FICHA TÉCNICA DE PRODUTO

Similar documents
600T Series Transmitters Model 653L Electronic temperature transmitter (PC programmable for RTD and resistance) Specification Sheet

600T Series Transmitters. Specification Sheet. Model 653T Electronic temperature transmitter (PC programmable)

Model 264IB. ABB 2600T Series Engineered solutions for all applications

Field IT 2600T Series Pressure Transmitters

FICHA TÉCNICA DE PRODUTO

600T EN Series Pressure Transmitters. Specification sheet. Model 624ES gauge/absolute with direct mount seal for pulp & paper application

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

Field indicator for current loops with HART communication Models DIH50, DIH52

FICHA TÉCNICA DE PRODUTO

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

Digital Indicator DS 96/48 PK

LST100 Ultrasonic level transmitter for upstream oil and gas

FieldIT Temperature Transmitter, field mounted TH202/TH202-Ex

ABB MEASUREMENT & ANALYTICS DATA SHEET. Ultrasonic level LST400 Open channel flow transmitter

Field indicator for current loops with HART communication Models DIH50, DIH52

DOC. NO. : C3200-E04A APPROVED. Smart PressureTransmitter for Gauge and Absolute Pressure Measurement MODEL APT3200

C1901 Single Pen Circular Chart Recorder. C1901 a rugged, reliable recorder for all single channel recording applications

ABB ME ASURE ME NT & AN AL YT ICS D AT A SHE ET. TTF200 Field-mount temperature transmitter

TEK-TEMP 2100A. Explosion-Proof Temperature Transmitter. TEMPERATURE. Technology Solutions

FICHA TÉCNICA DE PRODUTO

Field IT 2600T Series Pressure Transmitters

SITRANS T measuring instruments for temperature

IP26 Series Current to Pneumatic Converter

ABB MEASUREMENT & ANALYTICS DATA SHEET. TB82 2-wire conductivity transmitters

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Process display RIA 261

Digital Indicator DS 96/24

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

General Specifications

Rosemount 848L Logic Transmitter with FOUNDATION Fieldbus

Data Sheet SS/265VS-EN_1

RHE11. Hazardous Area Multifunction Coriolis Flow Transmitter. Features. Applications. Benefits

SOLENOID TYPE, CERTIFICATION & PROTECTION CONCEPTS

Loop Powered Indicator

Sarasota CM200 Sarasota HME900 Density Converter Electronics

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

Head mounted Temperature Transmitter TF02/TF02-Ex

LST400 Ultrasonic level / open channel flow transmitter

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

PRODUCT SPECIFICATION AND MODEL SELECTION GUIDE

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

Model 144H NEW. PC-Programmable Temperature Transmitter. Product Data Sheet

General Specifications

SFC Smart Field Communicator Model STS103. Specification 34-ST /24/06. Description. Function. Page 1 of 5

MHPS MHPS. Modular pressure transmitter. Technical documentation. Table of content. Characteristics - applications - technical data

Pressure transmitter with flameproof enclosure For applications in explosion-protected areas Models E-10 and E-11

FICHA TÉCNICA DE PRODUTO

2600T Series Pressure Transmitter Model 264DS Differential Pressure Transmitter. Kent-Taylor

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex

Level Measurement. Continuous level measurement Radar transmitters SITRANS LR460. 4/258 Siemens FI

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

Alphaline Temperature Transmitters

Field IT Electro-Magnetic Flowmeters Mini-Mag with integral XE converter

Level Measurement Continuous level measurement Radar transmitters

Process transmitter Model UPT-20, with pressure port Model UPT-21, with flush diaphragm

General Specifications

Specification DataFile

ChuteMaster Microwave-blocked chute detection and point level instrument

Rev ECN Description Approval Date AA Release to Approvals RCS 10/9/12

Wireless Dual Discrete Input Transmitter Series XYR 5000, Model WW59x Specifications - Americas

General Specifications

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Rosemount 3101, 3102, and 3105

APT3100 MODEL. Smart Pressure Transmitter. for Differential / Gauge / Absolute Pressure Measurement. Doc. No. : C3100-E05A

A BB ME ASU R E ME NT & AN AL Y T ICS D AT A S H E ET. TTR200 Rail-mount temperature transmitter

Compact Orifice Flow Meter

Model 266GSH Gauge Model 266ASH Absolute. 2600T Series Pressure Transmitters Engineered solutions for all applications

TTH200 Head-mount temperature transmitter

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

SensyTemp TSBA (BA R) Resistance thermometer for building automation, machine construction and environmental engineering

Single-Channel Safety Barriers Series 9001

PAD - Heavy Duty Differential Pressure Trasmitter

Wireless Temperature Transmitters Series XYR 5000, Model WT5xx/WT5xxR/WT5xxT Specifications - Americas

Level Measurement Continuous level measurement Radar transmitters

Flow Measurement SITRANS F M

Positioner with HART Communication Type 3780

OPTIFLUX 5000 Technical Datasheet

OriMaster FPD500 Compact orifice flowmeter. Orifice-based flow metering made simple

Temperature Measurement

Rail mounted Temperature Transmitter TH102/TH102-Ex

DPharp Differential Pressure and Pressure Transmitters

Temperature Transmitters TMT 136, TMT 137

Mobrey Ultrasonic. MSP422, MSP400RH, and MSP900GH Level Transmitters. Product Data Sheet February 2015 IP2045, Rev EA

SALES SERVICE +358 (0)

XYR 5000 Wireless Temperature Transmitters Model WT530 Specifications - Europe

Wireless Acoustic Transmitters Series XYR 5000, Model WN571 Specifications - Americas

Rosemount 5400 Series Radar Level Transmitter

Intrinsically Safe Pressure Transmitter for applications in hazardous environments and shipbuilding industry Model IS-20-S, IS-21-S, IS-20-F, IS-21-F

AT200 External Mount Magnetostrictive Level Transmitter

Smart Pressure Transmitter

Glass-fibre-reinforced polycarbonate. Dead zone Adaptive or fixed from % 1.5 s adjustable. 20 ms. 60 ms. 60 ms. Approx. 1.

Conductivity Analyzer

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

Certificate of Conformity

General Specifications

OEM miniature resistance thermometer Models TR31-3 and TR31-K, thread-mounted

General Specifications

Two-Wire Programmable Transmitter for:

Temperature Measurement Transmitters for mounting in sensor head

Temperature Measurement

Transcription:

FICHA TÉCNICA DE PRODUTO PRODUCT DATASHEET HI Automação e Instrumentação, Lda. Rua Dr. Oliveira Salazar, nº 88 4780-453 Santo Tirso PORTUGAL Web: www.hmi.pt Tel. +351 252 809 124 Fax. +351 252 859 298 Email: hmi@hmi.pt

Data Sheet Field Indicator Digital LCD or analog meter allows to select the proper indication Programmable meter and HART configurator combines signal display with password protected configuration capabilities for transmitter management Rugged, compact, lightweight, enclosure to IP67 enables installation in industrial environments Compatible with all 4-20 ma, 2-wire systems Square root signal characterization allows measurements linearization Comprehensive certification approvals give high applicability in plant hazardous areas

600T EN Series Transmitters field indicator provides simple and low cost remote indication of a pr ocess variable on an easy to r ead meter, ensuring the most useful display for any specific application. Traditional analog indicator is available with standar d 0-100% linear or 0-10 squar e root graduations or special scales to be specified. In addition to parallel transmitter wiring the terminal block 695FI provides series wiring through junction box connection facility. Alternatively to the pr evious options, model 695FI, of fers a programmable signal meter which integrates LCD plus bargraph indications (Proeter). This kind of display is also available with HART configuration capabilities (Coeter). Both these meters feature: - one 5-digit numeric indication (top) - one 10-segment bargraph indication (central) - one 7-digit alphanumeric indication (bottom) - a membrane keypad with 4 tactile feedback keys The functionality as ETER is achieved by the 10-segment bargraph which gives an analog 0-100% indication and by the 5- digit display which gives a digital indication programmable from the following options: 4 to 20 ma 0 to 100% engineering unit Programmability is carried out using the four keys, allowing to define linear or square root indication for ma or engineering unit; for this latter, also indication range (zer o and full scale values) can be chosen related to the unit which is defined in HART table; these parameters can be automatically uploaded fr om the transmitter where 695FI with Coeter is remotely connected. As CONFIGURATOR, the device keypad of Coeter only allows easy management of the associated transmitter; the 7- digit alphanumeric display provides comprehensive feedback via menù driven operations. This configuration device operates in compliance to standar d definition of universal and common practice HART commands as explained in the following list: PV reading Analog output and % output reading Secondary variables reading Transmitter tag reading Sensor number reading Up/Down scale setting reading Upper and Lower Range limit reading Change output transfer function (square root) Change units Change range (ranging) Change damping Transmitter number (assembly reference) Reranging (wet calibration) Loop test Output trimming (directly using Coeter or by external DV) Zero alignment (sensor trim) Overall passwor d pr otection ensur es operational security, avoiding unauthorized access to any Coeter operation. A Coeter remotely installed from transmitter allows convenient capability of configuration at easy accessible site. Password Configuration Trimming Damping Square root etc 2

600T EN Series Transmitters Functional specification Input range 4 to 20mA nominal Operating range 3.6 to 22mA (for Coeter ensuring HART functionality) aximum overload (for 2 minutes) Analog indicator : 150% of input range Coeter and Proeter: 110mA (23mA indication). A current less than 3.4mA will blank the display Voltage drop analog indicator : 0.2Vdc Proeter : 2Vdc Coeter: less than 2.6Vdc @ full scale and 20 C 2.8Vdc @ max temperature (including HART modulation) eter/indication range Coeter and Prometer LCD : 5-digit (±99999 counts) programmable with 7.6mm. high (3in), 7-segment numeric characters plus sign and digital point for digital indication of output value in percentage, current or engineer unit; 10-segment bargraph display (10% per segment) for analog indication of output in percentage; 7-digit with 6mm. high (2.3in), 14-segment alphanumeric characters, for engineer units and configuration display Analog : 36mm (1.4in) scale on 90 ; available scales are 0-100% linear, 0-10 square root or special on request. Update time Analog indicators : 0.5sec Coeter and Proeter: 0.7sec Operative limits Temperature limits Ambient (is the operating limit) analog indicator: 40 to +85 C ( 40 to +185 F) Coeter and Proeter : 20 to +70 C ( 4 to +158 F) Lower limit can be down to 40 C ( 40 F) keeping loop integrity and without meter damage (the display will be blank) Storage 40 to +85 C ( 40 to +185 F) Environmental limits Relative humidity Reference: 60% ±25% Operative, transportation and storage limits : 0 and 100% condensing permissible EI/RFI (SAA PC 33.1) Operative limits : Class 3 abc, field strengths up to 30V/m (Frequency range: 20 to 1000Hz) Wet and dust-laden atmospheres The field indicator is dust and sand tight and protected against immersion effect as defined by IEC 529 to IP 67 or by NEA 4X. Hazardous atmospheres INTRINSIC SAFETY/ EUROPE ATEX/CESI approval EC-Type Examination Certificate no. CESI 01ATEX015 Category 1 equipment for Zone 0 (Gas) and Zone 20 (Dust) For Category 1 Stainless Steel enclosure only ATEX II 1 G Ex ia IIC T6 T5 Ga ( 40 C Ta +40 C) ATEX II 1 G Ex ia IIC T4 Ga ( 40 C Ta +85 C) ATEX II 1 D Ex ia IIIC T50 C Da ( 40 C Ta +40 C) ATEX II 1 D Ex ia IIIC T95 C Da ( 40 C Ta +85 C) Category 2 equipment for Zone 1 (Gas) and Zone 21 (Dust) For Category 2 Aluminiun or alternatively Stainless Steel enclosure ATEX II 2 G Ex ia IIC T6 T5 Gb ( 40 C Ta +40 C) ATEX II 2 G Ex ia IIC T4 Gb ( 40 C Ta +85 C) ATEX II 2 D Ex ia IIIC T50 C Db ( 40 C Ta +40 C) ATEX II 2 D Ex ia IIIC T95 C Db ( 40 C Ta +85 C) FLAEPROOF/EUROPE ATEX/CESI approval EC-Type Examination Certificate no. CESI 01ATEX011 ATEX II 2 G Ex d IIC T6 ( 40 C Ta +70 C) ATEX II 2 G Ex d IIC T5 ( 40 C Ta +85 C) ATEX II 2 D Ex d td A21 IP67 T80 C ( 40 C Ta +70 C) ATEX II 2 D Ex d td A21 IP67 T95 C ( 40 C Ta +85 C) TYPE "N"/EUROPE ATEX CESI type examination Design compliance by Certificate no. CESI 02 ATEX074 II 3 GD T50 C, EEx nl IIC T6 ( 40 C Ta +40 C) T95 C, EEx nl IIC T4 ( 40 C Ta +85 C) CANADIAN STANDARDS ASSOCIATION and FACTORY UTUAL: Explosionproof: Class I, Div. 1, Group B, C, D Dust ignitionproof: Class II, Div. 1, Group E, F, G Suitable for: Class II, Div. 2, Group F,G; Class III, Div 1,2 Nonincendive: Class I, Div. 2, Group A,B,C,D Intrinsically safe: Class I, II, III, Div. 1, Group A,B,C,D,E,F,G GOST (Russia), GOST (Kazakistan), based on ATEX Operative limits Temperature limits Ambient (is the operating limit) analog indicator: 40 to +85 C ( 40 to +185 F) Coeter and Proeter : 20 to +70 C ( 4 to +158 F) Lower limit can be down to 40 C ( 40 F) keeping loop integrity and without meter damage (the display will be blank) Storage 40 to +85 C ( 40 to +185 F) 3

600T EN Series Transmitters Performance specification Stated at ambient temperature of 23 C ± 3K (75 F ± 5), relative humidity of 50% ± 20% and atmospheric pressure Electrical connections Two 1/2 NPT or 20x1.5 or PG 13.5 or 1/2 GK threaded conduit entries, direct on housing. Indication accuracy analog indicator : ± 2% fsd Coeter and Proeter digital : ± 0.10% of max span(16 ma) ± 1 digit analog (bargraph) : 10% Resolution for Coeter and Proeter ± 0.025% (12-bit conversion) Ambient temperature Total effect per 1K (1.8 F) change between the limits of 20 and +80 C ( 4 and +176 F). Coeter and Proeter: ± 0.15% of max span (16 ma) EI/RFI Total effect : ± 0.10% from 20 to 1000Hz and for field strengths up to 10V/m when instrument is properly installed. Terminal block Three screw terminals suitable for wirings up to 2.5mm 2 (14AWG) and three connection points for test and communication purposes. Grounding Internal and external 6mm 2 (10AWG) ground termination points are provided. ounting Vertical position on a 60mm or 2in pipe by bracket. Net weight 0.9kg. approx (2lb) (without mounting bracket). Packing Expanded polythene box. Physical specification aterials Housing and covers Aluminium alloy with light gray (RAL 9002) baked epoxy finish; AISI 316 L ss. Covers O-ring Buna N Identification tag AISI 316 ss permanently mounted. 40 characters max on three lines (legend to be specified). ounting bracket (*) Plated carbon steel with chrome passivation; AISI 316 L ss (*) U-bolt material: AISI 400 ss. 4

! 600T EN Series Transmitters OUNTING DIENSIONS (not for construction unless certified) - dimensions in mm (in) Electrical connection 100 (3.93) Locking fastener for cover (EEx d only) eter housing 95 (3.74) 15 (0.59) E QU NT TA CI LES CI RCUITS SON N E H E' W R RCUI T H TS T CLEB ENFE I AL GARDER LECOUVER SO IVE 12.000 * 0% / - - - - - / 100% ma U S TEN K EEP COVER TIG S ION 128 (5.03) Certification tag Terminals side 55 (2.17) 50 (1.97) 170 (6.69) 90 (3.54) 5

600T EN Series Transmitters WIRING DIAGRA 695FI as indicator only 2600T transmitter terminal Internal ground To receiver/ power supply TEST CO TEST CO WIRING DIAGRA AVAILABLE ONLY WITH ANALOG OUTPUT ETER External ground 2600T transmitter terminal 695FI as junction box To receiver/ power supply TEST CO TEST CO WIRING DIAGRA FOR ALL ETER VARIANTS 6

600T EN Series Transmitters ORDERING INFORATION model 695FI Field Indicator Select one character or set of characters from each category and specify complete catalog number. t BASE ODEL 1 to 5 th characters 6 9 5 F I XXXXX X X X X X Field Indicator 6 to 1 0 th characters Use code 00000 th ounting bracket 11 character Carbon steel (not suitable with AISI housing) AISI 316 ss 2 3 E lectrical certification 12 character General purpose ATEX Group II Category 2 GD - Flameproof Ex d II C T6, T5 ATEX Group II Category 1 GD - Intrinsic Safety Ex ia II C T6, T5, T4 ATEX Group II Category 2 GD - Intrinsic Safety Ex ia II C T6, T5, T4 ATEX Group II Category 3 GD - Type of protection "N" Ex nl design compliance Factory utual (F) and Canadian Standard Association (CSA) approvals GOST (Russia) EEx ia GOST (Russia) EEx d GOST (Kazakistan) EEx ia GOST (Kazakistan) EEx d th Housing material and electrical connection 13 character Aluminium alloy Aluminium alloy Aluminium alloy Aluminium alloy AISI 316L ss AISI 316L ss AISI 316L ss AISI 316L ss Output meter - 4 1 th character 1/2in NPT 20 x 1.5 (C20) Pg 13.5 1/2in GK 1/2in NPT 20 x 1.5 (C20) Pg 13.5 1/2in GK Proeter, Standard calibration Proeter, Special calibration Analog output indicator linear 0 100% scale Analog output indicator square root 0 10 scale Analog output indicator, special graduation (to be specified for linear scale) Analog output indicator, special graduation (to be specified for square root scale) Programmable signal meter and HART configurator (Coeter) Programmable signal meter and HART configurator (Coeter customer configuration) Labels language - 15 th characters English German (Note 3) (Note 3) (Notes 1, 3) (Notes 1, 3) (Note 2) (Note 2) (Notes 1, 2) (Notes 1, 2) 1 F L N 8 R U K A 1 2 3 4 A C D F 3 5 7 8 9 Z P W E G Note 1: Not available with Electrical certification code 8 Note 2: Not available with Carbon steel bracket code 2 Note 3: Not available with Electrical certification code L 7

Our offering: Actuators and Positioners Analytical Instruments Device anagement, Fieldbus and Wireless Flow easurement Force easurement Level easurement Natural Gas easurement Pressure easurement Recorders and Controllers Temperature easurement HI Automação e Instrumentação, Lda. Rua Dr. Oliveira Salazar, nº 88 4780-453 Santo Tirso PORTUGAL Web: www.hmi.pt Tel. +351 252 809 124 Fax. +351 252 859 298 Email: hmi@hmi.pt

Contact us ABB Ltd. Process Automation Howard Road St. Neots Cambridgeshire PE19 8EU UK Tel: +44 (0)1480 475321 Fax: +44 (0)1480 217948 ABB Inc. Process Automation 125 E. County Line Road Warminster PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 Note We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts is forbidden without prior written consent of ABB. Copyright 2013 ABB All rights reserved 02.2013 ABB Automation Products GmbH Process Automation Schillerstr. 72 32425 inden Germany Tel: +49 551 905 534 Fax: +49 551 905 555 Sales Service ABB S.p.A. Process Automation Via Statale 113 22016 Lenno (CO) Italy Tel: +39 0344 58111 Fax: +39 0344 56278 www.abb.com