Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Similar documents
INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Compensation for Voltage and Current in Multifeeder System Using MC-UPQC

Mitigation of Voltage Sag/Swell Using UPQC

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

2020 P a g e. Figure.2: Line diagram of series active power filter.

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Power Quality improvement of a three phase four wire system using UPQC

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

A Modified Control Method For A Dual Unified Power Quality Conditioner

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Downloaded from

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

Power Quality Improvement in Fourteen Bus System using UPQC

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

P.CHAITHANYAKUMAR, T.VARAPRASAD/

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances

Mitigation of Power system Disturbance by Using MC-UPQC with PI, ANN & FUZZY Controller Technique

SIMULATION OF MULTI CONVERTER BASED UNIFIED POWER-QUALITY (MC-UPQC) CONDITIONING SYSTEM ON VOLTAGE STABILITY OF RADIAL DISTRIBUTION SYSTEMS

Power Quality Improvement By Using DSTATCOM Controller

Modeling and Analysis of a Nonlinear Adaptive Filter Control for Interline Unified Power Quality Conditioner

Power Quality Improvement by Simultaneous Controlling of Active and Reactive Powers in UPQC-S

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

Control Strategy for a cross phase connected and a conventional UPQC

Authors K. Anandarao, K. Vijayabaskar

This is a refereed journal and all articles are professionally screened and reviewed. Electromechanical Active Filter as a Novel Custom Power device

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER OF UPQC

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

ISSN Vol.07,Issue.21, December-2015, Pages:

Mitigation of Voltage Sag/Swell by Using Battery Energy Storage DVR for Induction Motor Drive Applications

A NOVEL STRUCTURE FOR THREE-PHASE FOUR-WIRE DISTRIBUTION SYSTEM UPQC

A Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Interline Power Quality Conditioner for Power Quality Improvement

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Enhancement of Power Quality Using Advanced Series Active Power Filters

ISSN Vol.03,Issue.11, December-2015, Pages:

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

A Power Control Scheme for UPQC for Power Quality Improvement

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

ISSN Vol.04,Issue.08, July-2016, Pages:

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

Improvement of Power Quality Using a Hybrid Interline UPQC

Review on Shunt Active Power Filter for Three Phase Four Wire System

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Cascaded Two Level Electrical Converter-Based Multilevel STATCOM for High Power Utilization

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Performance Analysis of MC-UPQC Using Artificial Intelligence

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

American International Journal of Research in Science, Technology, Engineering & Mathematics

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

29 Level H- Bridge VSC for HVDC Application

Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Comparison of Three leg and Four Leg VSC DSTATCOM for Power Quality Assessment

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Dynamic Modeling and Simulation of Unified Power Quality Conditioner

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

WITH THE advent of advanced power-electronics technologies,

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

POWER QUALITY ASSESSMENT AND ENHANCEMENT IN A GRID CONNECTED RENEWABLE ENERGY SYSTEM USING DYNAMIC VOLTAGE RESTORER

A Multilevel Diode Clamped SVPWM Based Interline Dynamic Voltage Restorer with Sag & Swell Limiting Function

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Ripple Reduction Using Seven-Level Shunt Active Power Filter for High-Power Drives

A Voltage Controlled Dstatcom for Power Quality Improvement

DESIGN OF A HYBRID ACTIVE FILTER FOR HARMONICS SUPPRESSION WITH VARIABLE CONDUCTANCE IN INDUSTRIAL POWER SYSTEMS USING FUZZY

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

Transcription:

Vol.2, Issue.3, May-June 2012 pp-682-686 ISSN: 2249-6645 Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method C. Prakash 1, N. Suparna 2 1 PG Scholar, Department of EEE, SNS College of Technology, Coimbatore 2 Assistant Professor, Department of EEE, SNS College of Technology, Coimbatore Abstract: This project presents a power quality improvement of unified power quality conditioner (UPQC) to compensate current and voltage quality problems of sensitive loads. The UPQC consists of the series and shunt converter having a common dc link. The series converter mitigates voltage sag from the supply side and shunt converter eliminates current harmonics from the nonlimear load side. The developed controllers for series and shunt converters are based on a reference signal generation method(phase-locked loop). The dc link control strategy is based on the fuzzy-logic controllers. The conventional method using dq transformation to show the superiority of the proposed sag detection method. A fast sag detection method is also is presented. The efficiency of the proposed system is tested through simulation studies using the MATLAB/SIMULINK environment. Keywords: unified power quality conditioner (UPQC), reference signal generation, active filter, fuzzy-logic controller. 1. INTRODCTION Power quality is the set of limits of electrical properties that allows electrical systems to function in their intended manner without significant loss of performance or life. The term is used to describeelectric power that drives an electrical load and the load's ability to function properly with that electric power. Without the proper power, an electrical device (or load) may malfunction, fail prematurely or not operate at all. There are many ways in which electric power can be of poor quality and many more causes of such poor quality power[1]. With the increasing applications of nonlinear and electronically switched devices in distribution systems and industries, Power quality (PQ) problems, such as harmonics, flicker, and imbalance have become serious concerns. In addition Lighting strikes on transmission lines, switching of capacitor banks, and various network faults can also cause PQ problems, such as transients, voltage sag and interruption [2]. Voltage source converter (VSC)- based custom power (CP) devices are increasingly being used in custom power applications to mitigate these PQ problems in power distribution systems. A shunt converter (also known as the shunt active filter) can compensate for distortion and unbalance in a load so that a balanced sinusoidal current flows through the feeder. A series converter (also known as the dynamic voltage) can compensate for voltage sag and distortion in the supply side voltage so that the voltage across a sensitive load is perfectly regulated[3].control techniques play a vital role in the overall performance of the power conditioner. Instantaneous power theory is generally preferred to generate reference signals for the shunt converter [3]. An extended method based on instantaneous reactive power theory in a rotating reference frame is used to suppress the harmonics and to correct the power factor in [4]. Fuzzy logic is utilized to control the compensation currents of the shunt converter in [5]. There has also been interest in the circuit topologies of UPQC. UPQC is generally designed as a three-phase threewire (3P3W) systems. The three- phase four- wire system is also realized from the system where the neutral of series transformer used in series part UPQC is considered as the fourth wire for the 3P3W system. There are also single phase UPQC system. Various topologies, such as H- bridge converters, and single-phase UPQC with three legs are examined for the UPQC applications. This paper presents novel contributions for UPQC control and has the following functions: The new control approach based on enhanced phase-locked loop and a nonlinear adaptive filter for reference signals generation is derived for series and shunt converters analyzed. A fuzzy logic controller (FLC) in MATLAB to control dc- link voltage without any interfacing of other simulation programs. FLC of dc-link voltage is proposed which improves the current total harmonic distortion (THD) over the conventional PI controller. A fast algorithm for sag detection is also presented. Fig. 1. Schematic diagram of UPQC. 682 Page

Vol.2, Issue.3, May-June 2012 pp-682-686 ISSN: 2249-6645 The remainder of this paper is organized as follows. Section II of this paper presents a power circuit configuration of UPQC. Section III and IV, the controller algorithms of series and shunt converters are presented. In section V effectiveness of the proposed UPQC is tested. II. POWER CIRCUIT CONFIGURATION OF UPQC The UPQC shown in Fig. 1 consists of two VSCs (VSC 1 and VSC 2 ) that are connected back to back through common energy storage dc capacitor (C DC ). Series converter (VSC 1 ) is connected through transformers between the supply and point of common coupling (PCC). Shunt converter (VSC 2 ) is connected in parallel with PCC through the transformers. VSC 1 operates as a voltage source while VSC 2 operates as a current source. The main objective of VSC 1 is to mitigate voltage sag from the supply side. The ac filter inductor L f and capacitor C f are connected in each phase to prevent the flow of harmonics currents generated due to switching [2]. The objective of VSC 2 are to regulate the dc link voltage between both converters and to suppress the load current harmonics [6]. The switching devices in VSC 1 and VSC 2 are insulated-gate bipolar transistors (IGBT) with anti parallel diodes. C dc provides the common dc- link voltage to VSC 1 and VSC 2. The proposed UPQC system offers two mode of operation as follows. VSC 1 off and VSC 2 on: When the PCC voltage is within its operation limits, VSC 1 is closed and VSC 2 works as the current source.vsc 2 suppress the load current harmonics and regulate dc-link voltage during this mode of operation. VSC 1 on and VSC 2 on: When the PCC voltage is outside its operating range; both VSC 1 and VSC 2 are open. VSC 1 starts to mitigate sag using energy stored inv DC and VSC 2 continue to suppress the load current harmonics and to regulate dc- link voltage. Ideally once charged, the dc-link voltage V DC should not fall off its charge, but due to finite switching losses of the inverter. A. Reference Voltage Generation A block diagram of the proposed algorithm is shown in the Fig. 3. The proposed controller algorithm is derived from the findings of both enhanced PLL and nonlinear adaptive filter. The proposed controller minimizes the mathematical operands in the system and reduces complex parameter tuning. The measurements of supply voltages are required for the control strategy of VSC 1. The system receives the measured input signal A(t) and provides an online estimate of the following signals: B(t), the difference of input and the synchronized Fundamental component; C(t), the amplitude of D(t); D(t), the synchronized fundamental component; E(t), PLL signal; Θ(t), the phase angle of D(t). For the series converter, A(t) corresponds to the supply voltage V A, and E(t) corresponds to V PLL _ A as shown from the Figs. The required compensation signal V err_a is obtained from (V PLL _ A - V A ). C(t) corresponds to V amp_a and this signal is used to detect the voltage sag. The supply voltage and its extracted components, such as the difference of input and the synchronized fundamental component B(t), the amplitude C(t), synchronized fundamental component. Fig. 3. Block diagram of the proposed algorithm. B. Sag Detection Method The proposed sag detection method is compared with the conventional method using dq transformation to show the superiority of the proposed detection method. Fig. 2. Control block diagram of the series converter. 1. Conventional method: The phase voltages Va, VB, VC are transformed to the dq III. SERIES CONVERETER CONTROL The series converter includes the reference voltage and sag detection method. Fig. 2 shows the control algorithm of a series converter for phase A. This control algorithm is identical for the other phases. Fig. 4. (a) Conventional Method. 683 Page

Vol.2, Issue.3, May-June 2012 pp-682-686 ISSN: 2249-6645 Plane as given with the sag is obtained in the conventional method. In fig. 4.(a), the block diagram of the dq transformation- based sag detection method is shown. After the three-phase set of voltages is transformed into d and q components, the square root of the sum of square of these components is obtained. The obtained value is subtracted from the 1 (reference value) and then the absolute value of the resulting variable is filtered out with a 100-Hz low-pass filter to extract the positive- sequence component of voltage. If the negative sequence is generated by voltage sag or unbalance, it appears as an oscillating error in the dq- based sag detection method. The filtered output is subjected to a hysteresis comparator, and the output of this comparator generates the sag detection signal. The signal is high when sag occurs and is low otherwise. The most important disadvantage of this method is that is uses three-phase voltage measurements for the dection. 2. Proposed Method: Fig. 4.(b) Proposed sag detection method. The voltage sag detection method using PLL by subtracting the C(t) signal from the ideal voltage magnitude (1 p.u), the voltage sag depth can be detected. The comparison of this value with the limit value of 10% (0.1p.u) gives information as to whether voltage sag occurred. In fig. 4.b. the voltage sag are detected within a few milliseconds. The conventional method cannot detect the sag, but the proposed method can detect the depth with exact certainty. The single- phase voltage sag initiates at 0.3s with duration of 0.1s.The proposed method detect the voltage sag and balance without error. IV. SHUNT CONVERTER CONTROL The shunt converter includes the reference current computation and capacitor voltage control. Fig. 5. Shows the algorithm of the converter control. For the shunt converter,a(t) corresponds to I A, and B(t) corresponds to I err_a as shown fron figs. 3 and 7. The measurements of load currents (I L ), injected currents (Ii), and dc capacitor voltage (V DC ) are reqired for control strategy of VSC 1. In the proposed method, there is no need to measure supply voltages. The requirred compensation signal is obtained by subtracting the FLC output from I err_a. the obtained signal is then compared with a carrier signal. The required compensation signal is obtained by subtracting the FLC output from I err_a. The obtained signal is then compared with a carrier signal. B. Capacitor Voltage Control In the proposed method, V cap-err is obtained from the difference of the capacitor voltage and measured capacitor voltage. V cap-err and its rate off change are the inputs for the FLC. The input signal are fuzzified and represented in fuzzy set notations by the membership functions. The defined IF. THEN... rules produce the lingustic variables, and these variables are defuzzified into control slgnals. Membership functions and rules are obtained from the an understanding of system behavior and the application of the systematic procedure and are modified and tuned by the simulation preformance. The rules table and stability of the fine- tuned controller with simulation performance are justified by using the approach evalutated in deeply discussed. The systmatic approach evaluated in is used for the analysis and design of proposed FLC. Membership functions are preliminarily selected as a symmatrical, and the approach can be successfully applied to symmetrical membership functions. The output of FLC is added to the current compensating signal. FLC is developed in MATLAB is applied to control the dc-link voltage for the first time without any interfecing with other simulation programs. 5. SIMULATION RESULTS AND DISCUSSION The power quality improvement capability of the UPQC system is tested through MATLAB. A three phase diode bridge rectifier is used as a harmonic current producing load with a total harmonic distortion (THD) of 14.21%. Fig. 5. Control block diagram of the shunt converter. Fig. 6. Test system with UPQC. 684 Page

Vol.2, Issue.3, May-June 2012 pp-682-686 ISSN: 2249-6645 VI. Total harmonic distortion Fig. 6.a. Simulation results with series converter. Fig. 8.a. Total harmonic distortion in source current. Fig. 6.b. Simulation results with shunt converter. Fig. 8.b. Total harmonic distortion in nonlinear load current. Fig. 7. Dc-link capacitor voltage. VII. CONCLUSION The unified power quality conditioner is introduced and analyzed by the controlling voltage source converter (VSC 1 and VSC 2 ) based on enhanced PLL and nonlinear adaptive filter algorithms and dc-link voltage with a fuzzy logic controller. New functionally is added to the UPQC system to quickly extract the reference signals directly for load current and supply voltage with a minimal amount of mathematical operands. The number of parameters to be tuned has also been reduced by the use of the proposed controller. The performance of the proposed UPQC and controller for the PQ improvement is tested through the simulations. The proposed UPQC system provides simultaneous mitigation of a variety of PQ problems. 685 Page

Vol.2, Issue.3, May-June 2012 pp-682-686 ISSN: 2249-6645 REFERENCES [1] H. R. Mohammadi, A. Y. Varjani, and H. Mokhtari, Multiconverter unified power quality conditioning system MC-UPQC, IEEE Trans.Power Del., vol. 24, no. 3, Jul. 2009.pp. 1679 1686. [2] A. K. Jindal, A. Ghosh, and A. Joshi, Interline unified power quality conditioner, IEEE Trans. Power Del., vol. 22, no. 1, Jan.2007 pp. 364 372. [3] H. Fujita and H. Akagi, The unified power quality conditioner: The integration of series and shunt-active filters, IEEE Trans. Power Electron., vol. 13, no. 2, Mar. 1998, pp. 315 322. [4] M. Brenna, R. Faranda, and E. Tironi, A new proposal for power quality and custom power improvement OPEN UPQC, IEEE Trans. Power Del., vol. 24, no. 4, Oct. 2009 pp. 2107 2116. [5] A. Ghosh and G. Ledwich, A unified power quality conditioner (UPQC) for simultaneous voltage and current compensation, Elect. Power Syst. Res., vol. 59, 2001, pp. 55 63. [6] L. Qian, D. A. Cartes, and H. Li, An improved adaptive detection method for power quality mprovement, IEEE Trans. Ind. Appl., vol 44, no. 2, Mar./Apr. 2008, pp. 525 533. [7] H. S. Song, H. G. Park, and K. Nam, An instantaneous phase angle detection algorithm under unbalanced line voltage condition, in Proc. IEEE Power Electron. Specialis. Conf., 1999, vol. 1, pp. 533 537. [8] B. Wu and M. Bodson, A magnitude/phase-locked loop approach to parameter estimation of periodic signals, IEEE Trans. Autom. Control, vol. 48, no. 4,, Apr. 2003. pp. 612 618. [9] R. Rezaeipour and A. Kazemi, Review of novel control strategies for UPQC, Int. J. Elect. Power Eng., vol. 2, 2008. pp. 241 247. 686 Page