Motor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls

Similar documents
Bearing Currents. Introduction. What are Bearing Currents? Application Note AP040061E Effective January 2014

Mitigation Techniques of shaft voltage and bearing current in Inverter Driven Three Phase Induction Motor

Application Note. Motor Bearing Current Phenomenon. Rev: Doc#: AN.AFD.17 Yaskawa Electric America, Inc August 7, /9

Variable Frequency Drives Motor Bearing Failure Mitigation

Product Application Note

A PRACTICAL GUIDE TO UNDERSTANDING BEARING DAMAGE RELATED TO PWM DRIVES

INDUSTRY WHITE PAPER. Inverter-Driven Induction Motors Shaft and Bearing Current Solutions

CoolBLUE Inductive Absorbers NaLA Noise Line Absorbers

Application of Electrical Signature Analysis. Howard W Penrose, Ph.D., CMRP President, SUCCESS by DESIGN

ABB drives. Technical guide No. 5 Bearing currents in modern AC drive systems

A Novel Approach to Electrical Signature Analysis

SYNCHRONOUS MACHINES

Technical Guide No. 5. Bearing Currents in Modern AC Drive Systems

Technical White Paper

External Drive Hardware

Bearing Damage Analysis by Calculation of Capacitive Coupling between Inner and Outer Races of a Ball Bearing

VARIABLE SPEED DRIVES AND MOTORS

Placement Paper For Electrical

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Fluke MDA-510 and MDA-550 Motor Drive Analyzer

Bearing Fault Diagnosis

Industrial Electrician Level 3

Machinery Fault Diagnosis

ELECTRIC TOOL CORPORATION

Pulse Width Modulated Motor Drive Fault Detection Using Electrical Signature Analysis

Bearing Currents and Shaft Voltages of an Induction Motor Under Hard and Soft Switching Inverter Excitation

MA3. Miniature Absolute Magnetic Shaft Encoder Page 1 of 8. Description. Order Using #MA3 starting at $36.00 per unit. Features

WSG 8-115; 8-125; P; WSG ; WSG P; WSG PS; WSG P; WSG 15-70Inox

ECET Industrial Motor Control. Variable Frequency Drives. Electronic Motor Drives

Lightning Protection. Wisconsin Broadcasters Association Broadcasters Clinic. 14 th October 2009 Jeff Welton Regional Sales Manager, Central U.S.

MA3. Miniature Absolute Magnetic Shaft Encoder Page 1 of 8. Description. Mechanical Drawing. Features

Bearing fault detection of wind turbine using vibration and SPM

L E C T U R E R, E L E C T R I C A L A N D M I C R O E L E C T R O N I C E N G I N E E R I N G

Courseware Sample F0

REPAIR INSTRUCTIONS. Cat. No Cat. No MILWAUKEE ELECTRIC TOOL CORPORATION. SDS Max Demolition Hammer. SDS Max Rotary Hammer

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

EE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

Application Note. Applicable Product: AC Drives

6. du/dt-effects in inverter-fed machines

COOLTUBE Radiated Emissions Absorber

IT HAS LONG been recognized that bearing damage can be

The Multi-Technology Approach to Motor Diagnostics

What you discover today determines what you do tomorrow! Thomas Brown P.E. Published in Reliability Magazine Vol. 10 Issue 1, May 2003

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

MTE training MTE Corporation

Bico, Inc Valhalla Drive, Burbank, CA Tel. (818) Fax (818) BICO UD DIRECT DRIVEN PULVERIZER

Three-Phase Induction Motors. By Sintayehu Challa ECEg332:-Electrical Machine I

Experiment 2 IM drive with slip power recovery

Operating Instructions

Massachusetts Amusement Device Safety Seminar 2015

CHAPTER-6 MEASUREMENT OF SHAFT VOLTAGE AND BEARING CURRENT IN 2, 3 AND 5-LEVEL INVERTER FED INDUCTION MOTOR DRIVE

Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis

Application Note. GE Grid Solutions. Multilin 8 Series Applying Electrical Signature Analysis in 869 for Motor M&D. Overview.

Effects of Harmonic Distortion I

Vibration and Current Monitoring for Fault s Diagnosis of Induction Motors

9 questions to ask when specifying a slewing ring bearing

Motors: The Past. is Present. Hunting in the Haystack. Alignment: Fountain of Youth for Bearings. feb Windows to the IR World

Page ENSC387 - Introduction to Electro-Mechanical Sensors and Actuators: Simon Fraser University Engineering Science

Tapping Screw (W/Flange) 46 Cord Armor 47 Tube (D) 48 Cord. 45 Cord Clip. Tapping Screw (W/Flange) 10 Gear Cover Ass'y. 12 Socket (B) Ass'y

Electronic Speed Controls and RC Motors

MEASUREMENT AND QUANTITATIVE EVALUATION OF INVERTER-INDUCED BEARING CURRENTS

High Frequency/Precision Drives by Design

Suggesting a DC-DC Buck Converter for Compensating Shaft Induced Voltage and Bearing Current

SIGNATURE ANALYSIS FOR ON-LINE MOTOR DIAGNOSTICS

Introduction : Design detailed: DC Machines Calculation of Armature main Dimensions and flux for pole. Design of Armature Winding & Core.

The Generators and Electric Motor Monitoring and Diagnostics Systems

Options & Accessories

APPLICATION NOTE. Detecting Faulty Rolling Element Bearings. Faulty rolling-element bearings can be detected before breakdown.

Bahram Amin. Induction Motors. Analysis and Torque Control. With 41 Figures and 50 diagrams (simulation plots) Springer

Generator Advanced Concepts

PET*STAR 4 OPERATOR MANUAL

Motor makers gear up to provide the best servomotor for your application

VFD Level II: Application Considerations. Jason Fahey, Vice President John Fahey, President

Production power on a budget: How to generate clean reliable power, Part 2 By Guy Holt

ECET 211 Electrical Machines and Controls

Study on monitoring technology of aircraft engine based on vibration and oil

CEU Certification Test Drive Road Show: TRM040-DrivesRoadShow-CEU

TABLE OF CONTENTS SERIES SPINDLES Cartridge Block Belt-Driven Motorized GILMAN SPINDLE SYSTEMS... 4 PRODUCT FEATURES...

Job Sheet 2 Servo Control

Options & Accessories

PMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter

MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

MAHALAKSHMI ENGINEERING COLLEGE

R30D RVDTs DC-Operated Rotary Variable Differential Transformers

Frequently Asked Questions (FAQs) MV1000 Drive

VSD cables in. Working with. industrial & automation applications

An Introduction to Time Waveform Analysis

Metal Detector. Student Lab Guide. Engineering Teaching Laboratory. Lab Partner(s)

Geology, Prospectors, Mining, Metallurgy, Assaying, Environmental, Geotechnical

UNIT-III STATOR SIDE CONTROLLED INDUCTION MOTOR DRIVE

HARMONICS CAUSES AND EFFECTS

Best Practice Reducing The Risk of Arc Flash Cross Over

The Fundamental Characteristics of Novel Switched Reluctance Motor with Segment Core Embedded in Aluminum Rotor Block

Series Inline Oscillating Saw

Technical Explanation for Cam Positioners

Measuring Reflected Voltage Spikes in VFD Motor Applications

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

Stepper Motors WE CREATE MOTION

400 SERIES GRINDER PUMPS 41502, 42202,43302, AND MODELS

Transcription:

Motor Bearing Damage and Variable Frequency Drives: - Diagnosing the Causes, - Implementing a Cure, and - Avoiding the Pitfalls Tim Albers, Director of Product Mgt, NIDEC Motor Corporation Tim Jasina, Sr. Application Engineer / Engr. Team Leader Ken Fonstad, HVAC Sales / Application Support Principal Engineer tim.albers@nidec-motor.com jasinat@nsk-corp.com ken.a.fonstad@us.abb.com

Anatomy of an AC induction motor AC current in the stator windings produces a rotating magnetic field. This generates a current in the rotor bars, which makes its own magnetic field. 2 The interaction of the two magnetic fields produces the motor s torque.

Voltage Operation of an AC induction motor AC Line-to-Line Voltage L1-L2 L1-L3 L2-L3 The frequency of the AC in the stator controls the speed of the motor. 3

How does a variable frequency drive (VFD) work? VFD 4

How does a variable frequency drive (VFD) work? VFD Rectifier DC Bus Inverter 5

Voltage How is a VFD different from the AC power line? Fast-rising pulses AC Line-to-Ground Voltage PWM Voltage Pulses L1 L2 L3 The voltage of the AC power line changes gradually from minimum to maximum in about 8 ms 6 The voltage from the PWM VFD can change from minimum to maximum in less than 1 µs (0.001 ms)

How is a VFD different from the AC power line? Fast-rising pulses Air gap 7 Fast-rising voltage pulses can readily induce voltage across the air gap between the motor s stator and its rotor This can drive stray currents in the motor

Cause of current through a motor s bearings Circulating currents 8 Asymmetries in the motor can result in a circulating current between the motor s frame and the motor s shaft This seldom happens in motors < 50 HP; more common in 480 V and higher voltage AC motors

Voltage What causes bearing currents in smaller motors? Common mode voltage AC Line-to-Ground Voltage L1 L2 L3 When powered from a balanced center-grounded wye transformer, the net voltage with respect to ground is always 0 V (no common mode voltage) Common mode voltage can induce voltage on the motor s shaft 9

What causes bearing currents in smaller motors? Common mode voltage + When powered from a VFD, only two voltages (+ & -) make the three-phase voltage to the motor The 3-phase voltage applied to the motor isn't balanced with respect to ground 10

What causes bearing currents in smaller motors? Common mode voltage + If the stator has a net positive voltage, it will induce a positive voltage onto the shaft If the voltage on the shaft is high enough, current will arc through the grease in the bearings + 11

How can you detect the onset of bearing damage? Noise from the bearings That s a bit late Motor vibration That s a bit late and difficult Measure the current That s hard to do Measure the shaft voltage There s an idea 12

How can you detect the onset of bearing damage? Measuring shaft voltage Use a brush to contact the motor s shaft Home-made: fine steel wool brush Commercial: carbon fiber brush 13

How can you detect the onset of bearing damage? Measuring shaft voltage Use a magnetic stand to hold the brush in place 14

How can you detect the onset of bearing damage? Measuring shaft voltage Use a digital storage oscilloscope to capture the motor shaft voltage Use the trigger function to capture the highest shaft voltages Save the waveforms in computer files 15

How can you detect the onset of bearing damage? Interpreting the voltage waveforms 28.8 V peak 1 µs/div The shaft voltage smoothly increases and then quickly drops due to a discharge 16

How can you detect the onset of bearing damage? Interpreting the voltage waveforms 12.8 V peak 500 ns/div The shaft voltage oscillates, but no sharp drop is detected No shaft current was present 17

How can you detect the onset of bearing damage? Remotely detecting bearing discharges When a discharge occurs, it generates a pulse of electromagnetic noise, like radio static A hand-held radio frequency detector can detect the static and count the discharges 18

How can you detect the onset of bearing damage? Non-contact detection of bearing discharges Advantages Little set-up is required Counts the discharges over time Concerns Proper positioning of the meter is required for accurate readings Practice and experience are required 19

Identifying the cause of bearing damage Not all bearing damage is caused by bearing current There are also mechanical causes for bearing damage Before implementing a solution, it is important to understand the cause of the problem Study the damage to the bearings Ideally, the grease in the bearing should not be cleaned away before the bearing is submitted for evaluation 20

Identifying the cause of bearing damage Images of damaged bearings 21 Classic bearing fluting, likely caused by shaft voltage discharges

Identifying the cause of bearing damage Bearing electrical arc damage process 22 Damage occurs when current passes through bearing Oil film between balls and raceways acts as an insulator Film is only microns thick at most Shaft voltage can exceed dielectric strength (when insulating property fails) of film Arcing occurs melting a minute area of surfaces Melted metal enters grease or is rolled over onto raceways Initially forms a dull grey frosted or matte appearance Fluting can develop with continued arcing 0.003mm

Identifying the cause of bearing damage Initial electrical arc damage A frosted ball path appears Potentially electrical arc damage Potentially lubrication contamination Extreme magnification required to verify Scanning electron microscope Confocal microscope 0.007mm 23

Identifying the cause of bearing damage Advanced electrical arc damage Fluting Overlapping arcs Fluting s repetitive appearance related to dynamic system of arcing and rolling motion 24

Identifying the cause of bearing damage Images of damaged bearings Electrical arc damage similar to electric discharge machining (EDM) process Bearing surface material removed 0.0012mm 25

Identifying the cause of bearing damage Images of damaged bearings Likely caused by shaft voltage discharges, made worse by a large radial load With light radial loading, the insulating grease layer is uniform and thick A large radial load reduces the thickness of lubricant in the load zone 26

27 Identifying the cause of bearing damage Possible solutions for this problem Belt drive application: Reduce the belt tension Use larger diameter sheaves on the motor and the load When the load is shaft-mounted: Mount the load as close to the motor as possible Reduce the weight of the load Use external bearing(s) to support the load Increase the minimum speed

Identifying the cause of bearing damage Bearing Insulation Breakdown Voltage Why increase the minimum speed? Test on three motors with radial loads 50 V 40 V Effect of Motor Speed on Breakown Voltage 30 V 20 V 10 V Motor 1 Motor 2 Motor 3 0 V 33% 50% 67% 83% 100% Motor Speed 28

Identifying the cause of bearing damage Not all bearing damage is caused by bearing current The motor made a clicking noise when it was rotated slowly A fluting pattern is too dense to make such a sound The shaft voltage 2.84 V and hand-held detector showed no discharges 5 µs/div 29

Identifying the cause of bearing damage Study of the bearings The races of the bearing showed regularly spaced marks The spacing of the marks was the same as the spacing of the balls in the cage of the bearing 30

Identifying the cause of bearing damage Diagnosis: False Brinelling The motor was driving a shaftmounted fan wheel It appears that the problem was caused by vibration during shipping 31

Identifying the cause of bearing damage Other mechanical damage: Brinelling Brinelling is generally caused by a sharp impact on the bearing This causes an indent in the bearing s race It often indicates damage during the assembly of the equipment 32

33 Identifying the cause of bearing damage Summary Not all bearing damage is the result of electrical discharges through the bearings Mechanical damage Lubrication problems Too little Too much Contamination Overloading It is important to know the problem before developing a solution

Avoiding bearing discharge currents A variety of solutions are available 1. Proper wiring 2. VFD adjustments 3. System maintenance 4. High frequency toroids 5. Blocking the discharge 6. Re-routing the discharge 34

Avoiding bearing discharge currents 1. Proper wiring 35 The VFD sends pulses with high frequency content to the motor It is important to provide a low impedance return path for the high frequencies to protect the motor bearings the building from radio frequency noise

Avoiding bearing discharge currents 1. Wiring: only a safety ground 36 100% The VFD sends pulses with high frequency content to the motor Radio frequency noise in the facility It is important to provide a low impedance return path for the high frequencies to protect the motor bearings the building from radio frequency noise

Avoiding bearing discharge currents 1. Wiring: only a safety ground 100% Lab test 60 ft cable 24 V Discharge! 37

Avoiding bearing discharge currents 1. Wiring: traditional ground, motor to VFD Normally sized ground wire No conductive conduit 30% 70% 38

Avoiding bearing discharge currents 1. Wiring: large ground and conductive sheath 39 90 95*% 5* - 10% 1-3 large ground wires with large strand count Ground wires are close to the motor wires; this reduces magnetic fields to minimize impedance Grounded, conductive shield around all of the wires * With VFD s RFI/EMC filter engaged

Avoiding bearing discharge currents 1. Wiring: large ground and conductive sheath 90 95*% 5* - 10% Lab test 60 ft cable 0.92 V No discharge 40

Avoiding bearing discharge currents 1. Proper wiring Advantages No maintenance required Can have a major impact Concerns Requires attention to details VFD cable can be expensive, but it is not absolutely necessary; carefully installed conduit can be used 41

42 Reducing bearing discharge currents 2. VFD adjustments Enter the motor nameplate data Activate energy optimization in the VFD Both minimize the motor current Reduce the switching frequency Cutting the pulse rate reduces the number of possible discharges Increase the minimum frequency Helps center a radially-loaded shaft A sleep function could stop the motor automatically

Avoiding bearing discharge currents 2. VFD adjustments Advantages Easy to implement Concerns Mostly only extends the life of the bearings; doesn t eliminate the problem 43

Avoiding bearing discharge currents 3. System maintenance Check belt tension Check shaft alignment Check balancing of the load Check bearing lubrication Check environmental concerns 44

Avoiding bearing discharge currents 3. System maintenance Advantages Should be done anyway Concerns May not be the problem 45

Avoiding bearing discharge currents 4. High frequency toroids A high frequency toroidal core concentrates the magnetic field of high frequency currents passing through it, impeding their flow It can be used in two ways: To combat common mode voltage and current To combat the high frequency components of pulses to the motor 46

Avoiding bearing discharge currents 4. High frequency toroids Common mode filter Built into the VFD There are other designs of common mode filters 47

Avoiding bearing discharge currents 4. High frequency toroids Common mode filter Added between the VFD and the motor VFD The ground wire does not pass though the toroid 48

Avoiding bearing discharge currents 4. High frequency toroids High frequency filters, for circulating currents Added between the VFD and the motor VFD 49 The ground wire does not have a toroid around it

Avoiding bearing discharge currents 4. High frequency toroids Advantages No maintenance required Can be retrofit in most situations Concerns Requires proper wiring between the VFD and the motor 50

Avoiding bearing discharge currents 5. Blocking the discharge: insulating sleeve Doesn t need to block a particularly high voltage There are a number of ways to block the flow of current through a motor s bearings Add an insulating sleeve between the bearing and the motor 51

52 Avoiding bearing discharge currents 5. Blocking the discharge: insulating sleeve Advantages Blocks current flow through the bearing Concerns For retrofits, requires disassembling and machining of the motor Conductive dirt across the sleeve For common mode shaft voltage, both bearings must be insulated May transfer bearing damage to the connected load unless an insulated coupling is used

Avoiding bearing discharge currents 5. Blocking the discharge: insulated bearings Insulated bearings are of two general types: With rolling elements made of a nonconductive material, such as a ceramic Using an inner and/or outer ring with an electrically insulated mounting surface In most case, this does not impact the mounting dimensions of the bearing 53

54 Avoiding bearing discharge currents 5. Blocking the discharge: insulated bearings Advantages Blocks current flow through the bearing Can be a drop-in replacement Concerns For common mode shaft voltage, both bearings must be insulated May transfer bearing damage to the connected load unless an insulated coupling is used When the rolling element is non-metallic, the ratings of the bearing may be impacted

Avoiding bearing discharge currents 6. Re-routing the discharge By electrically grounding the motor s shaft to the motor s frame, shaft voltage can be dissipated around the bearing as long as the low impedance conductive path is maintained A number of methods are available 55

Avoiding bearing discharge currents 6. Re-routing the discharge Rotary contact Spring-loaded carbon brush Conductive fiber brush 56

Avoiding bearing discharge currents 6. Re-routing the discharge Advantages Can generally be retrofitted in the field For common mode voltage, only one may be needed Concerns For circulating current, using only one only makes the problem worse Often, insulating the other bearing is recommended 57

Avoiding bearing discharge currents 6. Re-routing the discharge Concerns, continued For large motors, multiple devices may be needed Proper mounting and shaft preparation are essential Environmental conditions may impact its operation May require periodic inspection and/or maintenance This band formed under the brushes. 58

VFDs and Motor Bearing Damage Review Background on motors, VFDs and bearing currents How to detect bearing current How to diagnose causes of bearing damage How to avoid damage due to bearing current Questions? 59