Effects of Harmonic Distortion I

Similar documents
BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP

Harmonic Distortion Evaluations

Voltage and Current Waveforms Enhancement using Harmonic Filters

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

HARMONICS CAUSES AND EFFECTS

Generator Advanced Concepts

Impact Assessment Generator Form

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Harmonic control devices

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Analysis of Harmonic Distortion in Non-linear Loads

Power Quality Analysis in Power System with Non Linear Load

Power Factor. Power Factor Correction.

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Low Pass Harmonic Filters

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants

Embedded Generation Connection Application Form

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

Thyristorised Automatic Power Factor

Embedded Generation Connection Application Form

CHAPTER 4. Distribution Transformers

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

Comparative study of the derating of distribution transformers

Emicon Engineering Consultants L.L.C.

Fluke 40/41 Power Harmonics Analysers

Harmonic Requirements

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

SYNCHRONOUS MACHINES

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Applying Low Voltage Harmonic Filters, Revisited By: Brian Prokuda, P.E. Keweenaw Power Systems, Howell, MI

Preface...x Chapter 1 Electrical Fundamentals

148 Electric Machines

Combined analytical and FEM method for prediction of synchronous generator no-load voltage waveform

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

POWER FACTOR CORRECTION AND ITS PITFALLS

Alternators Reactance for Nonlinear Loads

Code No: R Set No. 1

22.0 Harmonics in Industrial Power Systems

New Methods to Mitigate Distribution System Harmonics

6L]LQJ$8366\VWHP )RU1RQ/LQHDU/RDGV

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

Transformer Factory Testing

Harmonic Filters and Reactors

Loss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM

CHAPTER 4 HARMONICS AND POWER FACTOR

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

General Description & Features Selection Charts Definition of Terms... 42

NJWA - Harmonics and Drives Proper System Design

Inductance, capacitance and resistance

Harmonic Filters for Single Phase Equipment

3.1.Introduction. Synchronous Machines

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Do Capacitor Switching Transients Still Cause Problems?

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

MAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION

Presents. Harmonics Years

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

Conventional Paper-II-2013

Generator Protection GENERATOR CONTROL AND PROTECTION

GOVERNMENT COLLEGE OF ENGINEERING, BARGUR

Literature Review for Shunt Active Power Filters

Alternating Current Page 1 30

AGN 034 Alternator Reactance

Code No: R Set No. 1

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Conventional Paper-II-2011 Part-1A

1C.4.1 Harmonic Distortion

IOCL Electrical Engineering Technical Paper

p. 1 p. 6 p. 22 p. 46 p. 58

Effective Harmonic Mitigation with Active Filters

PowerMonitor 5000 Family Advanced Metering Functionality

Embedded Generation Connection Application Form

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Spring 2000 EE361: MIDTERM EXAM 1

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

GMD Impacts on Generators

Tech Byte 16: The Truths About Transformers Part 2

Sizing Generators for Leading Power Factor

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Load Isolation Transformers

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Harmonic control devices. ECE 528 Understanding Power Quality

Economical Solutions to Meet Harmonic Distortion Limits[4]

Failure of Transformers Due to Harmonic Loads

Pump ED 101. Two Steps To Increased Pump Life (Part Two) Voltage Unbalance

1249. Development of large salient-pole synchronous machines by using fractional-slot concentrated windings

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

A Guide to Power Quality Testing

Motor-CAD Brushless PM motor Combined electromagnetic and thermal model (February 2015)

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad

ZENER ELECTRIC PTY LTD

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

A Practical Guide to Free Energy Devices

Harmonic Distortion Effects and Mitigation in Distribution Systems

Transcription:

Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment, most notably capacitors, transformers, and motors, causing additional losses, overheating, and overloading. These harmonic currents can also cause interference with telecommunication lines and errors in power metering. 4.8.1 Impact on Capacitors A capacitor bank experiences high voltage distortion during resonance. The current flowing in the capacitor bank is also significantly large and rich in a monotonic harmonic. Figure 4.29 shows a current waveform of a capacitor bank in resonance with the system at the 11th harmonic. The harmonic current shows up distinctly, resulting in a waveform that is essentially the 11th harmonic riding on top of the fundamental frequency. This current waveform

typically indicates that the system is in resonance and a capacitor bank is involved. In such a resonance condition, the rms current is typically higher than the capacitor rms current rating. IEEE Standard for Shunt Power Capacitors (IEEE Standard 18-1992) specifies the following continuous capacitor ratings: 135 percent of nameplate kvar 110 percent of rated rms voltage (including harmonics but excluding transients) 180 percent of rated rms current (including fundamental and harmonic current) 120 percent of peak voltage (including harmonics) Figure 4.29 Typical capacitor current from a system in 11th-harmonic resonance. 4.8.2 Impact on Transformers Transformers are designed to deliver the required power to the connected loads with minimum losses at fundamental frequency. Harmonic distortion of the current, in particular, as well as of the voltage will contribute significantly to additional heating. To design a transformer to accommodate higher frequencies, designers make different design choices such as using continuously transposed cable instead of solid conductor and putting in more cooling ducts. As a general rule, a transformer in which the current distortion exceeds 5 percent is a candidate for derating for harmonics.

There are three effects that result in increased transformer heating when the load current includes harmonic components: RMS Current If the transformer is sized only for the kva requirements of the load, harmonic currents may result in the transformer rms current being higher than its capacity. The increased total rms current results in increased conductor losses. Eddy Current Losses These are induced currents in a transformer caused by the magnetic fluxes. These induced currents flow in the windings, in the core, and in other conducting bodies subjected to the magnetic field of the transformer and cause additional heating. This component of the transformer losses increases with the square of the frequency of the current causing the eddy currents. Therefore, this becomes a very important component of transformer losses for harmonic heating. Core losses The increase in core losses in the presence of harmonics will be dependent on the effect of the harmonics on the applied voltage and the design of the transformer core. Increasing the voltage distortion may increase the eddy currents in the core laminations. The net impact that this will have depends on the thickness of the core laminations and the quality of the core steel. Guidelines for transformer derating are detailed in ANSI/IEEE Standard C57.110-1998, Recommended Practice for Establishing Transformer Capability When Supplying Nonsinusoidal Load Currents. The common K factor used in the power quality field for transformer derating is also included in Table 4.1. The analysis represented in Table 4.1 can be summarized as follows. loss PEC: The load loss PLL can be considered to have two components: I2R loss and eddy current P LL I R P EC W ------------------ (4.18)

The I 2 R loss is directly proportional to the rms value of the current. However, the eddy current is proportional to the square of the current and frequency, which is defined by P EC K EC I 2 h 2 -------------------- (4.19) Where K EC is the proportionality constant. The per-unit full-load loss under harmonic current conditions is given by P LL I h I h h EC R --------------------- (4.20) 2 2 2 Where P EC _ R is the eddy current loss factor under rated conditions. The K factor commonly found in power quality literature concerning transformer derating can be defined solely in terms of the harmonic currents as follows: Type MVA Voltage P EC-R, % --- 3-8 Dry 1.5 5 kv HV 12-20 1.5 15 kv HV 9-15 2.5 480V LV 1 Oil- 2.5-5 480V LV 1-5 filled >5 480V LV 9-15 TABLE 4.1 Typical Values of PEC _ R I 2 h 2 K I 2 ------------------- (4.21) Then, in terms of the K factor, the rms of the distorted current is derived to be

I 2 1 P EC R ( pu) ----------------- (4.22) 1 K P EC R Where PEC _ R = eddy current loss factor h =harmonic number I h =harmonic current Thus, the transformer derating can be estimated by knowing the per unit eddy current loss factor. This factor can be determined by 1. Obtaining the factor from the transformer designer 2. Using transformer test data and the procedure in ANSI/IEEE Standard C57.110 3. Typical values based on transformer type and size 4.8.3 Impact on Motors Motors can be significantly impacted by the harmonic voltage distortion. Harmonic voltage distortion at the motor terminals is translated into harmonic fluxes within the motor. Harmonic fluxes do not contribute significantly to motor torque, but rotate at a frequency different than the rotor synchronous frequency, basically inducing high-frequency currents in the rotor. The effect on motors is similar to that of negative-sequence currents at fundamental frequency: The additional fluxes do little more than induce additional losses. Decreased efficiency along with heating, vibration, and high-pitched noises are indicators of harmonic voltage distortion. At harmonic frequencies, motors can usually be represented by the blocked rotor reactance connected across the line. The lower-order harmonic voltage components, for which the magnitudes are larger and the apparent motor impedance lower, are usually the most important for motors.

There is usually no need to derate motors if the voltage distortion remains within IEEE Standard 519-1992 limits of 5 percent THD and 3 percent for any individual harmonic. Excessive heating problems begin when the voltage distortion reaches 8 to 10 percent and higher. Such distortion should be corrected for long motor life. Motors appear to be in parallel with the power system impedance with respect to the harmonic current flow and generally shift the system resonance higher by causing the net inductance to decrease. Source : http://nprcet.org/e%20content/misc/e-learning/eee/iv%20year/ee1005%20- %20POWER%20QUALITY.pdf