. It has been ordered by Central Electricity Regulatory Commission (CERC), so as to meet the states objectives of ABT mechanism. Initially, the frequency range in UI price was set in between 49.0 Hz to 50.5 Hz (CERC, 2000) and the maximum price limit was 4800 INR/MWh at 49.0 Hz and the minimum price was zero INR/kWh at 50.5 Hz [2]. In CERC2009, the frequency range was set between 49.2 Hz to 50.3 Hz and the price limit was zero to 7350 INR/MWh. We have used the UI rate curve 2013, for frequency to UI price conversion as shown in Figure.3,. The actual frequency is the sum of the frequency deviation and the nominal frequency and it is given in equation (1) as follows, Frequency signal S1 (f) = Δf + f 0 Hz. Where, Δf is the change in frequency and f 0 is the nominal frequency 50 Hz. 102 Aravind.R, Jennathu Beevi.S, Jayashree.R

Fig 3: UI rate CERC, 2013 if u>50.05 y=0; elseif u<=50.05 y=35600*(50.05-u); elseif u>50 y=35600*(50.05-u); elseif u<=50 y=1780+155400*(50-u); elseif u>49.95 y=1780+155400*(50-u); elseif u<=49.95 y=9550+155400*(49.95-u); elseif u>49.94 y=9550+155400*(49.95-u); else u<=49.94 y=11104; end Fig 4: UI rate (CERC, 2013) block II. INCREMENTAL MARGINAL COST In general marginal cost of generation, ɤ is related to the turbine generator power output [2]. For each generator, Overall cost of the generation is given by the quadratic equation (2), C i (P gi) = a i + b i P gi + c i P gi 2 INR/h (2) Then, the incremental marginal cost of generator is given by equation (3), ɤ i = dci (Pgi) = 2 ci Pgi + bi INR/MWh (3) dpgi Incremental cost signal S4 (ɤ) is given by the following equation (4) S4 (ɤ) = 2 * c* S3 + b INR/MWh (4) Where c and b are the incremental cost coefficient of the system. S3 (P g) is given by the equation (5), S3 (P g) 0 = P g + ΔP g MW (5) 103 Aravind.R, Jennathu Beevi.S, Jayashree.R

Where, ΔP g is change in turbine generator output and P g 0 is an initial scheduled power of generation and Ρ 0 is the UI rate corresponding to nominal frequency f 0 = 50 Hz. Ρ 0 = 1650 INR/MWh shown in Figure.3. Further s2 (ρ) and S4 (ɤ) signal is compared as per the flowchart Fig 5.and generate the error called GCE. III. GENERATION CONTROL ERROR (GCE) Fig 5: Flowchart for Calculating GCE 5 SHUFFLED FROG LEAPING ALGORITHM A memetic algorithm known as Shuffled Frog Leaping Algorithm is used in this paper. A memetic algorithm (MA) is a population-based approach for a heuristic search in optimization problems. Meme (pronounced meem ) is a contagious information pattern that replicates by parasitically infecting human and/or animal minds and altering their behavior, which causes them to propagate the pattern. The actual content(s) of a meme, called memotype(s), are analogous to the chromosome(s) of a gene. An idea or information pattern is not a meme until it causes someone to replicate it or to repeat it to someone else Memes will be positively selected mainly for increased communicability among the hosts (described as frogs in the SFLA). Genes will be selected mainly for sexual reproducibility. Memetic and genetic evolution are subjected to the same basic principles, i.e. possible solutions are created, selected according to some measure of fitness, combined with other solutions and possibly mutated. Memetic evolution, however, is a much more flexible mechanism. Genes can only be transmitted from parents or parent in the case of asexual reproduction to offspring. Memes can, in principle, be transmitted between any two individuals. Since genes are transmitted between generations, higher organisms may take several years to propagate. Memes can be transmitted in the space of minutes. Gene replication is restricted by the rather small number of offspring from a single parent, whereas the number of individuals that can take over a meme from a single individual is almost unlimited. It is much easier for memes to undergo variation since the information in the nervous system is more plastic than that in deoxyribonucleic acid and since individuals can come into contact with many different sources of novel memes. Therefore, meme spreading is much faster than gene spreading. The other difference between 104 Aravind.R, Jennathu Beevi.S, Jayashree.R

memes and genes is that memes are processed and possibly improved by the person that holds them something that cannot happen to genes. The flowchart for the SFL algorithm is given in Fig 6. Begin - Initialize - Population size (N) - Number of memeplexes (m) - Number of evolution step Within each memeplex Generate population (P) Evaluate the fitness of (P) Sort (P) in descending order Partition (P) into m memeplexes Local Search Iterative updating the worst frog of each memeplex Shuffle the memeplexes Convergence criteria satisfied? No Yes Determine the best solution End Fig 6: Flowchart of SFLA 105 Aravind.R, Jennathu Beevi.S, Jayashree.R

6. SIMULATION DIAGRAM Fig 7: PBAGC model for Two Area four Generator System using MATLAB/SIMULINK The test system is a single area system having a capacity of 2000 MW supplied by three generating stations which follows the schedule as per merit order. The system data and Generator data are given in Table 1 and Table 2 respectively. 106 Aravind.R, Jennathu Beevi.S, Jayashree.R

Base power Area rated power Pr1=Pr2 Area inertia constant Input Data Area damping co-efficient : D1=D2 Droop of each generator:r1=r2=r3=r4 Governor time constant of each generator: Tg1=Tg2=Tg3=Tg4 Non reheat time constant of each turbine: Tt1=Tt2=Tt3=Tt4 Reheat unit of each turbine time constant : Tr1=Tr2=Tr3=Tr4 Table 1: System Data Reheat fraction unit of each turbine time constant : Kr1=Kr2=Kr3=Kr4 P tiemax Synchronizing co-efficient 2II*T12 2000 MW 2000 MW 5 seconds 8.33*10-3 pu MW/Hz 2.4 Hz/pu MW 0.08 seconds 0.3 10 0.5 200 MW 0.545 pu MW/Hz Ratings/Values Table 2: Generator Data Parameters Generators G1 G2 G3 G4 Capacity(MW) 1000 1000 1000 1000 b i (Rs./MWh) 1600 2000 2400 3600 c i ( Rs./MWh 2 ) 0.4 0.4 2 2.5 Disco Participation Matrix 0.5 0.25 0 0.3 DPM = 0.2 0.25 0 0 0 0.25 1 0.7 0.3 0.25 0 0 Table 3: Generation Schedule (in MW) System Marginal Cost (Rs./MWh) Generator 1(MW) Generator2(MW) Generator3(MW) Generator4(MW) 1850 775 275 400 80 107 Aravind.R, Jennathu Beevi.S, Jayashree.R

6. SIMULATION RESULT Case-1: The marginal cost of the system is higher than the nominal UI rate of year 2014; Fig 8 and 9 shows, the frequency deviation in area 1&2. Fig 10 shows, the response of load change in four generators and Fig 11 shows the tie-line actual and error power deviation. Fig 12,13,14 and 15 shows, response of change in GCE of all four generators. Fig 8: Area1 Frequency deviation vs. Time Fig 9: Area2 Frequency deviation vs. Time. Fig 10: Generated power vs Time Fig 11: Tie-Line Power flow vs Time Fig 12: Gce 1 vs Time Fig 13: Gce 2 vs. Time 108 Aravind.R, Jennathu Beevi.S, Jayashree.R

Fig 14: Gce 3 vs Time Fig 15: Gce 4 vs. Time Calculation for generation in MW Moreover, as given by Eq. (24), in the steady state, the Gencos must generate Similarly, G P 1 0.5(0.1) 0.25(0.1) 0(0.1) 0.3(0.1) = 0.105 pu MW= 210 MW P G2 = 0.045 pu MW = 90 MW P G3 = 0.195 pu MW = 390 MW P G4 = 0.055 pu MW = 110 MW 7. CONCLUSION This paper discusses Frequency linked price using unscheduled interchange price signal of two area power system. The effect of UI signals has been studied through different case of system marginal cost. The SFL algorithm is implemented to tune the gains of the Integral controllers in both areas. This helps in saving of unnecessary exchange of UI. REFERENCES [1]. B.Tyagi and S.C. Srivastava, A Mathematical Framework for Frequency-Linked Availability Based Tariff Mechanism in India, In Proceeding of 13 th National Power System Conference, IIT Chennai, India, December 2004,1,pp.516-521. [2]. S. Chanana and A. Kumar, A Price Based Automatic Generation Control Using Unscheduled Interchange Price Signals in Indian Electricity System, International Journal of Engineering, Science and Technology, vol- 2(2), 2010. pp. 23-30. [3]. S.K. Soonee, S. R. Narasimhan, and V. Pandey, Significance of Unscheduled Interchange Mechanism in Indian Electricity Supply Industry, ICPSODR-2006, Dept. of Electrical Engineering, ITBHU, India. [4]. Central Electricity Authority, 2012. Load Generation Balance Report 2012-13. CEA, New Delhi,IndiaAvailableonline:http://www.cercind.gov.in/2012/sharing_regulation/UI_Amendments_2011_dated_15.2. 2012.pdf [5]. J. Kumar, K. H. Ng and G. Sheble, AGC Simulator For Price-Based Operation Part -I: A Model, IEEE Transaction on Power System, 1997, 12(2), pp.527-532 [6]. J. Kumar, K. H. Ng and G. Sheble, AGC Simulator for Price Based Operation Part-II: Case Study Results, IEEE Transaction on Power System. May 1997, Vol.12 (2),Pp. 533-538. 109 Aravind.R, Jennathu Beevi.S, Jayashree.R

[7]. K. Bhatta charaya, Frequency Based Pricing as an Alternative to Frequency Regulation Ancillary Service, (NPSC 2000), Bangalore, India, December2000, pp.210-215r System, 1997, 12(2), pp.533-538. [8]. Pujara S., Kotwal C.: Optimized Integral Gain Controllers for Price Based Frequency Regulation of Single Area Multi-Unit Power System In: Int. Journal on Electrical Engineering and Informatics, accepted for to publish in Vol.6 (2), 2014.pp 306-323. [9]. Sandip Kumar Gupta, Deepak kumar, T.Ghose, Effect of Automatic Generation Controller of Participating Generators Under Frequency Linked Indian Tariff System 2010 Annual IEE Conference (INDICON). [10]. Unscheduled Interchange Charges and related matters; available online http://www.cercind.gov.in/regulations/unscheduled_sor-ui-final_26052010.pdf 110 Aravind.R, Jennathu Beevi.S, Jayashree.R