ANALYSIS OF UNIFIED POWER QUALITY CONDITIONER DURING VOLTAGE SAG AND SWELL CONDITIONS

Similar documents
UPQC (Unified Power Quality Conditioner)

Nagpur, INDIA Nagpur, INDIA

2020 P a g e. Figure.2: Line diagram of series active power filter.

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Power Quality improvement of a three phase four wire system using UPQC

Downloaded from

Power Quality Improvement by Simultaneous Controlling of Active and Reactive Powers in UPQC-S

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

P.CHAITHANYAKUMAR, T.VARAPRASAD/

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Power Quality Improvement in Fourteen Bus System using UPQC

Enhancement of Power Quality based on Unified Power Quality Conditioner (UPQC) K.S.Srikanth, Shaik. Musthak Ahmed, Y.Srinivasa Rao

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Application of Fuzzy Logic Controller in Shunt Active Power Filter

ISSN Vol.04,Issue.08, July-2016, Pages:

Enhancement of Power Quality Using Advanced Series Active Power Filters

LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER OF UPQC

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Power angle control of UPQC to compensate load reactive power and voltage sag /swells

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Unified Power Quality Conditioner (UPQC) in Alleviation of Power Quality Issues

MODELING AND SIMULATION OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

International Journal of Advancements in Research & Technology, Volume 3, Issue 1, January-2014 ISSN

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Quality Improvement And Mitigation Of Voltage Sag And Current Swell Using Distributed Power Flow Controller

Power Control Scheme of D-Statcom

Mitigation of Harmonics in Distribution System Using SAPF

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

A Power Control Scheme for UPQC for Power Quality Improvement

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Simulation Study of PWM Techniques for Voltage Source Converters

Power Quality Improvement using Shunt Passive Filter

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Interline Power Quality Conditioner for Power Quality Improvement

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Power Quality enhancement of a distribution line with DSTATCOM

UPQC for Improvement Power Quality.

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

Design of Unified Power Quality Conditioner (UPQC) for Power Quality Improvement in Distribution System

Power Quality Improvement in Distribution System Using D-STATCOM

Control Strategy for a cross phase connected and a conventional UPQC

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Power Control and Quality Management in DG Grid Interfaced Systems

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Power Quality Improvement By Using DSTATCOM Controller

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

A Review on Power Quality Improvement in Distribution System using UPQC

Mitigating Voltage Sag Using Dynamic Voltage Restorer

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Literature Review for Shunt Active Power Filters

Mitigation of Voltage Sag and Swell Using Distributed Power Flow Controller

Improvement of Power Quality Using a Hybrid Interline UPQC

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

A Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Power Quality Improvement using Active shunt Power filter using PI Controller

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

UPQC-S: A Novel Concept of Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Utilizing Series Inverter of UPQC

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Implementation of UPQC for Voltage Sag Mitigation

SHUNT ACTIVE POWER FILTER

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Voltage Flicker Compensation using STATCOM to Improve Power Quality

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Synchronous Reference Frame Theory (SRF) along with PI Controller Based Dynamic Voltage Restorer

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Dynamic Modeling and Simulation of Unified Power Quality Conditioner

A Control Scheme for Dual Unified Power Quality Conditioner to Improve Power Quality

Direct and Indirect Control Strategies of DSTATCOM Power Factor Controller

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

SPWM Switching Strategy for Compensation of Unbalanced and Non Linear Load Effects in Three Phase Four Wire System Using D-Statcom

Ripple Reduction Using Seven-Level Shunt Active Power Filter for High-Power Drives

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Modeling and Simulation of STATCOM

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

Transcription:

ANALYSIS OF UNIFIED POWER QUALITY CONDITIONER DURING VOLTAGE SAG AND SWELL CONDITIONS B. Jyothi 1, B. Jyothsna Rani 2, Dr.M.Venu Gopal Rao 3 1 Asst.professor, Dept of EEE, KL University, Andhra Pradesh, INDIA, jyo9290@gmail.com 2 Asst.professor, Dept of EEE, KL University, Andhra Pradesh, INDIA, jyosthsna. jyosthsna3@ gmail.com 3 Professor and HOD of EEE, KL University, Andhra Pradesh, INDIA, venumannam@gmail.com Abstract This paper deals with a three-phase unified power quality er (UPQC), with a combination of shunt active power filter and series active power filter is used to eliminate supply current harmonics, compensate reactive power, voltage sag and voltage swell compensation on distribution network. The performance of the active power filter mainly depends on control strategy used to generate reference current for shunt active power filter (APF) and generate reference voltage for series active power filter. The unified power quality er can work in zero active power consumption mode, active power consumption mode and active power delivering mode. The mathematical analysis is based on active power flow and reactive power flow through the shunt and series active power filter, where in series active power filter can absorb or deliver the active power whereas the reactive power requirement is totally handle by shunt active power filter alone during all s. The effect of load VAR variation and the impact of % sag or swell on the kva ratings of both shunt and series APF are also analyzed. This analysis can be very useful for selection of device ratings for both shunt APF and series APF.Simulation results of these two active power filters are carried out. Index Terms: Power quality, UPQC --------------------------------------------------------------------- *** ------------------------------------------------------------------------ 1. INTRODUCTION The power electronic loads in industry causes an increasing deterioration of the power system voltage and current waveforms. As a result, harmonics are generated from power converters or nonlinear loads. This causes the power system to operate at low power factor, low efficiency, increased losses in transmission and distribution lines, failure of electrical equipments, and interference problem with communication system. So, there is a great need to mitigate these harmonic and reactive current components. Active Power filters are a viable solution to these problems. The continuous usage of non- linear loads injects current and voltage harmonic components into the power system and increases reactive power demands and power system voltage fluctuations. Harmonic current components create several problems like, Increase in power system losses. Over heating and insulator failures in transformers, rotating machinery, Conductor and cables. Reactive power burden, low system efficiency, poor power factor, system unbalance and causes excessive neutral currents.malfunctioning of the protective relays and untimely tripping. The amount of distortion in the voltage or current waveform is quantified by means of an index called the total harmonic distortion (THD) [2]. unified power quality er can absorb active power or inject active power. One of the effective approaches is to use a unified power quality er (UPQC) at PCC to protect the sensitive loads. A UPQC is a combination of shunt and series APFs, sharing a common dc link [5-12]. It is a versatile device that can compensate almost all power quality problems such as voltage harmonics, voltage unbalance, voltage flickers, voltage sags & swells, current harmonics, current unbalance, reactive current, etc. This paper is based on the steady state analysis of UPQC during voltage sag and swells on the system. The main objective of this article is to maintain the load bus voltage sinusoidal and at desired constant level in all operating s. 2. UPQC CONFIGURATION The voltage at point of common coupling may be or may not be distorted depending on the other nonlinear loads connected at point of common coupling. Also, these loads may impose the voltage sag or swell during their switching ON and/or OFF operation. The unified power quality er is installed in order to protect a sensitive load from all disturbances. It consists of two voltage source inverters connected back to back, sharing a common dc link. One Available online @ http://www.ijesat.org 85

inverter is connected parallel with the load. It acts as shunt active power fitter, helps in compensating load harmonic current, reactive current and maintain the dc link voltage at constant level. The second inverter is connected in series with the line using series transformers, acts as a controlled voltage source maintaining the load voltage sinusoidal and at desired constant voltage level. A system configuration for unified power quality er shows in Fig 2.1[1]. Fig.2.2.Configuaration of three-phase Shunt Active Power Filter 3. STEADY STATE POWER FLOW ANALYSIS Steady state operating analysis is done on the basis of fundamental frequency component. The unified power quality er is controlled in such a way that the voltage at load bus is always sinusoidal and at desired magnitude. Therefore the voltage injected by series active power filter must be equal to the difference between the supply voltage and the ideal load voltage. Thus the series active power filter acts as controlled voltage source. The function of shunt active power filter is to maintain the dc link voltage at constant level. In addition to this the shunt active power filter provides the VAR required by the load, such that the input power factor will be unity and only fundamental active power will be supplied by the source[1]. Fig2.1.System Configuration of UPQC 2.1 Configuration Of Three Phase Shunt Active Power Filter The basic configuration of a three-phase three-wire active power filter is shown in Fig 2.2[3]. The diode bridge rectifier is used as an ideal harmonic generator to study the performance of the Active filter. The current-controlled voltage-source inverter (VSI) is shown connected at the load end. This PWM inverter consists of six switches with antiparallel diode across each switch. The voltage which must be supported by one switch is uni-polar and limited by the DC voltage V dc.the peak value of the current which is bidirectional is imposed by the active filter current. Thus the appropriate semiconductor device may be an IGBT or a MOSFET with an anti-parallel diode and must be protected against over current. The capacitor is designed in order to provide DC voltage with acceptable ripples. In order to assure the filter current at any instant, the DC voltage V dc must be equal to 3/2 of the peak value of the line AC mains voltage[3]. Fig3.1: equivalent circuit of UPQC The voltage injected by series active power filter can vary from 0 to 360.. However, in changing the voltage phase angle of series active power filter, the amplitude of voltage injected can increase, thus increasing the required KVA rating of series active power filter. In the following analysis, the load voltage is assumed to be in phase with terminal voltage even during voltage sag and swell. This is done by injecting the series voltage in phase or out of phase with respective to the source voltage during voltage sag and swell respectively. This suggests the real power flow through the series active power filter. The voltage injected by series active power filter could be positive or negative, depending on the source voltage magnitude, absorbing or supplying the real power. In this particular, the series active power filter could not handle reactive power and the load reactive power is supplied by shunt active power filter alone. The single phase equivalent circuit for a unified power quality er is shown in the Fig 3.1[1] 3. 1.Mathematical Equations The source voltage, terminal voltage at point of common coupling and load voltage are denoted by V S, V T and V L respectively. The source and load currents are denoted by I S and I L respectively. The voltage injected by series active Available online @ http://www.ijesat.org 86

power filter is denoted by Vs., where as the current injected by shunt active power filter is denoted by I Sh. Taking the load voltage, V L, as a reference phasor and suppose the lagging power factor of the load is cosφ L. = at an angle 0 o (3.1) I L = I L at an angle Φ L (3.2) V T = V L (1+K) at angle of 0 o (3.3) Where factor k represents the fluctuation of source voltage, defined as K = (V T - V L ) / V L (3.4) The voltage injected by series active power filter must be equal to, V Sr = V L V T = -K V L (3.5) The unified power quality er is assumed to be lossless and therefore, the active power demanded by the load is equal to the active power input at point of common coupling. The unified power quality er provides a nearly unity power factor source current, therefore, for a given load the input active power at Point of common coupling can be expressed by the following equations, P T = P L (3.6) V T = V L * I L *CosΦ L (3.7) V L = (1+K)* I S = V L * I L *CosΦ L (3.8) I S = I L / (1+K) * Cos Φ L (3.9) The above equation suggests that the source current I S depends on the factor k, since Φ L and I L are load characteristics and are constant for a particular type of load. The complex power absorbed by the series active power filter can be expressed as, S Sr = V Sr * I S (3.10) Psr= Vs*Is*CosФs=-k*V L *Is*CosФ S (3.11) Q Sr = V Sr * I S * SinФ S (3.12) Φ S =0 since unified power quality er is maintaining unity power factor Psr=Vsr*Is=-K*V L *I S (3.13) Q SR 0 (3.14) The complex power absorbed by the shunt active power filter can be expressed as, S Sh =V L *I Sh (3.15) The current provided by the shunt active power filter, is the difference between the input source current and the load current, which includes the load harmonics current and the reactive current. Therefore, we can write; = I S - I L (3.16) I Sh = I S at an angle 0 o - I L at an angle - Φ L (3.17) I Sh = I S - ( I L * CosФ L j* I L * SinФ L ) (3.18) I Sh = (I S - I L * CosФ L ) + j* I L * SinФ L (3.19) P Sh =V L *I Sh *CosФ Sh (3.20) = V L * (I S - I L *CosΦ L ) (3.21) Q Sr = V L * I Sh * SinФ Sh (3.22) = V L * I L * SinΦ L (3.23) P Sh = V L * I Sh * CosФ Sh 3.2 Operating Conditions 3.2.1 Case I The reactive power flow during the normal working when unified power quality er is not connected in the circuit is shown in the Figure3.2(a)[1When the unified power quality er is connected in the network and the shunt active power filter is put into the operation, the reactive power required by the load is now provided by the shunt active power filter alone; The reactive power flow during the entire operation of unified power quality er is shown in the Figure 3.2(b)[1]. Fig. Fig.3.2.(a)withoutUPQC Fig.3.2.(b)With shunt APF Fig.3.2 Overall Reactive Power Flow 3.2.2 Case II If k < 0, i.e. Vt < V L, then from equation (3.4) and (3.13), PSR, will be positive, means series active power filter supplies the active power to the load. This is possible during the utility voltage sag. From equation (3.9), I S will be more than the normal rated current. Thus we can say that the required active power is taken from the utility itself by taking more current so as to maintain the power balance in the network and to keep the dc link voltage at desired level[1]. Fig.3.3 Overall Active Power Flow During Sag Condition Ps -power supplied by the source to the load during sag voltage Available online @ http://www.ijesat.org 87

Psr -power injected by series APF in such a way that sum Ps"+ Psr" will be the required load power during normal working Psh =power absorbed by shunt APF during voltage sag Psr = Psh The overall active power flow is shown in Fig 3.3[1]. 3.2.3 Case III If k > 0, i.e. Vt > V L, then by equation (3.4) and (3.13), PSR, will be negative, this means series active power filter is absorbing the extra real power from the source. This is possible during the voltage swell.. In other words we can say that the unified power quality er feeds back the extra power to the supply system. The overall active power flow is shown in Fig.3.4 [1]. Fig.3.4. Overall Active Power Flow During Swell Condition Ps"-power supplied by the source to the load during voltage swell Psr"-power injected by series APF in such a way that sum Ps"- Psr" will be the required load power during normal working Psh"=power delivered by shunt APF during voltage sag Psr"= Psh" Psh=power delivered by shunt APF during voltage sag Psr= Psh 4. SIMULATION RESULTS 4.1 System Data To validate the proposed algorithm, the UPQC device with shunt APF and series APF was simulated using Power System Block set in MATLAB/SIMULINK. The system parameters are shown in Table 4.1. Table 4.1 system parameters Supply Voltage, Vs Supply frequency DC Bus voltage, Vdc, Injection Inductor, L DC side capacitor, C Sensitive load active power Sensitive load reactive power Series filter transformer 4.2 Simulink Model For Shuntapf 415 V 50 Hz 750 V 10 mh 5000 uf 2460 watts 1000 Vars 10 kva 3.2.4 Case IV If k = 0, i.e. Vt = V L, then there will not be any real power exchange though unified power quality er. This is the normal operating. The overall active power flow is shown in Fig. 3.5[1]. Fig4.1: SIMULINK MODEL FOR SHUNT APF Fig.3.5. Active Power Flow During Normal Working Condition Ps-power supplied by the source to the load during voltage swell Psr-power injected by series APF in such a way that sum Ps"=Psr" will be the required load power during normal working. The simulink model of the system used for simulating the ShuntAPF is shown in the Fig 4.1 Wave forms of load currents,, reference currents, compensating currents, D.C link capacitor voltage and source currents and source voltages are shown from Fig 4.2(a) to Fig 4.2(f). Available online @ http://www.ijesat.org 88

Fig4.3SIMULINK MODEL FOR SERIES APF 4.3.1During voltage sag Fig4.2(a) load currents (b) reference currents (c) compensating currents(d) D.C link capacitor voltage(e)source current(f) source voltage Thus results shows Shunt APF controller effectively compensates harmonics, reactive power compensation and maintains D.C link voltage constant. 4.3simulink Model For Series Apf Fig4.4(a)Terminal voltage(b) Reference Voltages from 0.04sec to 0.2sec(c).Voltage Injected by Series APF 0.04sec to 0.2sec During sag(d) voltage sag compensation Test system shown in Fig 4.3.Wave forms of load voltage, reference voltages, series injecting voltages, load voltages during sag, swell and both s are Available online @ http://www.ijesat.org 89

shown from Fig 4.4 to Fig 4.6. Thus results shows Series APF controller effectively compensates voltage sag and maintains load voltage constant. 4.4 Simulink Model Forupqc 4.3.2 During voltage Swell Fig 4.5 SIMULINK MODEL FOR UPQC Fig 4.5(a) Voltage Injected by Series APF 0.04sec to 0.2sec During swell(b) Load voltage Thus results shows Series APF controller effectively compensates voltage swell and maintains load voltage constant. 4.3.3 During voltage swell and sag Fig 4.6(a) Load from 0.04sec to 0.24sec During Sag and Swell terminal voltage(b) Loadvoltage 5. CONCLUSION From the simulation responses, it is evident that the Shunt APF, reference current generator, hysteresis current controller and also for Series APF, reference voltage generator, hysteresis voltage controller are performing satisfactorily. The source current waveform is in phase with the utility voltage and free from harmonic components. The load voltage waveform is maintain constant during voltage sag and swell s. The three phase terminal voltages, three phase load voltages, three phase source currents and the dc link voltage are sensed and used to generate the switching patterns for shunt and series APFs. The shunt active power filter helps series active power filter during voltage sag and swell by maintaining the dc link voltage at set constant level, such that series active power filter could effectively supply or absorb the active power. In addition to this shunt active power filter also provides the required load VARs and thus making the input power factor close to unity. This analysis is very useful in selection of kva ratings of both series and shunt active power filter s depending on the sag and swell needed to be compensated. Hard ware implementation can be carried out for all types of constant and variable loads. Regarding shunt APF instead of using PI controller with neural network we can achieve better performance than earlier. Thus results shows Series APF controller effectively compensates both voltage sag and swells and maintains load voltage constant. Available online @ http://www.ijesat.org 90

REFERENCES [1] Khadkikar.V, Chandra.A, Barry.A.O and Nguyen.T.D: Analysis of power flow in UPQC during voltage sag and swell s for selection device ratings Industrial Electronics. 2006 IEEE International Symposium on Volume 2, 9-13 May 2006. [2] H. Akagi: New trends in active filters for improving power quality.proceedings of the 1996 International Conference, Vol.1, Jan 1996, pp. 417 425. [3] B. Singh, K, Al-Haddad and A. Chandra: "A Review of Active Power Filters for Power Quality Improvement. IEEE Trans on Industrial Electronics, Vol.45,No.5,Oct1999, pp. 960-071. [4] H Sasaki, and T Machida, A New Method to Eliminate ac Harmonic Currents by Magnetic Compensation-- Considerations on Basic Design, IEEE Trans on PAS vol.pas-90,pp.2009, 1971 [5] H. Akagi, New trends in active filters for improvingpower quality, Proceedings of the 1996 International Confe,Vol.1, Jan 1996, pp. 417 425 [6] B. Singh, K. Al-Haddad, A. Chandra, A Review of Active Power Filters for Power Quality Improvement, IEEE Trans on Industrial Electronics, Vol. 45, No.5, Oct1999, pp. 960-071. [7] Khadkikar V, Agarwal P, Chandra A, Barry A O and Nguyen T.D, A simple new control technique for unified power quality er (UPQC), Harmonics and Quality of Power, 2004. 11th International Conference on 12-15 Sept.2004, pp. 289 293. [8] Muthu, S.; Kim, J.M.S, Steady-state operating characteristics of unified active power filters. Applied Power Electronics Conference and Exposition, 1997. APEC '97 Conference Proceedings 1997, Twelfth Annual, Volume: 1, 23-27 Feb 1997, pp. 199-205. [9] Li R.; Johns A T. and Elkateb M.M., Control concept of Unified Power Line Conditioner. Power Engineering Society Winter Meeting, 2000. IEEE, Volume:4, 23-27 Jan 2000, pp. 2594-2599. [10] Elnady A and Salama M.M.A., New functionalities of the unified power quality er. Transmission and Distribution Conference and Exposition, 2001 IEEE/PES,Volume: 1, 28 Oct.-2 Nov 2001, pp. 415-420. [11] Basu M, Das S.P. and Dubey G.K., Performance study of UPQC-Q for load compensation and voltage sag mitigation. IECON 02, IEEE, Volume: 1, 5-8 Nov 2002, pp. 698-703. BIOGRAPHIES B.Jyothi received the B.tech degree from S.K.University,Anathapur in 2002,M.tech Degree from JNTU Hyderabad in 2008.She is currently pursuing Phd at Acharya nagarjuna university,guntur,working as an Asst Professor in KL university,guntur,ap Her interest focus on Power Electronics,power electronics drives and Electrical machines. B.Jyothsna Rani received the B.tech degree from.jntu,hyderabad in 2003,M.tech Degree from ANU,Guntur in 2010.She is currently working as an Asst Professor in KL university,guntur,ap Her interest focus on Power quality and power systems. Dr.Venu Gopala Rao.M, at present is Professor & Head, department of Electrical & Electronics Engineering, K L University, Guntur, Andhra Pradesh, India. He received B.E. degree in Electrical and Electronics Engineering from Gulbarga University in 1996, M.E (Electrical Power Engineering) from M S University, Baroda, India in 1999, M.Tech (Computer Science) from JNT University, Hyderabad, India in 2004 and Doctoral Degree in Electrical & Electronics Engineering from J N T University, Hyderabad, India in 2009. He is Fellow of The Institute of Engineers (India), Life Member of Solar Energy Society of India and Member in IEEE professional society. He published more than 25 papers in various National, International Conferences and Journals. His research interests accumulate in the area of Power Quality, Distribution System, High Voltage Engineering and Electrical Machines Available online @ http://www.ijesat.org 91