Recent results on the Power Quality of Italian 2x25 kv 50 Hz railways

Similar documents
Experimental validation of the electric network model of the Italian 2x25 kv 50 Hz railway

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions

MEASURING ELECTROMAGNETIC EMISSIONS FROM LARGE POWER ROTATING MACHINES

An Audio Frequency Model of a 2x25 kv Traction Line for High Speed Railway Systems

A magnetic field probe for hostile environments

On the characterization of pantograph arc transients on GSM-R antenna. Andrea Mariscotti 1, Virginie Deniau 2

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson

New Features of IEEE Std Digitizing Waveform Recorders

p. 1 p. 6 p. 22 p. 46 p. 58

About the High-Frequency Interferences produced in Systems including PWM and AC Motors

System Inputs, Physical Modeling, and Time & Frequency Domains

European Infrastructure Compatibility Standards. Maya Petkova 7 March 2014

Electromagnetic Compatibility of Train Detection Infrastructure with Rail Vehicles

POWER QUALITY AND SAFETY

Power Quality Survey in a Distribution System, Standard Procedures and Limitations. H. Mokhtari S. Hasani and M. Masoudi

Trackside Static Converter Fed by Overhead Line

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

Jitter Analysis Techniques Using an Agilent Infiniium Oscilloscope

UNIT-4 POWER QUALITY MONITORING

A Unity Power Factor Boost Rectifier with a Predictive Capacitor Model for High Bandwidth DC Bus Voltage Control

ATYPICAL high-power gate-turn-off (GTO) currentsource

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

Roadmap For Power Quality Standards Development

System Identification and CDMA Communication

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

BOOST PFC WITH 100 HZ SWITCHING FREQUENCY PROVIDING OUTPUT VOLTAGE STABILIZATION AND COMPLIANCE WITH EMC STANDARDS

ON THE BIAS OF TERMINAL BASED GAIN AND OFFSET ESTIMATION USING THE ADC HISTOGRAM TEST METHOD

Power Quality and Digital Protection Relays

Improving histogram test by assuring uniform phase distribution with setting based on a fast sine fit algorithm. Vilmos Pálfi, István Kollár

3D Distortion Measurement (DIS)

Power Quality Measurements the Importance of Traceable Calibration

About Measurement Uncertainty of Conducted Emissions Generated by a Variable Speed Drive

ELT Receiver Architectures and Signal Processing Fall Mandatory homework exercises

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

ERTMS/ETCS UNIT INTERFACES BETWEEN CONTROL-COMMAND AND SIGNALLING TRACKSIDE AND OTHER SUBSYSTEMS

PANTOGRAPH ARC TRANSIENTS OCCURRENCE AND GSM-R CHARACTERISTICS

Narrow- and wideband channels

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed

Harmonizing the ANSI-C12.1(2008) EMC Tests. Harmonizing the ANSI-C12.1(2008) EMC Tests

ERTMS/ETCS UNIT INTERFACES BETWEEN CONTROL-COMMAND AND SIGNALLING TRACKSIDE AND OTHER SUBSYSTEMS EUROPEAN RAILWAY AGENCY.

Harmonic Distortion Evaluations

Overvoltage Protection of Light Railway Transportation Systems

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

SITE-TO-SITE REPRODUCIBILITY IN CONDUCTED IMMUNITY TESTS ON PC-BASED DATA ACQUISITION SYSTEMS

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

(i) Understanding of the characteristics of linear-phase finite impulse response (FIR) filters

Statistical Pulse Measurements using USB Power Sensors

Technical Note 2. Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment

Reconfigurable Low-Power Continuous-Time Sigma-Delta Converter for Multi- Standard Applications

RECOMMENDATION ITU-R SM.1268*

OVERVIEW OF IEEE STD GUIDE FOR VOLTAGE SAG INDICES

(i) Understanding of the characteristics of linear-phase finite impulse response (FIR) filters

Power Quality Evaluation of Electrical Distribution Networks

Vibration Transducer Calibration System

Harmonic Requirements

CEPT/ERC Recommendation ERC E (Funchal 1998)

ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION

Comparison Between two Single-Switch Isolated Flyback and Forward High-Quality Rectifiers for Low Power Applications

VHF LAND MOBILE SERVICE

Frequency Domain Analysis of Capacitor Transient Overvoltages

ON THE VALIDITY OF THE NOISE MODEL OF QUANTIZATION FOR THE FREQUENCY-DOMAIN AMPLITUDE ESTIMATION OF LOW-LEVEL SINE WAVES

Resonances in Collection Grids of Offshore Wind Farms

EWGAE 2010 Vienna, 8th to 10th September

WIRELESS COMMUNICATION TECHNOLOGIES (16:332:546) LECTURE 5 SMALL SCALE FADING

Narrow- and wideband channels

Discrete Fourier Transform (DFT)

SINOLA: A New Analysis/Synthesis Method using Spectrum Peak Shape Distortion, Phase and Reassigned Spectrum

Time-Frequency Analysis Method in the Transient Power Quality Disturbance Analysis Application

Voltage-controlled active filter gives standby generator power quality

A POWER QUALITY INSTRUMENT FOR HARMONICS INTERHARMONICS AND AMPLITUDE DISTURBANCES MEASUREMENTS

Considerations about Radiated Emission Tests in Anechoic Chambers that do not fulfil the NSA Requirements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Emission on the low voltage grid: measurements in an urban area

22 kw 4Q POWER AMPLIFIER RS232

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

16B2011B1 EASY HARMONICS USER MANUAL

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

ENGINEERING FOR RURAL DEVELOPMENT Jelgava, EDUCATION METHODS OF ANALOGUE TO DIGITAL CONVERTERS TESTING AT FE CULS

Southern Company Power Quality Policy

Frequency Domain Representation of Signals

ESA400 Electrochemical Signal Analyzer

UNIVERSITY OF JORDAN Mechatronics Engineering Department Measurements & Control Lab Experiment no.1 DC Servo Motor

III CHAPTER. Analysis Methodology. regarding data sampling, benchmarking indices and overall program layouts.

Brief review of the concept and practice of third octave spectrum analysis

Final Exam Fall 2018

Measurement Time Optimization of Impedance Spectroscopy Techniques Applied to a Vibrating Wire Viscosity Sensor

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

CHAPTER 4 HARMONICS AND POWER FACTOR

1. Introduction to Power Quality

CHAPTER 4. PULSE MODULATION Part 2

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

Applications Avionics Testing Power Line Simulation Production Test - Power Supplies - UPS - Telecom. SMARTWAVE Programmable AC/DC Power Source

Advanced Test Equipment Rentals ATEC (2832)

Grid Converters for Photovoltaic

SHF Communication Technologies AG. Wilhelm-von-Siemens-Str. 23D Berlin Germany. Phone Fax

A SIMPLE METHOD TO COMPARE THE SENSITIVITY OF DIFFERENT AE SENSORS FOR TANK FLOOR TESTING

Laboratory Experiment #1 Introduction to Spectral Analysis

Transcription:

th IMEKO TC4 International Symposium and 18th International Workshop on ADC Modelling and Testing Research on Electric and Electronic Measurement for the Economic Upturn Benevento, Italy, September 15-17, 14 Recent results on the Power Quality of Italian 2x25 kv Hz railways Jacopo Bongiorno 1, Andrea Mariscotti 1 1 DITEN University of Genova, Via Opera Pia 11A, 16145 Genova Italy, jacopo.bongiorno@edu.unige.it, andrea.mariscotti@unige.it Abstract The recordings of the pantograph voltage and current waveforms across Italian and French high speed railway lines (both Autotransformer 2x25 kv Hz systems) are analyzed to estimate some Power Quality indexes: harmonic spectra, harmonic distortion, displacement factor and fundamental component, in various rolling stock operating conditions. These indexes, that define the electrical interface between the rolling stock and the power supply, are all relevant in order to assess both the impact of the rolling stock on the network and the suitability of the latter to ensure agreed performances (electrical interoperability). I. INTRODUCTION The service conditions and the performance of the rolling stock taking power over a portion of a railway network are subject to the electrical interaction of the traction supply line and the rolling stock, while it is moving with different operating profiles and loading conditions. Rolling stock units are both separate lumped electric loads and distributed interacting loads, electrically coupled by the traction line. The compliance assessment is based on the evaluation of various Power Quality (PQ) indexes derived from the pantograph voltage and current waveforms. Current distortion is local to a single load, while voltage distortion is the byproduct of the interaction with the traction line impedance. Details of the PQ indexes are reported in [1]: harmonic distortion and overvoltages are considered in this work with attention to train operating conditions, attempting at separating its own contribution from the underlying network distortion. Autotransformer Hz railway networks are the most modern solution for high performance electric transportation systems. Focusing on the interaction between the power supply and the rolling stock, the following European standards apply: the EN 163 [2] specifies the voltage characteristics of the supply voltages of traction systems in steady and transient conditions; the EN 388 [3] sets up the requirements for the acceptance of rolling stock on infrastructure and defines requirements of the power supply at the interface between traction unit and fixed installations. Rolling stock emissions depend highly on its operating conditions and the position along the line, that in turn influences the pantograph impedance curve. Emissions are studied by means of the Fourier transform over a suitable time window, a tradeoff between frequency and time resolution, in order to track characteristic and noncharacteristic components also during transient conditions. The Hamming window is also extensively applied to prevent adverse effects when analyzing transients and in general when the fundamental frequency undergoes unavoidable fluctuations [4][5]. Hamming window is an advisable choice for practical reasons: it is widely accepted and it is used by the national standards collected in [6]. In the following the PQ indexes that will be analyzed are summarized and for their definition reference is made to available publications [6][7]. Recordings were made during the first test campaign of the European Union funded project EUREMCO [8]. II. POWER QUALITY ANALYSIS The rms value of the pantograph voltage V p is related to the so-called useful voltage, U av,u, that is the power supply index that is evaluated to assess the adequacy of the infrastructure (power supply network) to the prescribed performance of the circulating rolling stock. For high speed interoperable lines the lower limit is 2 V (as it will be considered in the present case), while for conventional interoperable and classic lines the limit is lowered to 2 V [3]. The U av,u (train) index is thus evaluated as the mean value for one particular train at each time step where the train is absorbing traction power (ignoring steps when the trains is stationary, regenerating or coasting). The useful voltage is different from the minimum values specified in [2], where the lowest permanent voltage and the lowest non-permanent voltage values (19 and 1 V respectively) indicate extreme cases related to correct train operation and safety of on-board equipment. The useful voltage is analyzed selecting acceleration ISBN-14: 978-92-9973-2-7 953

phases that represent network loading as prescribed by the EN 163 standard [2]. The useful voltage is made corresponding to the rms value of the fundamental that results from the calculation of the Fourier transform of the pantograph voltage; the Fourier time window is varied between.1 and.2 s ensuring a satisfactory time and frequency resolution over the entire frequency interval, subdivided in the dc- Hz and 1-15 khz ranges. The results consist of rms values and spectra of the pantograph voltage and current including its dependence on the train speed and tractive effort. Statistical and graphical processing is used to better highlight and interpret signal characteristics [6]. III. RESULTS: FUNDAMENTAL COMPONENT VERSUS OPERATING CONDITIONS AND TIME The rms of the fundamental of the pantograph voltage V p is plotted in Fig. 1 for an entire train run to give a graphical representation of U av,u (train). The two sudden reductions occur during the acceleration phases of the full speed test run shown in detail in Fig. 2: a current absorption of 2A causes a voltage drop of about V. The train load effect can be evaluated for each operating condition for two successive speed profiles: stationary, acceleration, coasting, braking. These four phases are shown in different tones of grey in Fig. 2, ranging from light grey to black respectively. The minimum absorbed current is nearly A due to the on board auxiliaries. The maximum current is reached during acceleration phase at about 2 A. Color coding will be used throughout this and the successive sections when showing results that are related to the train operating conditions. 5 Voltage [kv] Speed profile [km/h] 26.1 1 2 1 2 1 2 Time [s] Fig. 2. Pantograph voltage and current during a typical test run consisting of two complete accelerationcruising/coasting-braking profiles. The train load effect is better interpreted if the fundamental of V p is plotted versus the fundamental of I p, as it is shown in Fig. 3. The V-I plot (also called Lissajous chart or curve) is often used to highlight correlation versus some operating condition or external variable: while standstill and coasting conditions have no clear correlation, V p and I p are inversely proportional in acceleration as expected. Voltage [kv] 26.5 5 5 5 Voltage Hz [kv] 5 5 26.15 1 2 Fig. 3. VI plot of the fundamental 26.15 1 2 Time [s] Fig. 1. Voltage at fundamental during a full speed run IV. RESULTS: VOLTAGE AND CURRENT HARMONIC SPECTRA A frequency spectrum extended up to 15 khz is shown in Fig. 4, which illustrates the combined result of the cumulated single-frequency spectra computed over about 5 s of the recordings in the AV Turin-Milan section. The cumulative distribution function is considered by displaying for each frequency bin the voltage levels where the probability of exceedance p is >95% (light 954

gray), %<p 95% (medium gray), %<p % (dark gray), %<p % (black), %<p % (dark gray), 5%<p % (medium gray), and p 5% (light gray). The asymmetrical disposition of regions near the boundaries is due to the log-scale visualization of the small amplitude values, to avoid cluttering with large light-gray regions. 3 corresponding multiple of the switching frequency of the single converter; normally this value is between and Hz and in the following section this will be demonstrated by analyzing the correlation of the various voltage and current components. A preliminary analysis is shown in Fig. 5, where three spectra are shown for three different values of absorbed current intensity, roughly made correspond to the train operating condition. 2 2-1 -2-3 2 Fig. 5. Pantograph voltage spectrum for the Italian network over [5-] Hz frequency range; the absorbed current conditions are low (thick light gray), medium (medium thickness gray), high (thin black) -1-2 9 Fig. 4. Statistical distribution of the pantograph voltage spectrum (see text above for definition of histogram bins) The fundamental at 25 kv has a negligible dispersion, as expected when the power supply system is correctly sized. Even harmonics are all very low and with a significant dispersion. Odd harmonics are related to the supply or to the train: the distinction of the contributions is a common exigency when post-processing and interpreting measurement data; V-I plots are again used in the following to this aim. Nearly all trains operating under 25 kv ac supply are nowadays equipped with four-quadrant input converters responsible for the odd harmonic pattern. These converters are usually operated interlaced in banks of two or four and the resulting harmonics are located around the V. RESULTS: CORRELATION OF VOLTAGE AND CURRENT COMPONENTS V-I plots are shown in the following figures for frequency components that will be shown to belong to the supply or to the train distortion pattern. The supply is responsible for the large part of the distortion in the low frequency portion, where the voltage and current amplitude are weakly correlated each other and to the train operating conditions. The following figures are divided into three groups: 1) low order harmonics usually assigned to the power supply, 2) locomotive harmonics resulting from the Pulse Width Modulation pattern of the on-board converters, located in the usual frequency range of Hz and 3) higher frequency components due to many different sources, but not in direct relationship with the tractive effort. The three gray shades regard the absorbed current intensity as before: low absorbed current conditions (light gray), medium (dark gray), high (black). Low order harmonics appear in Fig. 6 to Fig. 8. The plots centered on the supposed frequency interval of loco emissions show a clear correlation. It is interesting to observe also the increasing voltage/current ratio, that indicates an increase of the traction line impedance (see Fig. 9 to Fig. 12). 955

9 2 19 1 1 1 1.5 1 1.5 2 2.5 Fig. 6. V-I plot of pantograph quantities at 2 Hz 1.9 1 1.1 1.2 1.3 1.4 Fig. 9. V-I plot of pantograph quantities at Hz 75 65 1 1 1 55 45 35 9.2.4.6.8 1 Fig. 7. V-I plot of pantograph quantities at 3 Hz.1.2.3.4.5.6 Fig.. V-I plot of pantograph quantities at 21 Hz 55 45 35 25 15.1.2.3.4.5.6.7 Fig. 8. V-I plot of pantograph quantities at 5 Hz 1 1 1.1.2.3.4.5 Fig. 11. V-I plot of pantograph quantities at 22 Hz 956

1 1 1 9.35.4.45.5.55.6.65.7 Fig. 12. V-I plot of pantograph quantities at 25 Hz Going to higher frequency, beyond the supposed interval of locomotive characteristic emissions, the V and I components are again uncorrelated, as it is shown for 29 and Hz in Fig. 13 and Fig. 14, respectively. The V/I ratio decreases, since the traction line impedance is approaching an anti-resonance point. 24 22 18 16 14 12 8 6 4.35.4.45.5.55.6.65 Fig. 13. V-I plot of pantograph quantities at 29 Hz 11 9 8 7 6 5 4 3 2 1.2.25.3.35.4.45.5 Fig. 14. V-I plot of pantograph quantities at Hz VI. CONCLUSIONS The reported results regard the measured pantograph voltage and current during test runs on the Italian High Speed line between Milan and Turin, fed at 25 kv Hz. The first more direct use is the quantification of the individual and total harmonic distortion of the line voltage as perceived by the test locomotive, as well as the line reaction to the load step changes. Results may be expressed as worst-case maximum values or as a statistical distribution, e.g. by showing a coarse histogram of the relative frequency for each component of the frequency spectrum of pantograph voltage and current. Then, regarding the identification of the single components appearing in the spectrum as originated by the locomotive or due to the underlying traction line distortion, the use of correlation between voltage and current quantities and versus train operating conditions is shown. The results confirm that low order harmonics are uncorrelated from the train operating conditions and evidence of correlation is found in the frequency interval where locomotive emissions are very likely, if the existing technology and design choices for four-quadrant converters are considered. As a confirmation, going beyond the first group of harmonics of the on-board converter the correlation is again lost. REFERENCES [1] A. Mariscotti, Results on the Power Quality of French and Italian 2x25 kv Hz railways, I2MTC 12, Graz, Austria, May 13-16, 12. [2] CENELEC EN 163 Std., Railway applications Supply voltages of traction systems, Nov. 4. [3] CENELEC EN 388, Railway applications Power supply and rolling stock Technical criteria for the coordination between power supply (substation) and rolling stock to achieve interoperability, Aug. 5. [4] A. Mariscotti and D. Slepicka, Analysis of frequency stability of 16.7 Hz railways, I2MTC 11, Hangzhou, China, May -12, 11. [5] A. Mariscotti and D. Slepicka, The Frequency Stability of the Hz French Railway, I2MTC 12, Graz, Austria, May -12, 12. [6] A. Mariscotti, Direct Measurement of Power Quality over Railway Networks with Results of a 16.7 Hz Network, IEEE Transactions on Instrumentation and Measurement, vol. n. 5, May 11, pp. 14-1612. [7] A. Mariscotti, Measuring and Analyzing Power Quality in Electric Traction Systems, International Journal of Measurement Technologies and Instrumentation Engineering, vol. 2 n. 4, Oct.-Dec. 12, pp. 21-42. [8] European Project EUREMCO web page, [online] www.euremco.eu 957