FAQ for SIMOREG 6RA70 and Control Module

Similar documents
22.0 Harmonics in Industrial Power Systems

SINAMICS DCM. DC converter Application - 12-pulse parallel connection with decoupled interphase transformer. Introduction 1

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

16B2011B1 EASY HARMONICS USER MANUAL

Harmonics White Paper

Economical Solutions to Meet Harmonic Distortion Limits[4]

Power Quality and Harmonic :Causes and Effects with Paper Mill Factory

Harmonic Requirements

Analysis of Harmonic Distortion in Non-linear Loads

ABB drives. Technical guide No. 6 Guide to harmonics with AC drives

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

ATYPICAL high-power gate-turn-off (GTO) currentsource

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

NJWA - Harmonics and Drives Proper System Design

CHAPTER 4 HARMONICS AND POWER FACTOR

Tuningintobetter power quality

Harmonic Distortion Evaluations

SINAMICS drives. SINAMICS DCM as a DC voltage source. Application. Answers for industry. Edition 01/2014

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

ELECTRICITY ASSOCIATION SERVICES LIMITED 2001

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

Low Pass Harmonic Filters

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Understanding Input Harmonics and Techniques to Mitigate Them

Harmonic Distortion and Variable Frequency Drives

Reduce harmonics in HVAC&R inverters through C-Less technology

POWER QUALITY AND SAFETY

p. 1 p. 6 p. 22 p. 46 p. 58

A. Harmonics. non-linear loads. are. required)

Harmonic Filters and Reactors

Emicon Engineering Consultants L.L.C.

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

7/15/2002 PP.AFD.08 1 of 28

Power Factor & Harmonics

Caution - leakage currents! Leakage currents in fault-current protected environments

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Southern Company Power Quality Policy

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Power Quality Analysers

Examples Paper 3B3/4 DC-AC Inverters, Resonant Converter Circuits. dc to ac converters

INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER

Effects of Harmonic Distortion I

OUTLINE. Introduction. Introduction. Conducted Electromagnetic Interference in Smart Grids. Introduction. Introduction

Technical Series, Edition 14

Improve Power Factor and Reduce the Harmonics Distortion of the System

Recommendations for Harmonic and Power Measurements in Electrical Networks

Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007

1C.4.1 Harmonic Distortion

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

THE FIRST STEP IN THE RESOLUTION OF VOLTAGE DISTORTION FOR SHARED GENERATORS AND MV UNDERSEA RING MAIN IN AN OFFSHORE OIL FIELD

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

ECE 528 Understanding Power Quality

Harmonic Filtering in Variable Speed Drives

The increase in the application

Conventional Paper-II-2013

STUDY OF THE EFFECTS OF HARMONICS IN THE DESIGN OF TRANSMISSION NETWORK SHUNT COMPENSATORS: NETWORK SIMULATION AND ANALYSIS METHODS

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Conventional Paper-II-2011 Part-1A

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Ferroresonance Experience in UK: Simulations and Measurements

SHARDA Make Harmonics Filter

Power Quality Summary

( ) ON s inductance of 10 mh. The motor draws an average current of 20A at a constant back emf of 80 V, under steady state.

Differential Protection with REF 542plus Feeder Terminal

Effect of Geomagnetically Induced Currents on Protection Systems

Understanding Harmonics

SIMULATION OF D-STATCOM IN POWER SYSTEM

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

CHAPTER ELECTROMAGNETIC COMPATIBILITY. Contents of this Chapter...

ZENER ELECTRIC PTY LTD

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

UNDERSTANDING POWER QUALITY

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

Single Switch Forward Converter

Application of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case

Reactors and Filters. Catalog LV SIDAC. Answers for industry.

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Power quality report. A Manufacturing Plant

POWERED electronic equipment with high-frequency inverters

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Application Note DSD

MERLIN GERIN KNOW HOW. THM filtering and the management of harmonics upstream of UPS

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

Evaluation and Updating of Harmonic Voltage Limits

Danfoss Harmonic Calculation Software 2.0 Handbook Basic Level

Harmonic control devices. ECE 528 Understanding Power Quality

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Putting a damper on resonance

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Principles for Controlling Harmonics

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Power Quality Solutions

Transcription:

I DT LD CS 28 / February / 2011 FAQ for SIMOREG 6RA70 and Control Module Question: What requirements apply for line quality and what line interference can occur? Answer: Line requirements: Voltage: rated voltage +10% -20%, (+15% for 400 V and 460 V devices) Frequency: 45 to 65 Hz (23 to 110 Hz on Request) Permissible speed of frequency change: 10 Hz/s Maximum asymmetry of the line: 3% U OS... Line-to-line voltage of the medium-voltage network on transformer primary side U US... Line-to-line voltage of the low-voltage side on transformer secondary side S K1... Short-circuit power of the medium-voltage network at the connection point of the converter transformer S K2... Short-circuit power of the secondary-side busbar of the converter transformer X N... Inductive resistance of the network relative to the secondary-side voltage of the transformer X T... Inductive resistance of the converter transformer relative to the secondary-side voltage of the transformer X D... Inductive resistance of the commutating reactor X K... Commutating reactance of the converter, X K = X N + X T + X D Id... DC current Lv Inductance of the smoothing reactor, La...Inductance of the motor SR... M... Converter DC motor 1

Line interference: Converters on the network cause two types of line interference: A) Commutating notches B) Harmonics This interference does not destroy the converters but it can have adverse effects on other loads on the same network. Commutating notches: Commutation reactor: If line-commutated current converters are used, commutation induction is always required in the supply circuit. In the simplest case, a commutation reactor is used. To protect the current converter, a commutation inductance is required that produces a 4% voltage drop at the rated current of the converter; Vimp = 4%. A separate commutation reactor or separate transformer winding with 4 % Vimp must be used for every current converter used on one power system. The permissible Vimp of the reactor/transformer winding for the current converter is 4% to 10% (worst case 15%). According to DIN EN 61800-3, voltage dips of up to 20% are permissible during commutation. The following applies: If the short-circuit power of the power system is higher than the connected load of the current converter by at least a factor of 100, commutation notches of maximum 20% of the peak voltage of the network will occur if a 4% commutation reactor is used. If several current converters are installed on the same power system, it can be assumed that these will not commutate at exactly the same time, so the reactor can be dimensioned for each current converter individually as a function of its power, as described above. Normally the commutation reactor is dimensioned as a function of the rated motor current; this saves costs as the rated current of the device is usually higher. If high acceleration currents are required on the motor, the reactor should be designed for a peak current / 1.6 due to the saturation that occurs during high currents. The alternating current of the reactor for the armature circuit infeed is: Direct current Id * 0.816 Help with calculation of the commutation notches: ΔU[%] = (x N + x T )/ (x N + x T + x D ) * 100%; where x N + x T = U US 2 / S k2 ; x D = L D * 2 * π * f; L D : reactor inductance, f = line frequency, ΔU: Commutation notch power system at current converter connecting point (line side directly before the commutation reactor) as a percentage. If only the short-circuit power S k1 on the high-voltage side of the line transformer is known, S k2 can be calculated as follows: S k2 = S T / (u k + S T / S k1 ); S T : Transformer apparent power, u k : Short-circuit power transformer in p.u. e.g. 0.06 for 6% uk. Effects of the commutation notches on loads in the same power system: If several SINAMICS DCM are operated in the same network, they do not usually affect each other, so long as the voltage dip is not higher than that defined by the threshold of the phasefailure monitoring in parameter P353 (factory setting 40% means 60% dip permissible). However, it cannot be ruled out that these steep-edged voltage dips might damage other loads. Examples of this are switched-mode power supplies for supplying power to automation units, computers and their monitors, but also loads such as fluorescent lamps with electronic starters and power-factor correction capacitors for low-voltage motors. That is one of the reasons why higher performance current converters are usually supplied via a separate converter transformer, fed from the high-voltage side of the power system. If problems arise with loads on the same network with line-commutated current converters, the 2

lower-cost solution is usually to provide a separate transformer for the weak network loads rather than implement additional measures on the high-power current converter. Harmonics: 6-pulse converter: 6-pulse line-commutated converters cause only odd harmonic currents and harmonic voltages that cannot be divided by 3 occur, with the following harmonic numbers v: ν = n * 6 ± 1 where n = 1, 2, 3... ν = 5, 7, 11, 13, 17, 19, 23, 25, 29, 31, 35, 37, 41, 43, 47, 49... 12-pulse converter: Due to the phase shift of 30 between the two secondary voltages, the harmonic currents with harmonic numbers v = 5, 7, 17, 19, 29, 31, 41, 43,..., which are still present in the input currents of the 6-pulse rectifiers, compensate one another so that theoretically only odd harmonic currents and voltages that cannot be divided by 3 with the following v numbers occur at the point of common coupling (PCC) on the primary side of the transformer: ν = n * 12 ± 1 where n = 1, 2, 3... ν = 11, 13, 23, 25, 35, 37, 47, 49... Which harmonics are acceptable? The following standards governing harmonics are applicable: EN 61000-2-2; Compatibility levels for low-frequency conducted disturbances and signaling in public low-voltage power supply systems. Applies to a frequency range from 0 to 9 khz. For rated voltages up to 420 V single-phase and 690 V three-phase. The compatibility levels are valid for the point of common coupling (PCC) with the public supply system. Limits for harmonic currents are not defined. The compatibility level for the total harmonic distortion factor of the voltage: THD(V) is 8%. EN61000-2-4: Compatibility levels for low-frequency conducted disturbance variables in industrial plants. Applies to a frequency range from 0 to 9 khz. Class 1: Refers to the operation of equipment which is highly sensitive to disturbances in the power supply. Class 2: This class generally applies to points of common coupling (PCCs) with the public supply system and to internal points of coupling (IPCs) with industrial or other private supply systems. Class 3: This class applies to internal points of coupling (IPCs) in industrial environments. This class should be considered, for example, if one of the following conditions applies: The main part of the load is supplied via converters Welding machines are present Large motors are started frequently Loads vary quickly Standard EN 61000-2-4 does not define limits for harmonic currents. Limits are only specified for harmonic voltages and the total harmonic distortion of the voltage THD(V). 3

Harmonic number ν Class 1 U ν in % Class 2 U ν in % Class 3 U ν in % 5 3 6 8 7 3 5 7 11 3 3.5 5 13 3 3 4.5 17 2 2 4 >17 to 49 2.27 * 17 / ν 0.27 2.27 * 17 / ν 0.27 4.5 * 17 / ν 0.5 Class 1 Class 2 Class 3 THD(V) 5% 8% 10% SIMOREG are normally operated in classes 2 and 3. SIMOREG are not affected by supply systems with a high harmonic content; the purpose of the classes specified above is therefore to define permissible values for other equipment connected to the point of common coupling (PCC). IEEE 519: IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems This standard is applied in the USA, Canada and many countries in Asia. It specifies limits for harmonic voltages and currents for both individual consumers and also for the sum of all consumers at the point of common coupling (PCC). Permissible harmonic voltages and THD(V). These limits are determined by the ratio between maximum demand load current of the individual consumer and the supply short-circuit current (averaged over 15 or 30 minutes). Permissible voltage levels at the PCC for each individual consumer: Ratio short-circuit current / max. demand load current Permissible values for each individual harmonic voltage Typical users 10 2.5 3% Special customers with special agreement 20 2.0 2.5% 1 2 large consumers 50 1.0 1.5% A few high energy consumers 100 0.5 1% 5 20 medium energy consumers 1000 0.05 0.1% A large number of low energy consumers Permissible voltage level at the PCC for the sum of all consumers: Voltage at the PCC Permissible value for each individual harmonic voltage 4 Permissible value for THD(V) U Supply 69 kv 3% 5%

Permissible harmonic currents and permissible total harmonic distortion of current THD(I): The limits depend on the ratio between the supply short-circuit current and the maximum demand load current at the PCC (averaged over 15 or 30 minutes). Permissible harmonic currents at the PCC in relation to the maximum demand load current at the PCC Ratio of short-circuit current/ max. demand load current < 11 11 v < 17 17 v < 23 23 v < 35 35 v THD(I) < 20 4% 2.0% 1.5% 0.6% 0.3% 5% 20 < 50 7% 3.5% 2.5% 1.0% 0.5% 8% 50 < 100 10% 4.5% 4.0% 1.5% 0.7% 12% 100 < 1000 12% 5.5% 5.0% 2.0% 1.0% 15% > 1000 15% 7.0% 6.0% 2.5% 1.4% 20% The limit values specified in IEEE519, especially those for low harmonic orders, are in some cases significantly lower than the limits defined by EN 61000-2-4. As a general rule, 6-pulse connections can operate within the specified limits only when a very low percentage of the total transformer load is made up of converter load. The high amplitude of the 5th and 7th harmonics typical of a 6-pulse converter makes compliance particularly difficult. The possibility of using a 12-pulse circuit must be examined, as this may comply with the limits specified by IEEE519. The harmonics will be calculated by the Siemens Technical Support; the following data are required to do this: a) Short-circuit power of the medium-voltage network b) Transformer data: input and output voltage, apparent power and uk. c) Line frequency f d) Inductance of the commutation reactor e) Inductance of the smoothing reactor and the motor f) Rated current and rated voltage of the motor g) 6-pulse or 12-pulse converter operation 5