1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide

Similar documents
1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide

1ZSC AAW en, Rev. 2. On-load tap-changers, type UC Technical guide

1ZSE en, Rev. 9. On-load tap-changers, type UC and VUC Technical guide

On-load tap-changers, type UC and VUC Technical guide

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA

TECHNICAL DATA TYPE SHZV VACUUM ON-LOAD TAP CHANGER FOR OIL-IMMERSED TRANSFORMER

On-load tap-changer VACUTAP VRD, VRF, VRG

Technical guide. Type VRLTC load tap changer

ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA

On-load tap-changer VACUTAP VRC and VRE

TAP CHANGER SELECTING MANUAL TECHNICAL DATA

Technical guide. Type VRLTC load tap changer

On-Load Tap Changer Type M

TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Regional Technical Seminar

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

INTERNATIONAL STANDARD

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

XY-Stages series 5102

Electrical Description

ABB Power Technologies

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

Basic Principles and Operation of Transformer

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

3. COMBINED TRANSFORMERS Oil-paper insulation

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

Instruction manual for STA 1 sectional door operator

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

Instruction manual for STA 1 sectional door operator

7. INSPECTION AND TEST PROCEDURES

INTERNATIONAL STANDARD

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Liquid-Filled Transformers

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

OIL-IMMERSED ARC-SUPPRESSION COILS

Overview of types. Technical data

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

POWER/DISTRIBUTION TRANSFORMER PERFORMANCE EVALUATION.

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

VACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS.

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

Functional data Factory settings Variable Settings

TECHNICAL SPECIFICATION

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Power transformers for Network, Rectifiers, Furnace

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Hands-On Transformer Testing and Maintenance

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

General Four-Way Operation, Maintenance & Service Manual

REF42plus HMI Cutting Tool Operating Guide

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

INTERNATIONAL STANDARD

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Servomotor for butterfly valves VF, VFH. delta-elektrogas.com EE157-01/16

Distribution transformers Part 2 Ground mounted transformers not closecoupled

CHAINSAW SHARPENER MODEL: ECSS-1

Operating and Maintenance Instructions Keep for future reference

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

MW3105 DIGITAL CLAMP MULTIMETER

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

Onsite Mobile AC High Voltage Test System

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Power consumption In operation At rest For wire sizing. Auxiliary switch NRF24A-SR-S2 NRF24A-SR-S2-O

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

Load Tap Changers for Power Transformers

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

SAT.. Electromotoric actuators for valves ACVATIX. with a 5.5 mm stroke and 300 N positioning force

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

Typical Group D Rear Acoustical Cover Installation

SECTION AUTOMATIC TRANSFER SWITCH

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

Installation guide 971 SmartRadar LTi

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

EN 1092 PN 10 EN 1092 PN 16 JIS B K ANSI B16.5 Class 150 ANSI B16.47 Class 150 BS 10 Table D

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Transcription:

1ZSE 5492-106 en, Rev. 6 On-load tap-changers, type UBB Technical guide

Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted.

Manufacturer s declaration The manufacturer Hereby declares that The products ABB AB Components SE-771 80 LUDVIKA Sweden On-load tap-changers, type UBB with motor-drive mechanisms, types BUE and BUL comply with the following requirements: By design, the machine, considered as component on a mineral oil filled power transformer, complies with the requirements of Machinery Directive 89/392/EEC (amended 91/368/EEC and 93/44/EEC) and 93/68/EEC (marking) provided that the installation and the electrical connection be correctly realized by the manufacturer of the transformer (e.g. in compliance with our Installation Instructions) and EMC Directive 89/336/EEC regarding the intrinsic characteristics to emission and immunity levels and Low Voltage Directive 73/23/EEC (modified by Directive 93/68/EEC) concerning the built-in motor and apparatus in the control circuits. Certificate of Incorporation: The machines above must not be put into service until the machinery into which they have been incorporated have been declared in conformity with the Machinery Directive. Date 2013-02-15 Signed by... Hans Linder Title Manager Tap-Changers, Local Product Group Unit Components

Content Design principles... 6 General information... 6 Tap-changer... 8 Selector switch... 8 Transition resistors... 8 Change-over selector... 8 Geneva gear... 8 Selector switch housing... 9 Oil conservator... 9 Motor-drive mechanism... 9 Accessories... 9 Principles of operation... 10 Switching sequence... 10 Selector switch... 10 Change-over selector for plus/minus switching... 11 Change-over selector for coarse/fine switching... 11 Coarse/fine regulation leakage inductance switching... 11 Tap-changer characteristics and technical data... 12 Type designation... 12 Rated phase step voltage... 12 Standards and testing... 13 Rating plate... 13 Rated through-current... 13 Maximum rated through-current... 13 Contact life... 13 Mechanical life... 14 lnsulation levels... 14 Short circuit current strength... 15 Highest phase service voltage across the regulating winding... 15 Tie-in resistors... 15 Occasional overloading... 15 Oil temperature... 15 Conductors from the windings... 15 Installation and maintenance... 16 Drying... 16 Painting... 16 Oil filling... 16 Installation... 16 Maintenance... 16 Oil filter unit... 16 Accessories and protection devices... 16 Ordering alternatives... 17 Dimensions... 18 Appendix: Single-phase diagrams... 20

Design principles General information When the on-load tap-changer operates, arcing occurs in the tap-changer. To avoid contamination of the transformer oil, the tap-changer is housed in its own oil compartment separated from the transformer oil. All components that make or break the current during the operation of the tap-changer are located in the on-load tap-changer compartment. The UB range of tap-changers operates according to the selector switch principle, that is, the tap selector and diverter switch functions are combined in one. The UB type of tap-changer is mounted on the inside of the transformer tank. Both cover-mounting and yoke-mounting may be specified. The tap-changer comes ready for mounting on the inside of the transformer tank, which simplifies installation procedures. All of the equipment necessary to operate the tap-changer is contained in a cylinder of glass fibre reinforced plastic - the selector switch housing. Driving is from a separate motordrive mechanism, fitted to the side of the transformer tank, and connected by means of drive shafts and bevel gears. Fig. 1. On-load tap-changer type UBB. 6 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

Oil valve Bevel gear Connection to oil conservator Pressure relay Top-cover Air release valves Flange Cylinder Position indicator window Change-over selector: Moving contacts Fixed contacts Selector switch: Fixed contacts Moving contacts Current collector terminal Selector switch shaft Transition resistor Shielding rings Bottom valve drain screw Bottom Fig. 2. On-load tap-changer (type UBBRT shown). 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 7

Tap-changer The tap-changer is built-up by using three single-phase units, mutually identical, mounted in the selector switch housing. Each single-phase unit consists of a selector switch and transition contacts. When plus/minus or coarse/fine switching there is also a change-over selector. Selector switch The selector switch consists of fixed contacts and a moving contact system. The fixed contacts are mounted on bushings which are inserted through the cylinder wall of the selector switch housing. Each fixed contact has two contact paths on each side, one for the moving main contact and one for the moving switching contacts. The moving contact system for a single-phase consists of the main contact, the main switching contact and two transition contacts. The system is built as a rigid unit rotated by a common insulated drive shaft. In the service position the load current is carried by the moving main contact, which consists of two fingers, pressed on the fixed contact by springs. The moving switching contact and the transition contacts are made as rollers, which move over the knife-like fixed contacts. See Fig. 3. The making and breaking take place between the fixed and moving switching contacts. The switching contacts are made of copper/tungsten or, in the case of tap-changers for lower currents, the contacts are made of copper. In service position the current is carried by clean surfaces of copper or silver, which are not subjected to arcing. Fixed contacts Transition resistors The resistors are made from spirally wound wire mounted on insulating bobbins. They are connected between the moving main contact and the transition contacts. Change-over selector The change-over selector is used for reversing the regulating winding or for changing connection in the coarse/fine regulation. One phase of the change-over selector consists of a moving contact and three fixed contacts. The moving contact is fixed to an insulated cylinder pivoted on the top of the drive shaft, see Fig. 4. The current is carried by the four contact fingers of the moving contact. The contact surfaces consist of silver and copper. The change-over selector does not make or break the current during operation. Fixed contacts Fig. 4. Change-over selector. Moving contacts Geneva gear The Geneva gear principle is used to change a rotary motion into a stepping motion. Drive is transmitted via a shaft system and bevel gears from the motor-drive mechanism. A spring energy accumulator actuates the Geneva gear. The Geneva gear operates the selector switch and the change-over selector. The Geneva gear is also used to lock the moving contact system into position. The gearing mechanism is maintenance-free. Moving contacts Fig. 3. Moving and fixed contacts. 8 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

Selector switch housing The tap-changer oil compartment is separated from the transformer oil by a vacuum-proof cylinder, designed to withstand a test pressure of 100 kpa or full vacuum. The cylinder is made of glass fibre reinforced plastic, which on its upper end has attached a metal flange and on the lower end a closed metal bottom. The bottom, the flange, the topcover and the accessories mounted on the cover are made from casted aluminium. The cylinder and the gasket are designed to be oil-tight, and the tightness is routinely tested with a vacuum/helium-method. This safety guarantees the contaminated tap-changer oil to remain separated from the transformer oil. The top-cover is provided with connecting flanges for pipes to the oil conservator and the pressure relay. The connections are stepless orientable. Oil conservator The tap-changer shall be connected to a separate oil conservator, preferably placed at the same height or just below the conservator for the transformer. Special applications, load conditions, environments and insulating liquids Please contact the supplier for advice in the following cases: For applications other than network. (Restrictions in number of operations might be valid.) In case of unusual load conditions such as overloads beyond IEC 60076-7 or IEEE C57.91-1995, extreme inductive or capacitive loads or loads beyond the given data in this document. In case of requirement of other insulating liquids than mineral oil. Current measurement in phase before star point. Motor-drive mechanism The motor-drive mechanism provides the drive to allow the tap-changer to operate. Energy is provided from a motor through a series of gears and out through a drive shaft. Several features are incorporated within the mechanism to promote long service intervals and reliability. Accessories For accessories available for both the tap-changer and the motor-drive mechanisms, consult ABB. Bevel gear Horizontal drive-shaft and protection cover Bevel gear Vertical drive-shaft and protection cover Tap-changer Hand crank Motor-drive mechanism Fig 5. Tap-changer system. 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 9

Principles of operation Switching sequence The switching sequence is designated the symmetrical flag cycle. This means that the main switching contact of the selector switch breaks before the transition resistors are connected across the regulating step. This ensures maximum reliability when the switch operates with overloads. 1 2 H M2 M1 At rated load the breaking takes place at the first current zero after contact separation, which means an average arcing time of approximately 6 ms at 50 Hz. The total time for a complete sequence is approximately 50 ms. The tap change operation time of the motor-drive mechanism is approximately 5 s per step. Fig. 8. The transition contact M1 has made on the fixed contact 2. The load current is divided between the transition contacts M1 and M2. The circulating current is limited by the resistors. Selector switch The switching sequence when switching from position 1 to position 2 is shown in the diagrams of Figs. 6-10. The moving contact H is shown as one contact but consists in fact of two, the main contact and the main switching contact. The main contact opens before and closes after the main switching contact. 1 2 H M2 M1 M2 1 2 H M1 Fig. 9. The transition contact M2 has broken at the fixed contact 1. The transition resistor and the transition contact M1 carry the load current. 1 2 Fig. 6. Position 1. The main contact H is carrying the load current. The transition contacts M1 and M2 are open, resting in the spaces between the fixed contacts. M2 H M1 1 2 H M2 M1 Fig. 10. Position 2. The main switching contact H has made on the fixed contact 2. The transition contact M1 has opened at the fixed contact 2. The main contact H is carrying the load current. For plus/minus and coarse/fine switching, the change-over selector is used. Fig. 7. The transition contact M2 has made on the fixed contact 1, and the main switching contact H has broken. The transition resistor and the transition contact M2 carry the load current. 10 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

Change-over selector for plus/minus switching The switching sequence, when the change-over selector R changes over for plus/minus switching, is shown in the diagrams of Figs. 11-12. The contact arm of the selector switch has reached the fixed contact K (=10) after switching from the fixed contact 9. It is connected to the end of the main winding. The load current goes directly from the main winding through the contact K and out through the current collector at the selector switch shaft. The upper end of the regulating winding is still connected to the main winding. This is the change-over position. The contact arm of the change-over selector R has travelled from the contact (+) to the contact ( ), through which the lower end of the regulating winding has been connected to the main winding. The load current still goes directly from the main winding through the contact K. After the change-over selector has finished its operation the contact arm of the selector switch starts moving towards contact 1. Both those movements above takes place in the same operation by the motor-drive, so there is no through position. Change-over selector for coarse/fine switching Mechanically, coarse/fine switching is carried out exactly the same as for the plus/minus switching. However, the electrical switching is different. The change-over selector connects or disconnects the coarse winding. 10 loops R - + 0 0 + 9 SELECTOR SWITCH 5 4 6 3 7 H 15 1 2 8 M1 M2-9 1 K H Main contact M1, M2 Transition contacts Fig. 11. Change-over position. 0 + 9 R - + 0 CURRENT COLLECTOR TERMINAL Coarse/fine regulation leakage inductance switching When changing from the end of the fine winding to the end of the coarse winding with resistor type tap-changers, a high leakage inductance can be set up with the two windings in series opposition. This can cause a phase shift between the switched current and recovery voltage of the diverter or selector switch. The result is extended arcing of the switch, and this should be limited. The leakage inductance shall be specified in the ordering data sheet. If there are any doubts about this, please consult ABB. Fig. 12. 1-3 2 4 5 6 H 15 M1 M2 1 9 K 7 8 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 11

Tap-changer characteristics and technical data Type designation Type Type of switching L Linear R Plus/Minus D Coarse/Fine U B B.. XXX/YYY Rated phase step voltage The maximum allowed step voltage is limited by the electrical strength and the switching capacity of the selector switch. It is therefore a function of the rated through-current as shown in Fig. 13. Step voltage (V) 1500 A B C Type of connection N Three-phase star point T Three-phase fully insulated Impulse withstand voltage to earth 200 kv, 350 kv Maximum rated through-current 150 A, 400 A, 500 A 1000 500 0 0 100 200 300 400 500 Rated throughcurrent (A) Maximum number of positions Linear switching: 14 positions Plus/minus switching: 27 positions Coarse/fine switching: 27 positions A. Tap-changer with: 13-14 positions linear 13,25-27 positions plus/minus 13, 25-27 positions coarse/fine B. Tap-changer with: 11-12 positions linear 11, 21-23 positions plus/minus 11, 21-23 positions coarse/fine C. Tap-changer with: max 10 positions linear 9, 15-19 positions plus/minus 9, 15-19 positions coarse/fine Fig. 13. Rated phase step voltage. 12 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

Standards and testing The UBB types of tap-changers fulfil the requirements according to IEC 60214-1. The type test include: Contact temperature rise test Switching tests Short-circuit current test Transition impedance test Mechanical tests Dielectric tests The routine test include: Check of assembly Mechanical test Sequence test Auxiliary circuits insulation test Vacuum test Final inspection Rating plate Maximum rated through-current The UB models are designed for maximum rated throughcurrents of 150 A, 400 A or 500 A. Contact life The predicted contact life of the fixed and moving contacts of the selector switch, is shown as a function of the rated through-current in Fig. 15. As most of the tap-changers are not working at maximum current the whole time, the estimated contact life for a tap-changer with 80 % mean load is indicated with a dashed line in the figure. The values are calculated from the results of the service duty test. For step voltages equal to or below 40 V at 50 Hz and equal to or below 50 V at 60 Hz the predicted contact life is always 500 000 operations. Number of operations 500 000 150A 80 % 400-500A 80 % 400 000 300 000 200 000 100 000 100 200 300 400 500 A Rated through-current Fig. 15. Predicted contact life at 50 Hz. At 60 Hz the predicted contact life is about 20 % higher, up to the maximum 500.000 operations. Fig. 14. Example of rating plate. Rated through-current The rated through-current of the tap-changer is the current which the tap-changer is capable of transferring from one tapping to the other at the relevant rated step voltage, and which can be carried continuously whilst meeting the technical data in this document. It is limited by the step voltage according to the curve in the diagram, Fig. 13. The rated through-current determines the dimensioning of the transition resistors and the contact life, and is stated on the rating plate, Fig. 14. 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 13

Mechanical life The mechanical life of the tap-changer is based on an endurance test. The test showed that the mechanical wear was negligible, and that the tap-changer was still mechanically sound after more than 500 000 operations. lnsulation levels The insulation levels are indicated as 1.2/50 µs impulse withstand voltage power frequency withstand voltage. Table 1. Type UBB Insulation levels kv to earth b1 between phases fully insulated 1) 200/... 220 70 200 70 36.5 350/... 350 140 350 140 76 1) Class II according to IEC 60214, clause 5.2.6. Max. service voltage between phases for fully insulated design UBB.T 1) Table 2. Insulation levels. Type of switching Number of Within one phase Between phases for neutral point type positions a2 Between the first and the c1 Across change-over b1 In selector d1 In change-over selector last contacts (Figs. 16 18) selector (Figs. 17-18) switch BIL 200 BIL 350 Linear 10 200 60 - - - - 12 180 60 - - - - 14 170 60 - - - - Plus/Minus 9, 15 19 200 60-250 60 250 60 350 140 11, 21 23 180 60-250 60 250 60 350 140 13, 25 27 170 60-250 60 250 60 350 140 Coarse/Fine 15 19 200 60 250 60 250 60 250 60 350 140 21 23 180 60 250 60 250 60 250 60 350 140 25 27 170 60 250 60 250 60 250 60 350 140 b1 is to the corresponding contacts in the next phase b1 and d1 is to the corresponding contacts in the next phase d1 b1 c1 b1 a2 c1 a2 a2 Fig. 16. Linear switching. Fig. 17. Plus/minus switching. Fig. 18. Coarse/fine switching. 14 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

Short circuit current strength The short circuit current strength is verified with three applications of 3 seconds duration, without moving the contacts between the three applications. Each application has an initial value of 2.5 times the rms value. Table 3. Max. rated through-current A, rms 150, 400, 500 8000 Three applications of 3 s duration A, rms Highest phase service voltage across the regulating winding The highest permissible phase service voltage is the product of the maximum number of steps and the allowable step voltage according to Fig. 13. Oil temperature The temperature of the oil surrounding the tap-changer shall be between -25 and +105 C for normal operation, as illustrated in Fig. 19. The range can be extended to -40 C provided that the viscosity of the tap-changer oil is between 2-800 mm 2 /s (= cst). C +115 +105 1) No operations allowed 2) Emergency overloading. The tap-changer will not restrict the occasional overloading of the transformer according to the standards in section Occasional overloading. 3) Normal operating range. Tie-in resistors If the service voltage and the winding capacitances are such that the recovery voltage of the change-over selector exceeds 25 kv, it must be limited to this value or lower, by means of a tie-in resistor. The tie-in resistors are placed under the bottom for star point types and on the connections outside the cylinder for fully insulated types. 0-25 -40 4) When operating within this range, no overload is allowed. 5) Operation with de-energized transformer only. Calculation rules for tie-in resistors are provided in a separate document, 5492 0030-39. Fig. 19. Tap-changer oil temperature. Occasional overloading If the rated through-current of the tap-changer is not less than the highest value of tapping current of the tapped winding of the transformer, the tap-changer will not restrict the occasional overloading of the transformer, according to IEC 60354, ANSI/IEEE C57.91 and CAN/CSA-C88-M90. Conductors from the windings The temperature of the conductors connected to the terminals on the back of the tap-changer must not exceed 30 K over the surrounding oil. To meet these requirements, the UB models have been designed so that the contact temperature rise over the surrounding oil, never exceeds 20 K at a current of 1.2 times the maximum rated through-current of the tap-changer. The contact life stated on the rating plate, and given in this guide, is given considering that overload currents of maximum 1.5 times the rated through-current occur during a maximum of 3 % of the tap-changer operations. Overloading beyond these values, results in increased contact wear and shorter contact life. 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 15

Installation and maintenance Drying The tap-changer should be stored indoors and left in its plastic shipping cover until time for assembly. Drying of the tap-changer is not necessary if the plastic cover not have been destroyed before assembly. The tap-changer can be dried together with the transformer according to one of the following processes: alternating hotair and vacuum or vapour-phase at a maximum temperature of 135 o C (275 o F) and a maximum pressure difference of 100 kpa between the tap-changer and the transformer. Painting The top section against air of the tap-changer is painted on surfaces facing the air. The painting system consist of 3 layers: 30 µm single component acrylic based primer 60 µm two component epoxy based primer and 60 µm two component polyurethane based finishing coat. The finishing colour is grey/blue according to Munsell 5.5B 5.5/1.25. Oil filling For the correct oil filling procedure, consult the installation and commissioning guide. Overhaul shall normally be carried out after one fifth of estimated contact life or at least every fifth year, whichever comes first. The overhaul must be carried out by personnel well acquainted with the product. At overhaul the oil is drained and the insert is lifted up. The overhaul mainly consist of cleaning, checking of the contacts (replacement if they are worn) and filtering or replacement of the oil. The motor-drive mechanism and shaft system should also be checked and lubricated, and the pressure relay checked. Consult the maintenance guide for further information. Oil filter unit The tap-changer can be equipped with an oil filter unit for continuous oil filtration. For further information, see the corresponding oil filter manual. Accessories and protection devices The tap-changer can be equipped with various protection devices. The standard protection device is the pressure relay. An oil flow relay is also available. Pressure relief device with alarm signal is also available as well as some other supervisory sensors. For more information about accessories and protection devices see technical description 1ZSC000562-AAD. Installation For installation instructions, consult the installation and commissioning guide. Maintenance The UB range of tap-changers has been developed to provide a maximum of reliability. The simple and rugged design gives a service life that equals the service life of the transformer. A minimum of maintenance is required for absolutely troublefree operation. The only parts that require maintenance during the service life are the contacts, the oil and the motor-drive mechanism. An annual inspection should be carried out while the transformer is in service. At this inspection the counter is read to determine when overhaul is due. 16 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

Ordering alternatives Pipe connection alternatives as shown in Figs. 20-22. Valve R ½ Pipe for connection to conservator Cover with air release valve Pressure relay Fig. 20. Pipe connection, standard. Pipe with air release valve for oil-draining Pipe for connection to conservator Cover with air release valve Pressure relay Fig. 21. Pipe connection, draining. For assembly of pipe and valve on the transformer. Pipe for connection to oil-filter, suction side Pipe for connection to conservator Pipe for connection to oil-filter, return pipe Pressure relay Fig. 22. Pipe connection, oil filtering. 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 17

Dimensions Table 4 contains the dimensions and weights of the models in the UBB range of tap-changers. The motor-drive mechanism and the drive shaft system are not included in the overall weight. Table 4. Dimensions and weights. Type designation Dimension H mm Approx. weight in kg Tap-changer without oil Required oil Total UBBLN XXX/YYY 1193 140 100 240 UBBRN XXX/YYY UBBDN XXX/YYY UBBLT XXX/YYY 1489 155 125 280 UBBRT XXX/YYY UBBDT XXX/YYY Motor-drive mechanism (BUL2): Motor-drive mechanism (BUE): Drive shaft system: 95 kg 130 kg Approx. 10 kg Ø 600 H (see Table 4) 132 To oil conservator Ø 394 Fig. 23. Tap-changer dimensions. All dimensions are in millimetres unless otherwise stated. 18 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

125 2) A A L 1 500 mm 1) A 70 A 45 o R67.5±0.5 M10 (4x) L 2 525 mm 1) 75 Ø 96 Ø92±1 Drillingplan for gearbox 1050 36 1274 1197 49 426 37 45 79 383 140 2) 243 440 213 192 408 75 202 475 626 BUE 2 BUL 2 90 if a pressure relief is used 1) Angle deviation max 4 2) The shaft can be mounted within these angles. (The gearbox stepless turnable). Fig. 24. Dimensions, drive shaft system and motor-drive mechanism. All dimensions are in millimetres unless otherwise stated. 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 19

Appendix: Single-phase diagrams The basic connection diagrams illustrate the different types of switching and the appropriate connections to the transformer windings. The diagrams illustrate the connections with the maximum number of turns in the transformer winding, with the tap-changer in position 1. The tap-changer can also be connected in such a way that position 1 gives a minimum effective number of turns in the transformer winding with the tap-changer in position 1. 8 steps Linear Plus/Minus Coarse/Fine Number of tap positions 9 steps 8 4 4 9 9 9 Number of tap positions 10 steps 9 10 10 5 5 Number of tap positions 11 11 11 20 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

11 steps Linear Plus/Minus Coarse/Fine Number of tap positions 12 steps 11 12 Number of tap positions 13 steps 12 6 6 13 13 13 Number of tap positions 14 steps 13 14 Number of tap positions 8 7 15 15 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 21

16 steps Linear Plus/Minus Coarse/Fine Number of tap positions 18 steps 8 8 17 17 Number of tap positions 20 steps 10 9 19 19 Number of tap positions 22 steps 10 10 21 21 Number of tap positions 12 11 23 23 22 Technical guide UBB 1ZSE 5492-106 en, Rev. 6

24 steps Linear Plus/Minus Coarse/Fine Number of tap positions 26 steps 12 12 25 25 Number of tap positions 14 13 27 27 1ZSE 5492-106 en, Rev. 6 Technical guide UBB 23

Contact us ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents Copyright 2014 ABB, All rights reserved. 1ZSE 5492-106 en, Rev. 6, 2014-05-30