A multi-loop controller for LCL-filtered grid-connected converters integrated with a hybrid harmonic compensation and a novel virtual impedance

Similar documents
University of Kurdistan. Adaptive virtual impedance scheme for selective compensation of voltage unbalance and harmonics in microgrids

Published in: Proceedings of the 39th Annual Conference of IEEE Industrial Electronics Society, IECON 2013

Indirect Current Control of LCL Based Shunt Active Power Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

PASSIVE DAMPING FILTER DESIGN AND APPLICATION FOR THREE-PHASE PV GRID-CONNECTED INVERTER

FFT Analysis of THD in Distribution System with Grid Connected RES

Published in: Proceedings of the 27th Annual IEEE Applied Power Electronics Conference and Exposition

Published in: Proceedings of the 37th Annual Conference of IEEE Industrial Electronics Society, IECON 2011

Resonant Current Control Of Three Phase Grid Connected Photovoltaic Inverters

Aalborg Universitet. Published in: I E E E Transactions on Smart Grid. DOI (link to publication from Publisher): /TSG.2015.

Robust current control design of a three phase voltage source converter

A Single-Stage Active Damped LCL-Filter-Based Grid-Connected Photovoltaic Inverter With Maximum Power Point Tracking

/$ IEEE

RECENTLY, the harmonics current in a power grid can

ISSN Vol.04,Issue.07, June-2016, Pages:

Multiple PR Current Regulator based Dead-time Effects Compensation for Grid-forming Single-Phase Inverter

Design of LCL-LCL Harmonic Filter for Grid Connected Photo Voltaic Cell Array

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

Flexible Voltage Control Scheme for Distributed Generation Systems under Grid Fault

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

UTILITY interactive inverters converting dc power sources

Phase Shift Modulation of a Single Dc Source Cascaded H-Bridge Multilevel Inverter for Capacitor Voltage Regulation with Equal Power Distribution

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Voltage Support and Reactive Power Control in Micro-grid using DG

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

A Dynamic Consensus Algorithm based Low-Voltage Ride-Through Operation of Power Converters in Grid-Interactive Microgrids

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

Design and Analysis of Stationary Frame PR Current Controller for Performance Improvement of Grid Tied PV Inverters

A Novel Control Method to Minimize Distortion in AC Inverters. Dennis Gyma

GRID CONNECTED HYBRID SYSTEM WITH SEPIC CONVERTER AND INVERTER FOR POWER QUALITY COMPENSATION

An Implementation of Grid Interactive Inverter with Reactive Power Support Capability for Renewable Energy Sources

Optimal LQR-based Multi-loop Linear Control Strategy for UPS Inverter Applications using Resonant Controller

Literature Review for Shunt Active Power Filters

Putting a damper on resonance

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Damping and Harmonic Control of DG Interfacing. Power Converters

An Accurate Power Sharing Method for Control of a Multi-DG Microgrid

ISSN Vol.07,Issue.11, August-2015, Pages:

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Harmonic Stability in Renewable Energy Systems: An Overview

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Published in: 28th Annual IEEE Applied Power Electronics Conference and Exposition, APEC 2013

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

LOW ORDER HARMONICS IMPROVEMENT OF A SINGLE GRID CONNECTED INVERTER SYSTEM UNDER PR CONTROL TECHNIQUE

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer

Performance Comparison of Sensor and Sensorless Active Damping LCL Filter for Grid Connected of Wind Turbine

Power Quality Improvement by DVR

Active damping of output LC filter resonance for vector controlled VSI- fed AC motor drive

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

Analysis of a Passive Filter with Improved Power Quality for PV Applications

Control of Active and Reactive Power Ripple to Mitigate Unbalanced Grid Voltages

Comparative Analysis of Control Strategies for Modular Multilevel Converters

Current Control for a Single-Phase Grid-Connected Inverter Considering Grid Impedance. Jiao Jiao

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

A Modified Direct Power Control Strategy Allowing the Connection of Three-Phase Inverter to the Grid through LCL Filters

Control of Grid- Interfacing Inverters with Integrated Voltage Unbalance Correction

Interactive Distributed Generation Interface for Flexible Micro-Grid Operation in Smart Distribution Systems

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

A Hierarchical Control Scheme for Compensating Voltage Distortions in an Inverter Based Microgrid

Design of a Hybrid Active Filter for Harmonics Suppression in Industrial Facilities

SPACE VECTOR PULSE WIDTH MODULATION SCHEME FOR INTERFACING POWER TO THE GRID THROUGH RENEWABLE ENERGY SOURCES

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

On-Line Dead-Time Compensation Method Based on Time Delay Control

A New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid

Cross-Circulating Current Suppression Method for Parallel Three-Phase Two-Level Inverters

ANALYSIS OF ACTIVE POWER FILTER FOR HARMONIC VOLTAGE RESONANCE SUPPRESSION IN DISTRIBUTION SYSTEM

HYBRID ACTIVE FILTER WITH VARIABLE CONDUCTANCE FOR HARMONIC RESONANCE SUPPRESSION USING ANN

A controller design method for 3 phase 4 wire grid connected VSI with LCL filter

A Hierarchical Control Approach for Voltage Unbalance Compensation in A Droop Controlled Micro-Grid

Current Control Strategy for Parallel Operation of Inverters Based On Micro grids M.Bavithra 1, Belwin J. Brearley 2

A Hybrid Cascaded Multilevel Inverter for Interfacing with Renewable Energy Resources

Aalborg Universitet. Suppression of synchronous resonance for VSGs Yang, Dongsheng; Wu, Heng; Wang, Xiongfei; Blaabjerg, Frede

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

ISSN Vol.03,Issue.22 September-2014, Pages:

Research and design of PFC control based on DSP

A MPPT ALGORITHM BASED PV SYSTEM CONNECTED TO SINGLE PHASE VOLTAGE CONTROLLED GRID

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

A Nested Control Strategy for Single Phase Power Inverter Integrating Renewable Energy Systems in a Microgrid

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Buck-Boost Converter based Voltage Source Inverter using Space Vector Pulse Width Amplitude modulation Jeetesh Gupta 1 K.P.Singh 2

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

A Three-Phase AC-AC Buck-Boost Converter using Impedance Network

A Current-Source Active Power Filter with a New DC Filter Structure

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

642 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 2, FEBRUARY 2014

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Design of a Power Flow Control Method for Hybrid Active Front-End Converters

Investigation of Sst Pwm in qzsi

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Transcription:

A multi-loop controller for LCL-filtered grid-connected converters integrated with a hybrid harmonic compensation and a novel virtual impedance Yonghwan Cho, Maziar Mobarrez, Subhashish Bhattacharya Department of Electrical and Computer Engineering North Carolina State University Raleigh, North Carolina, USA Abstract The LCL-filtered converter is widely adapted to interface renewable energy sources and energy storage devices to the grid. While the LCL filter is capable of eliminating current harmonics caused by the high-frequency PWM of the converter, low-order current harmonics are reduced selectively by the stationary-frame resonant harmonic compensators (HCs). There are two types of the harmonic compensator, namely, harmonic current compensator (HCC) and harmonic voltage compensator (HVC). HCCs are in general embedded in parallel with conventional grid current controllers by which the active and reactive power are regulated. If autonomous islanding operation is required, the active and reactive power are controlled by a V-f droop method and a filter capacitor voltage controller with which HCCs or HVCs are added in parallel. In this paper, a multi-loop controller is proposed as one possible alternative to the conventional grid current controller to improve the harmonic compensation performance by using both HCCs and HVCs, which is a hybrid harmonic compensation (HHC). In addition, a novel virtual impedance implementation technique which fits to the multi-loop frame is presented to maintain stability of the controller in case of large grid impedance. Index Terms LCL filter, multi-loop control, hybrid harmonic compensation, virtual impedance. I. INTRODUCTION With the increasing penetration of power-electronics-based power conversion such as uninterruptible power supplies (UPSs), distributed generation (DG) systems, etc., the LCLfiltered voltage-source converter (VSC) has drawn much attention due to its better attenuation of switching frequency current harmonics compared to L-filtered VSC [1]-[3]. However, the low-order current harmonics should be removed by using either HCCs or HVCs in order to prevent the grid from being polluted. It is typical to use HCCs when the LCL-filtered VSC controls the grid current to regulate both DC-link voltage and power factor [5], [6], [8]. When the autonomous islanding operation is required and the DC-link voltage is regulated by energy storage devices, the HVCs are used with the filter capacitor voltage controller [6] or the HCCs can be used as proposed in [11]. A major challenge of the harmonic compensation is to add enough number of HCs to meet total harmonic distortion (THD) standards and guarantee stability of the converter at the same time. The maximum frequency of the HC is limited since the phase margin of the harmonic compensation loop decreases as its harmonic frequency increases. Moreover, the stability is worse if the grid impedance is large due to long cable or transformer [4], [8]. To overcome the instability issue, phase compensation methods are presented in [7], [8]. In those methods, conventional resonant HC is modified to have trigonometric terms to compensate the phase of it. In this paper, a multi-loop controller is presented as a possible replacement for the conventional grid current controller to have enough phase margin at high harmonic frequencies without using trigonometric terms and to achieve sufficient harmonics attenuation by implementing both HCCs and HVCs, namely, a hybrid harmonic compensation (HHC). Conventional multiloop controller has an inner-loop of filter capacitor current or converter-side inductor current to improve dynamic performance and achieve active damping [2], [3], [6]. However, the proposed multi-loop controller has an inner-loop of filter capacitor voltage to provide not only the HHC but also a straightforward criteria of setting the controller gain of the outer-loop. It should be noted that active damping is also feasible with the proposed multi-loop frame by using a feed forward method presented in [2]. To improve the stability of the multi-loop controller at its fundamental frequency, a novel virtual impedance method is also proposed in this paper which fits to the multi-loop structure. Although the virtual impedance method is needed mainly for stabilizing LC-filtered VSC [2], [9], [10], the LCLfiltered VSC also faces the instability especially when the grid-side inductance of the LCL filter is small compared to the grid inductance. To implement differentiation of the grid current without high-frequency noise amplification, a highpass filter is used in [9] and a proportional gain is ignored in [2] which both degrade accuracy of the fundamental frequency controller. The new method implements only imaginary value of the differentiation term at fundamental frequency instead of

Fig. 1. * L grid R grid Z v v grid L g R g Circuit diagram of the LCL-filtered grid-connected VSC. G ch G c Z v * vcf Inner-loop v c v c C f R d f h G v G vh L i R i G pcc * v i v G i d G i v i v c CDC v DC Rload G LR Fig. 2. Block diagram of the proposed multi-loop controller integrated with the HHC and the virtual impedance method. the whole differentiation to avoid the noise amplification and the inaccuracy. It is based on the implementation method of imaginary value presented initially to extract positive sequence of the grid voltage [12] and the multi-loop structure proposed in this paper. Experiment results are presented to validate the proposed hybrid harmonic compensation scheme and virtual impedance method. II. PROPOSED MULTI-LOOP CONTROLLER AND HYBRID HARMONIC COMPENSATION Fig. 1 shows a single-phase LCL-filtered VSC connected to a point of common coupling (PCC). A damping resistor and the virtual impedance is connected in series with the filter capacitor and the grid-side inductor of the LCL filter, respectively. L grid and R grid represent the grid impedance. The proposed multi-loop structure is shown in Fig. 2, where the HHC and the virtual impedance method are integrated. In the inner-loop, the fundamental and harmonic capacitor voltages are controlled by non-ideal P+Resonant (PR) controllers G v = K pv + G vh = h 2K iv ω cv s s 2 +2ω cv s+ω f 2 (1) 2K ivh ω cvh s s 2 +2ω cvh s+ω h 2 (2) G pcc denote v c /v i and v c /, respectively. They can be mathematically expressed as follows: G i (s)= v c v i = Y i(s) E i (s) (3) Y i (s)=l g C f R d s 2 +(L g +R g R d C f )s+r g (4) E i (s)=l g L i C f s 3 + C f (L g (R i +R d )+L i (R g +R d ))s 2 +(L i +L g +C f (R i R g +R i R d +R g R d ))s + R g +R i. (5) G pcc (s)= v c = Y pcc(s) E pcc (s) Y pcc (s)=l i C f R d s 2 +(L i +R i R d C f )s+r i (7) E pcc (s)=l g L i C f s 3 + C f (L g (R i +R d )+L i (R g +R d ))s 2 +(L i +L g +C f (R i R g +R i R d +R g R d ))s (6) + R g +R i. (8) The proportional and integral gain at fundamental frequency can be designed by analyzing the Bode diagram of the open-loop transfer function, G v G d G i. It should have enough phase and gain margin for stability and large magnitude at fundamental frequency to both guarantee the accuracy of the controller and reject the disturbance term, G pcc. In the outer-loop, the fundamental and harmonic grid currents are controlled by G c and G ch which have same form as (1) and (2). Since the inner-loop is controlling the capacitor voltage, the outer-loop plant, G c, is simply grid admittance as described in (9). Therefore, the proportional and integral gain of the fundamental grid current controller can be set as (10) and (11), which is a widely used gain setting criteria for L- filtered VSCs or motor drive inverters [13]. In (10) and (11), ω cc denotes the bandwidth of the current controller. It should be imposed five ten times smaller than the bandwidth of the inner-loop in order to prevent undesired coupling effect. G c = 1 L g s+r g (9) K pc = L g ω cc (10) where ω f and ω h are the system fundamental and harmonic angular frequency, ω cv and ω cvh are cutoff bandwidth at fundamental and each harmonic frequency, K iv and K ivh are the integral gain at fundamental and each harmonic frequency, and K pv is the proportional gain at all frequencies. G d denotes PWM delay which is approximately one and a half of the sampling period since the delay is not compensated. G i and K ic = R g ω cc (11) The HHC is implemented by using both HCCs and HVCs in the outer-loop and inner-loop, respectively. Unlike HCCs, HVCs need a voltage reference, h, which is a sum of harmonic frequency components of the PCC voltage. By synthesizing the harmonics of the PCC voltage at the filter

capacitor, the harmonic frequency component of the voltage difference across the grid-side inductor of the LCL filter is removed and thus, only fundamental current flows. It should be noted that no filter is needed to extract the PCC voltage harmonics. Since the fundamental frequency component of the PCC voltage, f, is also needed as a feed forward in the outer-loop to improve dynamic performance of the current controller, the PCC voltage measured by a voltage sensor can be used directly to replace the two adding terms, f and h. The HVCs of the inner-loop are embedded mainly for attenuating high-frequency harmonic currents without any instability issue. The stability of the HCCs of a conventional single-loop controller shown in [1], [2] and that of the HVCs of the proposed multi-loop controller are compared in Fig. 3. The bode diagram of the open-loop transfer function of each case is depicted in Fig. 3(a) and Fig. 3(b), respectively. It is shown that the phase margin decreases as the harmonics frequency increases. In Fig. 3(a), the phase margin is almost zero at 11th harmonics and negative at 13th harmonics. It means that adding 11th or 13th HCCs in the single-loop controller causes instability issue and thus, harmonic currents at those frequencies cannot be suppressed. On the other hand, in Fig. 3(b), the phase margin is larger than 45 degree at both 11th and 13th harmonics. It can be seen that HVCs are better than HCCs in terms of the stability and can handle highfrequency harmonics. In the proposed HHC scheme, HVCs at all harmonic frequencies of interest are used and HCCs at whatever frequencies the system can maintain stability are also added to further attenuate the harmonic currents. It should be noted that the HHC can also be applied to the LCLfiltered VSC whose power is controlled by the V-f droop method and the filter capacitor voltage controller to achieve the autonomous islanding operation. In this application, the harmonic frequency component of the PCC voltage, h, should be extracted by a digital filter since the feed forward of the fundamental frequency component of the PCC voltage, f, becomes a considerable disturbance of the droop method. (a) (b) Fig. 3. (a) Bode diagram of the open-loop transfer function of the HCCs in the conventional single-loop controller. (b) Bode diagram of the open-loop transfer function of the HVCs in the proposed multi-loop controller. III. VIRTUAL IMPEDANCE METHOD The proposed virtual impedance implementation scheme is described in Fig. 4. It should be noted that the virtual impedance at only fundamental frequency is investigated in this paper. Instead of implementing the differentiation of the grid current to get the voltage drop across the virtual impedance, imaginary part of the voltage drop at fundamental frequency is calculated using the band-pass filter and the allpass filter Fig. 4. Band-pass Filter All-pass Filter -j f L v R v Block diagram of the proposed virtual impedance method. Z v H BPF = 2ζω f s s 2 +2ζω f s+ω f 2 (12) H APF = s ω f s+ω f (13) whereζ andω f denote damping ratio and fundamental angular frequency, respectively. When the grid current of fundamental frequency is filtered by the all-pass filter, it represents the pure imaginary value as shown in Fig. 4. Thus, the voltage drop

TABLE I: Parameters of the VSC (See Fig. 1) Parameter Value Grid Voltage (rms) 120 V Grid Frequency 60 Hz Sampling Frequency 15kHz V DC 200V L g,r g 1.0mH, 0.2Ω L i,r i 1.0mH, 0.2Ω C f,r d 10 µh, 10Ω C DC 2400 µf R load 44.0Ω L grid,r grid 5.0mH, 0.2Ω L v,r v 2.0mH, 0.0Ω (a) Fig. 5. Instability phenomenon of the 13th harmonic compensator of the conventional single-loop current controller. across the virtual inductance is generated by multiplying the reactance of the virtual impedance to the output of the allpass filter. The band-pass filter is used to get pure fundamental component of the grid current. The virtual resistance can also be implemented in the straightforward manner shown in Fig. 4. Finally, the voltage drop across the virtual impedance is subtracted from the output of the grid current controller to modify the reference of the capacitor voltage. In addition to the feed forward of the voltage drop of the virtual impedance, the proportional and integral gains of the grid current controller and the capacitor voltage controller should be updated. The L g and R g of (4), (5), (8), (10), and (11) need to be replaced by L g + L v and R g + R v. The gains of the current controller can be updated directly by the replacement. The capacitor voltage controller can be redesigned with the updated G i and G pcc. IV. EXPERIMENTAL RESULTS The performance of the HHC and the virtual impedance method are verified experimentally with a 1kW single-phase VSC shown in Fig. 1. The controllers of the VSC is developed on TMS320F28335 DSP. The power spectrum analyzer, YOKOGAWA WT3000, is used to analyze the current harmonics. The detailed parameters of the VSC are listed in Table I. The L grid and R grid denote an inductor for changing the grid impedance. The grid inductor was not connected for the experiments of the harmonic compensation to show the attenuation performance with lower inductance. It is used for verifying the virtual impedance method. (b) (c) Fig. 6. (a) THD analysis of the PCC voltage. (b) Grid current waveform and THD analysis for the HVC in the multi-loop controller. (c) Grid current waveform and THD analysis for the HCC+HVC in the multi-loop controller. In the following experiments, the magnitude of the grid current reference is generated by a DC-link voltage controller and the phase of it is synchronized to the PCC voltage for

Fig. 7. THD of the HCC and the HHC according to different output power of the converter. (a) unity power factor operation. The instability phenomenon of the conventional HCCs of the single-loop controller is shown in Fig. 5. At0.05s, the 13th HCC is turned-on which results in undesired amplification of the 13th harmonics due to its not enough phase margin. This coincides with the analysis in Fig. 3(a). On the contrary, the HVCs of the proposed multi-loop controller can be embedded up to 23rd harmonics. However, adding a HVC at a certain harmonic frequency affects also harmonics at nearby frequencies and can even amplify them. Moreover, admissible harmonic currents limited by IEEE Std 519-1992 decreases as harmonic frequency increases. Thus, to prevent the harmonic currents near 23rd frequency from being amplified, HVCs up to 17th harmonics are selected. In Fig. 6(b), the grid current is shown and its harmonics are analyzed when only HVCs are used in the multi-loop controller. Although the result is better than the case shown in Fig. 5, the 3rd and 5th harmonics are not attenuated enough. Therefore, the 3rd and 5th HCCs are added for further suppression, which is called the hybrid harmonic compensation (HHC) in this paper. In Fig. 6(c), it is shown that all harmonic components are attenuated more than 40dB. Although not applied in this paper, note that the time delay compensation in [14] can increase the stability of the HCs and allow harmonics reduction at even higher frequencies. The improved resonant controllers in [8] can also be used selectively with the proposed HHC. It is shown in this paper that the proposed HHC has better stability and attenuation capability than using only HCCs or only HVCs. The multiloop controller is also provided as a structure in which the HHC can be embedded. In Fig. 7, the THD of the HCC and the HHC is compared at different output power of the converter. The HCC is implemented with the conventional single-loop controller and (b) (c)

V. CONCLUSION A multi-loop controller for LCL-filtered grid-connected VSCs is proposed in this paper which is integrated with a hybrid harmonic compensation scheme and a novel virtual impedance method. The design criteria of the proportional and integral gains of the multi-loop controller is provided. The HVCs of the multi-loop controller are proved to have better stability than the HCCs of the conventional single-loop controller both by simulations and experiments. Moreover, it is verified that using both the HCCs and HVCs in the multi-loop controller maximizes the attenuation performance. The effectiveness of the virtual impedance method to the fundamental grid current controller is shown by analyzing step responses. The virtual impedance method will be investigated more to see if it is effective also at harmonic frequencies and will be discussed in the future work. (d) Fig. 8. The step responses of the DC-link voltage and the grid current. (a) Without Z grid. (b) With Z grid. (c) With Z grid and only the feed forward of the virtual impedance method. (d) With Z grid and the whole virtual impedance method. the HHC with the proposed multi-loop controller. The integral gain of the HCs of the HCC and the HHC are not changed according to the operating points. Overall, the THD of the HCC is higher than that of the HHC since the HCs of the HCC are used only up to 11th harmonics while the HCs of the HHC are used up to 17th harmonics. It should be noted that the THD variation of the HHC according to the load is smaller than that of the HCC. The HHC is more robust to the variation of the operating point of the converter. The proposed virtual impedance method for the stability of the fundamental grid current is verified by analyzing step responses of the DC-link voltage and the grid current as shown in Fig. 8. At 0.2s, the reference of the DC-link voltage is changed from 200V to 250V. In Fig. 8(a), the step responses are shown when the grid inductor, Z grid, is not connected. There is oscillation that lasts for roughly 0.4s. The oscillation is worse if the grid inductor is inserted in the circuit as shown in Fig. 8(b). The effectiveness of the virtual impedance method are shown in Fig. 8(c) and Fig. 8(d). The virtual resistance is set to zero to focus on the virtual inductance which is the main challenge as mentioned in the previous section. Firstly, to validate the feed forward of the voltage drop across the virtual inductance, the proportional gain of the grid current controller is not updated and results are shown in Fig. 8(c). It can be seen that the oscillation is reduced compared to the one in Fig. 8(b). Finally, in Fig. 8(d), results are depicted when the proportional gain is updated also. The oscillation is now almost removed and the DC-link voltage settles to 250V in about 0.1s. REFERENCES [1] M. S. Munir, J. He, and Y. Li, Comparative Analysis of Closed-Loop Current Control of Grid Connected Converter with LCL Filter, in Electric Machines & Drives Conference (IEMDC), 2011 IEEE International, 15-18 May 2011, pp. 1641-1646. [2] J. He and Y.W. Li, Generalized closed-loop control schemes with embedded virtual impedances for voltage source converters with LC or LCL filters, IEEE Trans. Power Electron., vol. 27, no. 4, pp. 1850-1861, Apr. 2012. [3] P. C. Loh and D. G. Holmes, Analysis of multiloop control strategies for LC/CL/LCL-filtered voltage-source and current-source inverters, IEEE Trans. Ind. Appl., vol. 41, no. 2, pp. 644-654, Mar./Apr. 2005. [4] M. Castilla, J. Miret, and J. Matas, Control design guidesline for single-phase grid-connected photovoltaic inverters with damped resonant harmonic compensators, IEEE Trans. Ind. Electron., vol.56, no. 11, pp. 4492-4501, Nov. 2009. [5] R. Teodorescu, F. Blaabjerg, M. Liserre, and P. C. Loh, Proportionalresonant controllers and filters for grid-connected voltage-source converters, in Proc. Inst. Elect. Eng. - Elect. Power Appl., vol. 153, no. 5, pp. 750-762, Sep. 2006. [6] J. He, Y. Li, and M. S. Munir, A flexible harmonic control approach through voltage-controlled DG-grid interfacing converters, IEEE Trans. Ind. Electron., vol. 59, no. 1, pp. 444-455, Jan. 2012. [7] A. G. Yepes, F. Freijedo, O. Lopez, and J. Gandoy, High-performance digital resonant controllers implemented with two integrators, IEEE Trans. Power Electron., vol. 26, no. 2, pp. 563-576, Feb. 2011. [8] Q. Qian, J. Xu, S. Xie, and L. Ji, Analysis and improvement of harmonic quasi resonant control for LCL-filtered grid-connected inverters in weak grid, in Proc. IEEE Appl. Power Electron. Conf. and Expo., 20-24 March. 2016, pp. 3446-3452. [9] J. M. Guerrero, L. G. Vicuna, J. Matas, M. Castilla, and J. Miret, A wireless controller to enhance dynamic performance of parallel inverters in distributed generation systems, IEEE Trans. Power Electron., vol. 19, pp. 1205-1213, Sep. 2004. [10] Y. W. Li and C. N. Kao, An accurate power control strategy for powerelectronics-interfaced distributed generation units operating in a lowvoltage multibus microgrid, IEEE Trans. Power Electron., vol. 24, no. 12, pp. 2977-2988, Dec. 2009. [11] J. He and Y. W. Li, Hybrid voltage and current control approach for DG-grid interfacing converters with LCL filters, IEEE Trans. Ind. Electron., vol. 60, no. 5, pp. 1797-1809, May 2013. [12] S.-J. Lee, J.-K. Kang, and S.-K. Sul, A new phase detecting method for power conversion systems considering distorted conditions in power system, in Conf. Rec. 34th IEEE IAS Annu. Meeting, Oct. 3-7, 1999, pp. 2167-2172. [13] H. J. Lee, S. Jung, and S. K. Sul, A current controller design for current source inverter-fed AC machine drive system, IEEE Trans. Power Electron., vol. 28, no. 3, pp.1366-1381, Mar. 2013. [14] H. Deng, R. Oruganti, and D. Srinivasan, PWM methods to handle time delay in digital control of a UPS inverter, IEEE Power Electron. Lett., vol. 3, no. 1, pp. 1-6, Mar. 2005.