Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Similar documents
Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

GIS Disconnector Switching Operation VFTO Study

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY. Approach for Fault Detection in GIS.

Tab 2 Voltage Stresses Switching Transients

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Generation of Sub-nanosecond Pulses

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

ANALYSIS OF VERY FAST TRANSIENT OVER VOLTAGES IN GAS INSULATED SUBSTATION

Lightning transient analysis in wind turbine blades

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Ferroresonance Experience in UK: Simulations and Measurements

Electric Stresses on Surge Arrester Insulation under Standard and

High voltage engineering

Abstract. 1 Introduction

Analysis of Very Fast Transient over Voltages of Transformer in Gas Insulated Substation (GIS) using Wavelet Technique

Simulation Study of Voltage Surge Distribution in a Transformer Winding

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

MAHALAKSHMI ENGINEERING COLLEGE

Sources of transient electromagnetic disturbance in medium voltage switchgear

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

EE 740 Transmission Lines

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Effect of Shielded Distribution Cable on Very Fast Transients

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Design and Simulation of 15 KV, 15 Stage Solid State Bipolar Marx Generator

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Investigation on the Performance of Different Lightning Protection System Designs

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

EE 1402 HIGH VOLTAGE ENGINEERING

EE 741. Primary & Secondary Distribution Systems

Analysis of lightning performance of 132KV transmission line by application of surge arresters

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Chapter 1. Overvoltage Surges and their Effects

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

ABSTRACT 1 INTRODUCTION

TECHNICAL REPORT. Insulation co-ordination

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

ANALYSIS OF A PULSED CORONA CIRCUIT

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Insulation Co-ordination For HVDC Station

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Alternating Current Page 1 30

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

Grounding System Theory and Practice

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Simulation Model of Partial Discharge in Power Equipment

Design and Construction of a150kv/300a/1µs Blumlein Pulser

Influence of Field Spacer Geometry on the Performance of a High Voltage Coaxial Type Transmission Line with Solid Dielectric Spacer in Vacuum

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

KEYWORDS: Impulse generator, Pspice software, spark gap, Power transformer, Hardware.

Over-voltage Trigger Device for Marx Generators

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

High Voltage Engineering

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

EE 340 Transmission Lines. Spring 2012

total j = BA, [1] = j [2] total

International Journal of Advance Research in Engineering, Science & Technology

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

DEPARTMENT OF EEE QUESTION BANK

In power system, transients have bad impact on its

ABSTRACTS of SESSION 6

Safety through proper system Grounding and Ground Fault Protection

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

Lightning performance of a HV/MV substation

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker

EE 340 Transmission Lines

Measurement of Surge Propagation in Induction Machines

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Transcription:

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com Joginpally B.R. Engineering College, Hyderabad 2 subramanyamps@gmail.com VBIT, Ghatkesar, Hyderabad Abstract: --This paper describes the VFTO are usually Transient vervoltages in a gas insulated substation. A few Gas Insulated Substation (GIS) units have been in and large number of units are under various stages of installation. These problems include, generation of the overvoltage during Dis-connector s, line to enclosure faults. The fast transient overvoltages obtained are due to switching s and with fixed arc resistance and variable arc resistance for different lengths of GIS. The Transients are calculated along with load and it was observed that the transients obtained in 5mts length GIS will affect the system more than that obtained in 10mts length GIS and control of secondary equipment in a Single-phase 220kv GIS. The variable arc resistance is calculated by Toepler s formulae. The equivalent circuits are developed for the components of GIS and voltages are calculated by using the Matlab 7.8 software. Keywords Gas Insulated Substation (GIS), Transient over voltages, Switching s, single-phase faults, MATLAB 7.8 software and Control circuitry I. INTRODUCTION Transient over voltages calculated on the basis of fixed arc resistance have presented. It is however, known that the resistance of the spark channels varies with current. At the instant of initiation of arc the resistance is very high[1][2]. As the current in the arc increases the value of resistance starts decreasing until it saturates at very low value. In general, the arc resistance appears to be inversely proportional to some function of current [3]. Several authors a have given arc resistance equations which can be divided into two groups as given below. 1. Inverse integral equation reported by Toepler et.al.[4] 2. Inverse exponential equation reported by Demenik et.al.[4] These equations were numerically evaluated for a given arc current and then normalized with the experimental arc resistance at = 0.5µs (approximate time of maximum current) of all these equations, one equation has been used for the analysis. Based on earlier studies in SF6 gas, Toepler s Sparks Law is valid for calculation of variable arc resistance. The variable arc resistance due to Toepler s formulae [ 4] is calculated as given below. Where KT = Toepler s Constant = 0.005 volt.sec /mt for SF6 under uniform Field conditions L = Spark Length in meters qo = Initial Charge t = Spark Collapse Time in sec The value of time varying spark resistance R( t) is calculated until it reaches a value of 1 to 3 ohm initial charge qo is an important parameter while considering the non-uniform fields. But the field between the dis-connector contacts is almost uniform. Therefore, initial charge qo is very small and can be neglected [5]. When a circuit breaker operates conducting spark channel is established with time lag of few nanoseconds after the breakdown channels is connected the electrodes [6][7]. During this time only the spark resistance changes from very large value to very small value, For homogeneous fields, this time is given by tz = 13.3 * KT Eo Where Eo = Breakdown field strength = 8.6 * 10 6 volt/mt for SF6 KT = Toepler s constant = 0.005 volt sec/mt II. MODELLING OF 220KV GIS SYSTEM For accurate analysis of transients, it is essential to find the VFTO s and circuit parameters. Due to the travelling nature of the transients the modelling of GIS makes use of 28

electrical equivalent circuits composed by lumped elements and especially by distributed parameter lines, surge impedances and travelling times. The simulation depends on the quality of the model of each individual GIS component. In order to achieve reasonable results in GIS structures highly accurate models for each internal equipment and also for components connected to the GIS are necessary. The dis-connector spark itself has to be taken into account by transient resistance according to the Toepler s equation and subsequent arc resistance of a few ohms. The wave shape of the over voltage surge due to dis-connector switch is affected by all GIS elements. Accordingly, the simulation of transients in GIS assumes an establishment of the models for the Bus, Bushing, Elbow, Transformers, Surge Arresters, Breakers, Spacers, dis-connectors, and Enclosures and so on. During the current of dis-connector switch in a GIS, re-strikes(pre-strikes) occur because of low speed of the dis-connector switch moving contact, hence Very fast Transient Over voltage are developed. These VFTO s are caused by switching s and single-phase fault When there is a fault occurs, there is a short circuit in the system. Transients are also produced due to the faults in the system. Due to this VFTO s are caused by switching can also lead to secondary breakdown with in GIS. Re-striking surges generated by the dis-connector switches at GIS generally possess extremely high frequencies ranging from several hundred KHz to several MHz. For the development of equivalent circuit low voltage step response measurements of the main GIS components have been made. Using MATLAB of the equivalent models is developed A. Capacitance calculation Calculation of Capacitance is done by using the standard formulae given below. C = 2πε 0ε r l 2.3 ln ( b a ) (1) Where, ε 0 = 8.854 10 12, ε r = 1& ε r = 4( for spacers)as they are filled with Alumina filled. Epoxy material: l = length of the section b = Outer cylinder radius a = Inner cylinder radius B. Calculation of Capacitance due to Spacers The spacer existed with finite thickness and develops some amount of capacitance in addition with existed capacitance. Spacers are used for supporting the inner conductor with reference to the outer enclosure. They are made with Alumina filled epoxy material whose relative permittivity (εr) is 4. The thickness of the spacer is assumed to be the length of the capacitance for calculation. C. Inductance calculation The inductance of the bus duct can be calculated by using the formula [8] given below, where r1, r2, r3, r4, are the radii of the conductors in the order of decreasing magnitude and l is the length of the section. L = 0.001 l ln r1 r3 2 r2 + ln r2 2 21 1 r2 r1 r1 r4 + ln + r3 2 ln r1 r2 1 (2) For estimating these voltages, the equivalent impedance networks for the components like capacitance, and the inductance of the ground wire, grounding grid, spark channel, the resistance of the grounding grid of the spark channel and switch (which follows Toepler s spark law) are required The variable arc resistance is calculated by using the Toepler s formula. The inductance of the bus bar is found out from the diameters of conductors and enclosure. The bus capacitance is calculated using formula for concentric cylinders. The entire bus length is modelled as distributed pinetwork To simulate the Very Fast Transient over Voltages in GIS, MATLAB is used. The equivalent circuit of GIS is shown in fig2. Where, Z1 = Surge Impedance of Gas Insulated Bas duct W.r.to Enclosure Interior surface Z2 = Surge Impedance of Overhead Transmission Line w.r.to Earth Surface Z3 = Surge Impedance of Enclosure Exterior Surface with respect to Earth Surface Cb = Capacitance of the Bushing C = Capacitance of the Current Transformer 29

Fig1Modeling diagram of 220kv GIS System Fig.2 Equivalent circuit of GIS Fig 3 MATLAB Circuit for 5 mts. length in a single -phase 220kv GIS with Variable arc resistance Fig4 MATLAB Circuit for 10 mts. length in a single -phase 220kv GIS with Variable arc resistance 30

TABLE II The modelling diagram of 220kv GIS system as in the fig,1 and the following arrangement is assumed for the developing the model and they are phenomena and gas insulated substation concepts can analysis by fig.3 & Fig4 apparatus as disconnected with an earthing switch, three disc type Spencer s, a load bus bar above to 5mts & 10mts long width three post type spacers and a 220kv gas bushing containing stress capacitor. The 1GHZ surge sensor method in the diagram is located at the distance of 1.6mts from disconnector further, holding the load side bus bar at zero potential, dc voltage was applied from the high voltage dc power supply to the bushing via a 1Mohm resistor and VFTO wave of the closing s was observed. III. SINGLE-PHASE EQUIVALENT CIRCUITS FOR 132KV GIS SYSTEM FOR 5MTS & 10MTS LENGTH The transient due to switching s for 5mts and 10mts length GIS with variable arc resistance, without load are presented and analysis. Due to trapped charge some voltage remains on the floating section which can create severe conditions because the first re-strike can occur at the peak of power frequency voltage giving a voltage of 2.0 p.u. On re-strike the voltage on each side will collapse initially zero and hence creating two 1.0pu voltage steps of opposite polarities. In this, it is assumed that re-striking is created at 1.0 p.u. respectively on either side of dis-connector switch (DS). The transients due to closing of the circuit breaker are calculated and maximum voltage obtained with a rise time. Transients are calculated along with load and it was observed that the transients obtained in 5mts length GIS will affect the system more than that obtained in 10mts length GIS..For different values of voltages on the load side the magnitudes and rise times of 5mts length GIS are Table I. Similarly For different values of voltages on the load side the magnitudes and rise times of 10mts length GIS are Table II. TABLE I TRANSIENTS DUE TO SWITCHING OPERATION FOR 5MTS LENGTH GIS WITH VARIABLE ARC RESISTANCE TRANSIENTS DUE TO SWITCHING OPERATION FOR 10MTS LENGTH GIS WITH VARIABLE ARC RESISTANCE Mode of During closing During opening During second restrike Magnitude of voltage(p.u) Rise time (Nano sec) 2.38 77 1.06 71 1.82 50 IV. RESULTS AND DISCUSSION The transients due to switching s and line to enclosure faults with fixed arc resistance for different length of GIS are found. Transients are calculated along with load and it was observed that the transients obtained in 5mts length GIS will affect the system more than that obtained in 10mts length GIS. As the distance between the fault point and load increase during fault analysis the magnitudes and rise times of the transients also increases.. To understand the effect of switching configuration on peak magnitude vs transient currents at different positions, fast transient currents have been estimated for the second switching configuration as shown in below figs. The maximum values of VFTO, the MATLAB7.8 software is used and a simulation is carried out by designing suitable equipment circuits and its models are developed. The main advantages of such models are used to enable the transient analysis in GIS. Using the equivalent circuit of 5mts length GIS given in Fig 3, transients due to closing of the circuit breaker are calculated as given in fig 5. From this graph, the maximum voltage obtained is 3.36 p.u with a rise time of 46ns. The difference between maximum value for Fixed and Variable Arc Resistance is found to be significant. Mode of During closing During opening During second restrike Magnitude of voltage(p.u) Rise time (Nano sec) 3.36 46 1.38 31 2.54 14 Fig. 5 Transient voltage waveform during closing of CB for 5mts GIS, with variable Arc Resistance phase 31

By using the above circuit, transients due to opening of the circuit breaker are calculated as given in fig 6. From this graph, the maximum voltage obtained is 1.38 p.u with a rise time of 31ns. The difference between maximum value for Fixed and Variable Arc Resistance is found to be significant. Fig. 8 Transient voltage waveform during closing of CB for10mts GIS, with variable Arc Resistance -phase By using the above circuit, transients due to opening of the circuit breaker are calculated as given in fig 9. From this graph, the maximum voltage obtained is 1.06 p.u with a rise time of 71ns. The difference between maximum value for Fixed and Variable Arc Resistance is found to be significant. Fig. 6 Transient voltage waveform during Opening of CB for 5mts GIS, with variable Arc Resistance Assuming that there is a second re-strike, another switch is connected in parallel to the circuit breaker for simulation in MATLAB 7.8. Transients are calculated by closing this switch when voltage difference across the contacts of the circuit breaker reaches maximum value. Transients calculated due to second re-strike gives the peak voltage of 2.54 p.u at arise time of 14ns as shown in Fig 7. The magnitudes and rise times of 5mts length GIS are Table I Fig. 9 Transient voltage waveform during Opening of CB for 10mts GIS, with variable Arc Resistance Assuming that there is a second re-strike, another switch is connected in parallel to the circuit breaker for simulation in MATLAB 7.8. Transients are calculated by closing this switch when voltage difference across the contacts of the circuit breaker reaches maximum value. Transients calculated due to second re-strike gives the peak voltage of 1.82 p.u at arise time of 50ns as shown in Fig 10. The magnitudes and rise times of 5mts length GIS are Table II. Fig. 7 transient voltage waveform during Second Re-strike for 5mts GIS, with Variable Arc Resistance. Using the equivalent circuit of 10mts length GIS given in Fig 4, transients due to closing of the circuit breaker are calculated as given in fig 8. From this graph, the maximum voltage obtained is 2.38 p.u with a rise time of 77ns. The difference between maximum value for Fixed and Variable Arc Resistance is found to be significant. Fig. 10 transient voltage waveform during Second Re-strike for 10mts GIS, with Variable Arc Resistance 32

V. CONCLUSION The variable arc resistance is calculated by Toepler s formulae. Transients are calculated due to switching s and faults with variable Arc resistance along with load. For any length of GIS it was found that transients due to variable arc resistance give lower value of peak voltages than that obtained with fixed arc resistance. When load is connected at the open end of GIS, the peak voltages that are obtained due to faults do not follow a definite pattern The peak magnitude of fast transient currents generated during switching event changes from one position to another in a 220kv GIS for a particular switching... The fast transient overvoltages obtained are due to switching s and with fixed resistance and variable arc resistance for different lengths of GIS. VI. REFERENCES [1] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Estimation Transient over voltages in gas insulated bus duct from 220kv gas insulated substation, International journal of Computer applications, (0975-8887) volume 20-no.8 April 2011. [2] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Analysis and Calculation of very fast transient over voltages in 220kv gas insulated Substation international Journal of Engineering &techsciencevol 2(4) 2011 [3] Li Liu-ling, Hu Pan-feng, Qiu Yu-chang, Analysis of Very Fast Transient Overvoltage Calculation Affected by Different Transformer Winding Models, Journal of Xi an Jiaotong University, 2005(10) Vol.39 No.10:1160-1164. [4] T.G Ebngel, Anthity L. Donaldson and Mange Kristiansen, the pulsed Discharge Arc Resistance and its Functional Behaviour IEEE Trans. on Plasma Science, Vol.17, No.2, April 1989, pp 323-329 [5] Boggs SA., Chu F.Y. and Pujimotor N. (IYXZ), 'Disconnect Switch Induced Transients and Trapped Charge in GIs', EEE Trans. PAS, Vol. PAS-101, No.IO, pp3593-3601. [6] MohanaRao M., Naidu M.S. (199% 'Estimation of Fast Transient Overvoltages in the case of Disconnnector in a GIS', 3d workshop & conference on EHV Technology, IISC Bangalore. [7] J.B. Kim,M.S. Kim,K.S.Park, W.P.Son.,.D.S. Kim, G.S. Kil. Development of monitoring and diagnostic system for SF6 gas insulated switchgear.ieee Conference Record of the 2002 IEEE International Symposium on Electrical Insulation. Boston, Massachusetts, United States, pp.453-456, 2002. 33